Attachment 6 - Asbestos Report.pdf
PDF 3 MB Posted
- Attached to
- Boiler Replacement (bldg. 2162) Federal contract opportunity
- Solicitation number
- W911S8-20-B-0004
About this file
This solicitation seeks bids for a boiler replacement project at Building 2162 on Joint Base Lewis-McChord in Washington. Bids are due by September 23, 2020 at 1:00 PM PDT. A site visit and pre-bid conference will be held on September 1, 2020 at 9:00 AM PDT at Building 2162. Interested bidders must RSVP with attendee information by August 31. The bid opening will occur on September 23 at 3:00 PM PDT at the MICC conference room on JBLM. Bidders must adhere to COVID-19 safety protocols including masks and social distancing. Questions are due by September 4 and must reference the applicable section. Answers will be provided in an amendment. Electronic submission of bids via email is required with the subject line specifying the solicitation number. The work includes replacing the boilers at Building 2162 on Joint Base Lewis-McChord in Washington.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 3 - Specifications and Drawings.pdf | ||
| Exhibit 1 - W911S8-20-B-0004 - Invitation For Bid.pdf | ||
| Attachment 4 - Wage Rates.pdf | ||
| Attachment 2 - Statement of Work.pdf | ||
| Attachment 1 - AT OPSEC.pdf | ||
| Attachment 5 - Post Access.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPORT OF BUILDING MATERIAL SURVEY, SAMPLING AND
EVALUATION OF ASBESTOS-CONTAINING MATERIALS
FOR
BUILDING 2162
JOINT BASE LEWIS-MCCHORD
WASHINGTON 98433
AIRQUEST PROJECT #15-01-9931
SOLICITATION NUMBER: W912DW-15-Q-0059
PREPARED FOR:
MR. THOMAS VAN ALSTYNE, JR.
CHIEF, PROJECT MANAGEMENT BRANCH B, ESD
PUBLIC WORKS
BUILDING 02012, ROOM 223
JOINT BASE LEWIS-MCCHORD, WASHINGTON 98433
PREPARED BY:
AIRQUEST ENVIRONMENTAL, INC.
6851 SOUTHWEST 45TH STREET
FORT LAUDERDALE, FLORIDA 33314
NOVEMBER 2015
ii
CERTIFICATION PAGE
REPORT OF BUILDING MATERIAL SURVEY, SAMPLING AND
EVALUATION OF ASBESTOS-CONTAINING MATERIALS
FOR
BUILDING 2162
JOINT BASE LEWIS-MCCHORD
WASHINGTON 98433
AIRQUEST PROJECT #15-01-9931
SOLICITATION NUMBER: W912DW-15-Q-0059
PREPARED FOR:
MR. THOMAS VAN ALSTYNE, JR.
CHIEF, PROJECT MANAGEMENT BRANCH B, ESD
PUBLIC WORKS
BUILDING 02012, ROOM 223
JOINT BASE LEWIS-MCCHORD, WASHINGTON 98433
PREPARED BY:
AIRQUEST ENVIRONMENTAL, INC.
6851 SOUTHWEST 45TH STREET
FORT LAUDERDALE, FLORIDA 33314
NOVEMBER 2015
Nicholas Nalepa Paul LeBlanc AHERA Inspector AHERA Inspector
Traci-Anne Boyle, CIH, CSP
AHERA Inspector / Management Planner/ Project Designer iii
EXECUTIVE SUMMARY
AirQuest Environmental, Inc. (“AirQuest”) performed an asbestos survey within Building 2162 at the Joint Base Lewis-McChord in Washington (“the site”). The survey was performed on October 19, 2015, by AirQuest Senior Project Manager Paul LeBlanc and Nicholas Nalepa, both trained Asbestos Hazard Emergency Response Act (AHERA) certified asbestos inspectors.
The purpose of this survey was to identify asbestos-containing materials (ACM) within the interior and exterior building. At the request of the Client, the roof was not included in the scope of the inspection.
The results of our observation and laboratory analysis identified the following ACM:
Homogeneous Area Number 2 Sample No.: 2162-04 and 2162-05 Material: Exterior Window Caulk Location: West Side of Building Results: 8% Chrysotile Quantity: Approximately Forty (40) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a Washington licensed asbestos abatement contractor, with prior notification to the appropriate County and State agencies.
Homogeneous Area Number 3 Sample No.: 2162-06 and 2162-07 Material: Exterior Door Caulk Location: South Side of Building Results: 2% Chrysotile Quantity: Approximately Ninety (90) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a iv
Homogeneous Area Number 7 Sample No.: 2162-15 and 2162-16 Material: White Plumbers Putty Location: @ Threaded Black Pipe Fittings Results: 6% Chrysotile Quantity: Throughout The Plant The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Homogeneous Area Number 12 Sample No.: 2162-25 and 2162-26 Material: Packing (Gasket) @ Boiler Exhaust Vent System Location: Black Interior Exhaust System Running East to West
Just North of the Boilers Within the Plant Results: 40% Chrysotile Quantity: Approximately Forty-Eight (48) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Homogeneous Area Number 13 Sample No.: 2162-27, 2162-28, QAQC 2162-28 and 2162-29 Material: Drywall Panels on Ceiling (Heat Resistant Panels) Location: North Area Ceiling Above Exhaust From Boilers #2 and #3 Results: 35-70% Chrysotile Quantity: Approximately Fifty (50) Square Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a v
In accordance with Washington Administrative Code (WAC) 296-62-07721, employers shall communicate the asbestos hazard to:
1) Employees
a. Include asbestos in the hazard communication program established to comply with the Hazard Communication Standard (HCS), WAC 296-901-140.
b. Employers shall ensure that each employee has access to labels on containers of asbestos and to safety data sheets, and is trained in accordance with the requirements of HCS and WAC 296-62-07722.
c. Housekeeping personnel must be informed of the presence and location of asbestos containing materials that may be disturbed during housekeeping and maintenance activities.
2) Contractors
a. Provide a copy of this asbestos report to any contractor conducting renovation or demolition activities within the facility.
3) Subsequent Owners
a. Provide a copy of this asbestos report to any future owner of the building.
All asbestos containing materials must be labeled in accordance with the requirements WAC 296-62-07721 (5). WAC 296-62-07721 (6) requires that the employer annually provide, at no cost to employees who perform housekeeping operations in a facility which contains ACM or Presumed ACM (PACM), an asbestos awareness training course to all employees who are or will work in areas where ACM and/or PACM is present who work in buildings containing asbestos containing materials.
The ACM identified in this survey was in generally good condition at the time of the survey.
The ACM should be monitored semi-annually for signs of deterioration or damage. Any ACM that are identified in poor condition (or that will be impacted by renovation or demolition activities) must be abated by a Washington licensed asbestos abatement contractor. An AHERA accredited Project Designer should design the asbestos abatement activities and the abatement should be monitored and cleared by an AHERA accredited Contractor/Supervisor and NIOSH 582 analyst.
The survey was limited to the client directed areas and/or building materials within the interior and exterior of the building. At the request of the Client, the roof was not included in the scope of the inspection. Destructive sampling procedures were not used to access the interior of wall cavities, fire doors or above hard ceilings, interior of boilers, electrical panels or electrical wiring. If any materials are encountered during renovation or demolition activities that were not sampled in this report, the materials should not be disturbed until they have been sampled and identified as non-asbestos containing materials through laboratory analysis.
vi
TABLE OF CONTENTS
PAGE
CERTIFICATION PAGE II
EXECUTIVE SUMMARY III
1 INTRODUCTION 1
2 FACILITY DESCRIPTION 2
3 SURVEY METHODS AND LABORATORY ANALYSIS 3
4 SUSPECT ASBESTOS-CONTAINING MATERIALS 4
5 ASBESTOS CONTAINING MATERIALS 7
6 CONCLUSIONS AND RECOMMENDATIONS 9
7 LIMITATIONS 12
TABLES
Table 1 - Laboratory Analysis and Summary
APPENDICES
Appendix I – Personnel and Laboratory Certifications
Appendix II – Laboratory Reports & Chain of Custody Records
Appendix III- Sample Location Diagram
Appendix IV- Photographs
Appendix V- Photographs of ACM Materials
1 INTRODUCTION
AirQuest Environmental, Inc. (“AirQuest”) performed an asbestos survey within Building 2162 at the Joint Base Lewis-McChord in Washington (“the site”). The survey was performed on October 19, 2015, by AirQuest Senior Project Manager Paul LeBlanc and Nicholas Nalepa, both trained Asbestos Hazard Emergency Response Act (AHERA) certified asbestos inspectors (see Appendix I).
The purpose of this survey was to identify asbestos-containing materials (ACM) within the interior and exterior building. At the request of the Client, the roof was not included in the scope of the inspection.
The scope of services for this project consisted of the following five steps:
Building Walk-Through and Observations, Bulk Sampling of Suspect Asbestos-Containing Building Materials (ACBM), Polarized Light Microscopy (PLM) Analysis of Bulk Samples, Hazard Assessment and Evaluation, and Final Report Preparation.
2 FACILITY DESCRIPTION
Building 2162 was located within the Joint Base Lewis-McChord (“JBLM”) in Washington. The 2,300 square foot structure functioned as a boiler plant with two (2) storage rooms at the north end of the building.
The building was constructed of concrete and brick on a concrete foundation. The interior walls were constructed of unfinished concrete, wood and brick. The ceilings of the plant were constructed of wood while the storage room ceilings were constructed of concrete. The floors within the plant and storage rooms consisted of unfinished concrete. The plant was furnished with a steel catwalk system to access upper portions of the boilers.
3 SURVEY METHODS AND LABORATORY ANALYSIS
The sampling protocol used in this asbestos survey are those detailed in Title 40, Code of Federal Regulations (CFR), Part 763.86 for the sampling of friable surfacing materials, thermal systems insulation and miscellaneous materials (i.e. ceiling tiles). The Environmental Protection Agency (EPA) regulations require that sample locations be randomly selected. Suspect ACBM were identified and samples of each different type of material were obtained.
The bulk sampling procedure utilized for the collection of samples suspected of being ACBM required the establishment of homogeneous sampling areas. A homogeneous sampling area is defined as an area of friable or non-friable material of similar type that appeared to be applied or constructed during the same general period of time. This is the most acceptable and cost-effective method for the sampling of suspect ACBM.
Samples of suspect materials were collected from predetermined homogeneous sampling areas and the location of each sample was recorded. Samples were labeled and transported to the laboratory for analysis, using polarized light microscopy (PLM) coupled with dispersion staining. The samples were analyzed in accordance with Title 61 Code of Federal Regulation.
Polarized light microscopy is a method of analysis that utilizes the unique optical crystallographic properties of the various crystalline forms in the samples. These properties, such as refractive indices, birefringence, sign of elongation and extinction angle, are unique to crystalline asbestos forms and therefore can be used to identify the type of asbestos mineral as chrysotile, amosite, crocidolite, anthophyllite, tremolite, or actinolite. Each type of asbestos displays unique characteristics when subjected to these tests. Percentages of the identified types of asbestos are determined by visual estimation. Any material containing over one percent (1%) by weight is considered by the U.S. Environmental Protection Agency (EPA) to be an asbestos containing material and if disturbed must be handled according to specific local, state and federal regulations.
4 SUSPECT ASBESTOS-CONTAINING MATERIALS
Thirteen (13) homogeneous areas (HA) of suspect material were identified and a total of twenty-nine (29) samples were collected, including two (2) quality assurance/ quality control (QAQC) samples that were sent to a separate laboratory for analysis. Sample descriptions and laboratory results can be found in Table 1 - "Laboratory Analysis and Summary". A copy of the laboratory reports and chain of custody records are included in Appendix II. A diagram denoting sample locations is included in Appendix III. Photographs denoting each HA are included in Appendix
IV.
Table 1 - Laboratory Analysis and Summary
Samples Collected on October 19, 2015
HA
Sample Number HA Description Sample Location Asbestos Content
1 2162-01 Exterior Window Glazing West Exterior Wall ND
1 2162-02 Exterior Window Glazing North Exterior Wall ND
1 2162-03 Exterior Window Glazing West Exterior Wall ND
2 2162-04 Exterior Window Caulk West Exterior Wall 8% Chrysotile
2 2162-05 Exterior Window Caulk West Exterior Wall Stopped at First
Positive
3 2162-06 Exterior Door Caulk South East Exterior Door 2% Chrysotile
3 2162-07 Exterior Door Caulk South West Exterior Door Stopped at First
Positive
4 2162-08 Interior Door Caulk East Interior Door ND
4 2162-09 Interior Door Caulk East Interior Door ND
5 2162-10 Exterior Mortar at Brick East Exterior Wall ND
5 2162-11 Exterior Mortar at Brick West Stack ND
5 2162-12 Exterior Mortar at Brick Exterior West Wall ND
6 2162-13 Exterior Cementitious Patch at Exhaust Pipe West Exterior Wall ND
6 2162-14 Exterior Cementitious Patch at Exhaust Pipe West Exterior Wall ND
7 2162-15 White Plumbers Putty East Side Boiler #3 6% Chrysotile
7 2162-16 White Plumbers Putty South Side Boiler #3 Stopped at First
Positive
8 2162-17 White Rope Packing (Gasket) at Boiler #1 North Side Boiler #1 ND
9 2162-18 Green Caulk at South Upper Fire Box Access Door South Side Boiler #2 ND
9 2162-19 Green Caulk at South Upper Fire Box Access Door South Side Boiler #2 ND
10 2162-20 Blue Caulk at Seam of Metal Jacket North Side Boiler #2 ND
10 2162-21 Blue Caulk at Seam of Metal Jacket North Side Boiler #2 ND
11 2162-22 White Paper Wrap With Fiberglass Insulation Southwest Area Pipe ND
11 2162-23 White Paper Wrap With Fiberglass Insulation Southwest Area Pipe ND
11 2162-24 White Paper Wrap With Fiberglass Insulation Southeast Area Pipe ND
12 2162-25 Packing (Gasket) at Boiler Exhaust Vent System North Area Exhaust 40% Chrysotile
HA
Sample Number HA Description Sample Location Asbestos Content
12 2162-26 Packing (Gasket) at Boiler Exhaust Vent System Northwest Area Exhaust Stopped at First
Positive
13 2162-27 Drywall Panels on Ceiling (heat resistant) North Area Ceiling above Boiler
#2 35% Chrysotile
13 2162-28 Drywall Panels on Ceiling (heat resistant) North Area Ceiling above Boiler
#2 Stopped at First
Positive
13 2162-29 Drywall Panels on Ceiling (heat resistant) North Area Ceiling above Boiler
#2 Stopped at First
Positive HA- Homogenous Area ND- None Detected
QA/QC Samples Collected on October 19, 2015
HA
Sample Number HA Description Sample Location Asbestos Content
4 2162-08 Interior Door Caulk East Interior Door ND
13 2162-28 Drywall Panels on Ceiling (heat resistant) North Area Ceiling above Boiler
#2 70% Chrysotile HA- Homogenous Area ND- None Detected
5 ASBESTOS CONTAINING MATERIALS
This section describes the asbestos-containing materials (ACM) observed during the inspection.
The quantities of material described herein are approximate and are not to be relied upon by asbestos abatement contractors for bidding purposes.
The results of our observation and laboratory analysis identified the following ACM:
Homogeneous Area Number 2 Sample No.: 2162-04 and 2162-05 Material: Exterior Window Caulk Location: West Side of Building Results: 8% Chrysotile Quantity: Approximately Forty (40) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Material: Exterior Door Caulk Location: South Side of Building Results: 2% Chrysotile Quantity: Approximately Ninety (90) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Sample No.: 2162-15 and 2162-16 Material: White Plumbers Putty Location: @ Threaded Black Pipe Fittings Results: 6% Chrysotile Quantity: Throughout The Plant The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Sample No.: 2162-25 and 2162-26 Material: Packing (Gasket) @ Boiler Exhaust Vent System Location: Black Interior Exhaust System Running East to West
Just North of the Boilers Within the Plant Results: 40% Chrysotile Quantity: Approximately Forty-Eight (48) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Material: Drywall Panels on Ceiling (Heat Resistant Panels) Location: North Area Ceiling Above Exhaust From Boilers #2 and #3 Results: 35% -70% Chrysotile Quantity: Approximately Fifty (50) Square Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Photographs of the ACM are included in Appendix V.
6 CONCLUSIONS AND RECOMMENDATIONS
The results of our observation and laboratory analysis identified the following ACM:
Homogeneous Area Number 2 Sample No.: 2162-04 and 2162-05 Material: Exterior Window Caulk Location: West Side of Building Results: 8% Chrysotile Quantity: Approximately Forty (40) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Material: Exterior Door Caulk Location: South Side of Building Results: 2% Chrysotile Quantity: Approximately Ninety (90) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Sample No.: 2162-15 and 2162-16 Material: White Plumbers Putty Location: @ Threaded Black Pipe Fittings Results: 6% Chrysotile Quantity: Throughout The Plant The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Sample No.: 2162-25 and 2162-26 Material: Packing (Gasket) @ Boiler Exhaust Vent System Location: Black Interior Exhaust System Running East to West
Just North of the Boilers Within the Plant Results: 40% Chrysotile Quantity: Approximately Forty-Eight (48) Linear Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
Material: Drywall Panels on Ceiling (Heat Resistant Panels) Location: North Area Ceiling Above Exhaust From Boilers #2 and #3 Results: 35% -70% Chrysotile Quantity: Approximately Fifty (50) Square Feet The material was in good condition and was non-friable. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities. If the material is to be impacted or removed, the removal must be conducted by a
In accordance with Washington Administrative Code (WAC) 296-62-07721, employers shall communicate the asbestos hazard to:
1) Employees
a. Include asbestos in the hazard communication program established to comply with the Hazard Communication Standard (HCS), WAC 296-901-140.
b. Employers shall ensure that each employee has access to labels on containers of asbestos and to safety data sheets, and is trained in accordance with the requirements of HCS and WAC 296-62-07722.
c. Housekeeping personnel must be informed of the presence and location of asbestos containing materials that may be disturbed during housekeeping and maintenance activities.
2) Contractors
a. Provide a copy of this asbestos report to any contractor conducting renovation or demolition activities within the facility.
3) Subsequent Owners
a. Provide a copy of this asbestos report to any future owner of the building.
All asbestos containing materials must be labeled in accordance with the requirements WAC 296-62-07721 (5). WAC 296-62-07721 (6) requires that the employer annually provide, at no cost to employees who perform housekeeping operations in a facility which contains ACM or Presumed ACM (PACM), an asbestos awareness training course to all employees who are or will work in areas where ACM and/or PACM is present who work in buildings containing asbestos containing materials.
The ACM identified in this survey was in generally good condition at the time of the survey.
The ACM should be monitored semi-annually for signs of deterioration or damage. Any ACM that are identified in poor condition (or that will be impacted by renovation or demolition activities) must be abated by a Washington licensed asbestos abatement contractor. An AHERA accredited Project Designer should design the asbestos abatement activities and the abatement should be monitored and cleared by an AHERA accredited Contractor/Supervisor and NIOSH 582 analyst.
7 LIMITATIONS
The survey was limited to the client directed areas and/or building materials within the interior and exterior of the building. At the request of the Client, the roof was not included in the scope of the inspection. Destructive sampling procedures were not used to access the interior of wall cavities, fire doors or above hard ceilings, interior of boilers, electrical panels or electrical wiring. If any materials are encountered during renovation or demolition activities that were not sampled in this report, the materials should not be disturbed until they have been sampled and identified as non-asbestos containing materials through laboratory analysis.
| Appendix | I | ||
| Personnel | and | Laboratory | Certifications |
STATE OF FLORIDA
DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
ASBESTOS LICENSING UNIT
1940 NORTH MONROE STREET
TALLAHASSEE FL 32399-0783
BOYLE, TRACI-ANNE
AIRQUEST ENVIRONMENTAL INC
6851 SW45 ST
DAVIE FL 33314
Congratulations! With this license you become one of the nearly one million Floridians licensed by the Department of Business and Professional Regulation. Our professionals and businesses range from architects to yacht brokers, from boxers to barbeque restaurants , and they keep Florida's economy strong.
Every day we work to improve the way we do business in order to serve you better. For information about our services, please log onto www.myfloridalicense.com. There you can find more information about our divisions and the regulations that impact you, subscribe to department newsletters and learn more about the Department's initiatives.
Our mission at the Department is: License Efficiently, Regulate Fairly.
We constantly strive to serve you better so that you can serve your customers. Thank you for doing business in Florida, and congratulations on your new license!
DETACH HERE
RICK SCOTT, GOVERNOR
STATE OF FLORIDA
(850) 487-1395
STATE OF FLORIDA
DEPARTMENT OF BUSINESS AND
PROFESSIONAL REGULATION
AX60 ISSUED: 09/28/2014
ASBESTOS CONSULTANT
BOYLE, TRACI-ANNE
AIRQUEST ENVIRONMENTAL INC
IS LICENSED under the provisions of Ch .469 FS .
Expiration date : NOV 30. 2016 L 1409280007658
KEN LAWSON, SECRETARY
DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
ASBESTOS LICENSING UNIT
The ASBESTOS CONSULTANT Named below IS LICENSED Under the provisions of Chapter 469 FS.
Expiration date: NOV 30, 2016
BOYLE, TRACI-ANNE
AIRQUEST ENVIRONMENTAL INC
6851 SW 45 ST
DAVIE FL 33314
~~~~ u=n· nAJ?R/?014 r11SPLAY AS REQUIRED BY LAW SEQ# L 1409280007658
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2005
NVLAP LAB CODE: 500085-0
EMSL Analytical, Inc.
Fort Lauderdale, FL is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2015-06-02 through 2016-06-30
Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2005.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).
National Voluntary Laboratory Accreditation Program
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005
For the National Voluntary Laboratory Accreditation Program
Effective 2015-06-02 through 2016-06-30
EMSL Analytical, Inc.
2700 West Cypress Creek Road
Bldg. B, Suite 111 Fort Lauderdale, FL 33309
Ms. Amrita Paul Phone: (954) 786-9331 Fax: (954) 941-4145
Email: apaul@emsl.com http://www.emsl.com
ASBESTOS FIBER ANALYSIS NVLAP LAB CODE 500085-0
Bulk Asbestos Analysis
Code Description 18/A01 EPA 600/M4-82-020: Interim Method for the Determination of Asbestos in Bulk Insulation Samples
18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials
| Appendix | II | ||
| Laboratory | Reports | and | |
| Chain | of | Custody | Records |
EMSL Analytical, Inc.
2700 West Cypress Creek Rd, Suite B-111, Fort Lauderdale, FL 33309
Phone/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com pompanobeachlab@emsl.com
561504224 CustomerID: AQE63 CustomerPO:
ProjectID:
EMSL Order:
Attn: Paul LeBlanc
AirQuest Environmental, Inc.
6851 Southwest 45th Street
Fort Lauderdale, FL 33314
Received: 10/21/15 10:15 AM
JBLM WA - Bldg. 2162
Fax: (954) 792-2221 Phone: (954) 792-4549
Project:
10/21/2015Analysis Date:
10/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
2162-01
561504224-0001
Glazing Brown/White None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-02
561504224-0002
Glazing Brown/Gray/White None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-03
561504224-0003
Glazing White None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-04
561504224-0004
Caulk Brown/Gray/White Non-Fibrous Homogeneous
Chrysotile8%Non-fibrous (other)92%
2162-05
561504224-0005
Caulk Stop Positive (Not Analyzed)
2162-06
561504224-0006
Caulk Gray/White Non-Fibrous Homogeneous
Chrysotile2%Non-fibrous (other)98%
2162-07
561504224-0007
Caulk Stop Positive (Not Analyzed)
2162-08
561504224-0008
Caulk White None Detected
Non-Fibrous Homogeneous
Cellulose3% Non-fibrous (other)97%
2162-09
561504224-0009
Caulk White None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
1Test Report PLM-7.28.9 Printed: 10/21/2015 5:28:25 PM
Amrita Paul, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Fort Lauderdale, FL
Initial report from 10/21/2015 17:28:25
Anne Paul (7) Divya Bhagwandin (16) http://www.EMSL.com mailto:pompanobeachlab@emsl.com
Phone/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com pompanobeachlab@emsl.com
561504224 CustomerID: AQE63 CustomerPO:
ProjectID:
EMSL Order:
Attn: Paul LeBlanc
AirQuest Environmental, Inc.
6851 Southwest 45th Street
Fort Lauderdale, FL 33314
Received: 10/21/15 10:15 AM
JBLM WA - Bldg. 2162
Fax: (954) 792-2221 Phone: (954) 792-4549
Project:
10/21/2015Analysis Date:
10/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
2162-10
561504224-0010
Mortar Gray None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-11
561504224-0011
Mortar Gray None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-12
561504224-0012
Mortar Gray None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-13
561504224-0013
Cementicious Patch
Gray None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-14
561504224-0014
Cementicious Patch
Gray None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-15
561504224-0015
Plumbers Putty White Fibrous Homogeneous
Chrysotile6%Cellulose5% Wollastonite3%
Non-fibrous (other)86%
2162-16
561504224-0016
Plumbers Putty Stop Positive (Not Analyzed)
2162-17
561504224-0017
Rope Packing White None Detected
Fibrous Homogeneous
Glass90% Non-fibrous (other)10%
2Test Report PLM-7.28.9 Printed: 10/21/2015 5:28:25 PM
Amrita Paul, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Fort Lauderdale, FL
Initial report from 10/21/2015 17:28:25
Anne Paul (7) Divya Bhagwandin (16)
Phone/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com pompanobeachlab@emsl.com
561504224 CustomerID: AQE63 CustomerPO:
ProjectID:
EMSL Order:
Attn: Paul LeBlanc
AirQuest Environmental, Inc.
6851 Southwest 45th Street
Fort Lauderdale, FL 33314
Received: 10/21/15 10:15 AM
JBLM WA - Bldg. 2162
Fax: (954) 792-2221 Phone: (954) 792-4549
Project:
10/21/2015Analysis Date:
10/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
2162-18
561504224-0018
Caulk Brown/Green None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-19
561504224-0019
Caulk Brown/Gray None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-20
561504224-0020
Caulk Blue None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-21
561504224-0021
Caulk Blue None Detected
Non-Fibrous Homogeneous
Non-fibrous (other)100%
2162-22
561504224-0022
Paper Wrap White/Silver None Detected
Fibrous Homogeneous
Glass10% Cellulose3%
Non-fibrous (other)87%
2162-23
561504224-0023
Paper Wrap White/Silver None Detected
Fibrous Homogeneous
Glass10% Cellulose3%
Non-fibrous (other)87%
2162-24
561504224-0024
Paper Wrap Brown/Gray/White None Detected
Fibrous Homogeneous
Cellulose20% Glass5%
Non-fibrous (other)75%
2162-25
561504224-0025
Packing White Fibrous Homogeneous
Chrysotile40%Cellulose30% Non-fibrous (other)30%
3Test Report PLM-7.28.9 Printed: 10/21/2015 5:28:25 PM
Amrita Paul, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Fort Lauderdale, FL
Initial report from 10/21/2015 17:28:25
Anne Paul (7) Divya Bhagwandin (16)
Phone/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com pompanobeachlab@emsl.com
561504224 CustomerID: AQE63 CustomerPO:
ProjectID:
EMSL Order:
Attn: Paul LeBlanc
AirQuest Environmental, Inc.
6851 Southwest 45th Street
Fort Lauderdale, FL 33314
Received: 10/21/15 10:15 AM
JBLM WA - Bldg. 2162
Fax: (954) 792-2221 Phone: (954) 792-4549
Project:
10/21/2015Analysis Date:
10/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
2162-26
561504224-0026
Packing Stop Positive (Not Analyzed)
2162-27
561504224-0027
Drywall Panels Gray Fibrous Homogeneous
Chrysotile35%Non-fibrous (other)65%
2162-28
561504224-0028
Drywall Panels Stop Positive (Not Analyzed)
2162-29
561504224-0029
Drywall Panels Stop Positive (Not Analyzed)
4THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 10/21/2015 5:28:25 PM
Amrita Paul, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Fort Lauderdale, FL
Initial report from 10/21/2015 17:28:25
Anne Paul (7) Divya Bhagwandin (16)
O r d e r I D
P a g e f d e r I D
P a g e d e r I D
P a g e
Attn:
Address: 6851 SW 45th St Order #: 148571 Fort Lauderdale, FL 33314
Project: JBLM WA Bldg 2162
AirQuest Environmental, Inc. (4739)Customer:
9931Number: PO Number:
Received 10/28/15
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
10/29/15
Location:
Analyzed
10/29/15Reported
Analysis Report
Cust. IDSample ID Location
PLM Analysis
Collected Asbestos Fibers Other Materials
EPA 600/R-93/116 & 600/M4-82-020Method:
E Int Door10/19/15 2162-08148571-001
White, Soft CaulkLayer 1: None Detected CELLULOSE FIBER2%
NON FIBROUS MATERIAL98%
N Area Ceil Abv Boiler 210/19/15 2162-28148571-002
White, Fibrous/Powdery PanelLayer 1: NON FIBROUS MATERIAL30%CHRYSOTILE70%
Microscopy Supervisor Reviewed By:
Analyst: Wilson, John
148571-10/29/15 11:38 AM
Hind Eldanaf
Total layers analyzed on order: 2
Method reporting limit is 1%. PLM analysis is based on Visual Estimation and NESHAP recommends that any asbestos content less than 10 percent be verified by PLM Point Count or TEM Analysis. This report must not be reproduced except in full with the approval of the laboratory. The test results reported relate only to the samples submitted.
| Appendix | III | |
| Sample | Location | Diagram |
Drywall
Panel
Building # 2162 Joint Base Lewis-McChord
Washington
ASBESTOS SURVEY
Sample Location Diagram
Prepared For:
Mr. Thomas W. VanAlstyne, Jr.
Chief, Project Management Branch B, ESD Public Works
Building 02012, Room 223 Joint Base Lewis-McChord, WA 98433
LEGEND
Non-Asbestos Containing Material Sample Locations
Asbestos Containing Material Sample Locations
NORTH
DATE:
November 2015
PROJECT #: 9931
2 1 3
13 &14
06 07
08 & QAQC 08
16 18 &19
20 & 21
27,28, 29 & QAQC 28
Drywall
Panel
Appendix IV Photographs
Joint Base Lewis McChord, Washington Building 2162 AQ Project #9931 November 2015
Exterior of Building 2162 HA-1 Exterior Window Glazing
HA-1 Exterior Window Glazing HA-1 Exterior Window Glazing
HA-2 Exterior Window Caulk HA-2 Exterior Window Caulk
HA-3 Exterior Door Caulk HA-3 Exterior Door Caulk
HA-4 Interior Door Caulk HA-4 Interior Door Caulk
HA-5 Exterior Mortar at Brick
HA-5 Exterior Mortar at Brick
HA-5 Exterior Mortar at Brick HA-6 Exterior Cementitious Patch at Exhaust Pipe
HA-6 Exterior Cementitious Patch at Exhaust Pipe
HA-7 White Plumbers Putty
HA-7 White Plumbers Putty HA-8 White Rope Packing (Gasket) at Boiler #1
HA-9 Green Caulk at South Upper Fire Box Access Door
HA-9 Green Caulk at South Upper Fire Box Access Door
HA-10 Blue Caulk at Seam of Metal Jacket HA-10 Blue Caulk at Seam of Metal Jacket
HA-11 White Paper Wrap With Fiberglass Insulation
HA-11 White Paper Wrap With Fiberglass Insulation
HA-11 White Paper Wrap With Fiberglass Insulation
HA-12 Packing (Gasket) at Boiler Exhaust Vent System
HA-12 Packing (Gasket) at Boiler Exhaust Vent System
HA-13 Drywall Panels on Ceiling (Heat Resistant Panel)
HA-13 Drywall Panels on Ceiling (Heat Resistant Panel)
HA-13 Drywall Panels on Ceiling (Heat Resistant Panel)
| Appendix | V | |
| Photographs | of | ACM |
Exterior of Building 2162
HA-2 Exterior Window Caulk
ASBESTOS CONTAINING MATERIAL
HA-3 Exterior Door Caulk
HA-3 Exterior Door Caulk
HA-12 Packing (Gasket) at Boiler Exhaust Vent System
HA-13 Drywall Panels on Ceiling (Heat Resistant Panel)