Attachment 4 Lighting System Protection System As Builts 2019.pdf

PDF 2 MB Posted

Attached to
J061--GENERATORS/ELECTRICAL | Electrical Breaker Testing (VA-23-00005524) Federal contract opportunity
Solicitation number
36C24423Q0532
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This is a combined synopsis/solicitation from the Department of Veterans Affairs seeking quotes for electrical breaker testing services at the Philadelphia VAMC. The solicitation number is 36C24423Q0532 and quotes are due by April 19, 2023 at 10:00 AM EST. The period of performance is estimated to be from May 1, 2023 to April 30, 2024. This is a total SDVOSB set-aside with a NAICS code of 334515 and business size standard of 750 employees. The statement of work provides details on the required electrical breaker testing services. Offerors must be registered in SAM to receive an award. Questions may be directed to the point of contact, Loretta Payne, by email until May 14, 2023 at 10:00 AM EST.

View the file

Other files for this federal contract opportunity

Other files attached to J061--GENERATORS/ELECTRICAL | Electrical Breaker Testing (VA-23-00005524), newest first.
File Type Posted
36C24423Q0532.pdf PDF
Attachment 1 Electrical Equipment Inventory.pdf PDF
Attachment 6 SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER (1).pdf PDF
36C24423Q0532 .pdf PDF
WD 2015-4233 Rev. 25 dated 27 Dec 2022.pdf PDF
Attachment 3 EPSS ATS INVENTORY.pdf PDF
Attachment 5 Air Permit.pdf PDF
Attachment 2 VHA Directive 1028.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

BY:

WLRC No.:

DRAWN:

REVISED:

AS BUILT:

SCALE:

COVER SHEET

SS

15230

08/16/2018

LIGHTNING

PROTECTION

SYSTEM

LIGHTNING PROTECTION SYSTEM PROJECT

BUILDINGS 1, 2 & 21 / PHILADELPHIA VA MEDICAL CENTER

3900 Woodland Ave / Philadelphia, PA 19103

CONTRACT #VA244-18-C-0165

GENERAL CONTRACTOR:

Home Maintenance Group PO Box 1276 Chadds Ford, PA 19317

LIGHTNING PROTECTION CONTRACTOR:

Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ

1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND 96A (2016).

2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED

METAL SURFACES; IN ACCORDANCE WITH NFPA 780 4.2, UL 96A 7, AND LPI 175 35-40.

3. SOME METAL PARTS OF THE STRUCTURE THAT HAVE A METAL THICKNESS OF 3

16" OR GREATER WILL BE USED AS STRIKE

TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.

SOME HANDRAILS THAT HAVE A METAL THICKNESS OF 1

8" (SCH. 40) OR GREATER WILL BE USED AS STRIKE TERMINATION

DEVICES IN ACCORDANCE WITH UL 96A 8.8.1.

SOME HANDRAILS THAT HAVE A METAL THICKNESS OF 0.064" OR GREATER WILL BE USED AS CONDUCTORS IN

ACCORDANCE WITH NFPA 780 4.9.3.2, UL 96A 9.1.2, AND LPI 175 110.

4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE WILL BE USED ON MEMBRANE ROOF AREAS TO SECURE THE CABLES AND BASES IN POSITION. NO MECHANICAL

FASTENERS WILL BE DRIVEN INTO MEMBRANE ROOFING.

5. CABLE FASTENERS WILL BE SPACED NO MORE THAN 3' O.C.

6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN

LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3, UL 96A 12.13--14, AND LPI 175 43.

7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).

8. EACH DOWN CONDUCTOR LOCATED IN A RUNWAY, DRIVEWAY, SCHOOL PLAYGROUND, CATTLE YARD, PUBLIC WALK OR

SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780

4.9.11, UL 96A 9.3.3, AND LPI 175 116.

9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI 148.

10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, AND LPI 175 151.

11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL

REMAIN IN INTACT, FUNCTIONAL AND ACCESSIBLE CONDITION.

12. INSTALLERS SHALL AT ALL TIMES UTILIZE PPE, INCLUDING HARD HAD, ANSI Z87 PROTECTIVE EYEWARE, ASTM

F24-12-2413 PROTECTIVE FOOTWEAR, AND WORK GLOVES.

GENERAL NOTES:

LOCATION MAP

02/01/2019

PROJECT DESIGNER

Scott Sweeney Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ / 08107 P: 856-854-7000 F: 856-854-1803

CONSULTING ENGINEER

Roland Batchelder Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ / 08107

PROJECT EXECUTIVE

Steven Humuniuk Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ / 08107

01 FEBRUARY 2019 / AS-BUILT

AS-BUILT DRAWING INDEX

1. COVER SHEET

2. LP-101-OAB -------------------------- OVERALL LIGHTNING PROTECTION SYSTEM PLAN

3. LP-101-AB ---------------------------- SW FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN

4. LP-102-AB ---------------------------- NW FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN

5. LP-103-AB ---------------------------- SE FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN

6. LP-104-AB ---------------------------- NE FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN

09/04/2018

Ph ila de lp hi a

VA

M ed ic al Ce nt er

W oo dl an d Av e, P la a, A

Co ra ct

C2

C0

Li gh tn in g Pr ot ec tio n fo r B ld gs

, 2

1.

PO

B ox

6;

C ha dd s

Fo rd

, P

02/01/201902/01/2019

LEGEND

AIR TERMINAL BONDED TO CONDUCTOR

AIR TERMINAL BONDED TO METAL

CABLE, CLASS I AND CLASS II

BOND

DOWN LEAD CONDUCTOR FROM ROOF TO GRADE AND

BONDED TO GROUND ROD ELECTRODE

BONDED TO GROUND PLATE ELECTRODE

ANTENNA

CAMERA

SATELLITE DISH

LADDER

LIGHT

CELLULAR ANTENNA

DOWN LEAD CONDUCTOR FROM HIGHER ROOF DOWN

TO LOWER ROOF

RAILING

THROUGH ROOF PENETRATION

DRAIN

GENERAL NOTES

1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION

ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND

2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED

TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.

4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE

6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN

LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,

7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).

SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780

9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI

10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL

MATERIALS (IN ACCORDANCE WITH UL 96)

CLASS I (≤ 75' IN HEIGHT)

COPPER:

AIR TERMINALS: 3/8" X 12" SOLID COPPER SCREWED ONTO SOLID BRONZE BASES WITH SCREW-PRESSURE CABLE

CONNECTORS. NOTE: AIR TERMINAL SHALL EXTEND NOT LESS THAN 10" ABOVE THE OBJECT IT PROTECTS.

CABLE: 29 STRAND, 17 GAUGE SOLID COPPER WEIGHING 192 POUNDS PER 1000'. EXCEEDS CLASS I REQUIREMENTS

ALUMINUM:

AIR TERMINALS: 1/2" X 12" SOLID ALUMINUM SCREWED ONTO SOLID ALUMINUM BASES WITH SCREW-PRESSURE CABLE

CABLE: 24 STRANDS, 14 GAUGE SOLID ALUMINUM WEIGHING 102 POUNDS PER 1000.'

GROUNDING

GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

OF GROUND RODS BELOW GRADE USING SOLID BRONZE CLAMPS WITH 2 STAINLESS STEEL BOLTS.

CLASS II (> 75' IN HEIGHT)

AIR TERMINALS: 1/2" X 12" SOLID COPPER SCREWED ONTO SOLID BRONZE BASES WITH SCREW-PRESSURE CABLE

CABLE: 28 STRAND, 0.066 GAUGE SOLID COPPER WEIGHING 385 POUNDS PER 1000'.

AIR TERMINALS: 5/8" X 12" SOLID ALUMINUM SCREWED ONTO SOLID ALUMINUM BASES WITH SCREW-PRESSURE CABLE

CABLE: 37 STRANDS, 13 GAUGE SOLID ALUMINUM WEIGHING 200 POUNDS PER 1000.'

GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

LP-101-OAB

0 16'

LOWER ROOF AREA IN

ZONE OF PROTECTION

PROJECT DESIGNERCONSULTING ENGINEERPROJECT EXECUTIVE

4TH FLOOR ROOF

REMOVE EXISTING

LPS AT RTU

1/16" = 1'

RF

BOND TO WATER PIPE

(IN BASEMENT)

BOND TO GAS PIPE

BOND TO

ELECTRIC

GROUND

INSTALLED IN SOIL BETWEEN

SIDEWALK AND CURB

(NEXT TO FIRE PIPE)

02/01/18 02/01/1802/01/18

D

E

F

G H

J

L

M N

Q

R

S

T

U

V

X

Y

4TH FLOOR ROOF

INSTALLED IN SOIL

BETWEEN SIDEWALK

AND CURB (NEXT

TO FIRE PIPE)

MATCH LINE SEE LP-103-AB MATCH LINE SEE LP-104-AB

MATCH LINE SEE LP-102-AB

GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

LP-101-AB

0 8'

LP-101-AB LP-102-AB

LP-103-AB LP-104-AB

1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION

ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND

2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED

TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.

4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE

6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN

LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,

7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).

SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780

9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI

10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL

02/01/2019 02/01/2019

1/8" = 1'

E

F

G H

BONDED TO GROUND ELECTRODE

REMOVE EXISTING

LPS AT RTU

MATCH LINE SEE LP-103-AB MATCH LINE SEE LP-104-AB

MATCH LINE SEE LP-101-AB

GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

LP-102-AB

1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION

ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND

2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED

TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.

4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE

6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN

LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,

7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).

SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780

9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI

10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL

L

M N

Q

1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND 96A (2016) .

2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR

EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED METAL SURFACES; IN ACCORDANCE WITH NFPA 780 4.2, UL 96A 7, AND

LPI 175 35-40.

16" OR GREATER WILL BE USED AS STRIKE TERMINATION DEVICES AND

CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.

8" (SCH. 40) OR GREATER WILL BE USED AS STRIKE TERMINATION DEVICES IN ACCORDANCE

WITH UL 96A 8.8.1.

SOME HANDRAILS THAT HAVE A METAL THICKNESS OF 0.064" OR GREATER WILL BE USED AS CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.9.3.2, UL 96A 9.1.2, AND LPI 175 110.

4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE WILL BE USED ON MEMBRANE ROOF AREAS TO SECURE THE CABLES AND BASES IN POSITION. NO MECHANICAL FASTENERS WILL BE DRIVEN INTO MEMBRANE ROOFING.

6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN LIEU OF EXOTHERMIC

WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3, UL 96A 12.13--14, AND LPI 175 43.

7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).

8. EACH DOWN CONDUCTOR LOCATED IN A RUNWAY, DRIVEWAY, SCHOOL PLAYGROUND, CATTLE YARD, PUBLIC WALK OR SIMILAR LOCATION WILL BE

PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780 4.9.11, UL 96A 9.3.3, AND LPI 175 116.

9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI 148.

10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, AND LPI 175 151.

11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL REMAIN IN INTACT, FUNCTIONAL AND ACCESSIBLE CONDITION.

12.REPAIRS TO EXISTING LPS, INCLUDING BONDING OF UNDERGROUND METALLIC PIPING SYSTEMS AND METAL BODIES, IS NOT INCLUDED. PROJECT DESIGNERCONSULTING ENGINEERPROJECT EXECUTIVE

LP-103-AB

MATCH LINE SEE LP-104-AB

MATCH LINE SEE LP-102-ABMATCH LINE SEE LP-101-AB

Y

BOND TO

ELECTRIC

GROUND

MATCH LINE SEE LP-103-AB

MATCH LINE SEE LP-102-ABMATCH LINE SEE LP-101-AB

1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION

ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND

2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED

TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.

4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE

6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN

LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,

7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).

SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780

9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI

10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL

12.REPAIRS TO EXISTING LPS, INCLUDING BONDING OF UNDERGROUND METALLIC PIPING SYSTEMS AND METAL BODIES, IS

NOT INCLUDED.

GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP

LP-104-AB

R

S

T

File details come from the government source that posted it. Updated .