Attachment 4 Lighting System Protection System As Builts 2019.pdf
PDF 2 MB Posted
- Attached to
- J061--GENERATORS/ELECTRICAL | Electrical Breaker Testing (VA-23-00005524) Federal contract opportunity
- Solicitation number
- 36C24423Q0532
About this file
This is a combined synopsis/solicitation from the Department of Veterans Affairs seeking quotes for electrical breaker testing services at the Philadelphia VAMC. The solicitation number is 36C24423Q0532 and quotes are due by April 19, 2023 at 10:00 AM EST. The period of performance is estimated to be from May 1, 2023 to April 30, 2024. This is a total SDVOSB set-aside with a NAICS code of 334515 and business size standard of 750 employees. The statement of work provides details on the required electrical breaker testing services. Offerors must be registered in SAM to receive an award. Questions may be directed to the point of contact, Loretta Payne, by email until May 14, 2023 at 10:00 AM EST.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24423Q0532.pdf | ||
| Attachment 1 Electrical Equipment Inventory.pdf | ||
| Attachment 6 SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER (1).pdf | ||
| 36C24423Q0532 .pdf | ||
| WD 2015-4233 Rev. 25 dated 27 Dec 2022.pdf | ||
| Attachment 3 EPSS ATS INVENTORY.pdf | ||
| Attachment 5 Air Permit.pdf | ||
| Attachment 2 VHA Directive 1028.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
BY:
WLRC No.:
DRAWN:
REVISED:
AS BUILT:
SCALE:
COVER SHEET
SS
15230
08/16/2018
LIGHTNING
PROTECTION
SYSTEM
LIGHTNING PROTECTION SYSTEM PROJECT
BUILDINGS 1, 2 & 21 / PHILADELPHIA VA MEDICAL CENTER
3900 Woodland Ave / Philadelphia, PA 19103
CONTRACT #VA244-18-C-0165
GENERAL CONTRACTOR:
Home Maintenance Group PO Box 1276 Chadds Ford, PA 19317
LIGHTNING PROTECTION CONTRACTOR:
Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ
1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND 96A (2016).
2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED
METAL SURFACES; IN ACCORDANCE WITH NFPA 780 4.2, UL 96A 7, AND LPI 175 35-40.
3. SOME METAL PARTS OF THE STRUCTURE THAT HAVE A METAL THICKNESS OF 3
16" OR GREATER WILL BE USED AS STRIKE
TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.
SOME HANDRAILS THAT HAVE A METAL THICKNESS OF 1
8" (SCH. 40) OR GREATER WILL BE USED AS STRIKE TERMINATION
DEVICES IN ACCORDANCE WITH UL 96A 8.8.1.
SOME HANDRAILS THAT HAVE A METAL THICKNESS OF 0.064" OR GREATER WILL BE USED AS CONDUCTORS IN
ACCORDANCE WITH NFPA 780 4.9.3.2, UL 96A 9.1.2, AND LPI 175 110.
4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE WILL BE USED ON MEMBRANE ROOF AREAS TO SECURE THE CABLES AND BASES IN POSITION. NO MECHANICAL
FASTENERS WILL BE DRIVEN INTO MEMBRANE ROOFING.
5. CABLE FASTENERS WILL BE SPACED NO MORE THAN 3' O.C.
6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN
LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3, UL 96A 12.13--14, AND LPI 175 43.
7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).
8. EACH DOWN CONDUCTOR LOCATED IN A RUNWAY, DRIVEWAY, SCHOOL PLAYGROUND, CATTLE YARD, PUBLIC WALK OR
SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780
4.9.11, UL 96A 9.3.3, AND LPI 175 116.
9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI 148.
10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, AND LPI 175 151.
11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL
REMAIN IN INTACT, FUNCTIONAL AND ACCESSIBLE CONDITION.
12. INSTALLERS SHALL AT ALL TIMES UTILIZE PPE, INCLUDING HARD HAD, ANSI Z87 PROTECTIVE EYEWARE, ASTM
F24-12-2413 PROTECTIVE FOOTWEAR, AND WORK GLOVES.
GENERAL NOTES:
LOCATION MAP
02/01/2019
PROJECT DESIGNER
Scott Sweeney Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ / 08107 P: 856-854-7000 F: 856-854-1803
CONSULTING ENGINEER
Roland Batchelder Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ / 08107
PROJECT EXECUTIVE
Steven Humuniuk Warren Lightning Rod Company 2 Richey Ave / Collingswood, NJ / 08107
01 FEBRUARY 2019 / AS-BUILT
AS-BUILT DRAWING INDEX
1. COVER SHEET
2. LP-101-OAB -------------------------- OVERALL LIGHTNING PROTECTION SYSTEM PLAN
3. LP-101-AB ---------------------------- SW FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN
4. LP-102-AB ---------------------------- NW FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN
5. LP-103-AB ---------------------------- SE FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN
6. LP-104-AB ---------------------------- NE FULL SIZE LIGHTNING PROTECTION SYSTEM PLAN
09/04/2018
Ph ila de lp hi a
VA
M ed ic al Ce nt er
W oo dl an d Av e, P la a, A
Co ra ct
C2
C0
Li gh tn in g Pr ot ec tio n fo r B ld gs
, 2
1.
PO
B ox
6;
C ha dd s
Fo rd
, P
02/01/201902/01/2019
LEGEND
AIR TERMINAL BONDED TO CONDUCTOR
AIR TERMINAL BONDED TO METAL
CABLE, CLASS I AND CLASS II
BOND
DOWN LEAD CONDUCTOR FROM ROOF TO GRADE AND
BONDED TO GROUND ROD ELECTRODE
BONDED TO GROUND PLATE ELECTRODE
ANTENNA
CAMERA
SATELLITE DISH
LADDER
LIGHT
CELLULAR ANTENNA
DOWN LEAD CONDUCTOR FROM HIGHER ROOF DOWN
TO LOWER ROOF
RAILING
THROUGH ROOF PENETRATION
DRAIN
GENERAL NOTES
1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION
ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND
2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED
TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.
4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE
6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN
LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,
7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).
SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780
9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI
10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL
MATERIALS (IN ACCORDANCE WITH UL 96)
CLASS I (≤ 75' IN HEIGHT)
COPPER:
AIR TERMINALS: 3/8" X 12" SOLID COPPER SCREWED ONTO SOLID BRONZE BASES WITH SCREW-PRESSURE CABLE
CONNECTORS. NOTE: AIR TERMINAL SHALL EXTEND NOT LESS THAN 10" ABOVE THE OBJECT IT PROTECTS.
CABLE: 29 STRAND, 17 GAUGE SOLID COPPER WEIGHING 192 POUNDS PER 1000'. EXCEEDS CLASS I REQUIREMENTS
ALUMINUM:
AIR TERMINALS: 1/2" X 12" SOLID ALUMINUM SCREWED ONTO SOLID ALUMINUM BASES WITH SCREW-PRESSURE CABLE
CABLE: 24 STRANDS, 14 GAUGE SOLID ALUMINUM WEIGHING 102 POUNDS PER 1000.'
GROUNDING
GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
OF GROUND RODS BELOW GRADE USING SOLID BRONZE CLAMPS WITH 2 STAINLESS STEEL BOLTS.
CLASS II (> 75' IN HEIGHT)
AIR TERMINALS: 1/2" X 12" SOLID COPPER SCREWED ONTO SOLID BRONZE BASES WITH SCREW-PRESSURE CABLE
CABLE: 28 STRAND, 0.066 GAUGE SOLID COPPER WEIGHING 385 POUNDS PER 1000'.
AIR TERMINALS: 5/8" X 12" SOLID ALUMINUM SCREWED ONTO SOLID ALUMINUM BASES WITH SCREW-PRESSURE CABLE
CABLE: 37 STRANDS, 13 GAUGE SOLID ALUMINUM WEIGHING 200 POUNDS PER 1000.'
GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
LP-101-OAB
0 16'
LOWER ROOF AREA IN
ZONE OF PROTECTION
PROJECT DESIGNERCONSULTING ENGINEERPROJECT EXECUTIVE
4TH FLOOR ROOF
REMOVE EXISTING
LPS AT RTU
1/16" = 1'
RF
BOND TO WATER PIPE
(IN BASEMENT)
BOND TO GAS PIPE
BOND TO
ELECTRIC
GROUND
INSTALLED IN SOIL BETWEEN
SIDEWALK AND CURB
(NEXT TO FIRE PIPE)
02/01/18 02/01/1802/01/18
D
E
F
G H
J
L
M N
Q
R
S
T
U
V
X
Y
4TH FLOOR ROOF
INSTALLED IN SOIL
BETWEEN SIDEWALK
AND CURB (NEXT
TO FIRE PIPE)
MATCH LINE SEE LP-103-AB MATCH LINE SEE LP-104-AB
MATCH LINE SEE LP-102-AB
GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
LP-101-AB
0 8'
LP-101-AB LP-102-AB
LP-103-AB LP-104-AB
1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION
ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND
2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED
TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.
4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE
6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN
LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,
7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).
SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780
9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI
10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL
02/01/2019 02/01/2019
1/8" = 1'
E
F
G H
BONDED TO GROUND ELECTRODE
REMOVE EXISTING
LPS AT RTU
MATCH LINE SEE LP-103-AB MATCH LINE SEE LP-104-AB
MATCH LINE SEE LP-101-AB
GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
LP-102-AB
1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION
ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND
2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED
TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.
4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE
6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN
LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,
7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).
SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780
9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI
10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL
L
M N
Q
1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND 96A (2016) .
2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR
EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED METAL SURFACES; IN ACCORDANCE WITH NFPA 780 4.2, UL 96A 7, AND
LPI 175 35-40.
16" OR GREATER WILL BE USED AS STRIKE TERMINATION DEVICES AND
CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.
8" (SCH. 40) OR GREATER WILL BE USED AS STRIKE TERMINATION DEVICES IN ACCORDANCE
WITH UL 96A 8.8.1.
SOME HANDRAILS THAT HAVE A METAL THICKNESS OF 0.064" OR GREATER WILL BE USED AS CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.9.3.2, UL 96A 9.1.2, AND LPI 175 110.
4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE WILL BE USED ON MEMBRANE ROOF AREAS TO SECURE THE CABLES AND BASES IN POSITION. NO MECHANICAL FASTENERS WILL BE DRIVEN INTO MEMBRANE ROOFING.
6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN LIEU OF EXOTHERMIC
WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3, UL 96A 12.13--14, AND LPI 175 43.
7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).
8. EACH DOWN CONDUCTOR LOCATED IN A RUNWAY, DRIVEWAY, SCHOOL PLAYGROUND, CATTLE YARD, PUBLIC WALK OR SIMILAR LOCATION WILL BE
PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780 4.9.11, UL 96A 9.3.3, AND LPI 175 116.
9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI 148.
10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, AND LPI 175 151.
11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL REMAIN IN INTACT, FUNCTIONAL AND ACCESSIBLE CONDITION.
12.REPAIRS TO EXISTING LPS, INCLUDING BONDING OF UNDERGROUND METALLIC PIPING SYSTEMS AND METAL BODIES, IS NOT INCLUDED. PROJECT DESIGNERCONSULTING ENGINEERPROJECT EXECUTIVE
LP-103-AB
MATCH LINE SEE LP-104-AB
MATCH LINE SEE LP-102-ABMATCH LINE SEE LP-101-AB
Y
BOND TO
ELECTRIC
GROUND
MATCH LINE SEE LP-103-AB
MATCH LINE SEE LP-102-ABMATCH LINE SEE LP-101-AB
1. ALL MATERIALS AND INSTALLATION WILL CONFORM TO THE CODE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION
ASSOCIATION 780 (2017), LIGHTNING PROTECTION INSTITUTE 175 (2014) AND UNDERWRITERS LABORATORIES 96 AND
2. COPPER MATERIALS WILL BE USED FOR CONTACT WITH COPPER SURFACES, THE EARTH, ALKALINE-BASE PAINT, CONCRETE OR MASONRY, OR EXCESSIVE MOISTURE SUCH AS FLAT ROOFS; LEAD OR TIN COATED COPPER WILL BE USED WITHIN 2 FEET OF THE TOP OF A CHIMNEY; AND ALUMINUM MATERIALS WILL BE USED ON ALUMINUM, GALVANIZED STEEL, OR PAINTED
TERMINATION DEVICES AND CONDUCTORS IN ACCORDANCE WITH NFPA 780 4.6.1.4, UL 96A 8.8.2, AND LPI 175 65.
4. CHEMLINK M-1, OR DURALINK ADHESIVE WILL BE USED FOR SECURING TO METAL SURFACES. AN APPROVED ADHESIVE
6. DUE TO SAFETY CONCERNS, THE WARREN LIGHTNING ROD COMPANY DOES NOT EXOTHERMICALLY WELD ABOVE GRADE. IN
LIEU OF EXOTHERMIC WELD, U.L. LISTED BOLT PRESSURE FITTINGS WILL BE USED IN ACCORDANCE WITH NFPA 780 4.12.3,
7. DOWN CONDUCTORS WILL BE ROUTED ON EXTERIOR OF EXISTING BUILDING (NOT CONCEALED INSIDE EXTERIOR WALLS).
SIMILAR LOCATION WILL BE PROTECTED FROM MECHANICAL DAMAGE OR DISPLACEMENT IN ACCORDANCE WITH NFPA 780
9. UNDERGROUND METALLIC PIPING SYSTEMS WILL BE BONDED AS REQUIRED BY NFPA 780 4.14.4, UL 96A 10.4.1, AND LPI
10.METAL BODIES WITHIN 6 FEET OF LPS CONDUCTORS WILL BE BONDED AS REQUIRED BY NFPA 780 4.16, UL 96A 11, 11.EXISTING THROUGH ROOF PENETRATIONS (CONNECTION TO DOWN LEAD CONDUCTOR OR TO STRUCTURAL STEEL) SHALL
12.REPAIRS TO EXISTING LPS, INCLUDING BONDING OF UNDERGROUND METALLIC PIPING SYSTEMS AND METAL BODIES, IS
NOT INCLUDED.
GROUND RODS: 1/2" X 9' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
GROUND RODS: 5/8" X 10' COPPERCLAD STEEL DRIVEN VERTICALLY AS POSSIBLE INTO THE EARTH. CONNECT CABLES TO TOP
LP-104-AB
R
S
T
File details come from the government source that posted it. Updated .