Cat® XQ425 Rental Generator Set
Standby 375 kW, 469 kVA Prime 340 kW, 425 kVA
U.S. EPA Tier 4 Final 50/60 Hz Switchable
1500-1800 rpm
Cat® C13 ACERT™ Diesel Engine Metric Imperial (English)
Configuration I-6, 4-Stroke-Cycle Water Cooled Diesel
Bore 130 mm 5.1 in
Stroke 157 mm 6.2 in
Displacement 12.5 L 763 in3
Aspiration Turbocharged-Aftercooled
Compression Ratio 17.0:1
Fuel System MEUIC
Governor Type ADEM™ A4
Aftercooler ATAAC
Turbocharger Single
Fuel Requires ULSD
Specification
Image shown may not reflect actual configuration
LEHE1123-06
Generator Frequency Speed rpm Voltage Standby kW (kVA) Prime kW (kVA) Phase Amp (A)
Standard
60 Hz 1800 480/277V 375 (469) 340 (425) 3-phase 511.19
60 Hz 1800 240/139V 375 (469) 340 (425) 3-phase 1110.29
60 Hz 1800 208/120V 350 (438) 320 (400) 3-phase 1022.39
50 Hz 1500 400/230V 320 (400) 290 (363) 3-phase 523.22
Optional 60 Hz 1800 600V 375 (469) 340 (425) 3-phase 408.96
60 Hz 1800 480V 320 (400) 292 (365) 3-phase 439.03
Benefits & Feature Fuel/Emissions Strategy
• Meets U.S. EPA Tier 4 Final and CARB
Certified for Non-Road Mobile applications at all 50 and 60 Hz ratings
Single-source Supplier
• Factory designed and fully prototype tested with certified torsion vibration analysis available
• ISO 9001:2000 compliant facility
Cat C13 ACERT Tier 4 Final Diesel Engine
• Uses ACERT Technology and Cat NOx
Reduction System (NRS)
• Four-stroke diesel engine combines consistent minimum weight
Cat CEM (Clean Emissions Module)
Diesel Exhaust Fluid (DEF) Tank
• 12 gallon DEF tank with on tank fill and integrated pump, level sensor and heating elements
• Electrically heated DEF lines from DEF tank to CEM
Cat EMCP 4.2 Control Panel
• Fully featured power metering, protective relaying and engine/generator control and monitoring
• Simple user friendly interface and navigation
• Automatic set-point adjustment integrated with voltage and frequency changes
Cat SR4B Series Generator
• Designed to match performance and output characteristics of Cat diesel engines
• Permanent magnet excitation
• Segregated AC/DC, low voltage accessory box provides single-point access to accessory connections
Cat Digital Voltage Regulator (Cat DVR)
• Three-phase sensing
• Adjustable volts-per-hertz regulation
• Provides precise control, excellent block loading, and constant voltage in the normal operating range
Enclosure
• Highly corrosion-resistant 12-gauge sheet steel construction
• Two-coat polyester powder-coated finish
• 7 doors and 3 access doors for ease of maintenance
• Secure and safe design with safety glass control panel viewing window with lockable access door
• Fuel fill and battery can only be reached through lockable access doors
Distribution Panel*
• Switchable via linkboard from 480/277V
3-phase to 240/139V 3-phase (can be adjusted down to 208/120V 3-phase)
Rear Customer Access
• Separate control panel and distribution panel access doors
• Hinged door over main bus connectors
• Emergency stop on panel
• Remote start/stop contacts
Reduced Environmental Impact
• EPA Tier 4 Final technology
• 110% spill containment of onboard engine fluids
• Meets 76 dB(A) at 7 m per SAE J1074
Rental Ready Features
• Anti-condensation heater 110-120 VAC
• Coolant heater 110-120 VAC
• UL Listed battery charger
• Solar powered battery maintainer
*N/A for 600V
LEHE1123-06
performance and excellent fuel economy with
Electronic engine controller
Aftertreatment module consists of Caterpillar Regeneration System (CRS), Diesel Oxidation Catalyst (DOC), Diesel Particulate Filter (DPF), and Selective Catalytic Reduction (SCR)
Single-point lift designed to lift complete package measurement procedure at 75% prime loads
• Variable speed cooling fan for reduced fuel consumption and reduced sound as part load
Factory-installed Standard Equipment Air Inlet
• Air cleaner, two-stage cyclonic/paper with dust cup and service indicator
• Turbocharger and air-to-air aftercooler
Charging System
• UL/CSA listed 120V, 20A battery charger, shock mounted and enclosed in dust-proof housing
• Charging alternator; 24V-45A, heavy-duty with integral regulator and belt guards
Control Panel
• EMCP 4.2 generator set mounted controller
• NEMA 2, IP23 dust-proof enclosure, UL508 listed
• Idle/rated and 50/60 Hz frequency switches
• Generator protection features: 32, 32RV, 46, 50/51, 27/59, 81 O/U
• Metering display: voltage, current, frequency, power factor, kW, WHM, and kVAR
• Panel illumination lights and emergency stop switch
Cooling System
• Package-mounted radiator with vertical air
• Blower fan, fan drive, fan guard, and belt guards
• 120VAC coolant heater, fuse protected, thermostatically controlled, automatically disconnected on start-up
• Coolant sight gauge, level switch, and shutdown
• 50% coolant antifreeze with corrosion inhibitor
Distribution System
• NEMA 1 steel enclosure, separate hinged, lockable door with rust-resistant pinned hinges
• Main bus connections with hinged load cover with Plexiglas window closed for operation
• Main circuit breaker 3-pole, 240/480V-1600A with
24V DC shunt trip wired to load door safety switch
• Current transformers, hard mounted
• Multiple duplex and twist-lock receptacles with individual circuit breakers
• Two-wire remote start/stop terminals and 120 VAC shore power connection for rapid starting
Enclosure
• Sound attenuating, 12-gauge sheet metal enclosure
• Modular panel construction and one-piece welded roof design with 2 degree pitch
• Interior walls and ceilings insulated with flame retardant, precision cut foam materials meeting
NFPA220
• Black stainless steel pad-lockable latches, doorkeepers on all doors and zinc die-cast hinges/grab handles
• Single-point lifting
• Painted Cat power module white with Cat rental decals Engine
• EPA Tier 4 Final certified Cat C13 ACERT
ATAAC heavy duty diesel engine
• Electronic ADEM A4 controls
CEM
• Cat CEM comes with integrated DOC, DPF, and
SCR and is located in separate compartment
DEF System
• DEF tank is equipped with integrated pump, level sensor to display the DEF level in EMCP panel, and electrically heated lines from DEF tank to CEM
• Equipped with low and critically low level alarms with a critically low shutdown
Fuel System
• 520 gal (1970 L) double wall fuel tank, UL142,
• Switch operated, electric priming pump
• Auxiliary connections for customer supplied fuel transfer system with 6-way fuel transfer valve
LEHE1123-06
discharge provides 43°C ambient capability base-frame Coolant drain line with shut off valve piped to
12 gal plastic DEF tank provides 33 hours run time @ 75% Prime
ULC, and Transport Canada certified, 29 hours run time @ 75% prime Engine mounted primary and secondary fuel filter with water separator
• Radiator mounted fuel cooler
LEHE1123-06 Page 4 of 8
Factory-installed Standard Equipment (continued) Generator
• SR4B 450 frame, three-phase, random wound, 12-lead design, permanent magnet excited,
0.750 pitch
• 240-480 volt link board built into distribution system provides either 480/277 volt or 240/139 volt*
• Coastal insulation protection
• Windings impregnated in a triple dip, thermo-setting moisture, oil and acid resisting polyester varnish; heavy coat of anti-tracking varnish for additional protection
• Cat DVR with VAR/PF control, RFI suppression, exciter diode monitor
• 120VAC anti-condensation heater
Lube System
• Pump, integral oil cooler, lube oil, filter, filler and dipstick, and oil sampling valve
• Open crankcase breather with 75% filter
• Oil drain line with internal brass ball valve routed to connection point accessible from exterior
• 500-hour oil change intervals
Mounting System
• Generator set soft mounted to the heavy-duty, fabricated steel base frame
• Skiddable steel base frame with tie-down eyes contains integral fuel tank
• Provides 110% spill containment of all engine fluids
Starting System
• Single electric starting motor, 24V
• Dual 12V (1400 CCA) maintenance free batteries with disconnect switch, battery rack, and cables
• UL listed, 120V single-phase jacket water heater with thermostat and shut-off valves
General
• Canadian Standards Authority (CSA) certified
• Factory testing of standard generator set
• Full manufacturer’s warranty
• O&M manuals
Optional Equipment Available Options
• Tandem axle trailer with electric brakes
Cat EMCP 4.4 Control Panel
• Simple user-friendly interface and navigation
• Automatic set-point adjustment integrated with voltage and frequency selection
• UL508A recognized
• Convenient service access for Cat service tools
(not included)
• Integration with the Cat DVR provides enhanced system monitoring
• Ability to view and reset diagnostics of all controls networked on primary CAN data link eliminates need for separate service tools for troubleshooting
• True RMS AC metering, 3-phase
• Multiple stored setpoint group selection via switched input eliminates need to reprogram control when switching voltages and frequencies
EMCP 4.4 Engine Operator Interface
• Controls
- Run/Auto/Stop - Emergency stop
- Speed adjust - Cycle crank
- Voltage adjust - Cool-down timer
• Digital indication for
- RPM - DC volts
- Operating hours - Oil pressure
- Coolant temperature - Oil temperature
- L-L volts, L-N volts, phase amps, Hz
- ekW, kVA, kVAR, kW-hr, %kW, PF
• Shutdowns with common indicating light for
- Low oil pressure - Overspeed
- High coolant temp - High oil temp
- Failure to start (overcrank) - Emergency stop
- Low coolant level
• Emergency stop pushbutton
• Panel illuminating lights
• Display navigation keys including two shortcut keys for engine parameters, generator parameters, control, and main menu
• Fuel level monitoring and control
EMCP 4.4 Generator Protective Relaying
• Phase over/under voltage (device 27/59)
• Over/under frequency (device 81 O/U)
• Reverse power (device 32/32RV)
• Current balance (46)
• Overcurrent (device 50/51)
• Bus phase sequence
*N/A for 600V
Technical Data Cat Generator
Frame size SR4B – 450 Pitch 0.750 No. of poles 4 Excitation Static regulated brushless PM excited Number of bearings Single bearing, close coupled Insulation Class H Temperature rise 105°C Enclosure Drip proof IP23 Overspeed capability – % of rated 125% of rated Voltage regulator 3-phase sensing with volts-per-hertz
Voltage regulation Less than ± 1/2% voltage gain (adjustable to compensate for engine speed droop and line loss)
Wave form deviation 3% Telephone Influence Factor (TIF Less than 50% Harmonic Distortion (THD) Less than 5%
Modes Of Operation
• Provides for:
- Single unit standalone mode
- Island mode paralleling and load sharing (multi-unit mode) with other EMCP4.4 product
• Single unit standalone mode
- The utility is providing power for the plant loads
- The PM generator breaker is open
- The PM is in automatic standby mode to respond to a utility failure
• Multi-unit mode
- Features auto synchronization (voltage and phase matching), load sharing (kW) analog signal (like units only), and load sharing (kVAR) analog signal (like units only)
- The customer protective relaying senses a utility abnormal condition
- A run request is sent to the PM generator plant
- The first PM generator to reach rated to voltage and frequency is closed to the bus and remaining units are paralleled to the bus as they reach rated voltage and frequency
- Plant load is transferred to the power modules, which share load equally via load share lines
Optional Equipment (continued)
LEHE1123-06
Weights and Dimensions
Model Length mm (in)
Width mm (in)
Height mm (in)
Weight with Lube Oil & Coolant kg (lbs)
Weight with Fuel, Lube Oil, & Coolant kg (lbs)
XQ425
without trailer
(208.7) (60)
(104)
(14,700)
(18,900)
XQ425
with trailer
(283.7)
(102)
(126.1)
(17,930)
10 036 (22,130)
LEHE1123-06
Technical Data (continued) Cat Generator Set
Units 50 Hz 60 Hz
Standby Prime Standby Prime
Performance Specification EM0677 EM0678 EM0675 EM0676 Power Rating kW (kVA) 320 (400) 290 (360) 375 (468) 340 (425)
Lubricating System
Total oil pan capacity L (gal) 37 (9.8) Fuel System
Fuel Consumption – 100% Load 75% Load 50% Load
Fuel Tank Capacity Running Time @ 75% rating
L/hr (gal/hr) L/hr (gal/hr) L/hr (gal/hr)
L (gal) Hr
82.1 (21.6)
62.4 (16.4)
43.9 (11.5) 1970 (520)
75.3 (19.8)
57.3 (15.1)
40.2 (10.6) 1970 (520)
95.7 (25.1)
73.4 (19.2)
52.3 (13.6) 1970 (520)
88.0 (23.1)
67.9 (17.7)
48.6 (12.7) 1970 (520)
DEF System
DEF Tank Capacity DEF Consumption – 100% Load
75% Load Running Time @ 75% rating
L (gal) L/hr (gal/hr) L/hr (gal/hr)
Hr
48 (12)
48 (12)
48 (12)
2.5 (0.7)
1.8 (0.5)
48 (12)
2.4 (0.6)
1.5 (0.4)
Cooling System
Ambient capability Engine & radiator coolant capacity
°C (°F)
L (gal)
61 (16.2)
Air Requirements
Combustion air flow m3/min (cfm) 19.7 (693.2) 18.3 (646.1) (828.3) (803.3) Exhaust System
Exhaust flow at rated (dry exhaust Exhaust temperature at rated kW m3/min (cfm) °C (°F)
13.8 (485.1)
496.4 (924.7)
13.1 (460.3)
488.9 (911.8)
16.0 (565.7)
473.4 (880)
15.9 (558.9)
454.1 (846.9)
Noise rating @ 7 meters and 75% load
25⁰C, Sea Level 43⁰C, 500m dB(A) dB(A)
Emissions (not to exceed data)
NOx
CO
HC
PM
g/hp-hr g/hp-hr g/hp-hr g/hp-hr
1.42 0.08 0.01 0.02
1.28 0.07 0.01 0.02
1.55 0.08 0.02 0.01
1.56 0.07 0.02 0.02
Standard Features
• NEMA 2, IP23 dust-proof enclosure with hinged lockable door and viewing window
• EMCP 4.2 display
• Panel light on/off switch
• Emergency stop pushbutton
• Lamp test/reset pushbutton
• Voltage adjust potentiometer
• Alarm and shutdown indicators
• Idle/rated switch
• Regeneration alarm indications for DPF 80% soot level and high exhaust temperature
• 50/60 Hz frequency adjustment
• Fuel level display
• Convenient service access for Cat dealers
(service tools not included)
EMCP 4.2 Engine Operator Interface
• Controls
- Run/Auto/Stop - Emergency stop
- Speed adjust - Cycle crank
- Voltage adjust - Cool-down timer
• Engine monitoring
- RPM - DC volts
- Operating hours - Oil pressure
- Coolant temperature - Oil temperature
- Crank attempt and successful start counter
• Generator monitoring
- L-L volts, L-N volts, current (phase)
- Average volts, amps, frequency
- ekW, kVA, kVAR, kW-hr
- Power factor (average, phase)
- kW-hr, kVA-hr (total)
- Excitation voltage and current (with Cat DVR)
• Shutdowns with common indicating light for
- Low oil pressure - Overspeed
- High coolant temp - High oil temp
- Failure to start (overcrank) - Emergency stop
- Low coolant level
EMCP 4.2 Generator Protective Relaying
• Generator phase sequence
• Over/under voltage (27/59)
• Over/under frequency (81 O/U)
• Reverse power (kW) (32)
• Reverse reactive power (kVAR) (32RV)
• Over current (50/51)
Distribution Panel
• Separate load and control sections
• Access using a hinged padlock-able door
• Main busbar with hinged cover door with a clear
Plexiglas window
• Customer convenience power receptacles protected by miniature circuit breaker:
1 – 240V, 50A California-style twist lock 1 – 240V, 20A twist lock 2 – 120V, 20A ground fault interrupters 2 – 120V, 15A duplex receptacles with GFI
Circuit Breaker
• Includes DC shunt trip coil activated on any monitored engine or electrical fault
• 100 KA-interrupting capacity at 480 VAC
• Undervoltage release
• 1600A fixed type, 3 poles, generator set mounted*
• 600A fixed type 3 poles, generator set mounted
(600 V only)
Link Board Assembly*
• High/low voltage output reconnection via movable link board
• Includes switch providing voltage setting input to the EMCP 4.2 for automatic set point configuration
*N/A for 600V
LEHE1123-06
www.cat.com/rentalpower ©2021 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, "Caterpillar Corporate Yellow", the "Power Edge" and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission. LEHE1123-06 (01/21)
Meets or Exceeds International Specifications:
CSA 22.0 No. 100, IEC60034-22, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-16, UL1004B, NEC,CEC, 2006/42/EEC, 2006/95/EC, 2004/108/EC, 2000/EC/14, UL142, Ulc601, IBC
CGSB43, API 546, EGSA 101P, IEEE 43, DEFRA,
UL1741, NFPA 99/110, OSHA, 97/68/EC, BS4999,
BS5000, IEC60034-5.
Fuel Rates are based on fuel oil of 35° API [16°C (60°F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29°C (85°F) and weighing 838.9 g/liter (7.001 lb/U.S. gal).
Additional ratings may be available for specific customer requirements, contact your Caterpillar representative for details. For information regarding low sulfur fuel and biodiesel capability, consult your Cat dealer.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.
Standby – Applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The generator on the generator set is peak prime rated (as defined in ISO8528 at 30°C (86°F).
Prime – Applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation on the annual hours of operation and the generator can supply 10% overload power.
Ratings Definitions and Condition www.Cat.com/rentalpower