Attachment 1 - WI Fiber Optic Shelter Specifications.pdf
PDF 51 KB Posted
- Attached to
- Fiber Optic Node Outdoor Shelter Federal contract opportunity
- Solicitation number
- FA521523Q0010
About this file
This document contains specifications for a fiber optic shelter and details for a related federal contract opportunity. The specifications call for an outdoor metal shelter measuring approximately 76.5" x 108" with a pitched roof, entry door, detachable awning, LED lighting, outlets, and insulation. The shelter should maintain positive pressure through a direct air cooling unit with high efficiency blowers, deep media filters, and variable speed fans capable of cooling up to 9kW of heat load.
The related federal contract opportunity is solicitation number FA521523Q0010 issued by the Department of the Air Force Pacific Air Forces to procure fiber optic node outdoor shelters meeting the specifications provided. The solicitation details were not included but responses are presumed to be sought.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation - FA521523Q0010 - Fiber Optic Shelters.pdf | ||
| Addendum To 52.211-1 Instructions to Offerors.pdf | ||
| Addendum to FAR 52.212-2 Evaluation Factors.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment 1
Wake Island Fiber Optic Shelter Specifications
American Products or equal metal shelter has a high strength to weight ratio for easy deployment with either fork-lift or crane.
The outdoor dimensions: 76.5”x108”
- ¼” thick galvanized steel lifting brackets on each corner
- Pitched roof that includes rubberized radiant barrier coating
- Industrial grade entry door with door closer and keyed doorknob
- Detachable awning
- Bright white interior steel ceiling panels
- 1/2" PVC white rigid plastic interior wall panel
- (2) 4’ LED lights and switch
- (6) 115V 20 amp outlets wired to breaker
- Industrial vinyl floor covering
- 100 amp 20 slot load center with main breaker, single phase
- R-13 insulated floor, wall, and ceilings
- Aluminum trim on interior
- S/S hardware
- 100 Amp Gen Plug Flush Mount
- Floor Cable Entrance
- 4"Ø - 8 Port Wall Cable Entrance
- 48" X 96" Interior Telco Board, White - for customer supplied material
- Schrofftech or equal Direct Air Cooling Unit - install location TBD Dual High Efficiency Blowers Applies Positive Pressure to the shelter Deep Media MERV14 Filters Ethernet enabled for remote communication SNMP Traps or From C contacts for Alarms variable speed fans - up to 1950 CFM controls shelter heat load up to 9kW
File details come from the government source that posted it. Updated .