Attachment 1 - Memphis VAMC Electrical Improvements.pdf
PDF 157 KB Posted
- Attached to
- J059--MEM Arc Flash Improvements Federal contract opportunity
- Solicitation number
- 36C24921Q0391
About this file
This combined synopsis and solicitation seeks quotes for arc flash improvements at the Memphis VA Medical Center. Required upgrades include replacing underrated electrical equipment and circuit breakers, adding new fused disconnect switches and trip units, and upgrading wiring and panels to mitigate arc flash risks. Quotes are due by September 13, 2021. The soliciting agency is the Department of Veterans Affairs Network Contracting Office, and the NAICS code is 541330. This opportunity is set aside for Service-Disabled Veteran Owned Small Businesses.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24921Q0391 0001.docx | DOCX document | |
| Continuation of 36C24921Q0391.docx | DOCX document | |
| LIMITATIONS ON SUBCONTRACTING CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION.docx | DOCX document | |
| WD 2015-4673 (REV 15) dated 07.21.2021.txt | TXT text file |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: 5/14/2021
Memphis VAMC Electrical System Improvements per 2016 Arc Flash Study Recommendations
PART 1: Under-Rated Existing Equipment to Change out:
BLDG 1 Existing Minimum Req'd
Item # OL/Loc. ID Description Type Rating Rating Device inside of: Location Comments:
1 103/F3 CB77 Siemens BDQ 15/3 Fixed TM 14kA 30kA Panel 2HEM - Siemens Type P2 - 400A MLO Rm 211 BDG Replacement: HED6, or
2 103/F3 CB78 Siemens FJ 150/3 Fixed Therm - Adj Mag 18kA 30kA Panel 2HEM 480Y/277V, 3-Ph 4W Rm 211 HED4, or HEG
3 103/F3 CB79 Siemens FJ 150/3 Fixed Therm - Adj Mag 18kA 30kA Panel 2HEM Rm 211
4 103/F3 CB331 Siemens BDQ 30/3 Fixed TM 14kA 30kA Panel 2HEM Rm 211 FJ Replacement: FD6-A
5 103/F3 CB332 Siemens BDQ 20/3 Fixed TM 14kA 30kA Panel 2HEM Rm 211
6 103/F3 CB333 Siemens BDQ 40/3 Fixed TM 14kA 30kA Panel 2HEM Rm 211
7 103/F3 CB334 Siemens BDQ 30/3 Fixed TM 14kA 30kA Panel 2HEM Rm 211
8 103/F3 CB341 Siemens BDQ 40/3 Fixed TM 14kA 30kA Panel 2HEM Rm 211
18 102/F7 CB43 Square-D LA36400 Fixed-Therm - Adj Mag 30kA 65kA Panel CDH AWG15
20 107/F2 CB389 Square-D EDB34100 Fixed TM 18kA 30kA Panel GRH AW 101 EDB Replacement: EGB
21 107/F2 CB393 Square-D EDB34090 Fixed TM 18kA 30kA Panel GRH AW 101
22 107/F2 CB396 Square-D EDB34125 Fixed TM 18kA 30kA Panel GRH AW 101
23 107/F2 CB329 Square-D EDB34020 Fixed TM 18kA 30kA Panel GRH AW 101
24 107/F2 CB348 Square-D EDB34020 Fixed TM 18kA 30kA Panel GRH AW 101
25 107/F2 CB354 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
26 107/F2 CB362 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
27 107/F2 CB364 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
28 107/F2 CB367 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
29 107/F2 CB368 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
30 107/F2 CB369 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
31 107/F2 CB372 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
32 107/F2 CB376 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
33 107/F2 CB377 Square-D EDB14020 Fixed TM 18kA 30kA Panel GRH AW 101
37 102/C5 CB MD-4 GE #TED134125 125/3 Fixed TM 18kA 35kA Panel MDC AWG 15 Replacement: FD3150, 35kA
Item 37 also includes (3): GE Type TEY 100/3 Fixed TM 14kA 35kA Panel MDC AWG 15 TEYH3100B (35kA)
TEYH3125B (35kA)
38 107/F5 CB HA-Main Siemens Type FJ 150/3 Fixed Therm - Adj Mag 18Ka 30kA Panel HA Main CB ?? (Near BW 120)
39 107/F5 CB HA-1 Siemens Type BQD 90/3 Fixed TM 14kA 30kA Panel HA Branch CB " Panel HA:
40 107/F5 CB HA-2 Siemens Type BQD 50/3 Fixed TM 14kA 30kA Panel HA Branch CB " (Only 4 Branch Bkrs + MCB.
41 107/F5 CB HA-7 Siemens Type BQD 50/1 Fixed TM 14kA 30kA Panel HA Branch CB " More Feasible to change out
42 107/F5 CB HA-8 Siemens Type BQD 30/1 Fixed TM 14kA 30kA Panel HA Branch CB " Panel??)
BLDG 1A Existing Minimum Req'd
ID Description Type Rating Rating Device inside of: Location
46 114/C5 CB173 C-H #FDB3150 150/3 Fixed TM 14kA 25kA Separate Breaker Enclosure in Generator Rm GB1103
Replacement:
50 109/D9 CB58 Siemens Type ED6 30/3 ? Fixed TM 25kA 65kA MCC-G-N1 Chiller Tower Main Rm HHED6
51 109/D13 CB63 Siemens Type ED6 50/3 ? Fixed TM 25kA 65kA MCC-G-N1 Chiller Tower Main Rm HHED6
52 109/D13 CB64 Siemens Type ED6 50/3 ? Fixed TM 25kA 65kA MCC-G-N1 Chiller Tower Main Rm HHED6
Date: 5/14/2021
Memphis VAMC Electrical System Improvements per 2016 Arc Flash Study Recommendations
PART 2: Change-Outs & Additions for Incident Energy Mitigation:
BLDG 1
Item # OL/Loc. Equip / Location Existing Equipment to Replace: Trip Type Replace with:
67 101/D13 Panel DPH: CB269 C-H #FD3175 175/3 35kA Fixed TM C-H Type FDE 160/3
(Rm. BEG 21) (feeds Xfmr T-DPL) SS Trip Unit w/160A Rating Plug
(For Mitigation at Panel DPL - TCC 39)
68 101/D14 T-LD DISC: CB279 C-H #FD3110 110/3 35kA Fixed TM C-H Type FDE 160/3
(Rm. BWG 9) (feeds Xfmr T-LD) SS Trip Unit w/100A Rating Plug
(For Mitigation at Panel LD - TCC 40)
69 106/D13 Panel 1AH: CB361 C-H #HKD3400F 400/3 65kA Adj. Mag. C-H Type HLD 400/3
(Rm. 1A) (feeds Xfmr T-1LDP) Trip Unit OPTIM 550/1050 L (I4t) w/400A Rating Plug
(For Mitigation at Panel 1LDP - TCC 53.1)
BLDG 5
Item # OL/Loc. Equip / Location Existing Equipment to Replace: Trip Type Replace with:
70 116/A6 MSB-Section 1: CB56 C-H #HFD 70/3 Fixed TM C-H Type HFDE 80/3
(Rm. 5165) SS Trip Unit w/60A Rating Plug
(For Mitigation at Panel P1)
71 116/A7 MSB-Section 1: CB58 C-H #HFD 70/3 Fixed TM C-H Type HFDE 80/3
(Rm. 5165) SS Trip Unit w/60A Rating Plug
(For Mitigation at Panel P2)
72 116/A9 MSB-Section 1: CB60 C-H #HFD 70/3 Fixed TM C-H Type HFDE 80/3
(Rm. 5165) SS Trip Unit w/60A Rating Plug
(For Mitigation at Panel P4)
73 116/A8 MSB-Section 1: CB62 C-H #HFD 70/3 Fixed TM C-H Type HFDE 80/3
(Rm. 5165) SS Trip Unit w/60A Rating Plug
(For Mitigation at Panel P3)
74 116/A11 MSB-Section 1: CB64 C-H #HFD 100/3 Fixed TM C-H Type HFDE 160/3
(Rm. 5165) SS Trip Unit w/100A Rating Plug
(For Mitigation at Main P5 DISC)
BLDG 7
Item # OL/Loc. Location Existing Equipment to Replace: Replace with:
75 118/B7 (Rm. BE132) T14 DISC 600V/200A/3W/NF/NEMA1 HD Disc. Switch 600V/200A/3W/Fused/NEMA1 HD Fused Disc. Sw.
(Non-Fused Disc Switch) Fuses: Gould Ferraz HSJ150 (Fuse903)
*Fed from MDP, CB85. Feeds Transf. T14 - Panel BEG in Rm BE132
76 118/C14 (Rm. BC143) T3 DISC 600V/200A/3W/NF/NEMA1 HD Disc. Switch 600V/200A/3W/Fused/NEMA1 HD Fused Disc. Sw.
(Non-Fused Disc Switch) Fuses: Gould Ferraz HSJ175 (Fuse904)
*Fed from MDP, CB114. Feeds Transf. T3 - Panels BCF and BCGin Rm BC143.
Item # OL/Loc. Location New Equipment to Add:
77 117/C4 (Near Rm BB136 ?) CB701 Separately Enclosed Circuit Breaker - Square-D Type LG400 w/Micrologic 6.3 A/E *This device is to be installed on the Line-Side of Transformer T4, which is fed from Main SWBD, CB5. T4 feeds Panels BBF and BBG, in room BB136.
78 117/D5 (Rm 1A100 ??... DISC & 600V/60A/3W/Fused/NEMA1 HD Fused Disconnect Switch or Near) Fuse901 Fuses: Littlefuse LLSRK60
*This device is to be installed on Line-Side of Transformer T5, which is fed from Panel 2AL. T5 feeds Panels 2AP and 2AB.
79 118/B6 (Rm. BE114) DISC & 600V/200A/3W/Fused/NEMA1 HD Fused Disconnect Switch Fuse902 Fuses: Gould Ferraz HSJ150
*This device is to be installed on Line-Side of Transformer T12, which is fed from MDP, CB67. T12 feeds Panel BEF in Rm BE114.
80 118/C15 (Chiller Room) DISC & 600V/100A/3W/Fused/NEMA1 HD Fused Disconnect Switch Fuse905 w/Fuses: Gould Ferraz HSJ100
*This device is to be installed on Line-Side of Transformer T24, which is fed from MDP, CB137. T24 feeds Panel 1DD in Chiller Rm.
*Provide required wire, conduit, connectors, mounting hardware, etc. for Replacements and Additions.
BLDG 10
Item # OL/Loc. Location New Equipment to Add:
81 116/F13 (Carpentry Shop) DISC & 600V/100A/3W/Fused/NEMA1 HD Fused Disconnect Switch
Fuse20 Fuses: Gould Ferraz HSJ70
*This device is to installed on the Line-Side of Transformer T21, which is fed from HP, CB59. T21 feeds Panel LP-1 in Carpentry Shop.
82 116/F14 (Welding Shop) DISC & 600V/100A/3W/Fused/NEMA1 HD Fused Disconnect Switch
Fuse21 Fuses: Gould Ferraz HSJ70
*This device is to installed on the Line-Side of Transformer T22, which is fed from HP, CB89. T22 feeds Panel LP-2.
83 116/F15 (Carpentry Shop) DISC & 600V/100A/3W/Fused/NEMA1 HD Fused Disconnect Switch
Fuse22 Fuses: Gould Ferraz HSJ70
*This device is to installed on the Line-Side of Transformer T23, which is fed from HP, CB90. T23 feeds Panel LP-3 in Carpentry Shop.
*Provide required wire, conduit, connectors, mounting hardware, etc. for Replacements and Additions.
From Arc Flash Study, Part II C (Other Issues):
BLDG 5
85 116/E7 Panel HLS2SE
50/3 Branch CB in Spaces 1,3,5 (Siemens BQD50/3) BQD30/3
#12 AWG Wire #10 AWG THHN to T-LS2SE
File details come from the government source that posted it. Updated .