Attach 2 - PERI HVAC Drawings Final.pdf
PDF 9 MB Posted
- Attached to
- PERI - HVAC REPLACEMENT Federal contract opportunity
- Solicitation number
- 140P6220R0005
About this file
This presolicitation notice provides information for the Pea Ridge National Military Park Visitor Center HVAC Replacement project. The work includes installing spray foam insulation, replacing the air-cooled chiller, buffer tank, propane boilers, controls, and adding a ductless split system and humidifiers. The contract type is firm-fixed price for $250,000 to $500,000, set aside for HUBZone small businesses under NAICS 238220. The period of performance is 180 days from notice to proceed by September 15, 2020. A telephonic site visit will be held on August 7 and an on-site visit must be scheduled by August 12. Questions are due by August 13. Proposals and proposal guarantees are due by September 3, with award expected in early-mid September 2020. The contractor must provide payment and performance bonds within 10 days of award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attach 1 - PERI Project Manual.pdf | ||
| Attach 3 - PERI HVAC Briefing Photos_5.6.20.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTRACTOR
PARKING
AREAS
TEMPORARY EQUIPMENT
AND MATERIALS STORAGE
AVAILABLE IN MAINTENANCE
SHOP
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
G 00
INDEX OF DRAWINGS
REPAIR/REHAB VISITOR CENTER HVAC
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732
FINAL CD SUBMITTAL
02/25/2020
07310007PERI- 0- G 00 INDEX OF DRAWINGS
ARCHITECTURAL
A 00 ARCHITECTURAL INFO SHEET
A101 ATTIC PLAN
A102 ROOF PLAN
GENERAL
G 00 INDEX OF DRAWINGS
MECHANICAL
M 00 MECHANICAL INFO SHEET
M001 DEMOLITION FLOOR PLAN - MECHANICAL
M101 FIRST FLOOR PLAN - MECHANICAL
M102 ATTIC LEVEL PLAN - MECHANICAL
M201 PIPING FLOOR PLAN - MECHANICAL
M401 DETAILS - MECHANICAL
M501 SCHEDULE - MECHANICAL
ELECTRICAL
E 00 ELECTRICAL INFO SHEET
E 01 ELECTRICAL GENERAL NOTES
E001 FIRST FLOOR PLAN - DEMOLITION
E101 FIRST FLOOR PLAN - POW. & AUX. SYS.
SCHEDULES
DRAWING INDEX
CODE ANALYSIS
2012 INTERNATIONAL BUILDING CODE W/ APPENDICES
2009 INTERNATIONAL MECHANICAL CODE
2006 INTERNATIONAL FUEL GAS CODE
2006 INTERNATIONAL PLUMBING CODE
2009 INTERNATIONAL ENERGY CONSERVATION CODE
2017 NATIONAL ELECTRICAL CODE
SCALE: NTS
PROJECT LOCATION
SCALE: NTS
CONTRACTOR PARKING AND STAGING
DATE INITIAL
A
TT
A C
H M
EN
T
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-P E
R I_ jf ie d le r.
rv t
JLF
Author
MJH
02/25/2020
07310.007
A 00
ARCHITECTURAL INFO SHEET
07310007PERI- 2- A 00 ARCHITECTURAL INFO SHEET
TRUE
NORTH
PLAN
NORTH
NORTH
NORTH
ARROW
NAME
ELEVATION
LEVEL
MATCHLINE
AREA A
AREA B
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
XXXX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
150 SF
ROOM
NUMBER
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL
NUMBER
SHEET NUMBER
INDICATES DIRECTION
OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME
DESIGNATION
ROOM NUMBER
DESIGNATION
ROOM AREA
DESIGNATION
ROOM /
FRAMING
ELEVATION
EXTERIOR
ELEVATION
XX-XX
XX-XX
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
DOOR
NUMBER
DOOR NUMBER10
WINDOW
DESIGNATION
WINDOW DESIGNATION000
TA-X
TOILET
ACCESSORY
TOILET ACCESSORY
NUMBER
WALL
TYPE
LETTER
INDICATES
PARTITION OR
WALL TYPE
X
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE
DRAWING
ABBREVIATIONSREFERENCE LEGEND
ARCHITECTURAL
SHEET LIST
GENERAL NOTES
X
PROJECT ARCHITECTURAL REFERENCED NOTES
REF. NOTES ( )
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SB SECURITY BARS
SB SPLASH BLOCK
SCH SCHEDULE
SCHED SCHEDULE
SCR SCREW
SCT STRUCTURAL CLAY TILE
SCUT SCUTTLE
SCW SOFT COLD WATER
SD STORM DRAIN
SD SUBDRAIN
SDI STEEL DECK INSTITUTE
SECT SECTION
SECY SECRETARY
SEQ SEQUENCE
SF SQUARE FOOT (FEET)
SFU STRUCTURAL FACING
UNIT
SHLD SHOULDER
SHT SHEET
SHTG SHEATHING
SHW SOFT HOT WATER
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SLBB SHORT LEG BACK TO
BACK
SM SPRINKLER MAIN
SOV SHUT OFF VALVE
SPA SPACE(ING)
SPEC SPECIFICATIONS
SPF SOUNDPROOF
SPH SPACE HEATER
SPKR SPEAKER
SPL SPECIAL
SQ SQUARE
SS SANITARY SEWER
SS STAINLESS STEEL
SSMR STANDING SEAM METAL
ROOFING
STA STATION
STAIR STAIRWAY
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STGR STRINGER
STIFF STIFFENER
STIRR STIRRUPS
STL STEEL
STN STONE
STOR STORAGE
STR STRUCTURAL
SUB FL SUB FLOOR
SUCT SUCTION
SUSP SUSPENDED
SVF SHEET VINYL FLOORING
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
T TREAD
T or TLT TOILET
TAN TANGENT
TBD TACK BOARD
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TERM TERMINAL
TGL TOGGLE
TH THRESHOLD
THK THICK
THRD THREAD
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOPO TOPOGRAPHIC
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TSTAT THERMOSTAT
TV TELEVISION
TW TEMPERED WATER
TWR TEMPERED WATER
RETURN
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UPS UNINTERRUPTIBLE
POWER SYSTEM
UR URINAL
UT UTILITY
UV UNIT VENTILATOR
V VOLT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VD VAULT DOOR
VEL VELOCITY
VENT VENTILATOR(ION)
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY
DRIVE
VOL VOLUME
VPC VERTICAL POINT OF
CURVATURE
VPI VERTICAL POINT OF
INTERSECTION
VPT VERTICAL POINT OF
TANGENCY
VS VENT STACK
VT VINYL-TILE
VTR VENT THRU ROOF
VWC VINYL WALL COVERING
W WEST
W WIDE (WIDTH)
W WIRE
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER CLOSET
WC WATER COLUMN
WD WASTE DRAIN
WD WOOD
WD BLKG WOOD BLOCKING
WD DR WOOD DOOR
WDW WINDOW
WF WIDE FLANGE
WG WIRE GLASS
WH WALL HYDRANT
WHT WHITE
WI WROUGHT IRON
WKSH WORK SHOP
WL WIND LOAD
WNSCT WAINSCOT
WP WEATHER PROOF
WP WORK POINT
WPF WATER PROOF
WPFG WATER PROOFING
WRB WARDROBE
WS WASTE STACK
WT WEIGHT
WWF WELDED WIRE FABRIC
WWM WOVEN WIRE MESH
XFMR TRANSFORMER
YD YARD or YARD DRAIN
LBS POUNDS
LD LOAD
LDG LOADING
LE LEFT END
LG LENGTH (LONG)
LIN LINEAR
LIS LAWN IRRIGATION
SYSTEM
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LP LOW POINT
LPG LIQUIFIED PETROLEUM
GAS
LPS LOW PRESSURE STEAM
LR LIVING ROOM
LS LAWN SPRINKLER
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LVT LUXURY VINYL TILE
M MIDDLE
M THOUSAND
M & B MATCHED AND BEADED
MA MAKE-UP AIR
MACH MACHINE
MAS MASONRY
MAT or
MATL
MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBH 1000 BTUH
MC MEDICINE CABINET
MC MISCELLANEOUS
CHANNELS
MECH MECHANICAL
MER MECHANICAL EQUIPMENT
ROOM
MET METAL
MFG MANUFACTURING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML METAL LATH
MLDG MOULDING
MO MASONRY OPENING
MONO MONOLITHIC
MT METAL THRESHOLD
MTD MOUNTED
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NR NOT REQUIRED
NS NEAR SIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OB WG OBSCURE WIRE GLASS
OBGL OBSCURE GLASS
OBSC OBSCURE
OC ON CENTER(S)
OCEW ON CENTER EACH WAY
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPS OPERATIONS
OS & Y OUTSIDE SCREW & YOKE
OSF OUTSIDE FACE
OV OVERFLOW VALVE
OX OXYGEN
OZ OUNCE
P PAINT
PA PUBLIC ADDRESS
PBS PUSH BUTTON STATION
PC PIECE
PC POINT OF CURVATURE
PC PRECAST
PCC PORTLAND CEMENT
CONCRETE
PCT PORCELAIN CERAMIC TILE
PD PRESSURE DROP
PE POLYETHYLENE
PEN PENETRATION
PERF PERFORATED
PH PHASE
PHAR PHARMACY
PI POINT OF INTERSECTION
PIV POST INDICATING VALVE
PL or P PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLATF PLATFORM
PLBG PLUMBING
PLG PILING
PLWD PLYWOOD
PNL PANEL
POL POLISH(ED)
PORC PORCELAIN
PPM PARTS PER MILLION
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PRESS PRESSURE
PROJ PROJECT
PRV PRESSURE REGULATING
VALVE
PS PRESSED STEEL
PSFT POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PT POINT
PT POINT OF TANGENCY
PTD PAINTED
PTN PARTITION
PVC POLYVINYL-CHLORIDE
PVMT PAVEMENT
PW PASS WINDOW
1/4 RD QUARTER ROUND
QT QUARRY TILE
QT QUART
QTRS QUARTERS
QTY QUANTITY
QTZ QUARTZ
R REGISTER
R RISER
RA RETURN AIR
RAD OR
R
RADIUS
RB RESILIENT BASE
RC REMOTE CONTROL
RCP REINFORCED CONCRETE
PIPE
RD ROOF DRAIN
RE RIGHT END
REC RECEIVER
RECP RECEPTACLE
RECR RECREATION
RECT RECTIFIER
REF REFERENCE
REFR REFRIGERANT
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCEMENT
REM REMOVE(ABLE)
REQD REQUIRED
RESIL RESILIENT
REV REVISIONS
RFG ROOFING
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RM ROOM
RND ROUND
RO ROUGH OPENING
RPM REVOLUTIONS PER
MINUTE
RT RUBBER TILE
RTU ROOF TOP UNIT
RUB RUBBER
DIAG DIAGONAL
DIM DIMENSION
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DIST DISTRIBUTION
DL DEAD LOAD
DMPR DAMPER
DN DOWN
DP DAMP PROOFING
DPT DEW POINT
DR DOOR
DRN DRAIN
DS DOWN SPOUT
DV DENTAL VACUUM
DWG DRAWING
DWLS DOWELS
DX DIRECT EXPANSION
E EAST
EA EACH
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY
RATIO
EJ EXPANSION JOINT
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
ENCL ENCLOSURE
ENT ENTERING
ENT ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EST ESTIMATE
EVAP EVAPORATOR
EW EACH WAY
EWC ELECTRIC WATER
COOLER
EXC EXCAVATE
EXD EXIT DEVICE
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPL EXPLOSION
EXPN EXPANSION
EXT EXTERIOR
F FAHRENHEIT
F FIRE
FA FRESH AIR
FCG FACING
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER
BRACKET
FEC FIRE EXTINGUISHER
CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FIX FIXTURE
FL or FLR FLOOR
FLASH FLASHING
FLEX FLEXIBLE
FLG FLANGE
FLG FLOORING
FLUOR FLUORESCENT
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPRF FIRE PROOF
FR FRAME
FRG FURRING
FS FAR SIDE
FS FLOOR SINK
FS FULL SIZE
FT FEET (FOOT)
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
G GRILLE
G NATURAL GAS
GA GAGE OR GAUGE
GAL GALLON
GALV GALVANIZED
GEN GENERAL
GFE GOVERNMENT FURNISHED
EQUIPMENT
GFE/CI GOVERNMENT FURNISHED
EQUIPMENT/CONTRACTOR
INSTALLED
GFI GROUND FAULT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GND GROUND
GOVT GOVERNMENT
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRADE
GRS GALVANIZED RIGID STEEL
CONDUIT
GRTG GRATING
GSU GLAZED STRUCTURAL
UNITS
GWB GYPSUM WALLBOARD
GWT GLAZED WALL TILE
GYP GYPSUM
H or HT HEIGHT (HIGH)
HB HOSE BIBB
HBD HARDBOARD
HC HANDICAPPED
HD HEAD
HDPE HIGH DENSITY
POLYETHYLENE
HDR HEADER
HDW HARDWARE
HIP HIGH PRESSURE
HM HOLLOW METAL
HORIZ HORIZONTAL(LY)
HP HORSE POWER
HPS HIGH PRESURE STEAM
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HSGYP HIGH STRENGTH GYPSUM
PLASTER
HTG HEATING
HTR HEATER
HW HEAD WALL
HW HOT WATER
HWH HOT WATER HEATER
HWR HOT WATER RETURN
(HEATING)
HWS HOT WATER SUPPLY
(HEATING)
HYD HYDRAULIC
I or FE IRON
IC INTERCOM
ID INSIDE DIAMETER
IE INVERT ELEVATION
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
INV INVERT OR INVERTER
IP IRON PIPE
ISF INSIDE FACE
JB JUNCTION BOX
JBOX JUNCTION BOX
JC JANITOR CLOSET
JCT JUNCTION
JST JOIST
JT JOINT
K KEY
KCP KEENE'S CEMENT
PLASTER
KIP or K KILOPOUND (1000 LBS)
KIT KITCHEN
KL KEY LOCK
KP KICK PLATE
KV KILOVOLTS
KVA KILOVOLT AMPERES
KW KILOWATT
LAB LABORATORY
LAU LAUNDRY
LAV LAVATORY
LBR LUMBER
A COMPRESSED AIR
A/C AIR CONDITIONING
AB ANCHOR BOLT
ABS ACRYLONITRILE BUTAD
STYRENE
AC ALTERNATING CURRENT
ACI AMERICAN CONCRETE
INSTITUTE
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
ACST ACOUSTIC
AD ACCESS DOOR
AD AREA DRAIN
ADMIN ADMIN ADMINISTRATION
(IVE)
AFF ABOVE FINISH FLOOR
AFFF AQUEOUS FILM FORMING
FOAM
AGG AGGREGATE
AHU AIR HANDLING UNIT
AI AREA INLET
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AL ACTIVE LEAF
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
AP ACCESS PANEL
APD AIR PRESSURE DROP
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR
ARCHITECT
ARI AMERICAN
REFRIGERATION
INSTITUTE
ASB ASBESTOS
ASPH ASPHALT
APC ACOUSTICAL PANEL
CEILING
AUTO AUTOMATIC
AV ACID VENT
AVG AVERAGE
AW ACID WASTE
AWC ACOUSTICAL WALL
COVERING
AWG AMERICAN WIRE GAUGE
L ANGLE
BATT BATT INSULATION
BB BULLETIN BOARD
BBO BOILER BLOW OFF
BC BOOKCASE
BD BOARD
BDY BOUNDARY
BEJ BRICK EXPANSION JOINT
BIT BITUMINOUS
BKR BREAKER
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BM BENCH MARK
BO BOTTOM OF
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
BUR BUILT-UP ROOFING
BW BOTH WAYS
C CENTER
C OR
CND
CONDUIT (ELECTRICAL
SHEETS)
C TO C CENTER TO CENTER
CAP CAPACITY
CB CATCH BASIN (OR CIRCUIT
BREAKER)
CC CENTER TO CENTER
CCT CIRCUIT
CD CONDENSATE DRAIN
CE COVER ELEVATION
CEM CEMENT
CF CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHIM CHIMNEY
CI CAST IRON
CI CURB INLET
CIP CAST IN PLACE
CIR CIRCULAR
CJ CONTROL JOINT
CKT CIRCUIT
CL CENTER LINE
CL WG CLEAR WIRE GLASS
CLG CEILING
CLKG CAULKING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY
UNIT
CNTR COUNTER
CO CLEAN OUT
CO2 CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINATION
COMB COMBUSTION
COMP COMPRESSIBLE
COMPR COMPRESSOR
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION
CONSTR CONSTRUCTION
CONSTR
JT
CONSTRUCTION JOINT
CONT CONTINUOUS
(CONTINUATION)
CONTR CONTRACTOR
COR CORNER
CORR COVERED
COV CORRIDOR
CPL CEMENT PLASTER
CPS CYCLES PER SECOND
(HERTZ)
CPT CARPET
CR CONDENSER WATER
RETURN
CRES CORROSIVE RESISTANT
STEEL
CRG CARRIAGE
CRSE COURSE
CS CONDENSER WATER
SUPPLY
CS COUNTER SINK
CSMT CASEMENT
CT CERAMIC TILE
CT CURRENT TRANSFORMER
CTL CARPET TILE
CU CONDENSING UNIT
CU YD CUBIC YARDS
CUH CABINET UNIT HEATER
CV CEILING VENT
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
CYL CYLINDER
D DEPTH (DEEP)
D DIFFUSER
d PENNY (as in nail - 10d)
D&M DRESSED AND MATCHED
DA DOUBLE ACTING
DB DRY BULB
dB DECIBEL
DBL DOUBLE
DC DIRECT CURRENT
DCJ DOWELED CONTROL
JOINT
DCJT DUMMY CONTROL JOINT
DCL DOOR CLOSER
DCW DOMESTIC COLD WATER
DEG DEGREE
DEMO DEMOLITION
DEPR DEPRESSION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DHW DOMESTIC HOT WATER
DI DEIONIZED WATER
DIA DIAMETER
CLO CLOSET
FR FIRE RATED
U/C UNDER CABINET
SYMBOL LEGEND
PLAN VIEW
SECTION / ELEVATION VIEW
SHEAR WALL
MASONRY-CMU
CONCRETE
GRAVEL
EARTH / COMPACTED
EARTH /
NONCOMPACTED
RIGID INSULATION
JOINT FILLER
STEEL
GYPSUM
MASONRY-VENEER
STUD WALL
FLEXIBLE INSULATION
GROUT
PLYWOOD
WOOD (FINISH)
MASONRY-CMU FACE
MASONRY-CMU
MASONRY-VENEER
A 00 ARCHITECTURAL INFO SHEET
A101 ATTIC PLAN
A102 ROOF PLAN
1 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION
TO THE BOTTOM SIDE OF THE EXPOSED ROOF DECK IN ATTIC
SPACE.
2 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION
TO THE BOTTOM SIDE OF ROOF DECK ABOVE CEILING IN
ASSEMBLY 103 ROOM BELOW.
3 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION
TO THE BOTTOM SIDE OF THE EXPOSED ROOF, DECK, AND
SOFFIT IN ATTIC SPACE.
4 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION
TO INTERIOR SIDE OF VERTICAL WALL IN ATTIC SPACE
5 JUNCTION BOXES AND ITEMS REQUIRING FUTURE ACCESS FOR
REPAIRS, MAINTENANCE, ETC TO REMAIN ACCESSIBLE AFTER
SPRAY INSULATION HAS BEEN INSTALLED. - COORDINATE W/
MECH AND ELEC
6 EXISTING RIDGE VENTS AND SOFFIT VENTS TO BE BLOCKED AND
SEALED PRIOR TO THE APPLICATION OF SPRAY FOAM
INSULATION. BLOCKING SHALL BE DARK OR BRONZE COLOR AND
OF WEATHER PROOF MATERIAL.
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND
LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER OF ANY
DISCREPANCIES OR VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO ADDITIONAL
EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF
DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL
NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF
DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE
FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO
ADDITIONAL EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS
WITH ALL OTHER TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN.
FULL-TONE LINES INDICATE NEW OR RELOCATED CONSTRUCTION.
E. DIMENSIONS ARE TYPICALLY TO FINISH FACE OF MASONRY, CONCRETE, GYPSUM
WALL BOARD, AND METAL FRAMES; OR CENTER LINE OF COLUMN OR BEAMS,
UNLESS NOTED OTHERWISE.
F. ALL ANGLES ON THE FLOOR PLANS ARE 45 OR 90 DEGREES UNLESS OTHERWISE
INDICATED.
G. PROVIDE FIRE TREATED 2x6 OR LARGER WOOD BLOCKING IN WALLS AND FURRING
SPACES AS REQUIRED FOR MOUNTING OF ALL WALL SUPPORTED ITEMS. WHETHER
OR NOT DETAILED ON THE DRAWINGS, THE CONTRACTOR SHALL COORDINATE AND
INSTALL ALL STIFFENERS, BRACING, BACK-UP PLATES, AND SUPPORTING BRACKETS
AS REQUIRED FOR THE INSTALLATION OF WALL MOUNTED OR SUSPENDED
MECHANICAL, ELECTRICAL, OR MISCELLANEOUS EQUIPMENT. THESE ITEMS
INCLUDE, BUT ARE NOT LIMITED TO, CONTROL PANELS, FIRE ALARM PANELS AND
MASTER CLOCKS, ETC.
H. PATCH EXISTING WALLS, FLOORS, AND CEILING SURFACES DEMOLISHED, CUT,
CORED, OR ALTERED IN ANY WAY TO ACCOMMODATE NEW CONSTRUCTION.
I. PATCH ALL CONCRETE SLAB LOCATIONS DEMOLISHED TO INSTALL NEW
STRUCTURAL, MECHANICAL, OR ELECTRICAL WORK.
DATE INITIAL
A
TT
A C
H M
EN
UP
UP
A
B
C
D
E
1 2 3 4 5
A101
A101
A101
A101
1 5
FIRST FLOOR
100' - 0"
ATTIC LEVEL
112' - 0"
AB
SPRAY FOAM INSUL
ON BOTTOM SIDE
OF ROOF DECK AND
INT. SIDE OF EXT
WALLS IN ATTIC
SPACE
FIRST FLOOR
100' - 0"
ATTIC LEVEL
112' - 0"
AB
FIRST FLOOR
100' - 0"
ATTIC LEVEL
112' - 0"
B
SPRAY FOAM INSUL
ON BOTTOM SIDE OF
ROOF DECK AND INT.
SIDE OF EXT WALLS
IN ATTIC SPACE
FIRST FLOOR
100' - 0"
ATTIC LEVEL
112' - 0"
B
SPRAY FOAM INSUL
ON BOTTOM SIDE OF
ROOF DECK
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-P E
R I_ jf ie d le r.
rv t
JLF
Author
MJH
02/25/2020
07310.007
A101
ATTIC PLAN
07310007PERI- 2- A101 ATTIC PLAN
1 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO THE
BOTTOM SIDE OF THE EXPOSED ROOF DECK IN ATTIC SPACE.
2 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO THE
BOTTOM SIDE OF ROOF DECK ABOVE CEILING IN ASSEMBLY 103 ROOM
BELOW.
3 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO THE
BOTTOM SIDE OF THE EXPOSED ROOF, DECK, AND SOFFIT IN ATTIC
SPACE.
4 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO
INTERIOR SIDE OF VERTICAL WALL IN ATTIC SPACE
5 JUNCTION BOXES AND ITEMS REQUIRING FUTURE ACCESS FOR REPAIRS,
MAINTENANCE, ETC TO REMAIN ACCESSIBLE AFTER SPRAY INSULATION
HAS BEEN INSTALLED. - COORDINATE W/ MECH AND ELEC
6 EXISTING RIDGE VENTS AND SOFFIT VENTS TO BE BLOCKED AND SEALED
PRIOR TO THE APPLICATION OF SPRAY FOAM INSULATION. BLOCKING
SHALL BE DARK OR BRONZE COLOR AND OF WEATHER PROOF MATERIAL.
REF. NOTES ( ):X
SCALE: 1/8" = 1'-0"
ATTIC LEVEL - AREA PLANS
NORTH
SCALE: 1/8" = 1'-0"
ATTIC SECTION 1
SCALE: 1/8" = 1'-0"
ATTIC SECTION 2
SCALE: 1/8" = 1'-0"
ATTIC SECTION 3
SCALE: 1/8" = 1'-0"
ATTIC SECTION 4
SPRAY FOAM INSUL
ON BOTTOM SIDE OF
ROOF DECK AND INT.
SIDE OF EXT WALLS
IN ATTIC SPACE
DATE INITIAL
A
TT
A C
H M
EN
A
B
C
D
E
1 2 3 4 5
A101
A101
A101
A101
4 1/2" / 12" 4 1/2" / 12"
2/A102
5/A102
4/A102
3/A102
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-P E
R I_ jf ie d le r.
rv t
JLF
Author
MJH
02/25/2020
07310.007
A102
ROOF PLAN
07310007PERI- 2- A102 ROOF PLAN
SCALE: 1/8" = 1'-0"
ROOF PLAN
ATTIC PHOTO 4
ATTIC PHOTO 1
ATTIC PHOTO 2
ATTIC PHOTO 3
DATE INITIAL
A
TT
A C
H M
EN
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY
THE OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS
AND NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES
OR VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO
ADDITIONAL EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE
SET OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK.
CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO
FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND
BE RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR
ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO
OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL
OTHER TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION
TO REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED
CONSTRUCTION.
E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL
DUCTWORK WITH STRUCTURE, CEILING, LIGHTING, AND PIPING.
F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL
EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.
G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL
PANELS. MAINTAIN ALL CODE REQUIRED CLEARANCES.
H. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,
MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED
PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT
BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL
IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT
THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE
WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND
CONTRACTOR.
I. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INTLET SIZE
UNLESS OTHERWISE NOTED.
J. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING
CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND
GENERAL CONTRACTOR.
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE
ORIGINAL DRAWINGS PROVIDED BY THE OWNER AND LIMITED
FIELD VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,
RELOCATED, OR SALVAGED ARE SHOWN AS DASHED, FULL-TONE
LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND
ARE SHOWN AS HALF-TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS
LISTED BELOW OR HERE-IN. THE CONTRACTOR SHALL
COORDINATE ALL REQUIRED RENOVATION AND NEW
CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE
TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED
BELOW.
C. THE REMOVAL OF HVAC AND PLUMBING EQUIPMENT FROM
FINISHED AREAS AND THROUGH WEATHER BARRIERS SHALL BE
COORDINATED WITH ARCHITECTURAL PLANS AND DETAILS AS
WELL AS NOTES ON THE MECHANICAL DRAWING TO ENSURE
PROPER PATCHING AND REPAIR IS MADE TO THE BUILDING.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION
AND REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS,
EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD,
ERECT, INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION
WITH THE OWNER HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.
E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED
SHALL BE CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT
DAMAGE AND STORED OR REINSTALLED ON THE SITE AS
DIRECTED. REMOVED OR SALVAGED ITEMS SHALL REMAIN THE
PROPERTY OF THE OWNER.
F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND
CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO
MECHANICAL REMOVALS.
G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,
MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED
PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT
BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL
IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT
THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE
WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND
ARCHITECT.
H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING
DEMOLITION SHALL BE COORDINATED WITH THE OWNER AND
GENERAL CONTRACTOR.
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M 00
MECHANICAL INFO SHEET
07310007PERI- 5- M 00 MECHANICAL INFO SHEET
TRUE
NORTH
PLAN
NORTH
NORTH
SYMBOL LEGEND
VOLUME DAMPER
DEMO TO EXISTING CONNECTION
SPRINKLER DRAIN
FIRE SUPPRESSION PIPING
ISOLATION VALVE
TAMPER SWITCH
MANUAL BALANCING VALVE
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
CONTROL VALVE (3 WAY)
CONTROL VALVE (2 WAY)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
HVAC DUCTWORK AND SPECIALTIES
(CONT.)
MISCELLANEOUS SYMBOLS
RETURN DUCT DOWN
AIR TERMINAL (VERTICAL MOUNTING)
ROUND DUCT UP / DOUBLE LINE PIPE
ROUND DUCT DOWN / DOUBLE
LINE PIPE
RETURN DUCT UP
TURNING VANES
SUPPLY AND FRESH AIR DUCT DOWN
SUPPLY AND FRESH AIR DUCT UP
SIZE/TYPE
SIZE/TYPE
FLOW
FLOW
SIZE/TYPE
FLOW
SMOKE DAMPER
FIRE DAMPER-HORIZ FIRE SEPARATION
MOTORIZED DAMPER-OPPOSED BLADE
MOTORIZED DAMPER-PARALLEL BLADE
ROUND AIR TERMINAL
(HORIZONTAL MOUNTING)
GRAVITY DAMPER
(OR) SAFETY VALVE-STEAM
TEMP & PRESS RELIEF
FLOOR SINK
FLOOR DRAIN
GRADE CLEANOUT
PLUMBING VENT THRU ROOF
CLEANOUT / WALL CLEANOUT
THERMOSTATIC MIXING VALVE
M
M
MANHOLE
TRENCH DRAIN
OVERFLOW ROOF DRAIN
OXYGEN OUTLET
PIPE CAP
ELBOW UP
AIR OUTLET
TEE
ELBOW DOWN
VACUUM OUTLET
ROOF DRAIN
SIZE/TYPE
FLOW
HUMIDISTAT
THERMOSTAT
FLEXIBLE DUCT
S
H
T
TEMPERATURE SENSORUNION
TEE DOWN
STRAINER
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
AIR VENT
TEE UP
FIRE/SMOKE DAMPER
RECTANGULAR RETURN AIR TERMINAL
(HORIZONTAL MOUNTING)
RECTANGULAR SUPPLY AIR TERMINAL
(HORIZONTAL MOUNTING)
SOLENOID VALVE
F
D
TS
VALVES
FS
M
M
S
LPR
HPS
MPR
MPS
LPS
HVAC PIPING
GHWR
GHWS
HWR
HWS
PC
HPR
ES
BBD BOILER BLOW DOWN
EXHAUST STEAM
PUMPED CONDENSATE
HIGH PRESSURE RETURN
HIGH PRESSURE STEAM
MEDIUM PRESSURE RETURN
MEDIUM PRESSURE STEAM
LOW PRESSURE RETURN
LOW PRESSURE STEAM
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
FS-_
FD-_
CO
VTR
GCO
ORD-_
MH
X
A
V
RD-_
PIPING SPECIALTIES AND FITTINGS
WCO
FIRE PROTECTION
SIZE/TYPE
FLOW
RECTANGULAR EXHAUST AIR TERMINAL
(HORIZONTAL MOUNTING)
CWS
GCWS
CWR
CR
CS
RL
RDL
RS
GCWR GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
REFRIGERANT LIQUID LINE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION LINE
HCWS
HCWR
HOT/CHILLED WATER SUPPLY
HOT/CHILLED WATER RETURN
DOMESTIC HOT WATER
RECIRCULATING (DHWR)
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
ST/OST
PLUMBING PIPING
ACID VENT
TW
AV
AW
W
DS
DSCW
TWR
DSHW
SANITARY VENT
BURIED EXTERIOR WATER
TEPID WATER RECIRCULATING
TEPID WATER
DISTILLED WATER
SOFTENED HOT WATER
SOFTENED COLD WATER
ACID WASTE
STORM DRAIN
SANITARY DRAIN (BELOW FLOOR)
SANITARY DRAIN (ABOVE FLOOR)
OXYGEN
VACUUM
OX
VAC
RO
A
REVERSE OSMOSIS WATER
COMPRESSED AIR
DEIONIZED WATERDI
AIR FLOW STATIONAFS
HPWR
HPWS
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
F
S
FS
NEW TO EXISTING CONNECTION
G NATURAL GAS
FOF
FOG
LPG
FOV
FOR
FOS
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL GAGE
FUEL OIL FILL
FUEL OIL VENT
LIQUEFIED PETROLEUM GAS
CD CONDENSATE DRAIN
EXHAUST DUCT DOWN
EXHAUST DUCT UP
CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR
NO2 NITROGEN DIOXIDE SENSOR
SENSOR WITH GUARD'X'
DOUBLE - GRADE CLEANOUTDGCO
ST/OST STORM DRAIN (BELOW FLOOR)
WASTE AND ANESTHETIC
GAS DISPOSAL
NITROGEN
WAGD
N
MEDICAL AIRMA
PIPE GUIDE
HOSE BIBB
THERMOMETER
PIPE ANCHOR
HB
STEAM TRAP
RHY
WH
ROOF HYDRANT
WALL HYDRANT
PRESSURE GAUGE
EXISTINGDEMO
EXISTINGNEW
18 Ø
18x10
18/10
ROUND DUCT
FLAT OVAL DUCT-1ST FIG IS SIDE
SHOWN
RECT DUCT-1ST FIG IS SIDE SHOWN
ACOUSTICAL DUCT LINER
HVAC DUCTWORK AND SPECIALTIES
HIGH EFFICIENCY TAKEOFF
HIGH EFFICIENCY TAKOFF
WITH VOLUME DAMPER
NITROGEN OUTLET
MEDICAL AIR OUTLET
WASTE AND ANESTHETIC GAS
DISPOSAL OUTLET
N
MA
V
FLEXIBLE DUCTWORK CONNECTION
ABBREVIATIONS
NORTH
ARROW
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XXXX
SIM/OPP
X
XXXX
XX-1
X
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
ROOM / SPACE
NUMBER
LETTER/NUMBER
INDICATES NEW
COLUMN LINE
LETTER/NUMBER
INDICATES EXISTING
COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DRAWING/DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
XXX-1
PLUMBING
FIXTURES PLUMBING FIXTURE
DESIGNATION
X"PIPE
SIZE
PIPE SIZE (DIAMETER)
X"xX"
DUCT
SIZE
WIDTH x HEIGHT
X"/X" WIDTH / HEIGHT
X" DIAMETER
REF. DEMO NOTES ( ) XX REF. NOTES ( )
SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.
GENERAL DEMOLITION NOTES GENERAL NOTES
MECHANICAL SHEET LIST
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPS
MD MOTORIZED DAMPER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
MPR MEDIUM PRESSURE
RETURN
MPS MEDIUM PRESSURE STEAM
MS MOP SINK
N NITROGEN
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPCW NONPOTABLE COLD WATER
NPHW NONPOTABLE HOT WATER
NPHWR NONPOTABLE HOT WATER
RECIRCULATING
OA OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
OX OXYGEN
P PUMP
PHC PREHEAT COIL
PIV POST INDICATING VALVE
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH,
GAUGE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
RA RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF AREA DRAINS
RL REFRIGERANT DISCHARGE LINE
RF RETURN FAN
RH RELIEF HOOD
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RELIEF AIR
RLF RELIEF FAN
RO REVERSE OSMOSIS WATER
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION LINE
RTU ROOF TOP UNIT
RV RELIEF VALVE
S SINK
SA SUPPLY AIR
SAN SANITARY SEWER
SD SMOKE DAMPER
SF SUPPLY FAN
SFU SANITARY FIXTURE UNIT
SH SHOWER
SP STATIC PRESSURE
SSS SURGICAL SCRUB SINK
ST STORM WATER
TD TRENCH DRAIN
TMV THERMOSTATIC MIXING VALVE
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T THERMOSTAT
UH UNIT HEATER
UR URINAL
V VENT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSETS
WCO WALL CLEANOUT
WF WASH FOUNTAINS
WFU WATER FIXTURE UNITS
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WS WATER SOFTENER
WSHP WATER SOURCE HEAT PUMP
WWHP WATER TO WATER HEAT PUMP
YH YARD HYDRANT
A COMPRESSED AIR
AC AIR COMPRESSOR
AD AIR DOOR
AFCV AUTO FLOW CONTROL VALVE
AHU AIR HANDLING UNIT
AMP AMPERE
APD AIR PRESSURE DROP
AS AIR SEPARATOR
AV ACID VENT
AW ACID WASTE
B BOILER
BC BLOWER COIL
BD BIDET
BFP BACKFLOW PREVENTER
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLKG BLOCKING
BLV BALANCING VALVE
BT BATHTUB
BV BALL VALVE
BW BEDPAN WASHER
CH CHILLER
CC COOLING COIL
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CUH CABINET HEATER
CI CAST IRON
CMU COMBINATION UNITS
CR CONDENSER WATER RETURN
CRAC COMPUTER ROOM AIR
CONDITIONER
CS CONDENSER WATER SUPPLY
CSS CLINICAL SERVICE SINKS
CT COOLING TOWER
CU CONDENSING UNIT - SPLIT SYSTEM
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DB DRY-BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DEG DEGREE
DF DRINKING FOUNTAIN
DGCO DOUBLE GRADE CLEANOUT
DH EMERGENCY DRENCH HOSES
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER
RECIRCULATING
DI DEIONIZED WATER
DOAS DEDICATED OUTDOOR AIR SYSTEM
DS DISTILLED WATER
DSA DUCT SOUND ATTENUATORS
DSCW DOMESTIC SOFT COLD WATER
DSHW DOMESTIC SOFT HOT WATER
DSHWR DOMESTIC SOFT HOT WATER
RECIRCULATING
DST DOMESTIC STORAGE TANK
DTW DOMESTIC TEPID WATER
DTWR DOMESTIC TEPID WATER
RECIRCULATING
EA. EACH
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE
WASH/SHOWER
EF EXHAUST FAN
EFF EFFICIENCY
EFW EMERGENCY FACE WASH
EH EXHAUST HOOD
ERV ENERGY RECOVERY
VENTILATOR
ES EMERGENCY SHOWER
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER
TEMPERATURE
ET EXPANSION TANK
F FIRE SUPPRESSION PIPING
F-_ FURNACE
FCO FLOOR CLEANOUT
FC FLUID COOLER
FCU FAN COIL UNIT
FD FIRE DAMPER
FLA FULL LOAD AMPS
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD FIRE/SMOKE DAMPER
FT FINNED TUBE
G GAS
GCWR GLYCOL CHILLED
WATER RETURN
GCWS GLYCOL CHILLED
WATER SUPPLY
GD GARBAGE DISPOSAL
GDH GAS DUCT HEATER
GHCR GLYCOL HOT/CHILLED
WATER RETURN
GHCS GLYCOL HOT/CHILLED
WATER SUPPLY
GHWR GLYCOL HOT WATER RETURN
GHWS GLYCOL HOT WATER SUPPLY
GI GREASE INTERCEPTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GAS VENT
GWH GAS WATER HEATER
HB HOSE BIBB
HC HEATING COIL
HCR HOT/CHILLED WATER RETURN
HCS HOT/CHILLED WATER SUPPLY
ACC AIR COOLED CONDENSER
ACCU AIR COOLED CONDENSING UNIT
ASHP AIR SOURCE HEAT PUMP
ARU AIR ROTATION UNIT
OI OIL INTERCEPTOR
SOI SAND OIL INTERCEPTOR
DSS DUCTLESS SPLIT SYSTEM
SP SUMP PUMP
OST OVERFLOW STORM WATER
WMB WASHING MACHINE BOX
OB OUTLET BOX
RH ROOF HYDRANT
H HUMIDIFIER
DHWP DOMESTIC HOT WATER
RECIRCULATING PUMP
DWET DOMESTIC WATER EXPANSION
TANK
HP HORSEPOWER
HPR HIGH PRESSURE RETURN
HPS HIGH PRESURE STEAM
HRC HEAT RECOVERY COIL
HWR HOT WATER RETURN (HEATING)
HWS HOT WATER SUPPLY (HEATING)
HX HEAT EXCHANGER
HY HYDRANTS
HP-_ HEAT PUMP
HVLS HIGH VOLUME LOW SPEED
IH INTAKE HOOD
IRH INFRARED RADIANT HEATER
KH KITCHEN HOOD
KW KILOWATT
KWH KILOWATT HOURS
L LAVATORY
LAT LEAVING AIR TEMPERATURE
LPR LOW PRESSURE RETURN
LPG LIQUIFIED PETROLEUM GAS
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPS
LS LAUNDRY SINK
LV LOUVER
LWT LEAVING WATER TEMPERATURE
PROJECT MECHANICAL REFERENCED DEMOLITION NOTES PROJECT MECHANICAL REFERENCED NOTES
M 00 MECHANICAL INFO SHEET
M001 DEMOLITION FLOOR PLAN - MECHANICAL
M101 FIRST FLOOR PLAN - MECHANICAL
M102 ATTIC LEVEL PLAN - MECHANICAL
M201 PIPING FLOOR PLAN - MECHANICAL
M401 DETAILS - MECHANICAL
M501 SCHEDULE - MECHANICAL
DATE INITIAL
A
TT
A C
H M
EN
M001
UH (E)
UH (E)
UH (E)
UH (E)
UH (E)UH (E)
VAV-1 (E)
VAV-3 (E)
VAV-7 (E)
VAV-5 (E)
VAV-2 (E)
VAV-4 (E) VAV-6 (E) VAV-8 (E)
VAV-9 (E)
VAV-10(E)
VAV-11(E)
VAV-12(E)
H-1 (E)
AHU-1(E)
A
B
C
D
E
2 3 4
EQUIP.
STORAGE
EQUIP.
STORAGE
SHOP
STOR.
STOR.
TOILET
SOLARIUM
ASSEMBLY
MUSEUM
FOYER
VIEW AREA
LOBBY
HISTORIAN
RANGER
SUPT.
MECH. EQUIP.
ROOM
WOMEN'S
MEN'S
OFFICE
PASSAGE
IT ROOM
EQUIPMENT LOCATED IN DASHED
AREA LOCATED IN PROJECTION
ROOM ABOVE CLOSETS.
EQUIPMENT AND PIPING LOCATED
IN DASHED AREA LOCATED
IN ATTIC SPACE.
H W
R H W
S
C W
R
C W
S
H W
S H W
R
B
MECH. EQUIP.
ROOM
L P
B
C
3 4
VAV-10(E)
VAV-11(E)
VAV-12(E)
VAV-9 (E)
VAV-8 (E)
AHU-1(E)
H-1 (E)
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M001
DEMOLITION FLOOR PLAN -
MECHANICAL
07310007PERI- 5- M001 DEMOLITION FLOOR PLAN - MECHANICAL
REF. DEMO NOTES ( ):X
1 DEMO EXISTING BOILERS, HOUSEKEEPING PAD, AND PIPING AS SHOWN
ON PLAN.
2 DEMO EXISTING SPLIT SYSTEM CONDENSING UNIT, INDOOR CONSOLE,
CONTROLS, AND REFRIGERANT LINES.
3 DEMO EXISTING AIR COOLED CHILLER, EQUIPMENT PAD, AND PIPING
BACK TO LOCATION SHOWN ON PLANS.
4 DEMO EXISTING HUMIDIFIER ON WALL. DEMO SUPPLY PIPING BACK TO
LOCATION SHOWN ON PLAN. SANITARY DRAIN TO REMAIN FOR FUTURE
USE.
5 DEMO BOILER FLUE AND INTAKE PIPING UP THROUGH CEILING AND ROOF.
TWO SET OF PENETRATIONS TO BE REUSED. PATCH ROOF WHERE FLUE
IS REMOVED TO MATCH EXISTING. COORDINATE WITH PARK STAFF FOR
LOCATION OF SPARE SHINGLES FROM PREVIOUS ROOFING SCOPE.
INFILL UNUSED PENETRATIONS THROUGH CEILING WITH MATERIALS TO
MATCH EXISTING CONSTRUCTION AND FINISHES.
6 DEMO SECTION OF CWR PIPING FOR INSTALLATION OF BUFFER TANK
PIPING.
7 REMOVE SECTION OF SUPPLY DUCT FOR INSTALLATION OF NEW
HUMIDIFIER DISTRIBUTION MANIFOLD AND STAINLESS STEEL DUCTWORK.
8 DEMO EXISTING HUMIDIFIER ON WALL. DEMO DISTRIBUTION MANIFOLD IN
SUPPLY DUCT. PATCH AND SEAL DUCT AIR TIGHT. PATCH DUCT
INSULATION TO MATCH EXISTING.
SCALE: 1/8" = 1'-0"
FIRST FLOOR DEMOLITION PLAN - MECHANICAL PIPING
SCALE: 1/4" = 1'-0"
ENLARGED MECHANICAL ROOM DEMOLITION PLAN - MECHANICAL
NORTH
SCALE: 1/8" = 1'-0"
PARTIAL ATTIC LEVEL PLAN - DEMO HVAC
DATE INITIAL
A
TT
A C
H M
EN
T T T
T
T T
T
T
T
T
T
H
H
T S
(TYPICAL)
CH-1
DSS-1B
DSS-1A
(TYPICAL)
A
B
C
D
E
2 3 4
EQUIP.
STORAGE
EQUIP.
STORAGE
SHOP
STOR.
STOR.
TOILET
IT ROOM
MECH. EQUIP.
ROOM
SUPT.
RANGER
HISTORIAN
VIEW AREA
LOBBY
OFFICE
MEN'S
WOMEN'S
SOLARIUM
FOYER
ASSEMBLY
MUSEUM
2 3
TO H-2
TO H-1
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M101
FIRST FLOOR PLAN -
MECHANICAL
07310007PERI- 5- M101 FIRST FLOOR PLAN - MECHANICAL
REF. NOTES ( ):X
1 NEW CONDENSING UNIT TO BE INSTALLED ON EXISTING CONCRETE
EQUIPMENT PAD.
2 SPLIT SYSTEM INDOOR UNIT TO BE MOUNTED HIGH ON WALL. PATCH
WALL AS NECESSARY WHERE EXISTING UNIT WAS REMOVED TO MATCH
ADJACENT CONSTRUCTION.
3 CONTROLS TO BE REPLACED WITH NEW BACNET SYSTEM. NEW DEVICES
TO BE LOCATED IN SAME LOCATION AS EXISTING DEVICES. PROVIDE
BACKING PLATE AS REQUIRED TO COVER EXISTING CONSTRUCTION.
4 LINE VOLTAGE CONTROLS FOR SHOP AND GARAGE UNIT HEATERS TO
REMAIN.
5 NEW 12" CONCRETE PAD SIZED TO ACCOMMODATE NEW CHILLER
DIMENSIONS PLUS 6" ON ALL SIDES. SEE DETAIL 6/M401 FOR PAD
CONSTRUCTION.
6 INSTALL NEW HUMIDIFIER HUMIDISTAT NEAR EXISTING THERMOSTAT.
7 WALL MOUNTED THERMOSTAT FOR DUCTLESS SPLIT SYSTEM TO BE
INSTALLED AT 48" A.F.F. PROVIDE SPACE TEMPERATURE SENSOR FOR
BMS SYSTEM TO MONITOR AND ALARM I.T. ROOM SPACE TEMPERATURE.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL
NORTH
DATE INITIAL
A
TT
A C
H M
EN
H
28 Ø SA
32x32 RA
20 Ø SA
H-2
(TYPICAL
OF ALL
VAVs)
H-1
VAV-3 (E) VAV-7 (E) VAV-5 (E)
VAV-1 (E)
VAV-2 (E)
VAV-4 (E)
VAV-6 (E) VAV-8 (E)
VAV-9 (E)
VAV-10(E)
VAV-11(E)
VAV-12(E)
AHU-1(E)
A
B
C
D
E
2 3 4
18x18 SA
5 (TYPICAL)
26x26 SA
Ø
S A
28 Ø
EF-1
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M102
ATTIC LEVEL PLAN -
MECHANICAL
07310007PERI- 5- M102 ATTIC LEVEL PLAN - MECHANICAL
REF. NOTES ( ):X
1 CONTROLS TO BE REPLACED WITH NEW BACNET SYSTEM. PROVIDE
INTERFACE FOR EXISTING DAMPER AND VALVE OPERATORS.
CONTRACTOR TO RECORD OPERATING SETPOINTS AND SET NEW
CONTROL SYSTEM TO MATCH.
2 NEW HUMIDIFIER STEAM GENERATOR HUNG ON WALL.
3 REPLACE DUCT WHERE HUMIDIFIER IS TO BE INSTALLED. REPLACE WITH
18X18 DUCT CONSTRUCTED OF STAINLESS STEEL. BOTTOM OF DUCT TO
BE SLOPED TO DRAIN CONDENSATE IN DUCT SYSTEM. PROVIDE 1/2"
DRAIN FROM BOTTOM OF DUCT TO NEAREST DRAIN OR CONDENSATE
PUMP.
4 REPLACE DUCT WHERE HUMIDIFIER IS TO BE INSTALLED. REPLACE WITH
26X26 DUCT CONSTRUCTED OF STAINLESS STEEL. BOTTOM OF DUCT TO
BE SLOPED TO DRAIN CONDENSATE IN DUCT SYSTEM. PROVIDE 1/2"
DRAIN FROM BOTTOM OF DUCT TO NEAREST DRAIN OR CONDENSATE
PUMP.
5 LOW PRESSURE DISTRIBUTION DUCTWORK AND AIR TERMINALS DOWN
STREAM OF VAV BOXES TO REMAIN.
6 EXISTING OUTDOOR, RELIEF, AND RETURN DUCTWORK TO REMAIN.
7 LOCATE STEAM DISPERSION TUBE IN DUCT PER MANUFACTURER
REQUIREMENTS.
8 EXTEND EXISTING VAV PRIMARY DUCT TO NEW DUCT DOWNSTREAM OF
STEAM DISPERSION MANIFOLD. DUCT CONNECTION TO BE PAST THE
STEAM ABSORPTION DISTANCE OUTLINED BY HUMIDIFIER
MANUFACTURER.
9 INSTALL EXHAUST FAN HIGH ON EXTERIOR WALL FOR ATTIC VENTILATION.
FAN TO BE CONTROLLED BY HUMIDISTAT TO ENERGIZE FAN WHEN ATTIC
SPACE RELATIVE HUMIDITY EXCEEDS 60%RH.
10 PROVIDE 12X12 TRANSFER GRILLE ON EACH SIDE OF DOOR. INSTALL
BOTTOM OF GRILLE 12" A.F.F.
SCALE: 1/8" = 1'-0"
ATTIC LEVEL PLAN - MECHANICAL
NORTH
DATE INITIAL
A
TT
A C
H M
EN
M
M201
H-2
AHU-1(E)
VAV-9 (E)
VAV-8 (E)VAV-6 (E)
VAV-4 (E)
VAV-2 (E)
VAV-1 (E)
VAV-3 (E)
VAV-7 (E) VAV-5 (E)
VAV-12(E)
VAV-11(E)
VAV-10(E)
DSS-1B
UH (E)
UH (E) UH (E)
UH (E)
UH (E)UH (E)
H-1
A
B
C
D
E
2 3 4
MUSEUM
FOYER
VIEW AREA
LOBBY
SOLARIUM
ASSEMBLY
STOR.
TOILET
IT ROOM
MECH. EQUIP.
ROOM
PASSAGE
WOMEN'S
MEN'S
OFFICE
SUPT.
RANGER
HISTORIAN
STOR.
SHOP
EQUIP.
STORAGE
EQUIP.
STORAGE
EQUIPMENT AND PIPING LOCATED
IN DASHED AREA LOCATED
IN ATTIC SPACE.
EQUIPMENT LOCATED IN DASHED
AREA LOCATED IN PROJECTION
ROOM ABOVE CLOSETS.
HWS
HWR
C D
3/4"
P-1
P-2
CD
CD
3/4"
CH-1
C W
S C
W R
H W
R
H W
S C W
R
C W
S
H W
S
H W
R
M501
B -1
B B
-1 A
W P
-2
E
W P
-1
E
WP-3 (E) WP-4 (E)
PIPING UP INTO
ATTIC SPACE
DSS-1A
BT-1
B
2 1/2"2 1/2"
R L
R S
EXISTING
GLYCOL
FEED TANK
L P
EXISTING LP LINE BELOW
GRADE TO STORAGE TANK
2"
L P
CONNECTION TO
EXISTING WATER HEATER
2 1/2"
1 1/4"
2"
2"
2"
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M201
PIPING FLOOR PLAN -
MECHANICAL
07310007PERI- 5- M201 PIPING FLOOR PLAN - MECHANICAL
REF. NOTES ( ):X
8 CONDENSATE PUMP LOCATED ON ATTIC FLOOR. PIPE 3/4" CONDENSATE
FROM PUMP TO EXISTING CONDENSATE DISPOSAL POINT IN PROJECTION
ROOM. HUMIDIFIER TO HAVE INTERNAL CONDENSATE COOLER.
9 PROPANE FLOW METER INSTALLED IN LP LINE TO BOILERS AND WATER
HEATER. METER TO LOG AND TRACK PROPANE USE TO NEW BUILDING
BMS SYSTEM. ONICON F-5500 OR EQUAL.
10 EXTEND DCW TO NEW HUMIDIFIER LOCATION.
11 STEAM DISTRIBUTION PIPING AND CONDENSATE DRAIN FROM STEAM
GENERATOR TO DISPERSION TUBES SIZED AND INSTALLED PER
MANUFACTURER REQUIREMENTS. SUPPLY AND DRAIN LINES TO BE
INSULATED PER SPECIFICATIONS.
12 PVC FLUE AND VENT UP THROUGH CEILING TO CONCENTRIC ROOF VENT.
REUSE EXISTING PENETRATIONS. PROVIDE NEW FLASHING AT
CONCENTRIC VENT THROUGH ROOF.
13 MAINTAIN EXISTING AIR SEPARATOR, EXPANSION TANK, AND MAKE-UP
WATER CONNECTION FOR HEATING HOT WATER SYSTEM.
1 NEW 12" CONCRETE PAD SIZED TO ACCOMMODATE NEW CHILLER
DIMENSIONS PLUS 6" ON ALL SIDES. SEE DETAIL 6/M401 FOR PAD
CONSTRUCTION.
2 EXTEND 2-1/2" CHILLED WATER SUPPLY AND RETURN LINES TO NEW
CHILLER CONNECTIONS.
3 ADD BUFFER TANK TO CHILLED WATER SYSTEM TO MEET NEW AIR
COOLED CHILLER SYSTEM VOLUME REQUIREMENT. TANK TO SIT ON
CONCRETE HOUSEKEEPING PAD.
4 EXTEND HOT WATER SUPPLY AND RETURN LINES AND LP GAS PIPING TO
NEW WALL HUNG BOILERS. SEE ELEVATION 1/M501.
5 CONDENSATE DRAIN FROM HIGH WALL UNIT TO BE PIPED TO TAILPIECE
OF LAVATORY DRAIN.
6 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
REQUIREMENTS AND THE SPECIFICATIONS. REFRIGERANT LINE ROUTING
TO FOLLOW PATH OF EXISTING LINESETS THAT WERE REMOVED.
7 PROVIDE BACKFLOW PREVENTER FOR HUMIDIFIER SUPPLY. PROVIDE 3/4"
DCW CONNECTION TO EACH HUMIDIFIER AFTER BACKFLOW PREVENTER.
SCALE: 1/8" = 1'-0"
FLOOR PLAN - MECHANICAL PIPING
SCALE: 1/4" = 1'-0"
FLOOR PLAN - MECHANICAL PIPING
NORTH
DATE INITIAL
A
TT
A C
H M
EN
T.O. EX. SLAB
INSULATION
THREADED ROD
INSULATION
THREADED ROD
HANGER, INSULATION ON
PIPE CONTINUOUS THROUGH
HANGER WITHOUT
SWALLOWING
PIPE, 1"Ø MAX
BAND
THREADED
ROD
HANGER
INSULATION
PIPE
SHIELD TO COVER
180° OF PIPE, SEE
CHART FOR LENGTH
SEE CHART
SHEILD LENGTH
SEE CHART
SHEILD LENGTH,
SWIVEL
SHIELD LENGTH FOR PIPE - NOT LESS THAN THE
FOLLOWING:
a. NPS 1/4" TO 3-1/2" 12" LONG AND .048" THICK
b. NPS 4" 12" LONG AND .06" THICK
NOTE:
1. THERMAL-HANGER SHIELDS: INSTALL WITH INSULATION SAME THICKNESS AS PIPING INSULATION.
SHIELD TO COVER
180° OF PIPE, SEE
CHART FOR LENGTH
SHIELD TO COVER
180° OF PIPE, SEE
CHART FOR LENGTH
THREADED ROD
U-BOLT (TYP.) UNISTRUT OR STEEL
ANGLE WITH LONG LEG
DOWN
SHIELD TO COVER
360° OF PIPE, SEE
CHART FOR LENGTH
HANGER, INSULATION ON
PIPE CONTINUOUS THROUGH
HANGER WITHOUT
SWALLOWING
PIPE (TYP.)
HANGER CLAMP
OR BAND
BOLT
STRAP
OR
ANGLE
ROD (TYP)
DUCT (TYP)
ANGLE (TYP)
NUT (TYP)
NOTES:
1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.
2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO DUCTWORK.
3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCT AS ROUND DUCT TENDS TO DEFORM ON TRAPEZE HANGERS.
4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINTAIN THE INTEGRITY OF THE VAPOR BARRIER.
5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALLY WRAPPED.
DIRT LEG
TO EQUIPMENT
SHUT-OFF VALVE
REMOVABLE
CAP
UNION
SUPPLY PIPING
PRESSURE REGULATOR (IF REQUIRED)
NOTE: FOLLOW ALL CODE
AND MANUFACTURERS
REQUIREMENTS FOR
AND INSTALLATION.
E X
H A
U S
T A
IR
IN
T
A K
E A
IR
CLAMP
ROOF BOOT AND
FLASHING
SHEET METAL STRAP
(CLAMP AND SHEET
METAL STRAP MUST BE
FIELD INSTALLED TO
SUPPORT THE WEIGHT
OF THE TERMINATION
KIT.)
10'-0" MIN.
M
IN
FASTEN FLASHING TO DECK
PER MANUFACTURER'S
REQUIREMETNS
CUT EXISTING SHINGLES AS
NECESSARY TO FIT AROUND
BOOT
EXISTING ROOF
PENETRATION
NOTES:
1/2"x1/2" CHAMFER STRIP
REMOVE AND CAULK.
6x6 - 10/10 WWF
#4 BENT RE-BAR
AT EACH CORNER
DRILL 3/4"Ø HOLE IN FLOOR SLAB
AND GROUT IN REBAR.
1. INSTALL NEW HOUSEKEEPING PADS AS INDICATED ON PLANS. VERIFY DIMENSIONS
WITH EQUIPMENT SIZES.
2. VERIFY SIZE AND LOCATION OF EQUIPMENT ANCHOR BOLTS.
3. PROVIDE DOWEL RODS 18" ON CENTER AROUND FULL PERIMETER OF PAD IF
LONG DIMENSION IS GREATER THAN 72".
4"
/256"
3-1/2"
FLOOR
UNDISTURBED SOIL
EXISTING PAVEMENT -
SEE PLAN
AIR COOLED CHILLER - SEE PLAN
12" DEEP CONCRETE FOUNDATION PAD
W/ #5 @ 12" O.C. E.W. TOP & BOTTOM
NOTES:
1. MINIMUM COMPRESSIVE STRENGTH (F'C AT 28 DAYS) SHALL BE
4,500 PSI WITH PORTLAND TYPE I CEMENT AND NORMAL
WEIGHT AGGREGATE 1 1/2" MAXIMUM SIZE - ASTM C33.
REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. 1/2"
PREFORMED EXPANSION JOINT PER D1751. MINIMUM
CONCRETE CLEAR COVER: 2" TOP, 3" BOTTOM, AND 3" SIDES.
2. CONTRACTOR SHALL ANCHOR EQUIPMENT PER EQUIPMENT
MANUFACTURER REQUIREMENTS USING HILTI KWIK BOLT III
EXPANSION ANCHORS OR HILTI HIT-HY 200 EPOXY ANCHORS.
3. CONTRACTOR SHALL VERIFY AND COORDINATE LENGTH AND
WIDTH OF PAD WITH SUBMITTED EQUIPMENT MANUFACTURER.
4. CONTRACTOR SHALL VERIFY AND COORDINATE ALL OPENING
SIZES AND LOCATIONS REQUIRED IN FOUNDATION PAD.
SEAL AROUND PERIMETER BETWEEN
NEW EQUIPMENT PAD AND EXISTING
PAVEMENT.
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M401
DETAILS - MECHANICAL
07310007PERI- 5- M401 DETAILS - MECHANICAL
SCALE: NOT TO SCALE
PIPE HANGER DETAIL
SCALE: NOT TO SCALE
DUCT HANGER DETAIL
SCALE: NOT TO SCALE
TYPICAL GAS PIPING DETAIL
SCALE: NOT TO SCALE
CONCENTRIC GAS FLUE DETAILS
SCALE: NOT TO SCALE
INTERIOR HOUSEKEEPING PAD DETAIL
SCALE: 1/2" = 1'-0"
EXTERIOR EQUIPMENT PAD DETAIL
DATE INITIAL
A
TT
A C
H M
EN
FIRST FLOOR
100' - 0"
FIRST FLOOR
100' - 0"
ATTIC LEVEL
112' - 0"
B
HWS
HWR
LP
4 Ø4 Ø 4 Ø4 Ø
2"2"
2"
B-1A
B-1B
PVC VENT AND FLUE
THROUGH ROOF TO
CONCENTRIC TERMINAL
EXISTING
SHAKE
SHINGLES
NEW SHAKE SHINGLES. USE
SHINGLES FROM EXISTING NPS
EXTRA STOCK FROM PREVIOUS
ROOFING SCOPE
FASTEN PATCH TO EXISTING
DECK AND SEAL PERIMETER
PATCH EXISTING ROOF
PENETRATION WITH PLYWOOD
THICKNESS TO MATCH
EXISTING WITH BACKER 2"
LARGER IS ALL DIRECTIONS
EXISTING
SHAKE
SHINGLES
EXISTING
UNDERLAYMENT
EXISTING
UNDERLAYMENT
15LB FELT UNDERLAYMENT.
INSERT UNDER EXISTING
UNDERLAYMENT ON HIGH SIDE
AND OVERLAP EXISTING
UNDERLAYMENT ON LOW SIDE.
EXISTING ROOF
STRUCTURE BEYOND
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
251315
00000
PEA RIDGE NATIONAL MILITARY PARK
15930 EAST US-62
GARFIELD, AR 72732C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
P E
R I_ a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
02/25/2020
07310.007
M501
SCHEDULE - MECHANICAL
07310007PERI- 5- M501 SCHEDULE - MECHANICAL
2. PROVIDE WITH BACNET CONTROLS INTERFACE.
NOTES: 1. UNIT TO HAVE FREEZE PROTECTION, SOUND ATTENUATION PACKAGE, AND ARCHITECTURAL LOUVERS.
CH-1 GRADE R410A 95 30 68.1 55 45 14.9 2 10.56 32.39 208 3 60 136.8 175 TRANE CGAM030 1-2
REFER
TYPE
AMB AIR ENT
COND (°F) MIN TONS
FLOW
(GPM) EWT (°F) LWT (°F)
PD (FT
WAT)
MIN COOL
STAGES
EFFICIENCY
(EER)
TOTAL
POWER
(KW) VOLTS PH HZ
MIN CIRC
AMPS
MAX OVERCURRENT
PROTECTION AMPSMARK LOCATION
CHILLER PERFORMANCE DATA UNIT ELECTRICAL DATA
BASIS OF DESIGN
MANUFACTURER AND
MODEL NUMBER REMARKS
AIR COOLED CHILLER SCHEDULE
NOTES: 1. PROVIDE WITH LOW AMBIENT COOLING, HARD-WIRED WALL MOUNTED THERMOSTAT, AND INTEGRAL CONDENSATE PUMP ACCESSORY.
DSS-1A/B DATA 320-425 80 67 12.0 20.8 14.0 10.2 MITSUBISHI PKA-A12 GRADE 95 R410A MITSUBISHI PUZ-A12 11 28 208 3 60 1
DB WB
AIRSIDE DATA EAT (°F)
MIN CAP
(MBH) EFF. (SEER)
HEATING @
47°F (MBH) EFF. (HSPF) MCA MOCP VOLTS PH HZLOCATION CFM
COOLING COIL DATA HEATING DATA
BASIS OF DESIGN
MANUFACTURER AND MODEL
NUMBER LOCATION
AMB
TEMP (°F)
REFER
TYPE
BASIS OF DESIGN
MANUFACTURER AND MODEL
NUMBERMARK
INDOOR UNIT DATA OUTDOOR UNIT DATA
ELECTRICAL DATA
REMARKS
DUCTLESS SPLIT SYSTEM AIR CONDITIONING SCHEDULE
2. PROVIDE WITH MANUFACTURER STAINLESS STEEL DISTRIBUTION TUBES.
NOTES: 1. UNIT TO HAVE INTEGRAL CONDENSATE COOLER, SCALE COLLECTOR, AND BACNET CONTROLS INTERFACE.
H-2 ATTIC AHU-1 1 RESISTIVE STEAM 20 2,530 18 18 55 68 9.8 27.2 35 208 3 60 NORTEC RS030 1-2
H-1 ATTIC AHU-1 1 RESISTIVE STEAM 36 4,510 26 26 55 68 16.2 45 60 208 3 60 NORTEC RS045 1-2
MAX CFM WIDTH HEIGHT TEMP (°F) % RH KW MCA MOCP VOLTS PH HZMARK LOCATION SERVES
NUMBER OF
MANIFOLDS TYPE
HUMIDIFICATION
CAPACITY
(LBS/HR)
DUCT CONDITIONS ELECTRICAL DATA
BASIS OF DESIGN
MANUFACTURER AND
MODEL NUMBER REMARKS
ELECTRIC HUMIDIFIER SCHEDULE
3. UNIT TO HAVE BUILT-IN CIRCULATING PUMP.
2. PROVIDE WITH CONDENSATE NEUTRALIZER, CONCENTRIC ROOF VENT TERMINAL, AND BACNET CONTROLS INTERFACE.
NOTES: 1. BOILER TO BE WALL MOUNTED.
B-1A/B MECH ROOM CONDENSING 399.2 10:1 20.0 >95 160 180 RIELLO CONDEXA PRO 117 1-3
EWT (°F) LWT (°F)MARK LOCATION TYPE
INPUT MBH
(NAT GAS) TURNDOWN FLOW (GPM)
COMBUSTION
EFFICIENCY (%)
BASIS OF DESIGN
MANUFACTURER AND
MODEL NUMBER REMARKS
PROPANE FIRED HOT WATER BOILER SCHEDULE
SCALE: 1/4" = 1'-0"
BOILER PIPING ELEVATION
3. TANK SIZED FOR BASE-OF-DESIGN CHILLER LOOP TIME REQUIREMENTS.
2. PROVIDE WITH BASE RING WITH ANCHOR CLIPS AND 1/2" CLOSED CELL INSULATION WRAP.
NOTES: 1. CONDENSATE PUMP TO BE RATED FOR A MAXIMUM WATER TEMPERATURE OF 150°F
BT-1 BUFFER TANK CH-1 MECH ROOM TANK VOLUME = 75 GALLONS -- TACO BTH0075F02-125N 2-3
P-2 CONDENSATE PUMP H-2 ATTIC 8' LIFT, 300 GAL/HR, 1 GALLON RESERVOIR 115 V, 3.1 FLA HARTELL A2-115 1
P-1 CONDENSATE PUMP H-1 ATTIC 8' LIFT, 300 GAL/HR, 1 GALLON RESERVOIR 115 V, 3.1 FLA HARTELL A2-115 1
MARK FUNCTION SERVES LOCATION OPERATING CONDITIONS CAPACITY AND MOTOR HP
BASIS OF DESIGN
MANUFACTURER AND
MODEL NUMBER REMARKS
MISCELLANEOUS MECHANICAL EQUIPMENT SCHEDULE
NOTES: 1. SCHEDULE INFORMATION FROM EXISTING PLANS. CONTRACTOR SHALL VERIFY EXISTING SYSTEM SETPOINTS AND PERFORMANCE PRIOR TO REMOVAL OF EXISTING CONTROLS. NEW CONTROL SETPOINTS TO MATCH EXISTING.
EX AHU-1 ATTIC EX VAVs 8,000 4.66 2.00 1,522 65.0 45.0 55.4 327.34 230.34 21.0 180.0 152.7 274.24 1,800 15 208 3 60 CARRIER 39MN17 1
CFM
TOT SP IN
WG
EXT SP IN
WG RPM GPM EWT (°F) LWT (°F)
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH) GPM EWT (°F) LWT (°F)
CAPACITY
(MBH) RPM HP VOLTS PH HZMARK LOCATION SERVES
FAN DATA COOLING COIL DATA HEATING COIL DATA MOTOR DATA
MANUFACTURER AND MODEL
NUMBER REMARKS
EXISTING AIR HANDLING UNIT SCHEDULE
PRIOR TO REMOVAL OF EXISTING CONTROLS. NEW CONTROL SETPOINTS TO MATCH EXISTING.
NOTES: 1. SCHEDULE INFORMATION FROM EXISTING PLANS. CONTRACTOR SHALL VERIFY EXISTING SYSTEM SETPOINTS AND PERFORMANCE
EX VAV-12 ASSEMBLY 1320 -- -- -- 39.7 2.6 TITUS DESV
EX VAV-11 EXHIBIT 900 -- -- -- 26.1 1.75 TITUS DESV
EX VAV-10 FOYER 160 -- -- -- 11.0 0.75 TITUS DESV
EX…