Attach 2 - PERI HVAC Drawings Final.pdf

PDF 9 MB Posted

Attached to
PERI - HVAC REPLACEMENT Federal contract opportunity
Solicitation number
140P6220R0005
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This presolicitation notice provides information for the Pea Ridge National Military Park Visitor Center HVAC Replacement project. The work includes installing spray foam insulation, replacing the air-cooled chiller, buffer tank, propane boilers, controls, and adding a ductless split system and humidifiers. The contract type is firm-fixed price for $250,000 to $500,000, set aside for HUBZone small businesses under NAICS 238220. The period of performance is 180 days from notice to proceed by September 15, 2020. A telephonic site visit will be held on August 7 and an on-site visit must be scheduled by August 12. Questions are due by August 13. Proposals and proposal guarantees are due by September 3, with award expected in early-mid September 2020. The contractor must provide payment and performance bonds within 10 days of award.

View the file

Other files for this federal contract opportunity

Other files attached to PERI - HVAC REPLACEMENT, newest first.
File Type Posted
Attach 1 - PERI Project Manual.pdf PDF
Attach 3 - PERI HVAC Briefing Photos_5.6.20.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONTRACTOR

PARKING

AREAS

TEMPORARY EQUIPMENT

AND MATERIALS STORAGE

AVAILABLE IN MAINTENANCE

SHOP

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

G 00

INDEX OF DRAWINGS

REPAIR/REHAB VISITOR CENTER HVAC

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732

FINAL CD SUBMITTAL

02/25/2020

07310007PERI- 0- G 00 INDEX OF DRAWINGS

ARCHITECTURAL

A 00 ARCHITECTURAL INFO SHEET

A101 ATTIC PLAN

A102 ROOF PLAN

GENERAL

G 00 INDEX OF DRAWINGS

MECHANICAL

M 00 MECHANICAL INFO SHEET

M001 DEMOLITION FLOOR PLAN - MECHANICAL

M101 FIRST FLOOR PLAN - MECHANICAL

M102 ATTIC LEVEL PLAN - MECHANICAL

M201 PIPING FLOOR PLAN - MECHANICAL

M401 DETAILS - MECHANICAL

M501 SCHEDULE - MECHANICAL

ELECTRICAL

E 00 ELECTRICAL INFO SHEET

E 01 ELECTRICAL GENERAL NOTES

E001 FIRST FLOOR PLAN - DEMOLITION

E101 FIRST FLOOR PLAN - POW. & AUX. SYS.

SCHEDULES

DRAWING INDEX

CODE ANALYSIS

2012 INTERNATIONAL BUILDING CODE W/ APPENDICES

2009 INTERNATIONAL MECHANICAL CODE

2006 INTERNATIONAL FUEL GAS CODE

2006 INTERNATIONAL PLUMBING CODE

2009 INTERNATIONAL ENERGY CONSERVATION CODE

2017 NATIONAL ELECTRICAL CODE

SCALE: NTS

PROJECT LOCATION

SCALE: NTS

CONTRACTOR PARKING AND STAGING

DATE INITIAL

A

TT

A C

H M

EN

T

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p

\0

-A R

C H

R

-P E

R I_ jf ie d le r.

rv t

JLF

Author

MJH

02/25/2020

07310.007

A 00

ARCHITECTURAL INFO SHEET

07310007PERI- 2- A 00 ARCHITECTURAL INFO SHEET

TRUE

NORTH

PLAN

NORTH

NORTH

NORTH

ARROW

NAME

ELEVATION

LEVEL

MATCHLINE

AREA A

AREA B

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

EXISTING

COLUMN

NEW

COLUMN

X

X

X

XX-XX

SIM

X

XX-XX

XXXX

DX

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

150 SF

ROOM

NUMBER

LETTER INDICATES

NEW COLUMN LINE

LETTER INDICATES

EXISTING COLUMN LINE

SECTION/DETAIL

NUMBER

SHEET NUMBER

INDICATES DIRECTION

OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME

DESIGNATION

ROOM NUMBER

DESIGNATION

ROOM AREA

DESIGNATION

ROOM /

FRAMING

ELEVATION

EXTERIOR

ELEVATION

XX-XX

XX-XX

ELEVATION LETTER

DIRECTION OF VIEW

SHEET NUMBER

ELEVATION LETTER

DIRECTION OF VIEW

SHEET NUMBER

DOOR

NUMBER

DOOR NUMBER10

WINDOW

DESIGNATION

WINDOW DESIGNATION000

TA-X

TOILET

ACCESSORY

TOILET ACCESSORY

NUMBER

WALL

TYPE

LETTER

INDICATES

PARTITION OR

WALL TYPE

X

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE

DRAWING

ABBREVIATIONSREFERENCE LEGEND

ARCHITECTURAL

SHEET LIST

GENERAL NOTES

X

PROJECT ARCHITECTURAL REFERENCED NOTES

REF. NOTES ( )

S SOUTH

SA SUPPLY AIR

SAN SANITARY

SB SECURITY BARS

SB SPLASH BLOCK

SCH SCHEDULE

SCHED SCHEDULE

SCR SCREW

SCT STRUCTURAL CLAY TILE

SCUT SCUTTLE

SCW SOFT COLD WATER

SD STORM DRAIN

SD SUBDRAIN

SDI STEEL DECK INSTITUTE

SECT SECTION

SECY SECRETARY

SEQ SEQUENCE

SF SQUARE FOOT (FEET)

SFU STRUCTURAL FACING

UNIT

SHLD SHOULDER

SHT SHEET

SHTG SHEATHING

SHW SOFT HOT WATER

SIM SIMILAR

SJI STEEL JOIST INSTITUTE

SL SNOW LOAD

SLBB SHORT LEG BACK TO

BACK

SM SPRINKLER MAIN

SOV SHUT OFF VALVE

SPA SPACE(ING)

SPEC SPECIFICATIONS

SPF SOUNDPROOF

SPH SPACE HEATER

SPKR SPEAKER

SPL SPECIAL

SQ SQUARE

SS SANITARY SEWER

SS STAINLESS STEEL

SSMR STANDING SEAM METAL

ROOFING

STA STATION

STAIR STAIRWAY

STC SOUND TRANSMISSION

COEFFICIENT

STD STANDARD

STGR STRINGER

STIFF STIFFENER

STIRR STIRRUPS

STL STEEL

STN STONE

STOR STORAGE

STR STRUCTURAL

SUB FL SUB FLOOR

SUCT SUCTION

SUSP SUSPENDED

SVF SHEET VINYL FLOORING

SW SWITCH

SWBD SWITCH BOARD

SYM SYMMETRICAL

T TREAD

T or TLT TOILET

TAN TANGENT

TBD TACK BOARD

TE TOP ELEVATION

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TERM TERMINAL

TGL TOGGLE

TH THRESHOLD

THK THICK

THRD THREAD

TO TOP OF

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOF TOP OF FOOTING

TOJ TOP OF JOIST

TOPO TOPOGRAPHIC

TOS TOP OF STEEL

TOW TOP OF WALL

TRANS TRANSVERSE

TSTAT THERMOSTAT

TV TELEVISION

TW TEMPERED WATER

TWR TEMPERED WATER

RETURN

TYP TYPICAL

UC UNIT COOLER

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UNEX UNEXCAVATED

UNFIN UNFINISHED

UNO UNLESS NOTED

OTHERWISE

UPS UNINTERRUPTIBLE

POWER SYSTEM

UR URINAL

UT UTILITY

UV UNIT VENTILATOR

V VOLT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VCP VITRIFIED CLAY PIPE

VCT VINYL COMPOSITION TILE

VD VAULT DOOR

VEL VELOCITY

VENT VENTILATOR(ION)

VERT VERTICAL

VEST VESTIBULE

VFD VARIABLE FREQUENCY

DRIVE

VOL VOLUME

VPC VERTICAL POINT OF

CURVATURE

VPI VERTICAL POINT OF

INTERSECTION

VPT VERTICAL POINT OF

TANGENCY

VS VENT STACK

VT VINYL-TILE

VTR VENT THRU ROOF

VWC VINYL WALL COVERING

W WEST

W WIDE (WIDTH)

W WIRE

W/ WITH

W/O WITHOUT

WB WET BULB

WC WATER CLOSET

WC WATER COLUMN

WD WASTE DRAIN

WD WOOD

WD BLKG WOOD BLOCKING

WD DR WOOD DOOR

WDW WINDOW

WF WIDE FLANGE

WG WIRE GLASS

WH WALL HYDRANT

WHT WHITE

WI WROUGHT IRON

WKSH WORK SHOP

WL WIND LOAD

WNSCT WAINSCOT

WP WEATHER PROOF

WP WORK POINT

WPF WATER PROOF

WPFG WATER PROOFING

WRB WARDROBE

WS WASTE STACK

WT WEIGHT

WWF WELDED WIRE FABRIC

WWM WOVEN WIRE MESH

XFMR TRANSFORMER

YD YARD or YARD DRAIN

LBS POUNDS

LD LOAD

LDG LOADING

LE LEFT END

LG LENGTH (LONG)

LIN LINEAR

LIS LAWN IRRIGATION

SYSTEM

LL LIVE LOAD

LLBB LONG LEG BACK TO BACK

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LNTL LINTEL

LP LOW POINT

LPG LIQUIFIED PETROLEUM

GAS

LPS LOW PRESSURE STEAM

LR LIVING ROOM

LS LAWN SPRINKLER

LT LIGHT

LT WT LIGHT WEIGHT

LTG LIGHTING

LVT LUXURY VINYL TILE

M MIDDLE

M THOUSAND

M & B MATCHED AND BEADED

MA MAKE-UP AIR

MACH MACHINE

MAS MASONRY

MAT or

MATL

MATERIAL

MAX MAXIMUM

MB MACHINE BOLT

MBH 1000 BTUH

MC MEDICINE CABINET

MC MISCELLANEOUS

CHANNELS

MECH MECHANICAL

MER MECHANICAL EQUIPMENT

ROOM

MET METAL

MFG MANUFACTURING

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

ML METAL LATH

MLDG MOULDING

MO MASONRY OPENING

MONO MONOLITHIC

MT METAL THRESHOLD

MTD MOUNTED

N NORTH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO NUMBER

NR NOT REQUIRED

NS NEAR SIDE

NTS NOT TO SCALE

OA OUTSIDE AIR

OB WG OBSCURE WIRE GLASS

OBGL OBSCURE GLASS

OBSC OBSCURE

OC ON CENTER(S)

OCEW ON CENTER EACH WAY

OD OUTSIDE DIAMETER

OFF OFFICE

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

OPS OPERATIONS

OS & Y OUTSIDE SCREW & YOKE

OSF OUTSIDE FACE

OV OVERFLOW VALVE

OX OXYGEN

OZ OUNCE

P PAINT

PA PUBLIC ADDRESS

PBS PUSH BUTTON STATION

PC PIECE

PC POINT OF CURVATURE

PC PRECAST

PCC PORTLAND CEMENT

CONCRETE

PCT PORCELAIN CERAMIC TILE

PD PRESSURE DROP

PE POLYETHYLENE

PEN PENETRATION

PERF PERFORATED

PH PHASE

PHAR PHARMACY

PI POINT OF INTERSECTION

PIV POST INDICATING VALVE

PL or P PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLATF PLATFORM

PLBG PLUMBING

PLG PILING

PLWD PLYWOOD

PNL PANEL

POL POLISH(ED)

PORC PORCELAIN

PPM PARTS PER MILLION

PR PAIR

PREFAB PREFABRICATED

PREFIN PREFINISHED

PRESS PRESSURE

PROJ PROJECT

PRV PRESSURE REGULATING

VALVE

PS PRESSED STEEL

PSFT POUNDS PER SQUARE

FOOT

PSI POUNDS PER SQUARE

INCH

PT POINT

PT POINT OF TANGENCY

PTD PAINTED

PTN PARTITION

PVC POLYVINYL-CHLORIDE

PVMT PAVEMENT

PW PASS WINDOW

1/4 RD QUARTER ROUND

QT QUARRY TILE

QT QUART

QTRS QUARTERS

QTY QUANTITY

QTZ QUARTZ

R REGISTER

R RISER

RA RETURN AIR

RAD OR

R

RADIUS

RB RESILIENT BASE

RC REMOTE CONTROL

RCP REINFORCED CONCRETE

PIPE

RD ROOF DRAIN

RE RIGHT END

REC RECEIVER

RECP RECEPTACLE

RECR RECREATION

RECT RECTIFIER

REF REFERENCE

REFR REFRIGERANT

REFR REFRIGERATOR

REG REGISTER

REINF REINFORCEMENT

REM REMOVE(ABLE)

REQD REQUIRED

RESIL RESILIENT

REV REVISIONS

RFG ROOFING

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RM ROOM

RND ROUND

RO ROUGH OPENING

RPM REVOLUTIONS PER

MINUTE

RT RUBBER TILE

RTU ROOF TOP UNIT

RUB RUBBER

DIAG DIAGONAL

DIM DIMENSION

DIP DUCTILE IRON PIPE

DISC DISCONNECT

DIST DISTRIBUTION

DL DEAD LOAD

DMPR DAMPER

DN DOWN

DP DAMP PROOFING

DPT DEW POINT

DR DOOR

DRN DRAIN

DS DOWN SPOUT

DV DENTAL VACUUM

DWG DRAWING

DWLS DOWELS

DX DIRECT EXPANSION

E EAST

EA EACH

EA EXHAUST AIR

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY

RATIO

EJ EXPANSION JOINT

EL OR

ELEV

ELEVATION - GRADE OR

BUILDING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

ENCL ENCLOSURE

ENT ENTERING

ENT ENTRANCE

EQ EQUAL

EQUIP EQUIPMENT

ES EACH SIDE

EST ESTIMATE

EVAP EVAPORATOR

EW EACH WAY

EWC ELECTRIC WATER

COOLER

EXC EXCAVATE

EXD EXIT DEVICE

EXH EXHAUST

EXIST EXISTING

EXP EXPOSED

EXPL EXPLOSION

EXPN EXPANSION

EXT EXTERIOR

F FAHRENHEIT

F FIRE

FA FRESH AIR

FCG FACING

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEB FIRE EXTINGUISHER

BRACKET

FEC FIRE EXTINGUISHER

CABINET

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIG FIGURE

FIN FINISH

FIX FIXTURE

FL or FLR FLOOR

FLASH FLASHING

FLEX FLEXIBLE

FLG FLANGE

FLG FLOORING

FLUOR FLUORESCENT

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPRF FIRE PROOF

FR FRAME

FRG FURRING

FS FAR SIDE

FS FLOOR SINK

FS FULL SIZE

FT FEET (FOOT)

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G GRILLE

G NATURAL GAS

GA GAGE OR GAUGE

GAL GALLON

GALV GALVANIZED

GEN GENERAL

GFE GOVERNMENT FURNISHED

EQUIPMENT

GFE/CI GOVERNMENT FURNISHED

EQUIPMENT/CONTRACTOR

INSTALLED

GFI GROUND FAULT

INTERRUPTER

GI GALVANIZED IRON

GL GLASS

GND GROUND

GOVT GOVERNMENT

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GR GRADE

GRS GALVANIZED RIGID STEEL

CONDUIT

GRTG GRATING

GSU GLAZED STRUCTURAL

UNITS

GWB GYPSUM WALLBOARD

GWT GLAZED WALL TILE

GYP GYPSUM

H or HT HEIGHT (HIGH)

HB HOSE BIBB

HBD HARDBOARD

HC HANDICAPPED

HD HEAD

HDPE HIGH DENSITY

POLYETHYLENE

HDR HEADER

HDW HARDWARE

HIP HIGH PRESSURE

HM HOLLOW METAL

HORIZ HORIZONTAL(LY)

HP HORSE POWER

HPS HIGH PRESURE STEAM

HPT HIGH POINT

HR HOUR

HS HIGH STRENGTH

HSGYP HIGH STRENGTH GYPSUM

PLASTER

HTG HEATING

HTR HEATER

HW HEAD WALL

HW HOT WATER

HWH HOT WATER HEATER

HWR HOT WATER RETURN

(HEATING)

HWS HOT WATER SUPPLY

(HEATING)

HYD HYDRAULIC

I or FE IRON

IC INTERCOM

ID INSIDE DIAMETER

IE INVERT ELEVATION

IES ILLUMINATING

ENGINEERING SOCIETY

IN INCH

INSUL INSULATION

INT INTERIOR

INV INVERT OR INVERTER

IP IRON PIPE

ISF INSIDE FACE

JB JUNCTION BOX

JBOX JUNCTION BOX

JC JANITOR CLOSET

JCT JUNCTION

JST JOIST

JT JOINT

K KEY

KCP KEENE'S CEMENT

PLASTER

KIP or K KILOPOUND (1000 LBS)

KIT KITCHEN

KL KEY LOCK

KP KICK PLATE

KV KILOVOLTS

KVA KILOVOLT AMPERES

KW KILOWATT

LAB LABORATORY

LAU LAUNDRY

LAV LAVATORY

LBR LUMBER

A COMPRESSED AIR

A/C AIR CONDITIONING

AB ANCHOR BOLT

ABS ACRYLONITRILE BUTAD

STYRENE

AC ALTERNATING CURRENT

ACI AMERICAN CONCRETE

INSTITUTE

ACSR ALUMINUM CONDUCTOR

STEEL REINFORCED

ACST ACOUSTIC

AD ACCESS DOOR

AD AREA DRAIN

ADMIN ADMIN ADMINISTRATION

(IVE)

AFF ABOVE FINISH FLOOR

AFFF AQUEOUS FILM FORMING

FOAM

AGG AGGREGATE

AHU AIR HANDLING UNIT

AI AREA INLET

AIC AMPS INTERRUPTING

CAPACITY (SYM RMS)

AISC AMERICAN INSTITUTE OF

STEEL CONSTRUCTION

AL ACTIVE LEAF

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

AP ACCESS PANEL

APD AIR PRESSURE DROP

APPD APPROVED

APPROX APPROXIMATE

ARCH ARCHITECTURAL OR

ARCHITECT

ARI AMERICAN

REFRIGERATION

INSTITUTE

ASB ASBESTOS

ASPH ASPHALT

APC ACOUSTICAL PANEL

CEILING

AUTO AUTOMATIC

AV ACID VENT

AVG AVERAGE

AW ACID WASTE

AWC ACOUSTICAL WALL

COVERING

AWG AMERICAN WIRE GAUGE

L ANGLE

BATT BATT INSULATION

BB BULLETIN BOARD

BBO BOILER BLOW OFF

BC BOOKCASE

BD BOARD

BDY BOUNDARY

BEJ BRICK EXPANSION JOINT

BIT BITUMINOUS

BKR BREAKER

BL BUILDING LINE

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BM BENCH MARK

BO BOTTOM OF

BOT BOTTOM

BRCG BRACING

BRDG BRIDGING

BRG BEARING

BRK BRICK

BRKT BRACKET

BS BOTH SIDES

BTU BRITISH THERMAL UNIT

BTUH BTU PER HOUR

BUR BUILT-UP ROOFING

BW BOTH WAYS

C CENTER

C OR

CND

CONDUIT (ELECTRICAL

SHEETS)

C TO C CENTER TO CENTER

CAP CAPACITY

CB CATCH BASIN (OR CIRCUIT

BREAKER)

CC CENTER TO CENTER

CCT CIRCUIT

CD CONDENSATE DRAIN

CE COVER ELEVATION

CEM CEMENT

CF CUBIC FEET

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CHIM CHIMNEY

CI CAST IRON

CI CURB INLET

CIP CAST IN PLACE

CIR CIRCULAR

CJ CONTROL JOINT

CKT CIRCUIT

CL CENTER LINE

CL WG CLEAR WIRE GLASS

CLG CEILING

CLKG CAULKING

CMP CORRUGATED METAL PIPE

CMU CONCRETE MASONRY

UNIT

CNTR COUNTER

CO CLEAN OUT

CO2 CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINATION

COMB COMBUSTION

COMP COMPRESSIBLE

COMPR COMPRESSOR

CONC CONCRETE

CONF CONFERENCE

CONN CONNECTION

CONSTR CONSTRUCTION

CONSTR

JT

CONSTRUCTION JOINT

CONT CONTINUOUS

(CONTINUATION)

CONTR CONTRACTOR

COR CORNER

CORR COVERED

COV CORRIDOR

CPL CEMENT PLASTER

CPS CYCLES PER SECOND

(HERTZ)

CPT CARPET

CR CONDENSER WATER

RETURN

CRES CORROSIVE RESISTANT

STEEL

CRG CARRIAGE

CRSE COURSE

CS CONDENSER WATER

SUPPLY

CS COUNTER SINK

CSMT CASEMENT

CT CERAMIC TILE

CT CURRENT TRANSFORMER

CTL CARPET TILE

CU CONDENSING UNIT

CU YD CUBIC YARDS

CUH CABINET UNIT HEATER

CV CEILING VENT

CW COLD WATER

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

CYL CYLINDER

D DEPTH (DEEP)

D DIFFUSER

d PENNY (as in nail - 10d)

D&M DRESSED AND MATCHED

DA DOUBLE ACTING

DB DRY BULB

dB DECIBEL

DBL DOUBLE

DC DIRECT CURRENT

DCJ DOWELED CONTROL

JOINT

DCJT DUMMY CONTROL JOINT

DCL DOOR CLOSER

DCW DOMESTIC COLD WATER

DEG DEGREE

DEMO DEMOLITION

DEPR DEPRESSION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DH DOUBLE HUNG

DHW DOMESTIC HOT WATER

DI DEIONIZED WATER

DIA DIAMETER

CLO CLOSET

FR FIRE RATED

U/C UNDER CABINET

SYMBOL LEGEND

PLAN VIEW

SECTION / ELEVATION VIEW

SHEAR WALL

MASONRY-CMU

CONCRETE

GRAVEL

EARTH / COMPACTED

EARTH /

NONCOMPACTED

RIGID INSULATION

JOINT FILLER

STEEL

GYPSUM

MASONRY-VENEER

STUD WALL

FLEXIBLE INSULATION

GROUT

PLYWOOD

WOOD (FINISH)

MASONRY-CMU FACE

MASONRY-CMU

MASONRY-VENEER

A 00 ARCHITECTURAL INFO SHEET

A101 ATTIC PLAN

A102 ROOF PLAN

1 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION

TO THE BOTTOM SIDE OF THE EXPOSED ROOF DECK IN ATTIC

SPACE.

2 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION

TO THE BOTTOM SIDE OF ROOF DECK ABOVE CEILING IN

ASSEMBLY 103 ROOM BELOW.

3 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION

TO THE BOTTOM SIDE OF THE EXPOSED ROOF, DECK, AND

SOFFIT IN ATTIC SPACE.

4 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION

TO INTERIOR SIDE OF VERTICAL WALL IN ATTIC SPACE

5 JUNCTION BOXES AND ITEMS REQUIRING FUTURE ACCESS FOR

REPAIRS, MAINTENANCE, ETC TO REMAIN ACCESSIBLE AFTER

SPRAY INSULATION HAS BEEN INSTALLED. - COORDINATE W/

MECH AND ELEC

6 EXISTING RIDGE VENTS AND SOFFIT VENTS TO BE BLOCKED AND

SEALED PRIOR TO THE APPLICATION OF SPRAY FOAM

INSULATION. BLOCKING SHALL BE DARK OR BRONZE COLOR AND

OF WEATHER PROOF MATERIAL.

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND

LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER OF ANY

DISCREPANCIES OR VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE

CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO ADDITIONAL

EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL

NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF

DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE

FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO

ADDITIONAL EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS

WITH ALL OTHER TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN.

FULL-TONE LINES INDICATE NEW OR RELOCATED CONSTRUCTION.

E. DIMENSIONS ARE TYPICALLY TO FINISH FACE OF MASONRY, CONCRETE, GYPSUM

WALL BOARD, AND METAL FRAMES; OR CENTER LINE OF COLUMN OR BEAMS,

UNLESS NOTED OTHERWISE.

F. ALL ANGLES ON THE FLOOR PLANS ARE 45 OR 90 DEGREES UNLESS OTHERWISE

INDICATED.

G. PROVIDE FIRE TREATED 2x6 OR LARGER WOOD BLOCKING IN WALLS AND FURRING

SPACES AS REQUIRED FOR MOUNTING OF ALL WALL SUPPORTED ITEMS. WHETHER

OR NOT DETAILED ON THE DRAWINGS, THE CONTRACTOR SHALL COORDINATE AND

INSTALL ALL STIFFENERS, BRACING, BACK-UP PLATES, AND SUPPORTING BRACKETS

AS REQUIRED FOR THE INSTALLATION OF WALL MOUNTED OR SUSPENDED

MECHANICAL, ELECTRICAL, OR MISCELLANEOUS EQUIPMENT. THESE ITEMS

INCLUDE, BUT ARE NOT LIMITED TO, CONTROL PANELS, FIRE ALARM PANELS AND

MASTER CLOCKS, ETC.

H. PATCH EXISTING WALLS, FLOORS, AND CEILING SURFACES DEMOLISHED, CUT,

CORED, OR ALTERED IN ANY WAY TO ACCOMMODATE NEW CONSTRUCTION.

I. PATCH ALL CONCRETE SLAB LOCATIONS DEMOLISHED TO INSTALL NEW

STRUCTURAL, MECHANICAL, OR ELECTRICAL WORK.

DATE INITIAL

A

TT

A C

H M

EN

UP

UP

A

B

C

D

E

1 2 3 4 5

A101

A101

A101

A101

1 5

FIRST FLOOR

100' - 0"

ATTIC LEVEL

112' - 0"

AB

SPRAY FOAM INSUL

ON BOTTOM SIDE

OF ROOF DECK AND

INT. SIDE OF EXT

WALLS IN ATTIC

SPACE

FIRST FLOOR

100' - 0"

ATTIC LEVEL

112' - 0"

AB

FIRST FLOOR

100' - 0"

ATTIC LEVEL

112' - 0"

B

SPRAY FOAM INSUL

ON BOTTOM SIDE OF

ROOF DECK AND INT.

SIDE OF EXT WALLS

IN ATTIC SPACE

FIRST FLOOR

100' - 0"

ATTIC LEVEL

112' - 0"

B

SPRAY FOAM INSUL

ON BOTTOM SIDE OF

ROOF DECK

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p

\0

-A R

C H

R

-P E

R I_ jf ie d le r.

rv t

JLF

Author

MJH

02/25/2020

07310.007

A101

ATTIC PLAN

07310007PERI- 2- A101 ATTIC PLAN

1 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO THE

BOTTOM SIDE OF THE EXPOSED ROOF DECK IN ATTIC SPACE.

2 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO THE

BOTTOM SIDE OF ROOF DECK ABOVE CEILING IN ASSEMBLY 103 ROOM

BELOW.

3 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO THE

BOTTOM SIDE OF THE EXPOSED ROOF, DECK, AND SOFFIT IN ATTIC

SPACE.

4 APPLY 2 LAYERS OF 2" CLOSED CELL, SPRAY FOAM INSULATION TO

INTERIOR SIDE OF VERTICAL WALL IN ATTIC SPACE

5 JUNCTION BOXES AND ITEMS REQUIRING FUTURE ACCESS FOR REPAIRS,

MAINTENANCE, ETC TO REMAIN ACCESSIBLE AFTER SPRAY INSULATION

HAS BEEN INSTALLED. - COORDINATE W/ MECH AND ELEC

6 EXISTING RIDGE VENTS AND SOFFIT VENTS TO BE BLOCKED AND SEALED

PRIOR TO THE APPLICATION OF SPRAY FOAM INSULATION. BLOCKING

SHALL BE DARK OR BRONZE COLOR AND OF WEATHER PROOF MATERIAL.

REF. NOTES ( ):X

SCALE: 1/8" = 1'-0"

ATTIC LEVEL - AREA PLANS

NORTH

SCALE: 1/8" = 1'-0"

ATTIC SECTION 1

SCALE: 1/8" = 1'-0"

ATTIC SECTION 2

SCALE: 1/8" = 1'-0"

ATTIC SECTION 3

SCALE: 1/8" = 1'-0"

ATTIC SECTION 4

SPRAY FOAM INSUL

ON BOTTOM SIDE OF

ROOF DECK AND INT.

SIDE OF EXT WALLS

IN ATTIC SPACE

DATE INITIAL

A

TT

A C

H M

EN

A

B

C

D

E

1 2 3 4 5

A101

A101

A101

A101

4 1/2" / 12" 4 1/2" / 12"

2/A102

5/A102

4/A102

3/A102

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p

\0

-A R

C H

R

-P E

R I_ jf ie d le r.

rv t

JLF

Author

MJH

02/25/2020

07310.007

A102

ROOF PLAN

07310007PERI- 2- A102 ROOF PLAN

SCALE: 1/8" = 1'-0"

ROOF PLAN

ATTIC PHOTO 4

ATTIC PHOTO 1

ATTIC PHOTO 2

ATTIC PHOTO 3

DATE INITIAL

A

TT

A C

H M

EN

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY

THE OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR

SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS

AND NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES

OR VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE

CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO

ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE

SET OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK.

CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO

FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND

BE RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO

OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL

OTHER TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION

TO REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED

CONSTRUCTION.

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL

DUCTWORK WITH STRUCTURE, CEILING, LIGHTING, AND PIPING.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL

PANELS. MAINTAIN ALL CODE REQUIRED CLEARANCES.

H. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,

MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED

PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT

BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL

IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT

THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE

WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE

RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND

CONTRACTOR.

I. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INTLET SIZE

UNLESS OTHERWISE NOTED.

J. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND

GENERAL CONTRACTOR.

A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE

ORIGINAL DRAWINGS PROVIDED BY THE OWNER AND LIMITED

FIELD VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,

RELOCATED, OR SALVAGED ARE SHOWN AS DASHED, FULL-TONE

LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND

ARE SHOWN AS HALF-TONE.

B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS

LISTED BELOW OR HERE-IN. THE CONTRACTOR SHALL

COORDINATE ALL REQUIRED RENOVATION AND NEW

CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE

TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED

BELOW.

C. THE REMOVAL OF HVAC AND PLUMBING EQUIPMENT FROM

FINISHED AREAS AND THROUGH WEATHER BARRIERS SHALL BE

COORDINATED WITH ARCHITECTURAL PLANS AND DETAILS AS

WELL AS NOTES ON THE MECHANICAL DRAWING TO ENSURE

PROPER PATCHING AND REPAIR IS MADE TO THE BUILDING.

D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION

AND REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS,

EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD,

ERECT, INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION

WITH THE OWNER HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.

E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED

SHALL BE CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT

DAMAGE AND STORED OR REINSTALLED ON THE SITE AS

DIRECTED. REMOVED OR SALVAGED ITEMS SHALL REMAIN THE

PROPERTY OF THE OWNER.

F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND

CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO

MECHANICAL REMOVALS.

G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,

MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED

PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT

BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL

IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT

THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE

WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE

RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND

ARCHITECT.

H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING

DEMOLITION SHALL BE COORDINATED WITH THE OWNER AND

GENERAL CONTRACTOR.

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M 00

MECHANICAL INFO SHEET

07310007PERI- 5- M 00 MECHANICAL INFO SHEET

TRUE

NORTH

PLAN

NORTH

NORTH

SYMBOL LEGEND

VOLUME DAMPER

DEMO TO EXISTING CONNECTION

SPRINKLER DRAIN

FIRE SUPPRESSION PIPING

ISOLATION VALVE

TAMPER SWITCH

MANUAL BALANCING VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

CONTROL VALVE (3 WAY)

CONTROL VALVE (2 WAY)

HOSE END DRAIN VALVE

PRESSURE REDUCING VALVE

AUTO FLOW CONTROL VALVE

CHECK VALVE

HVAC DUCTWORK AND SPECIALTIES

(CONT.)

MISCELLANEOUS SYMBOLS

RETURN DUCT DOWN

AIR TERMINAL (VERTICAL MOUNTING)

ROUND DUCT UP / DOUBLE LINE PIPE

ROUND DUCT DOWN / DOUBLE

LINE PIPE

RETURN DUCT UP

TURNING VANES

SUPPLY AND FRESH AIR DUCT DOWN

SUPPLY AND FRESH AIR DUCT UP

SIZE/TYPE

SIZE/TYPE

FLOW

FLOW

SIZE/TYPE

FLOW

SMOKE DAMPER

FIRE DAMPER-HORIZ FIRE SEPARATION

MOTORIZED DAMPER-OPPOSED BLADE

MOTORIZED DAMPER-PARALLEL BLADE

ROUND AIR TERMINAL

(HORIZONTAL MOUNTING)

GRAVITY DAMPER

(OR) SAFETY VALVE-STEAM

TEMP & PRESS RELIEF

FLOOR SINK

FLOOR DRAIN

GRADE CLEANOUT

PLUMBING VENT THRU ROOF

CLEANOUT / WALL CLEANOUT

THERMOSTATIC MIXING VALVE

M

M

MANHOLE

TRENCH DRAIN

OVERFLOW ROOF DRAIN

OXYGEN OUTLET

PIPE CAP

ELBOW UP

AIR OUTLET

TEE

ELBOW DOWN

VACUUM OUTLET

ROOF DRAIN

SIZE/TYPE

FLOW

HUMIDISTAT

THERMOSTAT

FLEXIBLE DUCT

S

H

T

TEMPERATURE SENSORUNION

TEE DOWN

STRAINER

EXPANSION JOINT

FLEXIBLE PIPE CONNECTION

AIR VENT

TEE UP

FIRE/SMOKE DAMPER

RECTANGULAR RETURN AIR TERMINAL

(HORIZONTAL MOUNTING)

RECTANGULAR SUPPLY AIR TERMINAL

(HORIZONTAL MOUNTING)

SOLENOID VALVE

F

D

TS

VALVES

FS

M

M

S

LPR

HPS

MPR

MPS

LPS

HVAC PIPING

GHWR

GHWS

HWR

HWS

PC

HPR

ES

BBD BOILER BLOW DOWN

EXHAUST STEAM

PUMPED CONDENSATE

HIGH PRESSURE RETURN

HIGH PRESSURE STEAM

MEDIUM PRESSURE RETURN

MEDIUM PRESSURE STEAM

LOW PRESSURE RETURN

LOW PRESSURE STEAM

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

FS-_

FD-_

CO

VTR

GCO

ORD-_

MH

X

A

V

RD-_

PIPING SPECIALTIES AND FITTINGS

WCO

FIRE PROTECTION

SIZE/TYPE

FLOW

RECTANGULAR EXHAUST AIR TERMINAL

(HORIZONTAL MOUNTING)

CWS

GCWS

CWR

CR

CS

RL

RDL

RS

GCWR GLYCOL CHILLED WATER RETURN

GLYCOL CHILLED WATER SUPPLY

REFRIGERANT LIQUID LINE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION LINE

HCWS

HCWR

HOT/CHILLED WATER SUPPLY

HOT/CHILLED WATER RETURN

DOMESTIC HOT WATER

RECIRCULATING (DHWR)

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

ST/OST

PLUMBING PIPING

ACID VENT

TW

AV

AW

W

DS

DSCW

TWR

DSHW

SANITARY VENT

BURIED EXTERIOR WATER

TEPID WATER RECIRCULATING

TEPID WATER

DISTILLED WATER

SOFTENED HOT WATER

SOFTENED COLD WATER

ACID WASTE

STORM DRAIN

SANITARY DRAIN (BELOW FLOOR)

SANITARY DRAIN (ABOVE FLOOR)

OXYGEN

VACUUM

OX

VAC

RO

A

REVERSE OSMOSIS WATER

COMPRESSED AIR

DEIONIZED WATERDI

AIR FLOW STATIONAFS

HPWR

HPWS

HEAT PUMP WATER RETURN

HEAT PUMP WATER SUPPLY

F

S

FS

NEW TO EXISTING CONNECTION

G NATURAL GAS

FOF

FOG

LPG

FOV

FOR

FOS

FUEL OIL RETURN

FUEL OIL SUPPLY

FUEL OIL GAGE

FUEL OIL FILL

FUEL OIL VENT

LIQUEFIED PETROLEUM GAS

CD CONDENSATE DRAIN

EXHAUST DUCT DOWN

EXHAUST DUCT UP

CO CARBON MONOXIDE SENSOR

CO2 CARBON DIOXIDE SENSOR

NO2 NITROGEN DIOXIDE SENSOR

SENSOR WITH GUARD'X'

DOUBLE - GRADE CLEANOUTDGCO

ST/OST STORM DRAIN (BELOW FLOOR)

WASTE AND ANESTHETIC

GAS DISPOSAL

NITROGEN

WAGD

N

MEDICAL AIRMA

PIPE GUIDE

HOSE BIBB

THERMOMETER

PIPE ANCHOR

HB

STEAM TRAP

RHY

WH

ROOF HYDRANT

WALL HYDRANT

PRESSURE GAUGE

EXISTINGDEMO

EXISTINGNEW

18 Ø

18x10

18/10

ROUND DUCT

FLAT OVAL DUCT-1ST FIG IS SIDE

SHOWN

RECT DUCT-1ST FIG IS SIDE SHOWN

ACOUSTICAL DUCT LINER

HVAC DUCTWORK AND SPECIALTIES

HIGH EFFICIENCY TAKEOFF

HIGH EFFICIENCY TAKOFF

WITH VOLUME DAMPER

NITROGEN OUTLET

MEDICAL AIR OUTLET

WASTE AND ANESTHETIC GAS

DISPOSAL OUTLET

N

MA

V

FLEXIBLE DUCTWORK CONNECTION

ABBREVIATIONS

NORTH

ARROW

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW

COLUMN

X

X

X

XXXX

SIM/OPP

X

XXXX

XX-1

X

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

ROOM / SPACE

NUMBER

LETTER/NUMBER

INDICATES NEW

COLUMN LINE

LETTER/NUMBER

INDICATES EXISTING

COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DRAWING/DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE DRAWING

XXX-1

PLUMBING

FIXTURES PLUMBING FIXTURE

DESIGNATION

X"PIPE

SIZE

PIPE SIZE (DIAMETER)

X"xX"

DUCT

SIZE

WIDTH x HEIGHT

X"/X" WIDTH / HEIGHT

X" DIAMETER

REF. DEMO NOTES ( ) XX REF. NOTES ( )

SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.

GENERAL DEMOLITION NOTES GENERAL NOTES

MECHANICAL SHEET LIST

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MBH 1000 BTUH

MCA MINIMUM CIRCUIT AMPS

MD MOTORIZED DAMPER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT

PROTECTION

MPR MEDIUM PRESSURE

RETURN

MPS MEDIUM PRESSURE STEAM

MS MOP SINK

N NITROGEN

NC NORMALLY CLOSED

NO NORMALLY OPEN

NPCW NONPOTABLE COLD WATER

NPHW NONPOTABLE HOT WATER

NPHWR NONPOTABLE HOT WATER

RECIRCULATING

OA OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

OX OXYGEN

P PUMP

PHC PREHEAT COIL

PIV POST INDICATING VALVE

PRV PRESSURE REGULATING VALVE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH,

GAUGE

PTAC PACKAGED TERMINAL AIR

CONDITIONER

RA RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF AREA DRAINS

RL REFRIGERANT DISCHARGE LINE

RF RETURN FAN

RH RELIEF HOOD

RHC REHEAT COIL

RL REFRIGERANT LIQUID LINE

RLA RELIEF AIR

RLF RELIEF FAN

RO REVERSE OSMOSIS WATER

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION LINE

RTU ROOF TOP UNIT

RV RELIEF VALVE

S SINK

SA SUPPLY AIR

SAN SANITARY SEWER

SD SMOKE DAMPER

SF SUPPLY FAN

SFU SANITARY FIXTURE UNIT

SH SHOWER

SP STATIC PRESSURE

SSS SURGICAL SCRUB SINK

ST STORM WATER

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVE

TONS TONS OF REFRIGERATION

TSP TOTAL STATIC PRESSURE

T THERMOSTAT

UH UNIT HEATER

UR URINAL

V VENT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

WB WET BULB

WC WATER CLOSETS

WCO WALL CLEANOUT

WF WASH FOUNTAINS

WFU WATER FIXTURE UNITS

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WS WATER SOFTENER

WSHP WATER SOURCE HEAT PUMP

WWHP WATER TO WATER HEAT PUMP

YH YARD HYDRANT

A COMPRESSED AIR

AC AIR COMPRESSOR

AD AIR DOOR

AFCV AUTO FLOW CONTROL VALVE

AHU AIR HANDLING UNIT

AMP AMPERE

APD AIR PRESSURE DROP

AS AIR SEPARATOR

AV ACID VENT

AW ACID WASTE

B BOILER

BC BLOWER COIL

BD BIDET

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BHP BRAKE HORSEPOWER

BLKG BLOCKING

BLV BALANCING VALVE

BT BATHTUB

BV BALL VALVE

BW BEDPAN WASHER

CH CHILLER

CC COOLING COIL

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CUH CABINET HEATER

CI CAST IRON

CMU COMBINATION UNITS

CR CONDENSER WATER RETURN

CRAC COMPUTER ROOM AIR

CONDITIONER

CS CONDENSER WATER SUPPLY

CSS CLINICAL SERVICE SINKS

CT COOLING TOWER

CU CONDENSING UNIT - SPLIT SYSTEM

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

DB DRY-BULB TEMPERATURE

DCW DOMESTIC COLD WATER

DEG DEGREE

DF DRINKING FOUNTAIN

DGCO DOUBLE GRADE CLEANOUT

DH EMERGENCY DRENCH HOSES

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER

RECIRCULATING

DI DEIONIZED WATER

DOAS DEDICATED OUTDOOR AIR SYSTEM

DS DISTILLED WATER

DSA DUCT SOUND ATTENUATORS

DSCW DOMESTIC SOFT COLD WATER

DSHW DOMESTIC SOFT HOT WATER

DSHWR DOMESTIC SOFT HOT WATER

RECIRCULATING

DST DOMESTIC STORAGE TANK

DTW DOMESTIC TEPID WATER

DTWR DOMESTIC TEPID WATER

RECIRCULATING

EA. EACH

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDH ELECTRIC DUCT HEATER

EEW EMERGENCY EYE WASH

EEWS EMERGENCY EYE

WASH/SHOWER

EF EXHAUST FAN

EFF EFFICIENCY

EFW EMERGENCY FACE WASH

EH EXHAUST HOOD

ERV ENERGY RECOVERY

VENTILATOR

ES EMERGENCY SHOWER

ESP EXTERNAL STATIC PRESSURE

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER

TEMPERATURE

ET EXPANSION TANK

F FIRE SUPPRESSION PIPING

F-_ FURNACE

FCO FLOOR CLEANOUT

FC FLUID COOLER

FCU FAN COIL UNIT

FD FIRE DAMPER

FLA FULL LOAD AMPS

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOOR SINK

FSD FIRE/SMOKE DAMPER

FT FINNED TUBE

G GAS

GCWR GLYCOL CHILLED

WATER RETURN

GCWS GLYCOL CHILLED

WATER SUPPLY

GD GARBAGE DISPOSAL

GDH GAS DUCT HEATER

GHCR GLYCOL HOT/CHILLED

WATER RETURN

GHCS GLYCOL HOT/CHILLED

WATER SUPPLY

GHWR GLYCOL HOT WATER RETURN

GHWS GLYCOL HOT WATER SUPPLY

GI GREASE INTERCEPTOR

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GV GAS VENT

GWH GAS WATER HEATER

HB HOSE BIBB

HC HEATING COIL

HCR HOT/CHILLED WATER RETURN

HCS HOT/CHILLED WATER SUPPLY

ACC AIR COOLED CONDENSER

ACCU AIR COOLED CONDENSING UNIT

ASHP AIR SOURCE HEAT PUMP

ARU AIR ROTATION UNIT

OI OIL INTERCEPTOR

SOI SAND OIL INTERCEPTOR

DSS DUCTLESS SPLIT SYSTEM

SP SUMP PUMP

OST OVERFLOW STORM WATER

WMB WASHING MACHINE BOX

OB OUTLET BOX

RH ROOF HYDRANT

H HUMIDIFIER

DHWP DOMESTIC HOT WATER

RECIRCULATING PUMP

DWET DOMESTIC WATER EXPANSION

TANK

HP HORSEPOWER

HPR HIGH PRESSURE RETURN

HPS HIGH PRESURE STEAM

HRC HEAT RECOVERY COIL

HWR HOT WATER RETURN (HEATING)

HWS HOT WATER SUPPLY (HEATING)

HX HEAT EXCHANGER

HY HYDRANTS

HP-_ HEAT PUMP

HVLS HIGH VOLUME LOW SPEED

IH INTAKE HOOD

IRH INFRARED RADIANT HEATER

KH KITCHEN HOOD

KW KILOWATT

KWH KILOWATT HOURS

L LAVATORY

LAT LEAVING AIR TEMPERATURE

LPR LOW PRESSURE RETURN

LPG LIQUIFIED PETROLEUM GAS

LPS LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LS LAUNDRY SINK

LV LOUVER

LWT LEAVING WATER TEMPERATURE

PROJECT MECHANICAL REFERENCED DEMOLITION NOTES PROJECT MECHANICAL REFERENCED NOTES

M 00 MECHANICAL INFO SHEET

M001 DEMOLITION FLOOR PLAN - MECHANICAL

M101 FIRST FLOOR PLAN - MECHANICAL

M102 ATTIC LEVEL PLAN - MECHANICAL

M201 PIPING FLOOR PLAN - MECHANICAL

M401 DETAILS - MECHANICAL

M501 SCHEDULE - MECHANICAL

DATE INITIAL

A

TT

A C

H M

EN

M001

UH (E)

UH (E)

UH (E)

UH (E)

UH (E)UH (E)

VAV-1 (E)

VAV-3 (E)

VAV-7 (E)

VAV-5 (E)

VAV-2 (E)

VAV-4 (E) VAV-6 (E) VAV-8 (E)

VAV-9 (E)

VAV-10(E)

VAV-11(E)

VAV-12(E)

H-1 (E)

AHU-1(E)

A

B

C

D

E

2 3 4

EQUIP.

STORAGE

EQUIP.

STORAGE

SHOP

STOR.

STOR.

TOILET

SOLARIUM

ASSEMBLY

MUSEUM

FOYER

VIEW AREA

LOBBY

HISTORIAN

RANGER

SUPT.

MECH. EQUIP.

ROOM

WOMEN'S

MEN'S

OFFICE

PASSAGE

IT ROOM

EQUIPMENT LOCATED IN DASHED

AREA LOCATED IN PROJECTION

ROOM ABOVE CLOSETS.

EQUIPMENT AND PIPING LOCATED

IN DASHED AREA LOCATED

IN ATTIC SPACE.

H W

R H W

S

C W

R

C W

S

H W

S H W

R

B

MECH. EQUIP.

ROOM

L P

B

C

3 4

VAV-10(E)

VAV-11(E)

VAV-12(E)

VAV-9 (E)

VAV-8 (E)

AHU-1(E)

H-1 (E)

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M001

DEMOLITION FLOOR PLAN -

MECHANICAL

07310007PERI- 5- M001 DEMOLITION FLOOR PLAN - MECHANICAL

REF. DEMO NOTES ( ):X

1 DEMO EXISTING BOILERS, HOUSEKEEPING PAD, AND PIPING AS SHOWN

ON PLAN.

2 DEMO EXISTING SPLIT SYSTEM CONDENSING UNIT, INDOOR CONSOLE,

CONTROLS, AND REFRIGERANT LINES.

3 DEMO EXISTING AIR COOLED CHILLER, EQUIPMENT PAD, AND PIPING

BACK TO LOCATION SHOWN ON PLANS.

4 DEMO EXISTING HUMIDIFIER ON WALL. DEMO SUPPLY PIPING BACK TO

LOCATION SHOWN ON PLAN. SANITARY DRAIN TO REMAIN FOR FUTURE

USE.

5 DEMO BOILER FLUE AND INTAKE PIPING UP THROUGH CEILING AND ROOF.

TWO SET OF PENETRATIONS TO BE REUSED. PATCH ROOF WHERE FLUE

IS REMOVED TO MATCH EXISTING. COORDINATE WITH PARK STAFF FOR

LOCATION OF SPARE SHINGLES FROM PREVIOUS ROOFING SCOPE.

INFILL UNUSED PENETRATIONS THROUGH CEILING WITH MATERIALS TO

MATCH EXISTING CONSTRUCTION AND FINISHES.

6 DEMO SECTION OF CWR PIPING FOR INSTALLATION OF BUFFER TANK

PIPING.

7 REMOVE SECTION OF SUPPLY DUCT FOR INSTALLATION OF NEW

HUMIDIFIER DISTRIBUTION MANIFOLD AND STAINLESS STEEL DUCTWORK.

8 DEMO EXISTING HUMIDIFIER ON WALL. DEMO DISTRIBUTION MANIFOLD IN

SUPPLY DUCT. PATCH AND SEAL DUCT AIR TIGHT. PATCH DUCT

INSULATION TO MATCH EXISTING.

SCALE: 1/8" = 1'-0"

FIRST FLOOR DEMOLITION PLAN - MECHANICAL PIPING

SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM DEMOLITION PLAN - MECHANICAL

NORTH

SCALE: 1/8" = 1'-0"

PARTIAL ATTIC LEVEL PLAN - DEMO HVAC

DATE INITIAL

A

TT

A C

H M

EN

T T T

T

T T

T

T

T

T

T

H

H

T S

(TYPICAL)

CH-1

DSS-1B

DSS-1A

(TYPICAL)

A

B

C

D

E

2 3 4

EQUIP.

STORAGE

EQUIP.

STORAGE

SHOP

STOR.

STOR.

TOILET

IT ROOM

MECH. EQUIP.

ROOM

SUPT.

RANGER

HISTORIAN

VIEW AREA

LOBBY

OFFICE

MEN'S

WOMEN'S

SOLARIUM

FOYER

ASSEMBLY

MUSEUM

2 3

TO H-2

TO H-1

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M101

FIRST FLOOR PLAN -

MECHANICAL

07310007PERI- 5- M101 FIRST FLOOR PLAN - MECHANICAL

REF. NOTES ( ):X

1 NEW CONDENSING UNIT TO BE INSTALLED ON EXISTING CONCRETE

EQUIPMENT PAD.

2 SPLIT SYSTEM INDOOR UNIT TO BE MOUNTED HIGH ON WALL. PATCH

WALL AS NECESSARY WHERE EXISTING UNIT WAS REMOVED TO MATCH

ADJACENT CONSTRUCTION.

3 CONTROLS TO BE REPLACED WITH NEW BACNET SYSTEM. NEW DEVICES

TO BE LOCATED IN SAME LOCATION AS EXISTING DEVICES. PROVIDE

BACKING PLATE AS REQUIRED TO COVER EXISTING CONSTRUCTION.

4 LINE VOLTAGE CONTROLS FOR SHOP AND GARAGE UNIT HEATERS TO

REMAIN.

5 NEW 12" CONCRETE PAD SIZED TO ACCOMMODATE NEW CHILLER

DIMENSIONS PLUS 6" ON ALL SIDES. SEE DETAIL 6/M401 FOR PAD

CONSTRUCTION.

6 INSTALL NEW HUMIDIFIER HUMIDISTAT NEAR EXISTING THERMOSTAT.

7 WALL MOUNTED THERMOSTAT FOR DUCTLESS SPLIT SYSTEM TO BE

INSTALLED AT 48" A.F.F. PROVIDE SPACE TEMPERATURE SENSOR FOR

BMS SYSTEM TO MONITOR AND ALARM I.T. ROOM SPACE TEMPERATURE.

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - MECHANICAL

NORTH

DATE INITIAL

A

TT

A C

H M

EN

H

28 Ø SA

32x32 RA

20 Ø SA

H-2

(TYPICAL

OF ALL

VAVs)

H-1

VAV-3 (E) VAV-7 (E) VAV-5 (E)

VAV-1 (E)

VAV-2 (E)

VAV-4 (E)

VAV-6 (E) VAV-8 (E)

VAV-9 (E)

VAV-10(E)

VAV-11(E)

VAV-12(E)

AHU-1(E)

A

B

C

D

E

2 3 4

18x18 SA

5 (TYPICAL)

26x26 SA

Ø

S A

28 Ø

EF-1

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M102

ATTIC LEVEL PLAN -

MECHANICAL

07310007PERI- 5- M102 ATTIC LEVEL PLAN - MECHANICAL

REF. NOTES ( ):X

1 CONTROLS TO BE REPLACED WITH NEW BACNET SYSTEM. PROVIDE

INTERFACE FOR EXISTING DAMPER AND VALVE OPERATORS.

CONTRACTOR TO RECORD OPERATING SETPOINTS AND SET NEW

CONTROL SYSTEM TO MATCH.

2 NEW HUMIDIFIER STEAM GENERATOR HUNG ON WALL.

3 REPLACE DUCT WHERE HUMIDIFIER IS TO BE INSTALLED. REPLACE WITH

18X18 DUCT CONSTRUCTED OF STAINLESS STEEL. BOTTOM OF DUCT TO

BE SLOPED TO DRAIN CONDENSATE IN DUCT SYSTEM. PROVIDE 1/2"

DRAIN FROM BOTTOM OF DUCT TO NEAREST DRAIN OR CONDENSATE

PUMP.

4 REPLACE DUCT WHERE HUMIDIFIER IS TO BE INSTALLED. REPLACE WITH

26X26 DUCT CONSTRUCTED OF STAINLESS STEEL. BOTTOM OF DUCT TO

BE SLOPED TO DRAIN CONDENSATE IN DUCT SYSTEM. PROVIDE 1/2"

DRAIN FROM BOTTOM OF DUCT TO NEAREST DRAIN OR CONDENSATE

PUMP.

5 LOW PRESSURE DISTRIBUTION DUCTWORK AND AIR TERMINALS DOWN

STREAM OF VAV BOXES TO REMAIN.

6 EXISTING OUTDOOR, RELIEF, AND RETURN DUCTWORK TO REMAIN.

7 LOCATE STEAM DISPERSION TUBE IN DUCT PER MANUFACTURER

REQUIREMENTS.

8 EXTEND EXISTING VAV PRIMARY DUCT TO NEW DUCT DOWNSTREAM OF

STEAM DISPERSION MANIFOLD. DUCT CONNECTION TO BE PAST THE

STEAM ABSORPTION DISTANCE OUTLINED BY HUMIDIFIER

MANUFACTURER.

9 INSTALL EXHAUST FAN HIGH ON EXTERIOR WALL FOR ATTIC VENTILATION.

FAN TO BE CONTROLLED BY HUMIDISTAT TO ENERGIZE FAN WHEN ATTIC

SPACE RELATIVE HUMIDITY EXCEEDS 60%RH.

10 PROVIDE 12X12 TRANSFER GRILLE ON EACH SIDE OF DOOR. INSTALL

BOTTOM OF GRILLE 12" A.F.F.

SCALE: 1/8" = 1'-0"

ATTIC LEVEL PLAN - MECHANICAL

NORTH

DATE INITIAL

A

TT

A C

H M

EN

M

M201

H-2

AHU-1(E)

VAV-9 (E)

VAV-8 (E)VAV-6 (E)

VAV-4 (E)

VAV-2 (E)

VAV-1 (E)

VAV-3 (E)

VAV-7 (E) VAV-5 (E)

VAV-12(E)

VAV-11(E)

VAV-10(E)

DSS-1B

UH (E)

UH (E) UH (E)

UH (E)

UH (E)UH (E)

H-1

A

B

C

D

E

2 3 4

MUSEUM

FOYER

VIEW AREA

LOBBY

SOLARIUM

ASSEMBLY

STOR.

TOILET

IT ROOM

MECH. EQUIP.

ROOM

PASSAGE

WOMEN'S

MEN'S

OFFICE

SUPT.

RANGER

HISTORIAN

STOR.

SHOP

EQUIP.

STORAGE

EQUIP.

STORAGE

EQUIPMENT AND PIPING LOCATED

IN DASHED AREA LOCATED

IN ATTIC SPACE.

EQUIPMENT LOCATED IN DASHED

AREA LOCATED IN PROJECTION

ROOM ABOVE CLOSETS.

HWS

HWR

C D

3/4"

P-1

P-2

CD

CD

3/4"

CH-1

C W

S C

W R

H W

R

H W

S C W

R

C W

S

H W

S

H W

R

M501

B -1

B B

-1 A

W P

-2

E

W P

-1

E

WP-3 (E) WP-4 (E)

PIPING UP INTO

ATTIC SPACE

DSS-1A

BT-1

B

2 1/2"2 1/2"

R L

R S

EXISTING

GLYCOL

FEED TANK

L P

EXISTING LP LINE BELOW

GRADE TO STORAGE TANK

2"

L P

CONNECTION TO

EXISTING WATER HEATER

2 1/2"

1 1/4"

2"

2"

2"

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M201

PIPING FLOOR PLAN -

MECHANICAL

07310007PERI- 5- M201 PIPING FLOOR PLAN - MECHANICAL

REF. NOTES ( ):X

8 CONDENSATE PUMP LOCATED ON ATTIC FLOOR. PIPE 3/4" CONDENSATE

FROM PUMP TO EXISTING CONDENSATE DISPOSAL POINT IN PROJECTION

ROOM. HUMIDIFIER TO HAVE INTERNAL CONDENSATE COOLER.

9 PROPANE FLOW METER INSTALLED IN LP LINE TO BOILERS AND WATER

HEATER. METER TO LOG AND TRACK PROPANE USE TO NEW BUILDING

BMS SYSTEM. ONICON F-5500 OR EQUAL.

10 EXTEND DCW TO NEW HUMIDIFIER LOCATION.

11 STEAM DISTRIBUTION PIPING AND CONDENSATE DRAIN FROM STEAM

GENERATOR TO DISPERSION TUBES SIZED AND INSTALLED PER

MANUFACTURER REQUIREMENTS. SUPPLY AND DRAIN LINES TO BE

INSULATED PER SPECIFICATIONS.

12 PVC FLUE AND VENT UP THROUGH CEILING TO CONCENTRIC ROOF VENT.

REUSE EXISTING PENETRATIONS. PROVIDE NEW FLASHING AT

CONCENTRIC VENT THROUGH ROOF.

13 MAINTAIN EXISTING AIR SEPARATOR, EXPANSION TANK, AND MAKE-UP

WATER CONNECTION FOR HEATING HOT WATER SYSTEM.

1 NEW 12" CONCRETE PAD SIZED TO ACCOMMODATE NEW CHILLER

DIMENSIONS PLUS 6" ON ALL SIDES. SEE DETAIL 6/M401 FOR PAD

CONSTRUCTION.

2 EXTEND 2-1/2" CHILLED WATER SUPPLY AND RETURN LINES TO NEW

CHILLER CONNECTIONS.

3 ADD BUFFER TANK TO CHILLED WATER SYSTEM TO MEET NEW AIR

COOLED CHILLER SYSTEM VOLUME REQUIREMENT. TANK TO SIT ON

CONCRETE HOUSEKEEPING PAD.

4 EXTEND HOT WATER SUPPLY AND RETURN LINES AND LP GAS PIPING TO

NEW WALL HUNG BOILERS. SEE ELEVATION 1/M501.

5 CONDENSATE DRAIN FROM HIGH WALL UNIT TO BE PIPED TO TAILPIECE

OF LAVATORY DRAIN.

6 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S

REQUIREMENTS AND THE SPECIFICATIONS. REFRIGERANT LINE ROUTING

TO FOLLOW PATH OF EXISTING LINESETS THAT WERE REMOVED.

7 PROVIDE BACKFLOW PREVENTER FOR HUMIDIFIER SUPPLY. PROVIDE 3/4"

DCW CONNECTION TO EACH HUMIDIFIER AFTER BACKFLOW PREVENTER.

SCALE: 1/8" = 1'-0"

FLOOR PLAN - MECHANICAL PIPING

SCALE: 1/4" = 1'-0"

FLOOR PLAN - MECHANICAL PIPING

NORTH

DATE INITIAL

A

TT

A C

H M

EN

T.O. EX. SLAB

INSULATION

THREADED ROD

INSULATION

THREADED ROD

HANGER, INSULATION ON

PIPE CONTINUOUS THROUGH

HANGER WITHOUT

SWALLOWING

PIPE, 1"Ø MAX

BAND

THREADED

ROD

HANGER

INSULATION

PIPE

SHIELD TO COVER

180° OF PIPE, SEE

CHART FOR LENGTH

SEE CHART

SHEILD LENGTH

SEE CHART

SHEILD LENGTH,

SWIVEL

SHIELD LENGTH FOR PIPE - NOT LESS THAN THE

FOLLOWING:

a. NPS 1/4" TO 3-1/2" 12" LONG AND .048" THICK

b. NPS 4" 12" LONG AND .06" THICK

NOTE:

1. THERMAL-HANGER SHIELDS: INSTALL WITH INSULATION SAME THICKNESS AS PIPING INSULATION.

SHIELD TO COVER

180° OF PIPE, SEE

CHART FOR LENGTH

SHIELD TO COVER

180° OF PIPE, SEE

CHART FOR LENGTH

THREADED ROD

U-BOLT (TYP.) UNISTRUT OR STEEL

ANGLE WITH LONG LEG

DOWN

SHIELD TO COVER

360° OF PIPE, SEE

CHART FOR LENGTH

HANGER, INSULATION ON

PIPE CONTINUOUS THROUGH

HANGER WITHOUT

SWALLOWING

PIPE (TYP.)

HANGER CLAMP

OR BAND

BOLT

STRAP

OR

ANGLE

ROD (TYP)

DUCT (TYP)

ANGLE (TYP)

NUT (TYP)

NOTES:

1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.

2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO DUCTWORK.

3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCT AS ROUND DUCT TENDS TO DEFORM ON TRAPEZE HANGERS.

4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINTAIN THE INTEGRITY OF THE VAPOR BARRIER.

5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALLY WRAPPED.

DIRT LEG

TO EQUIPMENT

SHUT-OFF VALVE

REMOVABLE

CAP

UNION

SUPPLY PIPING

PRESSURE REGULATOR (IF REQUIRED)

NOTE: FOLLOW ALL CODE

AND MANUFACTURERS

REQUIREMENTS FOR

AND INSTALLATION.

E X

H A

U S

T A

IR

IN

T

A K

E A

IR

CLAMP

ROOF BOOT AND

FLASHING

SHEET METAL STRAP

(CLAMP AND SHEET

METAL STRAP MUST BE

FIELD INSTALLED TO

SUPPORT THE WEIGHT

OF THE TERMINATION

KIT.)

10'-0" MIN.

M

IN

FASTEN FLASHING TO DECK

PER MANUFACTURER'S

REQUIREMETNS

CUT EXISTING SHINGLES AS

NECESSARY TO FIT AROUND

BOOT

EXISTING ROOF

PENETRATION

NOTES:

1/2"x1/2" CHAMFER STRIP

REMOVE AND CAULK.

6x6 - 10/10 WWF

#4 BENT RE-BAR

AT EACH CORNER

DRILL 3/4"Ø HOLE IN FLOOR SLAB

AND GROUT IN REBAR.

1. INSTALL NEW HOUSEKEEPING PADS AS INDICATED ON PLANS. VERIFY DIMENSIONS

WITH EQUIPMENT SIZES.

2. VERIFY SIZE AND LOCATION OF EQUIPMENT ANCHOR BOLTS.

3. PROVIDE DOWEL RODS 18" ON CENTER AROUND FULL PERIMETER OF PAD IF

LONG DIMENSION IS GREATER THAN 72".

4"

/256"

3-1/2"

FLOOR

UNDISTURBED SOIL

EXISTING PAVEMENT -

SEE PLAN

AIR COOLED CHILLER - SEE PLAN

12" DEEP CONCRETE FOUNDATION PAD

W/ #5 @ 12" O.C. E.W. TOP & BOTTOM

NOTES:

1. MINIMUM COMPRESSIVE STRENGTH (F'C AT 28 DAYS) SHALL BE

4,500 PSI WITH PORTLAND TYPE I CEMENT AND NORMAL

WEIGHT AGGREGATE 1 1/2" MAXIMUM SIZE - ASTM C33.

REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. 1/2"

PREFORMED EXPANSION JOINT PER D1751. MINIMUM

CONCRETE CLEAR COVER: 2" TOP, 3" BOTTOM, AND 3" SIDES.

2. CONTRACTOR SHALL ANCHOR EQUIPMENT PER EQUIPMENT

MANUFACTURER REQUIREMENTS USING HILTI KWIK BOLT III

EXPANSION ANCHORS OR HILTI HIT-HY 200 EPOXY ANCHORS.

3. CONTRACTOR SHALL VERIFY AND COORDINATE LENGTH AND

WIDTH OF PAD WITH SUBMITTED EQUIPMENT MANUFACTURER.

4. CONTRACTOR SHALL VERIFY AND COORDINATE ALL OPENING

SIZES AND LOCATIONS REQUIRED IN FOUNDATION PAD.

SEAL AROUND PERIMETER BETWEEN

NEW EQUIPMENT PAD AND EXISTING

PAVEMENT.

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M401

DETAILS - MECHANICAL

07310007PERI- 5- M401 DETAILS - MECHANICAL

SCALE: NOT TO SCALE

PIPE HANGER DETAIL

SCALE: NOT TO SCALE

DUCT HANGER DETAIL

SCALE: NOT TO SCALE

TYPICAL GAS PIPING DETAIL

SCALE: NOT TO SCALE

CONCENTRIC GAS FLUE DETAILS

SCALE: NOT TO SCALE

INTERIOR HOUSEKEEPING PAD DETAIL

SCALE: 1/2" = 1'-0"

EXTERIOR EQUIPMENT PAD DETAIL

DATE INITIAL

A

TT

A C

H M

EN

FIRST FLOOR

100' - 0"

FIRST FLOOR

100' - 0"

ATTIC LEVEL

112' - 0"

B

HWS

HWR

LP

4 Ø4 Ø 4 Ø4 Ø

2"2"

2"

B-1A

B-1B

PVC VENT AND FLUE

THROUGH ROOF TO

CONCENTRIC TERMINAL

EXISTING

SHAKE

SHINGLES

NEW SHAKE SHINGLES. USE

SHINGLES FROM EXISTING NPS

EXTRA STOCK FROM PREVIOUS

ROOFING SCOPE

FASTEN PATCH TO EXISTING

DECK AND SEAL PERIMETER

PATCH EXISTING ROOF

PENETRATION WITH PLYWOOD

THICKNESS TO MATCH

EXISTING WITH BACKER 2"

LARGER IS ALL DIRECTIONS

EXISTING

SHAKE

SHINGLES

EXISTING

UNDERLAYMENT

EXISTING

UNDERLAYMENT

15LB FELT UNDERLAYMENT.

INSERT UNDER EXISTING

UNDERLAYMENT ON HIGH SIDE

AND OVERLAP EXISTING

UNDERLAYMENT ON LOW SIDE.

EXISTING ROOF

STRUCTURE BEYOND

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

251315

00000

PEA RIDGE NATIONAL MILITARY PARK

15930 EAST US-62

GARFIELD, AR 72732C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

P E

R I_ a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

02/25/2020

07310.007

M501

SCHEDULE - MECHANICAL

07310007PERI- 5- M501 SCHEDULE - MECHANICAL

2. PROVIDE WITH BACNET CONTROLS INTERFACE.

NOTES: 1. UNIT TO HAVE FREEZE PROTECTION, SOUND ATTENUATION PACKAGE, AND ARCHITECTURAL LOUVERS.

CH-1 GRADE R410A 95 30 68.1 55 45 14.9 2 10.56 32.39 208 3 60 136.8 175 TRANE CGAM030 1-2

REFER

TYPE

AMB AIR ENT

COND (°F) MIN TONS

FLOW

(GPM) EWT (°F) LWT (°F)

PD (FT

WAT)

MIN COOL

STAGES

EFFICIENCY

(EER)

TOTAL

POWER

(KW) VOLTS PH HZ

MIN CIRC

AMPS

MAX OVERCURRENT

PROTECTION AMPSMARK LOCATION

CHILLER PERFORMANCE DATA UNIT ELECTRICAL DATA

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

AIR COOLED CHILLER SCHEDULE

NOTES: 1. PROVIDE WITH LOW AMBIENT COOLING, HARD-WIRED WALL MOUNTED THERMOSTAT, AND INTEGRAL CONDENSATE PUMP ACCESSORY.

DSS-1A/B DATA 320-425 80 67 12.0 20.8 14.0 10.2 MITSUBISHI PKA-A12 GRADE 95 R410A MITSUBISHI PUZ-A12 11 28 208 3 60 1

DB WB

AIRSIDE DATA EAT (°F)

MIN CAP

(MBH) EFF. (SEER)

HEATING @

47°F (MBH) EFF. (HSPF) MCA MOCP VOLTS PH HZLOCATION CFM

COOLING COIL DATA HEATING DATA

BASIS OF DESIGN

MANUFACTURER AND MODEL

NUMBER LOCATION

AMB

TEMP (°F)

REFER

TYPE

BASIS OF DESIGN

MANUFACTURER AND MODEL

NUMBERMARK

INDOOR UNIT DATA OUTDOOR UNIT DATA

ELECTRICAL DATA

REMARKS

DUCTLESS SPLIT SYSTEM AIR CONDITIONING SCHEDULE

2. PROVIDE WITH MANUFACTURER STAINLESS STEEL DISTRIBUTION TUBES.

NOTES: 1. UNIT TO HAVE INTEGRAL CONDENSATE COOLER, SCALE COLLECTOR, AND BACNET CONTROLS INTERFACE.

H-2 ATTIC AHU-1 1 RESISTIVE STEAM 20 2,530 18 18 55 68 9.8 27.2 35 208 3 60 NORTEC RS030 1-2

H-1 ATTIC AHU-1 1 RESISTIVE STEAM 36 4,510 26 26 55 68 16.2 45 60 208 3 60 NORTEC RS045 1-2

MAX CFM WIDTH HEIGHT TEMP (°F) % RH KW MCA MOCP VOLTS PH HZMARK LOCATION SERVES

NUMBER OF

MANIFOLDS TYPE

HUMIDIFICATION

CAPACITY

(LBS/HR)

DUCT CONDITIONS ELECTRICAL DATA

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

ELECTRIC HUMIDIFIER SCHEDULE

3. UNIT TO HAVE BUILT-IN CIRCULATING PUMP.

2. PROVIDE WITH CONDENSATE NEUTRALIZER, CONCENTRIC ROOF VENT TERMINAL, AND BACNET CONTROLS INTERFACE.

NOTES: 1. BOILER TO BE WALL MOUNTED.

B-1A/B MECH ROOM CONDENSING 399.2 10:1 20.0 >95 160 180 RIELLO CONDEXA PRO 117 1-3

EWT (°F) LWT (°F)MARK LOCATION TYPE

INPUT MBH

(NAT GAS) TURNDOWN FLOW (GPM)

COMBUSTION

EFFICIENCY (%)

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

PROPANE FIRED HOT WATER BOILER SCHEDULE

SCALE: 1/4" = 1'-0"

BOILER PIPING ELEVATION

3. TANK SIZED FOR BASE-OF-DESIGN CHILLER LOOP TIME REQUIREMENTS.

2. PROVIDE WITH BASE RING WITH ANCHOR CLIPS AND 1/2" CLOSED CELL INSULATION WRAP.

NOTES: 1. CONDENSATE PUMP TO BE RATED FOR A MAXIMUM WATER TEMPERATURE OF 150°F

BT-1 BUFFER TANK CH-1 MECH ROOM TANK VOLUME = 75 GALLONS -- TACO BTH0075F02-125N 2-3

P-2 CONDENSATE PUMP H-2 ATTIC 8' LIFT, 300 GAL/HR, 1 GALLON RESERVOIR 115 V, 3.1 FLA HARTELL A2-115 1

P-1 CONDENSATE PUMP H-1 ATTIC 8' LIFT, 300 GAL/HR, 1 GALLON RESERVOIR 115 V, 3.1 FLA HARTELL A2-115 1

MARK FUNCTION SERVES LOCATION OPERATING CONDITIONS CAPACITY AND MOTOR HP

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

MISCELLANEOUS MECHANICAL EQUIPMENT SCHEDULE

NOTES: 1. SCHEDULE INFORMATION FROM EXISTING PLANS. CONTRACTOR SHALL VERIFY EXISTING SYSTEM SETPOINTS AND PERFORMANCE PRIOR TO REMOVAL OF EXISTING CONTROLS. NEW CONTROL SETPOINTS TO MATCH EXISTING.

EX AHU-1 ATTIC EX VAVs 8,000 4.66 2.00 1,522 65.0 45.0 55.4 327.34 230.34 21.0 180.0 152.7 274.24 1,800 15 208 3 60 CARRIER 39MN17 1

CFM

TOT SP IN

WG

EXT SP IN

WG RPM GPM EWT (°F) LWT (°F)

TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH) GPM EWT (°F) LWT (°F)

CAPACITY

(MBH) RPM HP VOLTS PH HZMARK LOCATION SERVES

FAN DATA COOLING COIL DATA HEATING COIL DATA MOTOR DATA

MANUFACTURER AND MODEL

NUMBER REMARKS

EXISTING AIR HANDLING UNIT SCHEDULE

PRIOR TO REMOVAL OF EXISTING CONTROLS. NEW CONTROL SETPOINTS TO MATCH EXISTING.

NOTES: 1. SCHEDULE INFORMATION FROM EXISTING PLANS. CONTRACTOR SHALL VERIFY EXISTING SYSTEM SETPOINTS AND PERFORMANCE

EX VAV-12 ASSEMBLY 1320 -- -- -- 39.7 2.6 TITUS DESV

EX VAV-11 EXHIBIT 900 -- -- -- 26.1 1.75 TITUS DESV

EX VAV-10 FOYER 160 -- -- -- 11.0 0.75 TITUS DESV

EX…

This is the start of the file's text. The full file is on GovTribe.