Att 1 Specifications for CLIN 0001.pdf
PDF 362 KB Posted
- Attached to
- Frequency Converter Federal contract opportunity
- Solicitation number
- N0018922Q0144
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Att 3 SSJ Redacted N0018922Q0144_Redacted.pdf | ||
| 1 COMBINED SYNOPSIS- 4-18.pdf | ||
| Att 2 FARS and DFARS Provisions and Clauses 4-18.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS FOR CLIN 0001
90KVA SOLID STATE FREQUENCY CONVERTER
90KVA/ Dual Output/ Stainless steel enclosure/ Weather cover/ cable rack/ 36" floorstand/ 2 -120v-60hz duplex convenience receptacles.
OUTPUT POWER RATING: 400Hz - 90KVA (72KW @ 0.8 power factor, lagging) INPUT VOLTAGE: 480V/3ph/60Hz INPUT CONNECTION: 3 Pole Thermal Mag Trip Circuit Breaker OUTPUT VOLTAGE: 200/115V/3ph/400Hz (wye configuration) 400Hz OUTPUT CURRENT RATING: 260A RMS/LINE continuous, (125% / 10 minutes), (150% / 2 minutes), (200% / 20 seconds).
OUTPUT CONNECTION: TWO (2) - 3 Pole Contactors with Enable/Disable Control and Aircraft Interlock Circuit UNIT ENCLOSURE ENVIRONMENTAL RATING: NEMA 4X (equivalent) Stainless steel.
INCLUDED STANDARD FEATURES:
1.) 4 Line LED Display - allows viewing of three phase input and output: voltage, current, and frequency.
2.) MAIN DOOR CONTROLS 400Hz: START, STOP / RESET, OUTPUT 1 ON, OUTPUT 1 OFF, OUTPUT 2 ON, OUTPUT 2 OFF, EMERGENCY STOP
3.) MAIN DOOR STATUS INDICATORS 400Hz: POWER ON, CONVERTER
ON, MODULE FAULT, INPUT VOLTAGE FAULT, OUTPUT VOLTAGE FAULT,
OVERLOAD, 28V E/F PRESENT, 28VDC E/F BYPASS MODE, and ALARM
SILENCED.
4.) Digital diagnostic system with fault indications provided on the LED display.
5.) LAMP TEST push button (tests all door mounted lamps and the digital fault displays).
6.) Elapsed time indicator with 0 to 99,999 hr. range (non-resettable). ET meter includes 0.1 hr. digit.
7.) Audible Alarm with alarm silence switch and "Silence" indicator.