This specification statement of work outlines requirements for a chemical storage building to be installed at three Ranger District locations in Texas County, Missouri. The contractor shall furnish and install one building measuring a minimum of 176 square feet with 12-16 gauge galvanized steel exterior walls, 20 gauge galvanized steel interior walls, R-11 insulation, and a noncombustible steel roof. Additional requirements include a double 60" by 80" door with lockable hardware on the short end of the building, a basic electrical package with a 100-amp main breaker and three explosion-proof lights, four adjustable vent covers, and a 15-year manufacturer warranty. The related federal contract opportunity is solicitation number 12445523Q0120 for a chemical storage building through the Department of Agriculture Forest Service.

View the file

Other files for this federal contract opportunity

Other files attached to MTF HRCC Chemical Storage Building, newest first.
File Type Posted
Att 01_Schedule of Items (230628).docx DOCX document
Sol_12445523Q0120.pdf PDF
Att 03_Wage Rates (230414).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATION

Statement of Work Chemical Storage Buildings

Houston/Rolla/Cedar Creek Ranger District

Texas County

Missouri

A. SCOPE OF WORK: Contractor shall provide all equipment, labor and materials necessary to furnish and install in place one (1) Chemical Storage Buildings including (3) Explosion proof light fixtures (3) Tier wall shelving and with (4) adjustable building ventilations.

B. Building shall be constructed of either metal and meet the following specifications:

1. The dimensions of the building shall be a minimum of 176 square feet (22’ x 8’), with a minimum 8’ 4”ceiling.

2. Metal:

i. Exterior Wall: 12-16 gauge Galvanized Steel.

ii. Interior wall: 20 gauge Galvanized Steel.

iii. Minimum of a 3 inch air space.

iv. Minimum of 3 layers ¾” Gypsum Fire rated panels.

v. Insulation minimum of R11.

vi. Roof shall be noncombustible, permanently attached to the building, constructed of steel, and sloped to facilitate runoff.

3. Building shall have a double door (60”W x 80”H) with 36” active leaf located on the SHORT END of building, primed and painted. Doors shall open to the outside and have locking accessible locksets.

4. Buildings shall have a basic electrical package consisting of 12 space 100 amp main breaker on the FRONT LEFT corner, NEMA 3R panel with an explosion-proof switch and three explosion-proof lights.

5. Building shall be ventilated with (4) adjustable 18”W x 18”H vents with insulated covers.

6. Government will provide a pad of compacted crushed stone or concrete pad as a base for the buildings.

7. The Government shall mark the location of the building on the ground prior to contractors delivery of the building.

8. Building shall have a minimum 4 hour fire rating.

9. Minimum design loads shall be

i. Wall Wind Load: 70 mph

ii. Roof Live Load: 40 psf

iii. Floor Live Load 250 psf

10. Provide a minimum manufacturer’s warranty of 15 years.

11. Government will require a contractor site visit prior to installation.

Building needs to have door on the short end, not wide end of building.

** The power box needs to be located towards the front left corner of the building to allow for proper electric hookup.

** The nature of the delivery location may prevent delivery vehicle(s) from turning. Desired placement location is a concrete pad (approximately 14 Ft X 23 FT). A powerline runs to the east of the concrete pad, with a fence-line below the powerline. A warehouse sits to the left of the concrete pad. The parking lot is approximately 80 Ft X 65 Ft. Backing all the way from the road may be required for successful delivery.