Atch 1_Drawings_South Campus PRV replacement.pdf
PDF 12 MB Posted
- Attached to
- Replace pressure relief valve, Ames Federal contract opportunity
- Solicitation number
- 12639523Q0136
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Q and A from South Campus PRV replacement site visit_5_4_2023.docx | DOCX document | |
| Site Visit Sign In Sheet_5_4_2023.pdf | ||
| Atch 2_Federal construction wage rates_Story County.pdf | ||
| 12639523Q0136.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location Coordinator:Contracting Officer Rep.:Contracting Officer:Engineering Project Manager:
Task
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
Title
3/21/2023
Brandon Keith P01
23007 1 8
South Campus Pressure Reducing Valve Replacement project
Building 20
Main Gate
Gate 2
Gate 3
Building 21
Project Area:
South Campus Pressure Reducing Valve Vault
D a yt on A ve nu e
UNITED STATES DEPARTMENT OF AGRICULTURE
AGRICULTURE RESEARCH SERVICE
NATIONAL CENTERS FOR ANIMAL HEALTH
INDEX OF DRAWINGS
P02
Title
South PRV location
P03
P04
South PRV Details
P01
Existing south PRV one line
P06
New Work - PRV layout
Fire Pump Data
P07
P08
South PRV inlet/outlet
P05
South PRV outside vault
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
South PRV Location
3/21/2023
Brandon Keith P02
23007 2 8
South Campus PRV vault location
Gate 3
NORTH
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Brandon Keith TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
South PRV details
3/21/2023
Brandon Keith P03
23007 3 8
12 inch Pressure Reducing Valve To be replaced.
12 inch Butterfly Valve Typical (2). To be replaced.
6 inch to 3 inch Reducer (Remain in place)
6 inch Isolation Valve Typical (2)
12 inch Dismantling Joint
6 inch Dismantling Joint (Remain in place)
City of Ames Meter (Remain in place)
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
Existing South PRV one-line
3/21/2023
Brandon Keith P04
23007 4 8
12345
12" Pressure Reducing Valve
City of Ames Meter
Dismantling Joint Typical (3)
Check Valve Flanged Reducer
6" to 3" Flanged Reducer
6" to 3"
12"12" 12"
6" 6"
6"6" 3"3" 3" 3"
Incoming Water Supply
Flow to South Campus
Edge of Concrete Vault
Edge of Concrete Vault
As it is now, we cannot isolate this prv unless we shut down the water supply to the south campus. The existing 12 inch valves are connected by bolts through both flanges and do not allow for proper isolation of the pressure reducing valve.
We cannot isolate this valve for repair/replacement due to the bolts going through both flanges and the valve
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
New Work - PRV layout
3/21/2023
Brandon Keith P05
20037 5 8
12345
12" Pressure Reducing Valve
City of Ames Meter
Dismantling Joint Typical (3)
Check Valve Flanged Reducer
6" to 3" Flanged Reducer
6" to 3"
12"12" 12"
6" 6"
6"6" 3"3" 3" 3"
Incoming Water Supply
Edge of Concrete Vault
Edge of Concrete Vault
Move/shorten the 12 inch pipe and the dismantling joint to allow room to install 12 inch butterfly valve on the downstream side to have the ability to isolate the prv without shutting down the water supply to south campus.
New 12-inch Pressure Reducing Valve shall be installed in a manner that will allow the ability to isolate the valve for maintenance without having to shut down the south campus water supply.
New 12-inch Butterfly valves
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
Fire Pump Data
3/21/2023
Brandon Keith P06
20037 6 8
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
South PRV, inlet/outlet
3/21/2023
Brandon Keith P07
23007 7 8
EASTWEST
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith NA
South Campus PRV
REPLACEMENT
project
South PRV outside vault
3/21/2023
Brandon Keith P08
23007 8 8
Gate 3 Guard shelter
Round Manhole to PRV vault
Entrance hatch to PRV vault
File details come from the government source that posted it. Updated .