This document is a combined synopsis/solicitation for commercial items requesting quotes for mold remediation services at Building 89 located at 13601 Old Cutler Road, Miami, FL 33158. The Department of Agriculture, Agricultural Research Service is seeking a contractor to provide mold remediation services. The associated NAICS code is 562910 (Environmental Remediation Services) with a small business size standard of 1,000 Employees. A site visit is scheduled for July 24, 2024 and quotes are due by July 30, 2024. The basis for award is Lowest Price Technically Acceptable. Contractors must be registered in the System for Award Management (SAM) and have a UEI (Unique Entity ID) number to be eligible for award. All invoices shall be submitted and paid electronically.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Appendix A Lab Report - USDA Building 89.pdf | ||
| Service Provisions 1135441.docx | DOCX document | |
| PWS B89 Mold Remediation Miami FL.docx | DOCX document | |
| Wage Rates.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
13601 Old Cutler Rd SEA SUBTROPICAL HORTICULTURE RESEARCH
Eco Air Mold Assessors Page 1 of 56
ECO AIR MOLD ASSESSORS
9547078671
Gerardo@ecoairmoldtesting.com https://ecoairmold.com/
MOLD ASSESSMENT REPORT
13601 Old Cutler Rd Miami, FL 33156
SEA SUBTROPICAL HORTICULTURE RESEARCH
MAY 29, 2024
Inspector
Gerardo Espinoza Licensed Mold Assessor #MRSA4897
954-707-8671 admin@ecoairmoldtesting.com tel:9547078671 mailto:Gerardo@ecoairmoldtesting.com https://ecoairmold.com/ tel:954-707-8671 mailto:admin@ecoairmoldtesting.com
Eco Air Mold Assessors Page 2 of 56
TABLE OF CONTENTS
1: Project Subject
2: Outside - Baseline Air Sample
3: Main Entrance
4: A/C Room Pipes
5: Women's Locker Room Ceiling
6: RM 126
7: RM 136 Karla Agurto O�ce
8: RM 201
9: RM 202
10: RM 205
11: RM 211
12: RM 212
13: RM 213
14: RM 218
15: RM 232
16: Laboratory Mold Results
17: Mold Remediation Protocol
18: FL Inspector Credentials
Standards of Practice
Eco Air Mold Assessors Page 3 of 56
Results of Testing
Inspection Property
ELEVATED: MAIN ENTRANCE
Mold concentrations in the air samples are ELEVATED: "means that the amount and/or diversity of spores, as compared to the control sample(s), and other samples in our database, are higher than expected. This can indicate that fungi have grown because of a water leak or water intrusion. Fungi that are considered to be indicators of water damage include, but are not limited to: Chaetomium, Fusarium, Memnoniella, Stachybotrys, Scopulariopsis, Ulocladium." (Direct words from Laboratory).
UNUSUAL: 201 PAINT BELOW WINDOW, 232 BACK WALL DRYWALL WINDOW, 218 BACK RM DRYWALL, 213 DOOR PAINT, 213 DRYWALL UNDER CABINET, A/C RM PIPES, WOMENS LOCKERS RM CEILING, 126 SINK CABINET, 126 A/C VENTS, 213 SINK CABINET, 212 CABINETS, 211 A/C VENT, 211 DRAWERS, 205 WINDOW AREA, & 202
DRAWERS
Mold concentrations in the surface samples are reported as UNUSUAL: "means that the presence of growth was observed in the analyzed sample. An abundance of spores are present, and/or growth structures including hyphae and/or fruiting bodies are present and associated with one or more of the types of mold/fungi identi�ed in the analyzed sample". (Direct words from Laboratory).
1: PROJECT SUBJECT
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = De�ciency
Information section-ZDcxYTZmZmUtYTFhZS00MGNjLWFhZWItNjdjZGFmYjUzOTIz
Eco Air Mold Assessors Page 4 of 56
Cause of Loss
Narrative
Eco Air conducted a Mold Assessment (Pre-Testing) on May 29th, 2024. Eco Air was retained by Karla Agurto to conduct a Mold Assessment within SEA SUBTROPICAL HORTICULTURE RESEARCH.
Eco Air was engaged in response to a water damage and indoor air quality claim that had arisen due to the unfortunate development of mold growth within the interior of the government building. Our initial assessment, focused on the entire building which revealed the presence of visible mold colonies growing on the mentioned areas within this report. All O�ces, Labs, Storage Rooms, Restrooms, A/C Machine Rooms, Conference Room, Lunch Rooms, etc. were provided a detailed visual inspection along with moisture reading scanning of all mentioned areas.
During our inspection, we found signs of visible mold and moisture throughout the building, in areas mentioned within this report. Based on our professional evaluation, it is our opinion that the source of the water intrusion can be traced back to di�erent leaks throughout the building. We recommend for mold removal and treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Along with detecting the source of water intrusion within the building, and providing the necessary solutions to prevent further leaks. Areas that have been tested and sent to a third party lab came back positive for mold growth, along with the active moisture readings that have been detected from the found a�ected areas. We never recommend conducting Mold Remediation treatments or removal done by a company that does not have a Mold Remediator license in Florida! We also recommend �xing the water leak before any reconstruction work begins in order to avoid future water damage problems. Please keep in mind the above report is a summary of project conditions based on visual site observations only. Eco Air will not be held liable for any assumptions made based on these �ndings. As a routine matter, to avoid possible misunderstanding, nothing in this report should be construed directly or indirectly as a guarantee for any portion of the structure. This is not a complete inspection of all systems or components of the building and this inspection issues no warranty or guarantee for any part of the subject structure or systems. Conditions inside wall cavities are not visible and unknown. Eco Air only focused on speci�c requested areas within this building, the condition of other areas or future areas with water damage or mold are unknown.
Once the areas have been treated and mold removal has taken place, Eco Air should be hired to perform Post Remediation Test (PRV) to ensure areas are within normal limits before reconstruction of building materials begin.
Water Intrusion Category
Category 1
Category 1 water originates from a sanitary water source and does not pose a substantial risk from dermal, ingestion, or inhalation exposure. Examples of Category 1 water sources can include but are not limited to broken water-supply lines; tub or sink over�ows with no contaminants; appliance malfunctions involving water-supply lines; melting ice or snow; falling rainwater; broken toilet tanks, and toilet bowls that do not contain contaminants or additives. However, once clean water leaves the exit point, it may not remain clean once it contacts other surfaces or materials.
Recommendations
Inspection
During our inspection we recommended the following:
*Contract a Certi�ed Mold Remediation company to remediate the discovered a�ected areas.
Mold Remediation Protocol
Protocol
Please See Mold Remediation Protocol section within this document.
A Mold Remediation Protocol is typically written when items or areas have been identi�ed containing an unacceptable amount or type of mold and a client requires an industry recognized method of removal or cleaning instructions. From basic clean-ups to complete restructuring, when left alone, mold can have devastating e�ects on your house and health. Proper protocol for mold remediation helps mitigate risks such as ill-health, and even future mold revival.
Eco Air Mold Assessors Page 5 of 56
Location of Sample - Outside Baseline
Outside Baseline Air Quality Sample
Sample Media Outside - Baseline
CONTROL is a baseline sample showing what the spore count and diversity is at the time of sampling. The control sample(s) is usually collected outside of the structure being tested and used to determine if this sample(s) is similar in diversity and abundance to the inside sample(s).
Building Inspection Property
13601 OLD CUTLER ROAD MIAMI FL, 33158
2: OUTSIDE - BASELINE AIR SAMPLE
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = De�ciency section-NjFmMGNlZDgtZjkxZi00ZWVlLWJjMmQtMjlkYWY3MzYxNjg5
Eco Air Mold Assessors Page 6 of 56
Main Entrance - Area of Concern
Sample Area 1: Location of Sample
Main Entrance
During our Mold Assessment, this area came back ELEVATED within the air quality sampling. No visible mold or moisture was detected within this area, only air quality concern. Treatment for this area is mentioned within
REMEDIATION SUGGESTIONS.
Area Location of Air Quality Sample Air Quality Sample taken
Sample Area 1: Sample Media
Air-O-Cell
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in question contains more organisms than would normally be present.
3: MAIN ENTRANCE
section-NWQ1ZTBiZDMtNTA5Ny00OGQ0LWIyZmItMmY1OGNjZmM4OWU1
Eco Air Mold Assessors Page 7 of 56
Sample Area 1: Remediation Suggestions
Air Quality Treatment
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Sanitization: MAIN ENTRANCE
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Before taking down containment and starting reconstruction, have a licensed mold assessment company perform secondary microbial testing to ensure the remediation has been a success.
Bio Pumps Calibration Bio Pumps Calibrated BUCK Pumps Calibrated
Sample Area 1: Bio-Pump Calibration
It is recommended that the Bio-Pump be calibrated and veri�ed for every project for an accurate mold spore reading.
Eco Air Mold Assessors Page 8 of 56
A/C Room - Area of Concern Location of Sample Visible mold detected in this area, we believe mold has appeared on this surface due to the porous material wrapped around the pipes.
Sample Area 1: Location of Sample
A/C Room Pipes
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. Visible mold was detected within this area, only surface concern. Treatment for this area is mentioned within REMEDIATION SUGGESTIONS.
A/C Room A/C Pipes Area of Sample
A/C Pipes Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in question contains more organisms than would normally be present.
4: A/C ROOM PIPES
section-OWRmNjMxM2UtNjBlMi00YzkwLWJlZWQtNmIzNjZhODg3ZTdm
Eco Air Mold Assessors Page 9 of 56
Sample Area 1: Remediation Suggestions
Microbial Treatment & Sealant
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Contents: A/C PIPES
-All porous A/C Pipes inside the workspace should be cleaned using microbial solutions and sealed with microbial sealant to avoid future mold growth.
Sanitization: A/C PIPES
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Before taking down containment and starting reconstruction, have a licensed mold assessment company perform secondary microbial testing to ensure the remediation has been a success.
Eco Air Mold Assessors Page 10 of 56
60% - Active moisture within drywall detected
Sample Area 1: Moisture Readings
60 %
Active moisture within drywall detected
5: WOMEN'S LOCKER ROOM CEILING
section-NTdjNDc0OWItM2Y4Ny00YzI4LTg2YmYtZjI2NGNlMzg1ZjU5
Eco Air Mold Assessors Page 11 of 56
Women's Locker Room Ceiling - Area of Concern
Signs of moisture detected, paint bubbles due to leak
Signs of moisture detected, paint bubbles due to leak
Signs of moisture detected, paint bubbles due to leak
Visible Mold Detected behind ceiling paint
Sample Area 1: Location of Sample
Women's Locker Room Ceiling
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. Visible mold was detected within this area, only surface concern. We recommend for mold removal and treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Along with detecting the source of water intrusion within the building, and providing the necessary solutions to prevent further leaks. Treatment for this area is mentioned within REMEDIATION SUGGESTIONS. The Women's Locker Room is located in the �rst �oor at the end of the hall.
Location of Sample - Ceiling Womens Locker Room Ceiling - Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in question contains more organisms than would normally be present.
Eco Air Mold Assessors Page 12 of 56
Active moisture detected on ceiling
Sample Area 1: Infrared thermography
ACTIVE MOISTURE
Active moisture detected
(Infrared thermography: is a fast and non-destructive technology that can accurately track down sources of moisture in the buildings using an infrared camera. Infrared can track down sources of moisture even when it's hidden behind interior walls, within insulation, or in the ceiling.)
Eco Air Mold Assessors Page 13 of 56
Sample Area 1: Remediation Suggestions
Yes Removal
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Contents:
-All non-porous and semi-porous furnishings (wood, plastic, glass, etc.) inside the workspace should be cleaned and moved to conditioned storage outside or an una�ected area of the residence.
-All porous materials (linens, clothes, fabrics, etc.) inside the containment should be laundered and moved to conditioned storage outside or an una�ected area of the residence.
-Some items that fall into this category will not be able to be cleaned properly for reuse later and should be disposed of (fabric couches, wicker furnishings, mattresses, etc.). These items should be discussed with the remediation contractor to determine their abilities of cleaning.
Containment:
-After all contents have been moved away from the workspace, the remediator should establish containment around the a�ected materials. Containment should be constructed of 6 mil �re retardant poly following the IICRC-S520 guidelines.
-Seal o� all HVAC vents inside the contained areas (supply and return).
-Apply a negative pressure to the containment. How this negative pressure is achieved will be left up to the remediation contractor but should follow IICRC-S520 guidelines.
-A minimum of 4 air exchanges per hour are recommended.
Drying Equipment:
-Dehumidi�cation equipment and Air Filtration Devices (AFDs), commonly known as air scrubbers, should be used while utilizing HEPA �ltration. This is to help stabilize the contained work area environment.
-Negative pressure is recommended using a lay-�at tube exhausting the work area air to the outside of the building envelope.
-After the removal of the a�ected materials, negative pressure can be stopped, and the air �ltration device with HEPA �ltration can be used to further clean the contained work environment ambient air.
Remove and Discard: Women's Locker Room Drywall Ceiling
-Remove and discard any sheetrock with discoloration/growth/wetness or embedded microbial growth, continuing 2
ft. past any visual damage.
-Remove and discard water-damaged and/or a�ected porous �oorings, such as carpet, laminate, and wood, 2 ft.
beyond visible water damage.
-Observe the underlying materials, such as insulation, trusses, studs, etc., and remove materials as necessary.
-It is recommended to remove any water-damaged framework. If it is decided not to be removed, then it should be wire-brushed or sanded to remove the wood grain discoloration and/or microbial growth, sanitized, allowed to dry completely, and then sealed with a clear encapsulate.
-All removed damaged materials should be bagged inside the containment before being removed outside the containment.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Sanitization:
After the removal of the a�ected materials, sanitize the work area:
-HEPA-vacuum the entire work area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
Eco Air Mold Assessors Page 14 of 56
Women's Locker Rm Ceiling Removal
Eco Air Mold Assessors Page 15 of 56
RM 126 RM 126 - Area of Concern Lab
Mold Assessor inspected sink cabinet, surface sample was conducted on base of cabinet
A/C Vent - Located inside RM 126, the A/C vent was visibly dirty.
Surface Sample taken in this A/C Vent
Sample Area 1: Location of Sample
RM 126
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. We found evidence of mold below the sink cabinet and A/C Vent of RM 126. This can cause health issues and structural damage if left untreated.
Our �ndings suggest that immediate Mold Remediation measures should be taken to address the active mold issue and prevent further mold growth.
6: RM 126
section-NGNmNjgyZTItYjI5Yy00MjMxLWIwMjUtYzY5NmMwNzVkMmY3
Eco Air Mold Assessors Page 16 of 56
Mold Assessor inspected sink cabinet, surface sample was conducted on base of cabinet
RM 126 SINK CABINET - Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in
Eco Air Mold Assessors Page 17 of 56
126 Sink Cabinet - Sanitize the a�ected area, If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
126 A/C VENT - Sanitize the a�ected area, If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
Sample Area 1: Remediation Suggestions
Microbial Treatment
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Sanitization: 126 SINK CABINET & A/C VENT
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Eco Air Mold Assessors Page 18 of 56
Rm 136 Admin O�ce - Karla Agurto 136 Ceiling - Area of Concern
Our concern for this area is an active leak coming from the ceiling, we detected this leak using infrared imaging. We recommend having the Mold Remediation company removing the a�ected ceiling tile and addressing the active leak.
Sample Area 1: Location of Sample
During our Mold Assessment, we found evidence of active moisture no sampling was conducted within this area as there were no visible mold concerns. Our concern for this area is an active leak coming from the ceiling, we detected this leak using infrared imaging. We recommend having the Mold Remediation company removing the a�ected ceiling tile and addressing the active leak.
7: RM 136 KARLA AGURTO OFFICE
section-Y2U1MjBjYmItMmM3MS00NmE0LWI3NWEtZjJjYzIxYTcwZmUx
Eco Air Mold Assessors Page 19 of 56
Active moisture detected
Sample Area 1: Infrared thermography
316 Ceiling
Active moisture detected
(Infrared thermography: is a fast and non-destructive technology that can accurately track down sources of moisture in the buildings using an infrared camera. Infrared can track down sources of moisture even when it's hidden behind
Eco Air Mold Assessors Page 20 of 56
100% - Active moisture within drywall detected
Sample Area 1: Moisture Readings
100 %
Active moisture within drywall detected
8: RM 201
section-OGNiZTAxYzUtNjE5ZC00ZDI0LWE1NDItMWIxZTdjODc4YzNl
Eco Air Mold Assessors Page 21 of 56
RM 201 LRM 201 - Area of Concern LAB
Paint bubbles detected under window (Lab back wall)
Mold Assessor peeled back paint which revealed visible mold on drywall below window
Sample Area 1: Location of Sample
RM 201
During our Mold Assessment, this area came back UNUSUAL within the BULK sampling. Visible mold was detected within this area, only surface concern. We recommend for mold removal and treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Along with detecting the source of water intrusion within the building, and providing the necessary solutions to prevent further leaks. Treatment for this area is mentioned within REMEDIATION SUGGESTIONS. We also recommend sealing with caulk all drywall window openings which was mentioned during our inspection.
201 PAINT BELOW WINDOW - BULK
SAMPLE
Sample Area 1: Sample Media
Bulk
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in
Eco Air Mold Assessors Page 22 of 56
Sample Area 1: Remediation Suggestions
Yes Removal
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Contents:
-All non-porous and semi-porous furnishings (wood, plastic, glass, etc.) inside the workspace should be cleaned and moved to conditioned storage outside or an una�ected area of the residence.
-All porous materials (linens, clothes, fabrics, etc.) inside the containment should be laundered and moved to conditioned storage outside or an una�ected area of the residence.
-Some items that fall into this category will not be able to be cleaned properly for reuse later and should be disposed of (fabric couches, wicker furnishings, mattresses, etc.). These items should be discussed with the remediation contractor to determine their abilities of cleaning.
Containment:
-After all contents have been moved away from the workspace, the remediator should establish containment around the a�ected materials. Containment should be constructed of 6 mil �re retardant poly following the IICRC-S520 guidelines.
-Seal o� all HVAC vents inside the contained areas (supply and return).
-Apply a negative pressure to the containment. How this negative pressure is achieved will be left up to the remediation contractor but should follow IICRC-S520 guidelines.
-A minimum of 4 air exchanges per hour are recommended.
Drying Equipment:
-Dehumidi�cation equipment and Air Filtration Devices (AFDs), commonly known as air scrubbers, should be used while utilizing HEPA �ltration. This is to help stabilize the contained work area environment.
-Negative pressure is recommended using a lay-�at tube exhausting the work area air to the outside of the building envelope.
-After the removal of the a�ected materials, negative pressure can be stopped, and the air �ltration device with HEPA �ltration can be used to further clean the contained work environment ambient air.
Remove and Discard: Drywall Under Window (Lab Back Wall)
-Remove and discard any sheetrock with discoloration/growth/wetness or embedded microbial growth, continuing 2
ft. past any visual damage.
-Remove and discard water-damaged and/or a�ected porous �oorings, such as carpet, laminate, and wood, 2 ft.
beyond visible water damage.
-Observe the underlying materials, such as insulation, trusses, studs, etc., and remove materials as necessary.
-It is recommended to remove any water-damaged framework. If it is decided not to be removed, then it should be wire-brushed or sanded to remove the wood grain discoloration and/or microbial growth, sanitized, allowed to dry completely, and then sealed with a clear encapsulate.
-All removed damaged materials should be bagged inside the containment before being removed outside the containment.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Sanitization:
After the removal of the a�ected materials, sanitize the work area:
-HEPA-vacuum the entire work area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
Eco Air Mold Assessors Page 23 of 56
Location of Removal - Lab Back Wall Drywall Under Window (Lab Back Wall) Removal 2' Past
Eco Air Mold Assessors Page 24 of 56
RM 202 RM 202 - Area of Concern LAB
Drawers with visible mold (corner of back wall in Lab)
Sample Area 1: Location of Sample
RM 202
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. Visible mold was detected within this area, only surface concern on drawers. We recommend for mold treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Treatment for this area is mentioned within
REMEDIATION SUGGESTIONS.
Location of Sample RM 202 Drawers - Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in question contains more organisms than would normally be present.
9: RM 202
section-NDJlMzU0NjctOGI2OS00OTM5LTgwYmMtYWU1NGFkMThmZjZh
Eco Air Mold Assessors Page 25 of 56
Sample Area 1: Remediation Suggestions
Microbial Treatment
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Sanitization: RM 202 DRAWERS
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
-Place dehumidi�er to lower humidity levels within this area. (Number of Air-Scrubbers is up to the Remediator)
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Before taking down containment and starting reconstruction, have a licensed mold assessment company perform secondary microbial testing to ensure the remediation has been a success.
69% - High Relative Humidity, we recommend placement of dehumidi�ers within this lab to lower humidity levels
Sample Area 1: Relative Humidity
69 %
Normal Relative Humidity within a home is between 40-60% in the state of Florida.
Eco Air Mold Assessors Page 26 of 56
RM 205 RM 205 O�ces - Area of Concern O�ces
O�ce side window - settled mold on base of window
Sample Area 1: Location of Sample
RM 205
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. Visible mold was detected within this area, only surface concern. We recommend for mold treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Treatment for this area is mentioned within REMEDIATION SUGGESTIONS. We also recommend sealing with caulk all drywall window openings which was mentioned during our inspection.
10: RM 205
section-NTU3ZjU5MmYtZDBhOC00MzAzLTgxZGMtNTZhYWNhOTJiNmZm
Eco Air Mold Assessors Page 27 of 56
Location of Sample 205 Window Area - Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in question contains more organisms than would normally be present.
RM 205 O�ces Microbial Treatment on all window surfaces
Sample Area 1: Remediation Suggestions
Microbial Treatment
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Sanitization: RM 205 Window Area
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Eco Air Mold Assessors Page 28 of 56
RM 211 - Area of Concern LAB Mold Assessor pulled out and inspected drawers
Mold growth detected on surrounding cardboard boxes, we recommend throwing these boxes away and replacing with plastic containers
Mold growth detected on surrounding cardboard boxes, we recommend throwing these boxes away and replacing with plastic containers
Visible mold detected on rim of drawers as well as inside the drawer
Mold growth detected on A/C Vent Mold growth detected on A/C Vent
Sample Area 1: Location of Sample
RM 211
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. We found evidence of mold in drawers and A/C Vent of RM 211. This can cause health issues and structural damage if left untreated. Our �ndings suggest that immediate Mold Remediation measures should be taken to address the active mold issue and prevent further mold growth.
11: RM 211
section-MjhiNGI4YjAtN2Y5NC00ZDYyLThiOGMtZmFjZjZjMWNlNWY2
Eco Air Mold Assessors Page 29 of 56
Location of Sample A/C Vent - Surface Sample Location of Sample
Drawers - Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in
Eco Air Mold Assessors Page 30 of 56
Drawers - Microbial Treatment of all Drawers Inside and Outside
Drawers - Microbial Treatment of all Drawers
Location of A�ected Vent
A/C Vent - Microbial Treatment
Sample Area 1: Remediation Suggestions
Microbial Treatment
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Sanitization: 211 DRAWERS & A/C VENT
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Eco Air Mold Assessors Page 31 of 56
RM 212 LAB Mold Assessor inspected all drawers
Mold growth detected on surrounding drawers and boxes
Mold growth detected on surrounding drawers and boxes
We recommend throwing away all a�ected materials and replacing with plastic containers
Mold growth detected on top of drawers
Sample Area 1: Location of Sample
During our Mold Assessment, this area came back UNUSUAL within the surface sampling. We found evidence of mold in drawers of RM 212. This can cause health issues and structural damage if left untreated. Our �ndings suggest that immediate Mold Remediation measures should be taken to address the active mold issue and prevent further mold growth.
12: RM 212
section-ZWM1NTM3MWItMGJkNS00OWYzLTg4Y2EtZDg3MTkwZjA3NTUx
Eco Air Mold Assessors Page 32 of 56
Location of Sample 212 Cabinets - Surface Sample
Sample Area 1: Sample Media
Surface Swab
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in question contains more organisms than would normally be present.
Microbial Treatment to all surrounding cabinets inside and outside, throw away any porous material
Microbial Treatment to all surrounding cabinets inside and outside, throw away any porous material
Microbial Treatment to all surrounding cabinets inside and outside, throw away any porous material
Sample Area 1: Remediation Suggestions
Microbial Treatment
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Sanitization: 212 DRAWERS
Sanitize the a�ected area.
-HEPA-vacuum the entire area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces and with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
-Place Air-Scrubbers to �lter the air quality within this area. (Number of Air-Scrubbers is up to the Remediator)
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Eco Air Mold Assessors Page 33 of 56
13: RM 213
section-NjNkNzc0ODItYmYwNC00M2MwLWJkYTktMDFjNjg3ODg3YjAz
Eco Air Mold Assessors Page 34 of 56
RM 213 - Area of Concern LAB Mold Assessor took a surface sample for the a/c vent which came back
NORMAL for mold growth, but we still recommend a microbial cleaning for all dirty vents
Mold Assessor inspected sink cabinet
Mold growth on base of cabinet Visible mold detected on all of these cabinets, microbial cleaning required
Visible mold detected inside and outside drawer
LAB Side Wall - Moisture detected on wall, must remove wall shelf
Moisture stains on wall detected
Moisture stains under cabinet detected
Mold Assessor took a wall sample underneath the shelf which came
Visible mold growth behind drywall
Sample Area 1: Location of Sample
RM 213
During our Mold Assessment, this area came back UNUSUAL within the BULK & SURFACE sampling. Visible mold was detected within this area, only surface concern. We recommend for mold removal and treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Along with detecting the source of water intrusion within the building, and providing the necessary solutions to prevent further leaks. Treatment for this area is mentioned within REMEDIATION SUGGESTIONS. We also recommend sealing with caulk all drywall window openings which was mentioned during our inspection.
Eco Air Mold Assessors Page 35 of 56 back positive for mold growth, removal of wall recommended
LAB Door - Area of Concern Mold assessor peeled back paint on wall of door. Visible mold growth and
HIGH moisture readings detected
Mold Bulk Sample came back positive for MOLD
LAB Floor - Area of Concern Lab Floor - Moisture and mold detected underneath �ooring, �ooring must be removed.
Eco Air Mold Assessors Page 36 of 56
Location of Sample SINK CABINET - SURFACE SAMPLE Location of Sample
DRYWALL UNDER CABINET - BULK
SAMPLE
Location of Sample DOOR PAINT - BULK SAMPLE
Sample Area 1: Sample Media
Surface Swab, Bulk
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in
Eco Air Mold Assessors Page 37 of 56
Location of Infrared Active moisture detected Location of Infrared
Active moisture detected
Sample Area 1: Infrared thermography
Active moisture detected
Active moisture detected
(Infrared thermography: is a fast and non-destructive technology that can accurately track down sources of moisture in the buildings using an infrared camera. Infrared can track down sources of moisture even when it's hidden behind
Eco Air Mold Assessors Page 38 of 56
Sample Area 1: Remediation Suggestions
Yes Removal
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Contents:
-All non-porous and semi-porous furnishings (wood, plastic, glass, etc.) inside the workspace should be cleaned and moved to conditioned storage outside or an una�ected area of the residence.
-All porous materials (linens, clothes, fabrics, etc.) inside the containment should be laundered and moved to conditioned storage outside or an una�ected area of the residence.
-Some items that fall into this category will not be able to be cleaned properly for reuse later and should be disposed of (fabric couches, wicker furnishings, mattresses, etc.). These items should be discussed with the remediation contractor to determine their abilities of cleaning.
Containment:
-After all contents have been moved away from the workspace, the remediator should establish containment around the a�ected materials. Containment should be constructed of 6 mil �re retardant poly following the IICRC-S520 guidelines.
-Seal o� all HVAC vents inside the contained areas (supply and return).
-Apply a negative pressure to the containment. How this negative pressure is achieved will be left up to the remediation contractor but should follow IICRC-S520 guidelines.
-A minimum of 4 air exchanges per hour are recommended.
Drying Equipment:
-Dehumidi�cation equipment and Air Filtration Devices (AFDs), commonly known as air scrubbers, should be used while utilizing HEPA �ltration. This is to help stabilize the contained work area environment.
-Negative pressure is recommended using a lay-�at tube exhausting the work area air to the outside of the building envelope.
-After the removal of the a�ected materials, negative pressure can be stopped, and the air �ltration device with HEPA �ltration can be used to further clean the contained work environment ambient air.
Remove and Discard: REMOVE LAB SIDE WALL DRYWALL & TOP CABINETS, TREATMENT OF LOWER CABINETS, TREATMENT OF A/C VENTS, REMOVE DOOR DRYWALL & FLOORING
-Remove and discard any sheetrock with discoloration/growth/wetness or embedded microbial growth, continuing 2
ft. past any visual damage.
-Remove and discard water-damaged and/or a�ected porous �oorings, such as carpet, laminate, and wood, 2 ft.
beyond visible water damage.
-Observe the underlying materials, such as insulation, trusses, studs, etc., and remove materials as necessary.
-It is recommended to remove any water-damaged framework. If it is decided not to be removed, then it should be wire-brushed or sanded to remove the wood grain discoloration and/or microbial growth, sanitized, allowed to dry completely, and then sealed with a clear encapsulate.
-All removed damaged materials should be bagged inside the containment before being removed outside the containment.
-All removed top cabinets and �ooring.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Sanitization:
After the removal of the a�ected materials, sanitize the work area:
-HEPA-vacuum the entire work area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
Eco Air Mold Assessors Page 39 of 56
Microbial treatment on A/C Vents recommended
Microbial treatment on sink cabinets recommended
Microbial treatment on drawers recommended, Inside & Outside
Remove �ooring, until no more mold or moisture is visible
Remove door drywall, until no more mold or moisture is visible
(RED) Remove drywall until no more mold or moisture is visible. (Orange)
Remove top cabinet in order to detect leak, and determine if more drywall has to be removed
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing these newly found items and vents.
Eco Air Mold Assessors Page 40 of 56
Location of Reading 100% - Active moisture within drywall detected
Location of Reading 100% - Active moisture within drywall detected
Sample Area 1: Moisture Readings
100 %
Active moisture within drywall detected
Eco Air Mold Assessors Page 41 of 56
218 218 - Area of Concern LAB
218 Back Room 218 Back Room Wall 50% - Active moisture detected on this wall near window
Bulk sample taken directly from wall
Sample Area 1: Location of Sample
RM 218
During our Mold Assessment, this area came back UNUSUAL within the BULK sampling. Visible mold was detected within this area, only surface concern. We recommend for mold removal and treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Along with detecting the source of water intrusion within the building, and providing the necessary solutions to prevent further leaks. Treatment for this area is mentioned within REMEDIATION SUGGESTIONS. We also recommend sealing with caulk all drywall window openings which was mentioned during our inspection.
14: RM 218
section-OTdiNzFmNzktOGIyMi00MmYwLTkxZTAtZjVlMDg5N2M4YWIz
Eco Air Mold Assessors Page 42 of 56
218 BACK ROOM 218 BACK ROOM WALL 218 BULK SAMPLE
Sample Area 1: Sample Media
Bulk
The goal of biological sampling is to help determine whether the biological particles present in a particular environment are a�ecting or causing irritation in certain individuals. Sampling is also used to locate the sources of indoor microorganisms and facilitate e�ective remediation. While we are typically surrounded by a wide variety of di�erent microorganisms every day, sampling provides us with a method to establish scienti�cally whether the environment in
Eco Air Mold Assessors Page 43 of 56
Sample Area 1: Remediation Suggestions
Yes Removal
The Red Squares indicates our suggested removal and area treatment:
(These steps are just suggestions, Mold Remediation Procedures may di�er due to Remediator)
Contents:
-All non-porous and semi-porous furnishings (wood, plastic, glass, etc.) inside the workspace should be cleaned and moved to conditioned storage outside or an una�ected area of the residence.
-All porous materials (linens, clothes, fabrics, etc.) inside the containment should be laundered and moved to conditioned storage outside or an una�ected area of the residence.
-Some items that fall into this category will not be able to be cleaned properly for reuse later and should be disposed of (fabric couches, wicker furnishings, mattresses, etc.). These items should be discussed with the remediation contractor to determine their abilities of cleaning.
Containment:
-After all contents have been moved away from the workspace, the remediator should establish containment around the a�ected materials. Containment should be constructed of 6 mil �re retardant poly following the IICRC-S520 guidelines.
-Seal o� all HVAC vents inside the contained areas (supply and return).
-Apply a negative pressure to the containment. How this negative pressure is achieved will be left up to the remediation contractor but should follow IICRC-S520 guidelines.
-A minimum of 4 air exchanges per hour are recommended.
Drying Equipment:
-Dehumidi�cation equipment and Air Filtration Devices (AFDs), commonly known as air scrubbers, should be used while utilizing HEPA �ltration. This is to help stabilize the contained work area environment.
-Negative pressure is recommended using a lay-�at tube exhausting the work area air to the outside of the building envelope.
-After the removal of the a�ected materials, negative pressure can be stopped, and the air �ltration device with HEPA �ltration can be used to further clean the contained work environment ambient air.
Remove and Discard: Drywall Under Window (RM 218 Back Room)
-Remove and discard any sheetrock with discoloration/growth/wetness or embedded microbial growth, continuing 2
ft. past any visual damage.
-Remove and discard water-damaged and/or a�ected porous �oorings, such as carpet, laminate, and wood, 2 ft.
beyond visible water damage.
-Observe the underlying materials, such as insulation, trusses, studs, etc., and remove materials as necessary.
-It is recommended to remove any water-damaged framework. If it is decided not to be removed, then it should be wire-brushed or sanded to remove the wood grain discoloration and/or microbial growth, sanitized, allowed to dry completely, and then sealed with a clear encapsulate.
-All removed damaged materials should be bagged inside the containment before being removed outside the containment.
It should also be noted that during the remediation process, additional areas of growth may be discovered and should be addressed. Addendums to this protocol will be written if deemed necessary.
Sanitization:
After the removal of the a�ected materials, sanitize the work area:
-HEPA-vacuum the entire work area.
-Fog all open spaces with an anti-microbial solution.
-Damp-wipe all vertical and horizontal surfaces with an anti-microbial solution.
-HEPA-vacuum the entire work area after the fogging and damp wipe-down.
- If other items such as cabinets or other A/C Vents are found with visible mold growth continue sanitizing
Eco Air Mold Assessors Page 44 of 56
218 Backroom location Location of Removal, cut 2ft past until no more moisture or mold is visible
Eco Air Mold Assessors Page 45 of 56
RM 232 RM 232 LAB
Back Wall - Area of Concern Sample taken directly from back wall Visible mold behind drywall
99% - Active moisture detected on moisture meter within wall
Active moisture detected on infrared within wall
Sample Area 1: Location of Sample
RM 232
During our Mold Assessment, this area came back UNUSUAL within the BULK sampling. Visible mold was detected within this area, only surface concern. We recommend for mold removal and treatment to be taken place within the found a�ected areas by a licensed Mold Remediation Company. Along with detecting the source of water intrusion within the building, and providing the necessary solutions to prevent further leaks.