Annexures 1-3 B30 Equip-Layout-Pictures.pdf
PDF 14 MB Posted
- Attached to
- Switchgear Replacement Building 30 at DLA Distribution San Joaquin CA DDJC Federal contract opportunity
- Solicitation number
- SP3300-23-B-0004
- Issued by
- Defense Logistics Agency Distribution
About this file
This document provides details on a federal contract opportunity for switchgear replacement. The Defense Logistics Agency Distribution is soliciting proposals under solicitation number SP3300-23-B-0004 to replace switchgear at Building 30 of the DLA Distribution facility in San Joaquin, California. Supporting documentation includes three annexures totaling 14MB of pictures related to the equipment layout. Proposals are due under a pre-solicitation notice to replace aging electrical infrastructure and upgrade the switchgear servicing Building 30 to improve reliability and safety. Interested contractors should monitor the Federal Business Opportunities website for additional details and the full solicitation releasing in the coming months.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| DrawingsBldg30SwgrReplace 1-2.pdf | ||
| Specifications Bldg30SwgrReplace.pdf | ||
| SOW Bldg.30SwgrReplace.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 30 SWITCHGEAR REPLACEMNET DDJC
ANNEXURE 1
1/10
BUILDING 30 EXISTING SUBSTATION EQUIPMENT SUMMARY
a. Unit 1 (CSF-1)
i. Two (2) Medium Voltage Switches.
ii. One (1) 1MVA Dry Type Transformer.
iii. One (1) 480V Switchgear.
iv. One (1) Voltmeter.
v. One (1) Amp Meter.
vi. One (1) 3200A Main Breaker.
vii. Eleven (11) 800A Frame Feeder
Breakers.
b. Unit 2 (CSF-2)
i. Two (2) Medium Voltage Switches.
ii. One (1) 1MVA Dry Type Transformer.
iii. One (1) 480V Switchgear.
iv. One (1) Voltmeter.
v. One (1) Amp Meter.
vi. One (1) 1600A Main Breaker.
vii. Five (5) 400A Frame Feeder Breakers.
2/10
BUILDING 30 SUBSTATION EXISTING EQUIPMENT DETAILS
CSF-1 Selector switch # 1 Manufacturer- Industrial Electrical Type- Fused Voltage Rating - 12KV Interrupting Rating - 40 KA Current Rating - 600 Amp Type of Operating Mechanism - Mechanical BIL Rating - 95kv Momentary Fault Closing - 40 KA
CSF-1 Air Fused Disconnect Switch Manufacturer Gould Type 80E, Load Break Catalog # A1550X80E-1 Interrupting Rating 40KA Voltage Rating 15 KV Current Rating 600 AMP
CSF-2 Selector switch # 2 Manufacturer - Industrial Electrical Type Fused Voltage Rating 12KV Interrupting Rating 40 KA Current Rating 600 Amp Type of Operating Mech. Mech.
BIL Rating 95kv Momentary Fault Closing 40 KA
CSF-2 Air Fused Disconnect Switch Manufacturer - Type 80E, Load Break Catalog # Interrupting Rating 40KA Voltage Rating 15 KV Current Rating 600 A
CSF-1 Transformer nameplate data Serial number E6099-0192 Manufacturer International Transformer Corporation Manufacturing year 1993 No. phases 3 Hz - 60 Manufacturer type HV15HTUL Vector group Dyn1 Catalog # A6T1000HNE-00106 Aluminum Winding Voltage ratings Winding Voltage L-L Voltage L-N Insulation level L-L
H 12.000 kV 95 kV X 0.480 kV 0.277 kV 10 kV
Rated power Cooling class Temp. rise wind.
1033.000 MVA AA/FA 150 degree C
Impedances – 5.69% at 170 degree C Category Indoor Distribution Status In operation Insulation medium- Dry type Total weight 6800 lbs
3/10
Tap Changers nameplate data.
Winding H Tap scheme 1...N No. of taps 5
Tap Voltage 1 12600.0 V 2 12300.0 V 3 12000.0 V 4 11700.0 V 5 11400.0 V
CSF-1 Switchboard Manufacturer Industrial Electrical Type 3Ph 4Wire Voltage Rating 480Y/277 Current Rating 3200 Operating Voltage 480 Withstand Rating 50KA
Installed Devices # of Breakers 12 # of Bays - 4 # of Panel Meters - 1 # of KWHR Meters - 1 # of CTs - 3 # of CPTs 1
CSF-1 CIRCUIT BREAKER DATA
CSF-1 MAIN BREAKER
Manufacturer GENERAL ELECTRIC Catalog # AKR-7F-75 Frame Type AKR Serial # 0343A8149-007-001 Frame Rating 3200AMP Volt Rating 480V Trip Unit Mfg GENERAL ELECTRIC Trip Rating X=1600 CT-1600A Trip Unit Type MICROVERSATRIP RMS-9 Int Capacity 65KA Trip Device Settings LPTU=0.9X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5c-9c STD=INT 12T-OUT GFPU=0.2S Range 0.2S-0.37S GFD=MAX 12T-OUT INST=10X Range 1.5X-13X
4/10
CSF-1 QUAD #4 POWER BUS WAY
Manufacturer GENERAL ELECTRIC Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-001-001 Frame Rating 800AMP Volt Rating 480V Trip Unit Mfg. GENERAL ELECTRIC Trip Rating X=800 CT-800A Trip Unit Type MICROVERSATRIP RMS-9 Int Capacity 42KA Trip Device Settings LPTU=0.5X Range 0.5-1.1 LTD=4 Range 1-4 STPU=7C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
CSF-1 QUAD #3 POWER BUSWAY
Manufacturer GENERAL ELECTRIC Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-005-003 Frame Rating 800AMP Volt Rating 480V Trip Unit Mfg GENERAL ELECTRIC Trip Rating X=400 CT-800A Trip Unit Type MICROVERSATRIP RMS-9 Int Capacity 42KA Trip Device Settings LPTU=0.5X Range 0.5-1.1 LTD=4 Range 1-4 STPU=7C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
CSF-1 PANEL PDP
Manufacturer GENERAL ELECTRIC Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-005-006 Frame Rating 800AMP Volt Rating 480V Trip Unit Mfg GENERAL ELECTRIC Trip Rating X=800 CT-800A Trip Unit Type MICROVERSATRIP RMS-9 Int Capacity 42KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=2 Range 1-4 STPU=7C Range 1.5c-9c STD=INT 12T-OUT INST=7X Range 1.5X-15X
CSF-1 PANEL DPE
Manufacturer GE Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-008-001 Frame Rating 800Amp Volt Rating 480 Volt Trip Unit Mfg GE Trip Rating 400/225 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
5/10
CSF-1 PANEL DPH1
Manufacturer GE Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-006-001 Frame Rating 800Amp Volt Rating 480 Volt Trip Unit Mfg GE Trip Rating 400/200 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
CSF-1 PANEL DPH2
Manufacturer GE Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-003-001 Frame Rating 800Amp Volt Rating 480 Volt Trip Unit Mfg GE Trip Rating 400/225 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4
CSF-1 LIGHTING BUSWAY # 1
Frame Type AKR Serial # 0343A8149-005-005 Frame Rating 800Amp Volt Rating 480 Volt Trip Unit Mfg GE Trip Rating 400/200 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
CSF-1 LIGHTING BUSWAY # 2
Manufacturer GE Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-006-001 Frame Rating 800Amp Volt Rating 480 Volt
6/10
Trip Unit Mfg GE Trip Rating 400/200 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4
CSF-1 LIGHTING BUSWAY # 3
Frame Type AKR Serial # 0343A8149-005-004 Frame Rating 800Amp Volt Rating 480 Volt Trip Unit Mfg GE Trip Rating 400/200 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
CSF-1 LIGHTING BUSWAY #4
Manufacturer GENERAL ELECTRIC Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-005-002 Frame Rating 800AMP Volt Rating 480V Trip Unit Mfg. GENERAL ELECTRIC Trip Rating X=200 CT=400A Trip Unit Type MICROVERSATRIP RMS-9 Int Capacity 42KA Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5c-9c STD=INT 12T-OUT INST=13X Range 1.5X-15X
CSF-1 MCC1
Manufacturer GE Catalog # AKR-7D-30H Frame Type AKR Serial # 0343A8149-006-001 Frame Rating 800Amp Volt Rating 480 Volt Trip Unit Mfg GE Trip Rating 400/225 Trip Unit Type RMS-9 Micro Versa trip Int Capacity 42 KA Trip Device Settings LPTU=0.9X Range 0.5-1.1 LTD=4 Range 1-4 STPU=9C Range 1.5C-9C STD= MIN OUT INST=10X Range 1.5X-15X
INCOMINMG LINE #1 Selector Switch Manufacturer Powercon Corp Type B-2691
7/10
Catalog # S10659 Serial # 02-25463 Voltage Rating - 15 KV Current Rating - 600A Type of Operating Mechanism- Mechanical BIL Rating – 95 KV Momentary Fault Closing 40KA
AIR FUSED DISCONNECT SWITCH
Manufacturer – GE Type – FJ Interrupting Rating 50A Voltage Rating – 15KV Current Rating 80A
INCOMING LINE #2 Selector Switch
Manufacturer Powercon Corp Type B-2691 Catalog # S10659 Serial # 02-25463 Voltage Rating - 15 KV Interrupting Rating NA Current Rating - 600A Type of Operating Mechanism- Mechanical BIL Rating – 95 KV Momentary Fault Closing 40KA
AIR FUSED DICONNECT SWITCH
Interrupting Rating 50A Voltage Rating – 15KV Current Rating 80
CSF-2 Transformer nameplate data Serial number 24-34644L01 Manufacturer GE Feeder MSB 2 Manufacturing year 1993 No. phases 3 Hz - 60 Manufacturer type Dry Type Vector group Dyn1 Voltage ratings Winding Voltage L-L Voltage L-N Insulation level L-L
H 12.000 kV 60 kV X 0.480 kV 0.277 kV 10 kV
Rated power Cooling class Temp. rise wind.
1.000 MVA AN/AA 150
Winding H X Rated power
48.000 A 1203.000 A 1.000 MVA
Impedances at 120 °C Zk[%] Base power Base voltage
5.540 % 1.000 MVA 12.000 kV Category Indoor Distribution Status In operation Insulation medium Dry type Total weight 6000 lbs Tap Changers nameplate data No. of taps 5
8/10
Tap Voltage A 12600.0 V B 12300.0 V C 12000.0 V D 11700.0 V E 11400.0 V
CSF-2 MAIN SWITCHBOARD
Manufacturer GE Type PowerBreak Catalog # 960803 Serial # NA Voltage Rating - 480V Current Rating - 1600A Operating Voltage 480/277 Withstand Rating 65KA Installed Devices # of Breakers – 6 # of Bays – 8 # of panel meters - 3
CSF -2 MAIN BREAKER -1
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 123991 Frame Rating 1600 Volt Rating 600 Trip Unit Mfg GE Trip Rating 1600 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.0 LTD=4 Range 1-4 STPU= Range STD= INST=2 Range 1.5X-15X
CSF-2 BREAKER PNL C1
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # NA Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 225 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=1 Range 1-4 STPU=9C Range 1.5C-9C STD=3 OUT Range 1 - 3 GFPU=0.5 Range 0.2-0.6 GFD=3OUT Range 1 - 3 INST=10X Range 1.5X-15X
CSF-2 BREAKER Panel HA
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 168560 Frame Rating 400 Volt Rating 600
9/10
Trip Unit Mfg GE Trip Rating 225 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=3X Range 1.5X-15X
CSF-2 CIRCUIT BREAKER Panel 2HB Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 123981 Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 400 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=3X Range 1.5X-15X
CSF-2 CIRCUIT BREAKER POWER BUSS 4-2
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 1234982 Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 400 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=2X Range 1.5X-15X
CSF-2 CIRCUIT BREAKER POWER BUSS 3-2
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 123983 Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 400 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=2X Range 1.5X-15X
10/10
CSF-2 CIRCUIT BREAKER PANEL HA
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 168560 Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 225 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=3X Range 1.5X-15X
CSF-2 CIRCUIT BREAKER PANEL 2HB
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 123981 Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 400 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=2X Range 1.5X-15X
CSF-2 CIRCUIT BREAKER PANEL C1
Manufacturer GE Catalog # TC84TTR Frame Type TC Serial # 123981 Frame Rating 400 Volt Rating 600 Trip Unit Mfg GE Trip Rating 225 Trip Unit Type MicroVersaTrip Plus Int Capacity 42 @ 480 Trip Device Settings LPTU=1.0X Range 0.5-1.1 LTD=4 Range 1-4 STPU= Range STD= Range GFPU= Range GFD= Range INST=2X Range 1.5X-15X
DAK0013
Rectangle
DAK0013
Polygon
DAK0013
Rectangle
DAK0013
Typewritten Text
12 KV SWITCHGEAR
CAGE
DAK0013
Typewritten Text
CONSTRUCTION AREA
EXCLUDING LUNCH ROOM
AND FORKLIFT CHARGING
AREA
DAK0013
Line
DAK0013
Line
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Typewritten Text
POWER OUTGAE BACKUP GENERATOR LOCATIONS
DAK0013
Typewritten Text
BUILDING 30 SWITCHGEAR REPLACEMENT
DAK0013
Rectangle
DAK0013
Typewritten Text
G1-250KW,480V,3P4W
DAK0013
Typewritten Text
G3-250KW,480V,3P4W
DAK0013
Typewritten Text
G4-500KW,480V,3P4W
DAK0013
Typewritten Text
G5-100KW,480V,304W
DAK0013
Typewritten Text
G6-100KW,480V,
3P4W
DAK0013
Typewritten Text
G7-100KE,480V,3P4W
DAK0013
Typewritten Text
G9-250KW,480,
3P4W
DAK0013
Typewritten Text
G2-100KW,480V,3P4W
DAK0013
Rectangle
DAK0013
Typewritten Text
G8-100KW,480V,3P4W
DAK0013
Rectangle
DAK0013
Typewritten Text
G10-100KW,480V,3P4W
DAK0013
Typewritten Text
POWER BUS 4-2
DAK0013
Typewritten Text
POWER BUS 4-1
DAK0013
Typewritten Text
POWER BUS 3-2
DAK0013
Typewritten Text
POWER BUS 3-1
DAK0013
Typewritten Text
LIGHTING BUS-1
DAK0013
Typewritten Text
LIGHTING BUS-2
DAK0013
Typewritten Text
PANEL DPE
DAK0013
Typewritten Text
PANEL DPH2
DAK0013
Typewritten Text
MCC-1
DAK0013
Typewritten Text
PANEL PDP
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Typewritten Text
PANEL DPH1
DAK0013
Line
DAK0013
Typewritten Text
PANEL C1
DAK0013
Typewritten Text
PANEL 2HB
DAK0013
Rectangle
DAK0013
Typewritten Text
NOTES:
1. G1- FEED POWERBUS 4-1 & 4-2
2. G2- FEED PANEL DPE
3. G3-FEED POWERBUS 3-1 & 3-2
4. G4- FEED LIGHTING BUS 1&2, PANEL DPH2, MCC1
5. G5- FEED PANEL PDP, G6- FEED PANEL 4HB
6. G7- FEED PANEL 3HB, G8- FEED PANEL C1
7. G9- FEED PANEL HA & DPH1
8. G10- FEED PANEL 2HB
DAK0013
Typewritten Text
PANEL 4HB
DAK0013
Typewritten Text
PANEL 3HB
DAK0013
Typewritten Text
DAK0013
Typewritten Text
9. POWER BUS 3-1, 3-2, 4-1, 4-2 ARE AT 50 FEET HIGH
10. CONTRACTOR TO VERIFY ALL LOCATIONS
11. ALL GENERATOR CABLES MUST BE TEMPORARILY
INSTALLED ON THE WALL OR CEILING OR
VERTICAL COLUMNS. NO CABLE SHALL BE LAYED
ON THE FLOOR
12. GENERATOR LOCATIONS ARE SUBJECT TO CHANGE
BUILDING 30 SWITCHGEAR REPLACEMENT ANNEXURE 3
ANNEXURE 3BUILDING 30 SWITCHGEAR REPLACEMENT