Amendment 2_RFP# 202511156.docx

DOCX document 158 KB Posted

Attached to
Fire Alarm & Fire Suppression System Testing and Inspection State and local contract opportunity
Solicitation number
RFP - 03A - 202511156
Issued by
Maine

About this file

This is a solicitation amendment issued by the State of Maine Department of Corrections for RFP #202511156 regarding fire alarm and fire suppression system testing and inspection services. Amendment 2 corrects three significant omissions from the original RFP: the addition of Long Creek Youth Development Center (675 Westbrook Street, South Portland, ME) as a seventh service location, the inclusion of device counts for Downeast Correctional Facility that were previously missing from Attachment A, and the addition of device counts for Package 2 services covering fire extinguishers and hood suppression systems. The contract encompasses preventive maintenance and repair services across seven Maine correctional facilities, including Maine Correctional Center, Women's Reentry Center, Maine State Prison, Bolduc Correctional Facility, Mountain View Correctional Facility, Downeast Correctional Facility, and Long Creek Youth Development Center. Attachment A provides detailed device counts and inspection frequencies for each facility, including fire alarm panels, pull stations, smoke detectors, duct detectors, audio-visual devices, heat detectors, sprinkler systems, backflow preventers, fire hydrants, fire extinguishers, and hood agent systems. The contract is scheduled to commence March 1, 2026, with a base term through June 30, 2028, and two optional renewal periods potentially extending through June 30, 2031. Questions regarding the solicitation are due by December 30, 2025 at 4:00 p.m., and proposals must be submitted by January 20, 2026 at 4:00 p.m. through the Vendor Self Service system.

The amended RFP indicates that the Department reserves the right to make multiple awards and may award service packages separately, allowing for the possibility of different vendors serving different facilities or service categories. Vendors are required to possess active professional licenses in relevant areas such as backflow certification, fire sprinkler system contracting, inspection technician certification, and mobile elevated work platform (MEWP) certification, and all personnel must undergo background checks and comply with Maine Department of Corrections security regulations. Inspections must be conducted during normal business hours, Monday through Friday, 6:00 a.m. to 4:30 p.m., with coordination required through facility maintenance superintendents and local fire stations. Inspection reports identifying any deficiencies must be submitted within seven days of completion, and all services must adhere to applicable NFPA standards and state fire codes. The RFP does not specify set-aside designations or restrictions for disadvantaged enterprises, and vendors currently not providing maintenance or servicing the Department's existing systems are eligible to bid. The amendment does not disclose a specific budget range; however, the comprehensive scope across seven facilities with numerous devices and systems suggests substantial contract value.

View the file

Other files for this state and local contract opportunity

Other files attached to Fire Alarm & Fire Suppression System Testing and Inspection, newest first.
File Type Posted
RFP# 202511156 Fire Alarm and Suppression System_Final.docx DOCX document
Amendment 1_RFP# 202511156.docx DOCX document
RFP# 202511156 Q —
RFP# 202511156 Fire Alarm and Suppression System_Final.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATE OF MAINE

Solicitation Amendment

Department of Corrections

RFP # 202511156

Fire Alarm and Fire Suppression System Testing and Inspection

Amendment Details

Amendment Number:
2
Amendment Issued:
Refer to Attachment date in Vendor Self Service

Description of Changes

1. Long Creek Youth Development Center was inadvertently omitted from the list of Service Locations shown on page 7 of the RFP. Long Creek is included and is located at 675 Westbrook Street, South Portland, ME.

2. Device counts were inadvertently omitted from Attachment A for Downeast Correctional Facility. The corrected Attachment A is made available here:

3. Device counts for “Package 2” services (Fire Extinguishers and Hood Suppression) were inadvertently omitted from Attachment A. The corrected Attachment A is made available in item #2 above.

Revised Language in Solicitation

1. Part II-A is amended as follows:

A. Service Locations MDOC must develop a comprehensive maintenance plan and procure a qualified vendor to deliver preventive maintenance and repair services across all facilities. The successful bidder must be capable of providing service at the following MDOC facilities:

1. Maine Correctional Center –17 Mallison Falls Road, Windham, ME

2. Women’s Reentry Center – 230 River Road, Windham, ME

3. Maine State Prison – 807 Cushing Road, Warren, ME

4. Bolduc Correctional Facility – 516 Cushing Road, Warren, ME

5. Mountain View Correctional Facility – 1182 Dover Road, Charleston, ME

6. Downeast Correctional Facility – 64 Base Road, Machiasport, ME

7. Long Creek Youth Development Center – 675 Westbrook St., South Portland, ME

2. Attachment A is amended as attached here:

Revised 10/16/2025 – DAFS/Office of State Procurement Services pg. 1 image1.emf

ATTACHMENT A (Amended) - Device Counts by Facility .xlsx Downeast

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Simplex 4100ES

Fire Panel(s) 1

Pull Stations 8

SmokeDetectors - Test & Inspect 3

Duct Detectors - Functional test 2

AV's, Horn/Strobes 48

Gas Detectors 1

Co Alarm 12

Power Supply 2

Battery 6

Sprinkler System (Test & Inspect)

Backflow Preventers 5 Quarterly

Fire Pump 1 Quarterly

Wet Pipe 15 Annual

Fire Extinguishers 15 Annual

Hood Agent System(s) 1 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

Bolduc

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Simplex 4002; 4100; 4100ES

Fire Panel(s) 5

Pull Stations 6

SmokeDetectors - Test & Inspect 100

Duct Detectors - Functional test 5

AV's, Horn/Strobes 17

Heat Detectors 113

Sprinkler System (Test & Inspect)

Wet Risers 2 Quarterly

Dry Risers 1 Quarterly

Anti-Freeze Loops 1 Annual

Fire Extinguishers 77 Annual

Hood Agent System(s) 4 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

Maine State Prison

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Simplex 4100

Fire Panel(s) 7

Pull Stations 101

SmokeDetectors - Test & Inspect 346

Duct Detectors - Functional test 114

AV's, Horn/Strobes 239

Heat Detectors 144

NAC 6

Annunciator 4

Sprinkler System (Test & Inspect)

Wet Risers 10 Quarterly

Dry Risers 1 Quarterly

Anti-Freeze Loops 1 Annual

Backflow Preventer (Sprinkler, Domestic, Irrigation) 10 Annual

Fire Extinguishers 245 Annual

Hood Agent System(s) 3 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

Maine Correctional Center

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Simplex 4005; 4010ES; 4001; 4005; 4002; 4100; 2001

Fire Panel(s) 10

Pull Stations 58

SmokeDetectors - Test & Inspect 292

Duct Detectors - Functional test 34

AV's, Horn/Strobes 78

Heat Detectors 160

NAC 1

Annunciator 1

Sprinkler System (Test & Inspect)

Wet Risers 9 Quarterly

Dry Risers 1 Quarterly

Anti-Freeze Loops 2 Annual

Backflow Preventer (Sprinkler, Domestic, Irrigation) 8 Annual

Fire Extinguishers** 180 Annual

Hood Agent System(s)** 2 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

**These totals represent MCC and Women's Re-Entry Combined

Women's Re-Entry

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Edwards (EST i0500)

Fire Panel(s) 1

Pull Stations 11

SmokeDetectors - Test & Inspect 65

Duct Detectors - Functional test 20

AV's, Horn/Strobes 58

NAC 1

Sprinkler System (Test & Inspect)

Wet Risers 1 Quarterly

Backflow Preventer (Sprinkler, Domestic, Irrigation) 2 Annual

Fire Extinguishers** 180 Annual

Hood Agent System(s)** 2 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

**These totals represent MCC and Women's Re-Entry Combined

Long Creek Youth

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Simplex 4020; 4008; 4100ES

Fire Panel(s) 3

Pull Stations 40

SmokeDetectors - Test & Inspect 227

Duct Detectors - Functional test 86

AV's, Horn/Strobes 267

Heat Detectors 25

NAC 5

Annunciator 2

Other (AHU input, relays, etc.) 6

Door Holder 2

Sprinkler System (Test & Inspect)

Wet Risers 2 Quarterly

Anti-Freeze Loops 2 Annual

Private Fire Hydrants 3 Annual

Fire Extinguishers 48 Annual

Hood Agent System(s) 2 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

Mt. View Correctional

Fire Alarm (Test & Inspect) Quantity: Inspection Frequency: Proposed Inspection Month(s)*

Make/Model: Quarterly

Simplex 4001; 4007ES; 4002; 4100; 4020

Fire Panel(s) 9

Pull Stations 65

SmokeDetectors - Test & Inspect 275

Duct Detectors - Functional test 52

AV's, Horn/Strobes 292

Heat Detectors 95

NAC 4

Annunciator 1

Sprinkler System (Test & Inspect)

Wet Risers 9 Quarterly

Dry Risers 2 Quarterly

Backflow Preventer (Sprinkler, Domestic, Irrigation) 4 Annual

Fire Extinguishers 139 Annual

Hood Agent System(s) 5 Quarterly

*Assuming a contract start date of 3/1/2026, provide proposed inspection month(s) for the first year of the contract.

image2.jpeg