214 W. Fourth St., Greenville, OH 45331 937.548.7511 www.moteassociates.com
Engineering, Land Surveying
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO:
OF
MICHAEL J. BRUNS P.E. # 66091
TITLE SHEET
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH
1 9
4/28/15
DEL03081314 1D12975
1. ACCURACY OF DIMENSIONS AND CONDITIONS ARE TO BE FIELD VERIFIED. CONTRACTORS MUST EXAMINE THE JOB CONDITIONS
AND VERIFY ALL MEASUREMENTS, DISTANCES, ELEVATIONS, CLEARANCES, ETC. AND BASE THE BID AND WORK ON VERIFIED
CONDITIONS.
2. ALL FIELD DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE OWNER OF RECORD AND ENGINEER BEFORE
INCORPORATING THE DISCREPANCIES INTO NEW WORK.
3. DO NOT SCALE DRAWINGS TO DETERMINE DIMENSIONS. IF A REQUIRED DIMENSION IS NOT INDICATED, CONTACT THE ENGINEER OF
RECORD FOR DETERMINATION.
4. ALL AREAS OF THE SITE DISTURBED BY CONSTRUCTION ARE TO BE RESTORED BY THE RESPONSIBLE CONTRACTOR. PROVIDE
TOPSOIL AND SEED FOR ALL AFFECTED GRADED AREAS, PER SPECIFICATIONS. DAMAGED AND/OR TRENCHED PAVEMENTS ARE TO
BE SAW CUT AND FULL-DEPTH PATCHED WITH EQUIVALENT MATERIALS AND COMPACTION TO SUPPORT TRAFFIC WITHOUT
SETTLING. REPLACE ALL CONCRETE SIDEWALKS DAMAGED BY CONSTRUCTION ACTIVITIES.
5. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO TAKE EVERY MEASURE NECESSARY TO COMPLY WITH ANY FEDERAL OR
JURISDICTIONAL DUST CONTROL ORDINANCE.
6. CONTRACTORS SHALL IMMEDIATELY REMOVE ANY CONSTRUCTION DEBRIS OR MUD TRACKED ONTO EXISTING ROADWAYS.
7. SCHEDULE ALL SHUT DOWNS OF UTILITIES WITH THE OWNER 48 HOURS IN ADVANCE AS SPECIFIED. PREPARE SITE BEFORE HAND TO
MINIMIZE THE DURATION OF SHUT DOWNS. COMBINE SHUT DOWNS WHERE POSSIBLE.
8. ALL CONTRACTORS SHALL PROVIDE NEW, UNDAMAGED MATERIAL UNLESS OTHERWISE SPECIFIED.
9. INSTALL ALL WORK IN ACCORDANCE WITH CURRENT APPLICABLE CODES, PUBLISHED STANDARDS AND ACCEPTABLE
CONSTRUCTION STANDARDS. ALL NEW WORK SHALL BE STRAIGHT, SQUARE, PLUMB, AND LEVEL UNLESS OTHERWISE NOTED.
10. CONCRETE FOOTINGS: CONCRETE SHALL BE PLACED ON ORIGINAL UNDISTURBED EARTH. FOOTINGS SHALL NOT BE PLACED ON
FROZEN EARTH, MUD, ORGANIC SILT, OR UNPREPARED FILL. IT IS THE INTENT OF THESE PLANS THAT THE BOTTOM OF FOOTINGS
SHALL BE BELOW THE LOCAL FROST LINE AND SHALL DISTRIBUTE THE MAXIMUM DESIGN LOAD AS SPECIFIED IN BEARING CAPACITY
NOTE BELOW. FOOTINGS SHALL COMPLY WITH APPLICABLE REQUIREMENTS OF ACI 318. CONCRETE ULTIMATE COMPRESSIVE
STRENGTH SHALL BE 4000 PSI OR GREATER AT 28 DAYS. PROTECT CONCRETE FROM FREEZING FOR A MINIMUM OF 5 DAYS UPON
PLACEMENT.
11. PRESUMPTIVE SOIL BEARING CAPACITY IS 2000 PSF.
12. CONCRETE: UNLESS OTHERWISE NOTED, ALL EXTERIOR CONCRETE DRIVEWAYS, SIDEWALKS, AND APRONS SHALL BE 4000 PSI
CONCRETE AND RECEIVE A LIGHTLY BROOMED, NONSKID CONCRETE FINISH. ALL INTERIOR CONCRETE SLABS SHALL RECEIVE A
FLOATED AND STEEL TROWEL FINISH.
13. ALL CAST-IN-PLACE CONCRETE WORK INCLUDING BUT NOT LIMITED TO MECHANICAL EQUIPMENT BASES, PLUMBING BASES, AND
ELECTRICAL EQUIPMENT BASES SHALL BE PERFORMED BY A PROFESSIONAL CONCRETE CONTRACTOR UNLESS NOTED OTHERWISE.
14. THE CONCRETE CONTRACTOR SHALL SUPPLY THE OWNER WITH UP TO FOUR 2' x 2' FINISH SAMPLES FOR DETERMINATION OF FINISH
ON EXPOSED CONCRETE SLABS PRIOR TO INSTALLATION. SAMPLES SHALL BE SUBMITTED TO ALLOW THE DECIDING COMMITTEE A
MINIMUM OF TWO WEEKS TO OBSERVE AND CHOOSE A FINISH. CONTACT THE OWNER PRIOR TO MAKING SAMPLES TO DETERMINE
TYPES OF FINISHES TO BE SAMPLED. SAMPLES SHALL NOT INCLUDE COLORANTS.
15. ALL AGGREGATE FILL SHALL BE PLACED ON UNDISTURBED OR WELL COMPACTED EARTH SUBGRADE. ALL FILL UNDER CONCRETE
SLABS SHALL LOOSE FILL AGGREGATE IN 6" LIFTS.
16. MATERIAL COMPACTION STANDARDS: ALL COMPACTED MATERIALS IN BUILDING PADS, TRENCHES, EMBANKMENTS, ETC. SHALL BE IN
COMPLIANCE WITH CONTRACT DOCUMENTS FOR THE MATERIALS SPECIFIED.
17. ALL REINFORCING STEEL SHALL BE MINIMUM GRADE 60.
18. REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE ACI STANDARDS: SPECIFICATIONS FOR
STRUCTURAL CONCRETE FOR BUILDINGS (ACI 310), DETAILS AND DETAILING OF CONCRETE REINFORCEMENT (ACI 315-99), AND THE
MANUAL OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE STRUCTURES (ACI 315R) BY THE AMERICAN
CONCRETE INSTITUTE. THE MOST CURRENT EDITIONS OF CONCRETE REINFORCING STEEL INSTITUTE'S REINFORCING BAR
DETAILING AND PLACING REINFORCING BARS MAY ALSO BE USED.
19. OWNER WILL PROVIDE SPACE IN NEARBY ADJACENT BUILDING FOR CONSTRUCTION OFFICE AND CONSTRUCTION STORAGE.
20. THE FIRE EXTINGUISHERS WILL BE PROVIDED AND INSTALLED BY THE OWNER IN ACCORDANCE WITH THE REQUIREMENTS OF LOCAL
FIRE DEPARTMENT HAVING JURISDICTION.
PROJECT GENERAL NOTES
DRAWING INDEX
TITLE SHEET
SHEET 2
SHEET 1
SITE PLAN
SHEET 5FLOOR & ROOF PLAN
SHEET 6
ELECTRICAL PLAN
ELEVATIONS
PLUMBING PLAN
VICINITY MAP
UNITED STATES DEPARTMENT OF AGRICULTURE
FORESTRY SCIENCES LABORATORY
GREENHOUSE REPLACEMENT PROJECT
LOCATION MAP
PROPOSED
GREENHOUSE
LOCATION
M A
IN
R
O A
D
USDA FORESTRY
COMPLEX
ASPHALT DRIVE
SHEET 7
SHEET 8
APPLICABLE CODES:
2012 INTERNATIONAL BUILDING CODE
NFPA 101 LIFE SAFETY CODE
INTERNATIONAL PLUMBING CODE
INTERNATIONAL MECHANICAL CODE
NFPA 70 NATIONAL ELECTRICAL CODE
INTERNATIONAL ENERGY CONSERVATION CODE
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY GUIDELINES (ABAAG)
SUMMARY OF WORK:
THIS PROJECT INVOLVES THE CONSTRUCTION OF A NEW 1,800 S.F. 1-STORY GREENHOUSE TO REPLACE AN EXISTING "BUBBLE HOUSE"
GREENHOUSE. THE EXISTING "BUBBLE HOUSE" GREENHOUSE WILL BE REMOVED BE OWNER.
AN EXISTING 1-STORY MASONRY HEADHOUSE BUILDING WITH BASEMENT REMAINS IN OPERATION SERVING AS A HEADHOUSE FOR THE
NEW GREENHOUSE, PROVIDING UTILITIES, OFFICES, TOILET FACILITIES AND OTHER FUNCTION. NO ALTERATIONS TO THIS EXISTING
HEADHOUSE ARE PROPOSED, EXCEPT FOR PHYSICAL CONNECTION OF THE NEW GREENHOUSE AND UTILITY CONNECTIONS, CONTROLS, ETC.
THE GREENHOUSE WILL BE USED FOR RESEARCH USE FOR USDA FORESTRY AND IS OWNED BY THE FEDERAL GOVERNMENT.
USE GROUP: CONSTRUCTION TYPE:
'U' UTILITY "GREENHOUSE" TYPE VB
BUILDING HEIGHT: BUILDING AREA - ALLOWABLE FOR FLOOR:
ALLOWABLE: 1 STORY ALLOWABLE (AT): 5,000 SF USE GROUP U, CONSTRUCTION TYPE 5B
PROPOSED: 1 STORY, HEIGHT UNDER 40 FEET ACTUAL: 1,800 SF
OCCUPANCY LOAD PER UBC TABLE 1004.1.2: INTERIOR FINISHES:
AGRICULTURAL USE = 1 PERSON/300 SF = 6 PERSONS ROOMS AND ENCLOSED SPACES: CLASS C, FLAME 76-200, SMOKE -450
FIRE PROTECTION SYSTEMS:
AN AUTOMATIC SPRINKLER SYSTEM IS NOT REQUIRED
PORTABLE FIRE EXTINGUISHERS ARE REQUIRED THROUGHOUT THE BUILDING - TO BE PROVIDED AND INSTALLED BY BUILDING
OWNER
A FIRE ALARM AND DETECTION SYSTEM IS NOT REQUIRED
MEANS OF EGRESS:
COMMON PATH OF TRAVEL <30 PERSONS IS 100 FEET - TABLE 1014.3 "COMMON PATH OF EGRESS TRAVEL"
MAXIMUM EXIT ACCESS TRAVEL DISTANCE: 100FEET*
EXIT SIGNS NOT REQUIRED IN GROUP 'U' OCCUPANCY
*OCCUPANCY TRAVEL DISTANCE FOR ONE EXIT BUILDING IBC 1011.1 EXCEPTION 51, 3, AND IBC 1021.2, EXCEPTION 1
CODE ANALYSIS
GAS
TELEPHONE
UTILITY COMPANIES
ELECTRIC
ENGINEER
COLUMBUS SOUTHERN POWER
DEPARTMENT OF PUBLIC UTILITIES
910 DUBLIN RD.
COLUMBUS, OH 43215
PHONE: 614-645-8276
FRONTIER NORTH COMMUNICATIONS
PHONE: 1-855-626-8452
COLUMBIA GAS OF OHIO
PHONE: 1-800-344-4077
MICHAEL J. BRUNS, P.E.
MOTE & ASSOCIATES, INC.
214 WEST FOURTH ST.
GREENVILLE, OHIO 45331
PHONE: 937-548-7511
EMAIL: MBRUNS@MOTEASSOCIATES.COM
OWNER
MIKE ASH - CONTRACTING OFFICER
U.S. FOREST SERVICE
1992 FOLWELL AVE.
ST PAUL, MN 55108
PHONE: 651-649-5204
FAX 651-649-5285
RICHARD SINDT - PROJECT MANAGER
U.S. FOREST SERVICE
1992 FOLWELL AVE.
ST PAUL, MN 55108
PHONE: 651-649-5204
FAX 651-649-5285
ART HICKS - OPERATIONS SPECIALIST
U.S. FOREST SERVICE
359 MAIN ROAD
DELAWARE, OH 43015
PHONE: 740-368-0153
WATER/SANITARY/STORM
USDA FOREST SERVICE (PRIVATE SYSTEMS)
PROJECT COORDINATOR
MICHAEL W. HENDERSON, LEED GA
MOTE & ASSOCIATES, INC.
214 WEST FOURTH ST.
GREENVILLE, OHIO 45331
PHONE: 937-548-7511
EMAIL:
MHENDERSON@MOTEASSOCIATES.COM
SHEET 3SITE DETAILS
SHEET 4SITE DETAILS
ELECTRICAL PANELS & DETAILS SHEET 9
EXISTING "BUBBLE"
HOUSE TO BE
REMOVED BY OWNER
BUILDING CODE:
DESIGN LOADS
ROOF DEAD LOAD:
ROOF LIVE LOAD:
ROOF SNOW LOAD:
COLLATERAL LOAD:
WIND DESIGN DATA
BASIC WIND SPEED:
IMPORTANCE FACTOR:
EXPOSURE CATEGORY:
MEAN ROOF HEIGHT:
SNOW DESIGN DATA
GROUND SNOW LOAD:
SNOW LOAD IMPORTANCE FACTOR, I:
THERMAL FACTOR, CT:
SEISMIC DESIGN DATA
SEISMIC USE GROUP:
SEISMIC IMPORTANCE FACTOR, I E:
SEISMIC SITE CLASS
IN DESIGNING FOR THE ABOVE LOADS, THE
LOADS MAY BE CONSIDERED TO ACT IN
ANY OF THE FOLLOWING COMBINATIONS:
1.
2.
3.
4.
5.
6.
IBC 2012, ASCE 7-05
STRUCTURE & EQUIPMENT PLUS 1.0 PSF FOR 8MM POLYCARBONATE
12 PSF ON HORIZONTAL AREA
20 PSF
7.5 PSF (APPLIED TO TOP AND BOTTOM CHORDS OF TRUSSES)
90 MPH
1.0
B
20'-3"
20.0 PSF
1.0
NO THERMAL DEDUCTION SHALL BE TAKEN DUE TO NON-HEATED WINTER
CONDTIONS
I
1.0
B
DEAD LOAD
DEAD LOAD PLUS LIVE LOAD
DEAD LOAD PLUS SNOW LOAD
DEAD LOAD PLUS WIND LOAD PLUS LIVE LOAD
DEAD LOAD PLUS WIND LOAD PLUS SNOW LOAD
0.6 DEAD LOAD PLUS WIND LOAD
MICHAEL
J.
BRUNS
#E-66091
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO:
OF
MICHAEL J. BRUNS P.E. # 66091
SITE DETAILS
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH
3 9
1/4" = 1'-0"
4/28/15
DEL03081314 1D12977
4" PVC CAP AND
COVER (TOP AT FINAL
GRADE)
4" SCHEDULE 40 PVC
C.O. RISER
4" SCHEDULE 40 PVC
SEWER LATERAL TO
HEADHOUSE BASEMENT
CONNECTION, SLOPE 1/8"
PER FOOT
4" SANITARY
PROPOSED
GREENHOUSE
1'-6"
SANITARY LATERAL CLEANOUT DETAIL
SCALE: NONE
PIPE SHALL BE
EMBEDDED ON A 4"
MIN. #8 STONE BASE
TO MIN. 12" ABOVE
PIPE
TRENCH WIDTH
PIPE DIA. + 12"
EXCAVATED
MATERIAL
COMPACTED IN 8"
LIFTS
STORM SEWER OR
SANITARY SEWER
TRENCH BACKFILL DETAIL
SCALE: NONE
2 3/8" x 3 1/4" GALVANIZED
CORRUGATED DOWNSPOUT
3" x 4" TO 4"Ø PVC
DOWNSPOUT ADAPTER
4" SCHEDULE 40 PVC
TILE
ELBOW
4" SCHEDULE 40 PVC
TILE TO TEE INTO
EXISTING STORM TILE
DOWNSPOUT TILE ADAPTER DETAIL
SCALE: NONE
EXISTING STORM TILE,
EXACT SIZE UNKNOWN
PIPE SHALL BE
EMBEDDED ON A 4"
MIN. NATURAL SAND
BASE TO MIN. 12"
ABOVE PIPE
TRENCH WIDTH
PIPE DIA. + 12"
EXCAVATED
MATERIAL
COMPACTED IN 8"
LIFTS
K COPPER
WATER LINE
(EXTERIOR AND
BENEATH SLABS)
6" MIN. TOPSOIL, WITH
SEEDING AND MULCHING AS
SPECIFIED AND DIRECTED BY
OWNER
TRENCH BACKFILL DETAIL
SCALE: NONE
8"
12"
6" WIDE POLYPROPYLENE
TRENCH DRAIN
4000 PSI CONCRETE
TRENCH DRAIN SECTION
SCALE: NONE
TRENCH DRAIN DETAIL
SCALE: NONE
DUCTILE CAST
IRON GRATE
POLYPROPYLENE BODY
6" x 24"
POLYPROPYLENE
CATCH BASIN WITH
STRAINER
4" SANITARY LINE
947.45
TOP OF GRATE
DUCTILE CAST IRON GRATE
6" MIN. TOPSOIL, WITH
SEEDING AND
MULCHING AS
DIRECTED BY OWNER
END CAP
NOTE:
PROVIDE BEDDING AND
BACKFILL PER "TRENCH
BACKFILL DETAIL"
NOTE:
PROVIDE BEDDING AND
BACKFILL PER "TRENCH
BACKFILL DETAIL"
946.70
4" INV.
1'
2'-6" MIN.
VENT OUTSIDE APPARATUS DETAIL
SCALE: NONE
VENT MOTOR
1. CONCRETE SHALL BE 4000 PSI MINIMUM.
2. ALL VENT COMPONENTS INCLUDING MOTOR, SUPPORT
MEMBERS, FASTENERS, RACKS, GLAZING BARS, ETC TO BE
PROVIDED BY GREENHOUSE MANUFACTURER.
3. SUPPORT, AND RACK SPACING DETERMINED BY GREENHOUSE
PROVIDER.
GENERAL NOTES:
2" STEEL
SUPPORT SYSTEM
VENT RACK
VENT GLAZING BAR
GREENHOUSE
GRADE
MICHAEL
J.
BRUNS
AMMENDED 01/19/16: R. SINDT
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO:
OF
MICHAEL J. BRUNS P.E. # 66091
SITE DETAILS
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH
4 9
1/4" = 1'-0"
4/28/15
DEL03081314 1D12978
6"
PERIMETER FILTER FABRIC FENCE
MATERIALS:
FURNISH 30" WIDE FILTER FABRIC WITH SOUND WOOD SUPPORTS WITH MAXIMUM ON-CENTER
SPACING OF 10'. USE FILTER FABRIC CONFORMING TO 712.09 TYPE C. THE CONTRACTOR MAY
ELECT TO USE STRAW OR HAY BALES. USE 30" LONG 2"X2" WOODEN STAKES, REINFORCING
BARS OR FENCE POSTS FOR THE STRAW BALES.
TRENCH THE FILTER FABRIC FENCE AS DETAILED. THE CONTRACTOR MAY ELECT TO TRENCH
THE FENCE DETAILED ON STEPS 1 THROUGH 3 IN ONE PLOWING OPERATION.
CONSTRUCTION:
EXCAVATE A 6"x6" (150x150) TRENCH ALONG THE PROPOSED
FENCE LINE.
PLACE FABRIC AND SUPPORT STAKES AND EXTEND FABRIC INTO
THE TRENCH.
BACKFILL AND COMPACT THE EXCAVATED SOIL.
CONCRETE WASHOUT AREA NOTES
CONCRETE WASHOUT AREA FOR READY MIX TRUCKS SHALL BE:
PREFABRICATED WASHOUT CONTAINER
-THE CONTRACTOR MUST SIZE AND PROVIDE A WASHOUT AREA TO HANDLE SOLIDS,
WASH WATER AND RAINFALL TO PREVENT
-OVERFLOW. PROVIDE MINIMUM 12” OF OVERFLOW FREEBOARD.
OR,
ABOVE-GRADE SELF-INSTALLED CONCRETE WASHOUT
-THE CONTRACTOR MUST SIZE AND PROVIDE A WASHOUT AREA TO HANDLE SOLIDS,
WASH WATER AND RAINFALL TO PREVENT OVERFLOW. PROVIDE MINIMUM 12” OF
OVERFLOW FREEBOARD.
-MINIMUM 10' WIDE X 10' LONG AND SIZED TO CONTAIN ALL LIQUID AND SOLID WASTE
EXPECTED TO GENERATE BETWEEN CLEANOUT PERIODS.
-SUPPORT FRAMING TO INCLUDE AT LEAST TRIPLE LINED 10 MIL PLASTIC SHEETING.
PLACEMENT:
WASHOUT MUST BE 50' FROM ALL STORM DRAINS, SWALES AND CATCH BASINS
PREFERABLY NEAR THE AREA OF CONCRETE BEING POURED. PLACEMENT SHALL BE
APPROVED BY THE CITY ENGINEER PRIOR TO USE.
OPERATION:
INSPECT ALL FACILITIES DAILY TO VERIFY IF THEY ARE FILLED TO 75% OF CAPACITY.
REMOVE MATERIAL NEARING CAPACITY, VACUUM, AND DISPOSE OF IN AN APPROVED
MANNER. DO NOT DISCHARGE LIQUID TO WATERWAYS, SANITARY SEWERS, STORM
DRAINS OR DIRECTLY ON GROUND.
PLACE A SECURE, NON-COLLAPSING, NON-WATER COLLECTING COVER OVER THE
CONCRETE WASHOUT FACILITY PRIOR TO PREDICTED WET WEATHER TO PREVENT
ACCUMULATION AND OVERFLOW.
INSPECT DAILY FOR SIGNS OF CHANGE OR WEAKENING OF CONTAINER.
CONCRETE WASHOUT SHALL COMPLY WITH ALL FEDERAL, STATE AND LOCAL
REGULATIONS.
USE:
PROVIDE CONVENIENT ACCESS FOR TRUCKS.
PREVENT PAD TRACKOUT WITH A PAD OF ROCK OR QUARRY SPALLS.
ISOLATE FROM CONSTRUCTION TRAFFIC TO PREVENT ACCIDENTAL DAMAGE OR SPILLS.
INCORPORATE REQUIREMENTS FOR CONCRETE WASTE MANAGEMENT INTO CONCRETE
SUPPLIER AND SUBCONTRACTOR AGREEMENTS.
REMOVAL:
WHEN CONCRETE WASHOUT FACILITIES ARE NO LONGER NEEDED, THE HARDENED
CONCRETE, SLURRIES, AND LIQUIDS SHALL BE REMOVED AND PROPERLY DISPOSED OF
OR RECYCLED. HOLES, DEPRESSIONS OR OTHER GROUND DISTURBANCES CAUSED BY
THE REMOVAL OF THE TEMPORARY CONCRETE WASHOUT FACILITIES SHALL BE
BACKFILLED, REPAIRED AND STABILIZED TO PREVENT EROSION.
NON-SEDIMENT POLLUTION CONTROL
1. CONSTRUCTION PERSONNEL, INCLUDING SUBCONTRACTORS WHO USE OR HANDLE
HAZARDOUS OR TOXIC MATERIALS, SHALL BE AWARE OF THE FOLLOWING GENERAL
GUIDELINES:
DISPOSAL AND HANDLING
OF
HAZARDOUS AND OTHER CONSTRUCTION WASTE
DO:
PREVENT SPILLS
USE PRODUCTS UP
FOLLOW LABEL DIRECTIONS FOR DISPOSAL
REMOVE LIDS FROM EMPTY BOTTLES AND CANS WHEN DISPOSING IN TRASH
RECYCLE WASTE WHENEVER POSSIBLE
DON'T:
DON'T POUR INTO WATERWAYS, STORM DRAINS OR ONTO THE GROUND
DON'T POUR DOWN THE SINK, FLOOR DRAIN OR SEPTIC TANKS
DON'T BURY CHEMICALS OR CONTAINERS
DON'T BURN CHEMICALS OR CONTAINERS
DON'T MIX CHEMICALS TOGETHER
2. CONTAINERS SHALL BE PROVIDED FOR COLLECTION OF ALL WASTE MATERIAL INCLUDING
CONSTRUCTION DEBRIS, TRASH, PETROLEUM PRODUCTS AND ANY HAZARDOUS MATERIALS
TO BE USED ON-SITE. ALL WASTE MATERIAL SHALL BE DISPOSED OF AT FACILITIES APPROVED
FOR THAT MATERIAL.
3. NO WASTE MATERIALS SHALL BE BURIED ON-SITE.
4. MIXING, PUMPING, TRANSFERRING OR OTHERWISE HANDLING CONSTRUCTION CHEMICALS
SUCH AS FERTILIZER, LIME, ASPHALT, CONCRETE DRYING COMPOUNDS, AND ALL OTHER
POTENTIALLY HAZARDOUS MATERIALS SHALL BE PERFORMED IN AN AREA AWAY FROM ANY
WATERCOURSE, DITCH OR STORM DRAIN.
5. EQUIPMENT FUELING AND MAINTENANCE, OIL CHANGING, ETC., SHALL BE PERFORMED AWAY
FROM WATERCOURSES, DITCHES OR STORM DRAINS, IN AN AREA DESIGNATED FOR THAT
PURPOSE. THE DESIGNATED AREA SHALL BE EQUIPPED FOR RECYCLING OIL AND CATCHING
SPILLS.
6. CONCRETE WASH WATER SHALL NOT BE ALLOWED TO FLOW TO STREAMS, DITCHES, STORM
DRAINS, OR ANY OTHER WATER CONVEYANCE. A SUMP OR PIT SHALL BE CONSTRUCTED IF
NEEDED TO CONTAIN CONCRETE WASH WATER.
7. IF HAZARDOUS SUBSTANCES SUCH AS OIL, DIESEL FUEL, HYDRAULIC FLUID, ANTIFREEZE, ETC.
ARE SPILLED, LEAKED, OR RELEASED ONTO SOIL, THE SOIL SHOULD BE DUG UP AND
DISPOSED OF WITH THE TRASH AT A LICENSED SANITARY LANDFILL (NOT A
CONSTRUCTION/DEMOLITION DEBRIS LANDFILL). SPILLS ON A PAVEMENT SHALL BE
ABSORBED WITH SAWDUST OR KITTY LITTER AND DISPOSED OF WITH THE TRASH AT A
LICENSED SANITARY LANDFILL. HAZARDOUS OR INDUSTRIAL WASTE SUCH AS MOST
SOLVENTS GASOLINE, OIL-BASED PAINTS, AND CEMENT CURING COMPOUNDS REQUIRE
SPECIAL HANDLING. CONTACT OHIO EPA (1-800-282-9378).
8. SPILLS OF 25 GAL OR MORE OF PETROLEUM PRODUCTS SHALL BE REPORTED TO OHIO EPA
(1-800-282-9378), THE LOCAL FIRE DEPARTMENT, AND THE LOCAL EMERGENCY PLANNING
COMMITTEE WITHIN 30 MIN. OF THE DISCOVERY OF THE RELEASE.
SEDIMENT AND EROSION CONTROL FOR COMPLIANCE WITH OEPA'S INDIVIDUAL LOT
PERMIT FOR CONSTRUCTION PRESERVING EXISTING VEGETATION
WHENEVER POSSIBLE, PRESERVE EXISTING TREES, SHRUBS, AND OTHER VEGETATION,
EXCEPT WHEN NOTED TO BE REMOVED.
TO PREVENT ROOT DAMAGE, DO NOT GRADE, PLACE SOIL PILES, OR PARK
VEHICLES NEAR TREES MARKED FOR PRESERVATION.
SILT FENCE
PUT UP BEFORE ANY OTHER WORK IS DONE.
INSTALL ON DOWNSLOPE SIDE(S) OF SITE WITH ENDS EXTENDED UP SIDESLOPES A
SHORT DISTANCE.
PLACE PARALLEL TO THE CONTOUR OF THE LAND TO ALLOW WATER TO POND BEHIND
FENCE.
ENTRENCH 6 INCHES DEEP.
STAKE (1 STAKE EVERY 3 FEET FOR SILT FENCE).
LEAVE NO GAPS BETWEEN SECTIONS OF SILT FENCE.
INSPECT AND REPAIR ONCE A WEEK AND AFTER EVERY % INCH RAIN. REMOVE
SEDIMENT IF DEPOSITS REACH HALF THE FENCE OR STRAW BALE HEIGHT.
MAINTAIN UNTIL PLANTING AREAS ESTABLISHED.
SOIL PILES
LOCATED AWAY FROM ANY DOWNSLOPE STREET, DRIVEWAY, STREAM, LAKE,
WETLAND, DITCH OR DRAINAGE.
WAY
TEMPORARY SEED SUCH AS ANNUAL RYE IS RECOMMENDED FOR TOPSOIL PILES.
SURROUND WITH SILT FENCE ENCLOSURE.
GRAVEL DRIVE
INSTALL A SINGLE ACCESS DRIVE USING 2" AGGREGATE.
USE TO PREVENT TRACKING DIRT ONTO THE ROAD BY ALL VEHICLES.
MAINTAIN THROUGHOUT CONSTRUCTION UNTIL DRIVEWAY IS PAVED.
PARK ALL CONSTRUCTION VEHICLES ON THE STREET AND OFF OF THE SITE.
SEDIMENT CLEANUP
BY THE END OF EACH WORK DAY, SWEEP OR SCRAPE UP SOIL TRACKED ONTO THE
ROAD AND IN THE
GUTTERS
BY THE END OF THE NEXT WORK DAY AFTER A STORM, CLEAN UP SOIL WASHED
OFFSET, AND CHECK STRAW BALES AND SILT FENCE FOR DAMAGE OR SEDIMENT
BUILDUP.
DOWNSPOUT EXTENDERS
NOT REQUIRED, BUT HIGHLY RECOMMENDED.
INSTALL AS SOON AS GUTTERS AND DOWNSPOUTS ARE COMPLETED.
ROUTE WATER TO AREAS DIRECTED BY THE CITY ENGINEER.
STEP 1 STEP 2 STEP 3
MICHAEL
J.
BRUNS
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO:
OF
MICHAEL J. BRUNS P.E. # 66091
FLOOR & ROOF PLAN
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH
5 9
1/4" = 1'-0"
4/28/15
DEL03081314 1D12979
FLOOR PLAN
SCALE: 1/4" = 1'-0"
ROOF PLAN
SCALE: 1/4" = 1'-0"
KEYNOTES
1. PROPOSED 6' X 10' ROLL-UP STYLE DOOR.
2. PROPOSED 3'-6" X 7'-0" DOOR.
3. PROPOSED SINGLE SPEED EXHAUST FAN.
4. PROPOSED TWO SPEED EXHAUST FAN.
5. PROPOSED NATURAL GAS FIRED SUSPENDED UNIT HEATER FROM UNI-STRUT
SUPPORT SYSTEM WITH THERMOSTAT.
6. PROPOSED 3' DOUBLE RIDGE VENT.
7. PROPOSED RIDGE VENT MOTOR.
8. PROPOSED OUTSIDE APPARATUS 4' GABLE VENT.
9. PROPOSED GABLE VENT MOTOR.
10. PROPOSED EVAPORATIVE COOLING PAD.
11. PROPOSED EVAPORATIVE COOLING PUMP & TANK.
12. PROPOSED HORIZONTAL AIR FLOW FAN.
13. PROPOSED TRENCH DRAIN.
14. PROPOSED 8MM POLYCARBONATE GLAZING.
15. PROPOSED INSULATED PANEL.
16. PROPOSED GALVANIZED GUTTER.
17. PROPOSED DOWNSPOUT TO TILE.
18. PROPOSED CONCRETE FOUNDATION.
19. PROPOSED GALVANIZED STEEL GREENHOUSE FRAME.
20. PROPOSED CONTROL JOINT. 15' MAXIMUM SPACING.
SLOPE - 3/16" PER 1'-0"SLOPE - 3/16" PER 1'-0"
S L
O P
E
P
E R
S
L O
P
P
ID
30'-0"
60'-0"
12'-0" 12'-0" 12'-0" 12'-0" 12'-0"
A B C D E F
30'-0"
60'-0"
12'-0" 12'-0" 12'-0" 12'-0" 12'-0"
A B C D E F
20 20
MICHAEL
J.
BRUNS
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO:
OF
MICHAEL J. BRUNS P.E. # 66091
ELEVATIONS
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH
6 9
AS NOTED
4/28/15
DEL03081314 1D12980
12'-0" SIDEWALL HEIGHT
EAST ELEVATION
SCALE: 1/4" = 1'-0"
WEST ELEVATION
NORTH ELEVATION
SOUTH ELEVATION
GABLE SECTION
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
SLOPE - 3/16" PER 1'-0" SLOPE - 3/16" PER 1'-0"
KEYNOTES
ID
12'-0" SIDEWALL HEIGHT
12'-0" SIDEWALL HEIGHT
1'-6"
10"
3'-0" MIN.
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
#4 BARS @ 15" O.C.
LONGITUDINAL IN
FOOTING 3" COVER, TYP.
1/2" EXPANSION JOINT
WITH SEALANT
#4 L-SHAPED BAR
@ 18" O.C., TYP.
4" CONCRETE SLAB WITH 6 X 6-W2.0 X W2.0
WWF REINFORCEMENT ON 8" COMPACTED
AGGREGATE FILL COURSE WITH SMOOTH
TROWELED FINISH. PREPARE CONCRETE WITH
MANUFACTURER'S RECOMMENED PRODUCT,
LIKE SILOXANE WB SEALANT WITH SALTGUARD
WB (BY CONSOLIDEK OR APPROVED EQUAL).
2" R-10 RIGID FOUNDATION
INSULATION, TYP.
#4 BARS @ 8" O.C.
3" COVER, TYP.
8"
GRADE
#4 BARS @ 18" O.C.
VERTICAL, CENTERED
IN WALL, TYP.
#4 BARS @ 10" O.C.
3" MIN. COVER, TYP.
30'-0"
30'-0"
30'-0"
1'-0"
1. PROPOSED 6' X 10' ROLL-UP STYLE DOOR.
2. PROPOSED 3'-6" X 7'-0" DOOR.
3. PROPOSED SINGLE SPEED EXHAUST FAN.
4. PROPOSED TWO SPEED EXHAUST FAN.
5. PROPOSED NATURAL GAS FIRED SUSPENDED
UNIT HEATER FROM UNI-STRUT SUPPORT
SYSTEM WITH THERMOSTAT.
6. PROPOSED 3' DOUBLE RIDGE VENT.
7. PROPOSED RIDGE VENT MOTOR.
8. PROPOSED OUTSIDE APPARATUS 4' GABLE
VENT.
9. PROPOSED GABLE VENT MOTOR.
10. PROPOSED EVAPORATIVE COOLING PAD.
11. PROPOSED EVAPORATIVE COOLING PUMP &
TANK.
12. PROPOSED HORIZONTAL AIR FLOW FAN.
13. PROPOSED TRENCH DRAIN (SEE DETAIL).
14. PROPOSED 8MM POLYCARBONATE GLAZING.
15. PROPOSED INSULATED PANEL.
16. PROPOSED GALVANIZED GUTTER.
17. PROPOSED DOWNSPOUT TO TILE.
18. PROPOSED CONCRETE FOUNDATION.
19. PROPOSED GALVANIZED STEEL GREENHOUSE
FRAME.
20. PROPOSED UNI-STRUT IRRIGATION GRID
HANGING SYSTEM.
21. PROPOSED COMPACTED SUBGRADE.
22. PROPOSED MINIMUM 8" COMPACTED
AGGREGATE BASE.
23. PROPOSED VAPOR RETARDER IN
CONFORMANCE WITH ASTM E 1745. MINIMUM
THICKNESS OF 10 MIL.
FOUNDATION SECTION @ DOOR
SCALE: 1" = 1'-0"
#4 BARS @ 15" O.C.
LONGITUDINAL IN
FOOTING 3" COVER, TYP.
#4 L-SHAPED BAR
@ 18" O.C., TYP.
2" R-10 RIGID FOUNDATION
INSULATION, TYP.
#4 BARS @ 8" O.C.
3" COVER, TYP.
#4 BARS @ 18" O.C.
VERTICAL, CENTERED
IN WALL, TYP.
PROPOSED
ROLL-UP OR WALK
THROUGH DOOR
PER FLOOR PLAN
CONCRETE (SEE
SITE DETAILS)
947.73
947.75
1/2" EXPANSION JOINT
WITH SEALANT
947.70
2880'-0"
COMPACTED SUBGRADE,
TYP.
MINIMUM 10 MIL VAPOR
RETARDER, TYP.
12 55
6"
6"
MICHAEL
J.
BRUNS
Mote& Associates Engineering, Land Surveying
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO: OF
MICHAEL J. BRUNS P.E. # 66091
PLUMBING PLAN
FSL DELAWARE GREENHOUSE REPLACEMENT
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH 7 9
1/4" = 1'-0"
4/28/15
DEL03081314 1D12981
PLUMBING PLAN
SCALE: 1/4" = 1'-0" N
KEYNOTESID
30'-0"
60'-0"
12'-0" 12'-0" 12'-0" 12'-0" 12'-0"
A B C D E F
1. ALL UNDER FLOOR WASTE PIPING SHALL BE SCHEDULE 40 PVC EXCEPT THAT ALL PIPING WITHIN 10 FEET OF FLOOR DRAINS RECEIVING DISCHARGE FROM PRESSURE RELIEF VALVES SHALL BE CAST IRON.
2. ALL VENT PIPING SHALL BE SCHEDULE 40 PVC.
3. VENT PIPING SHALL SLOPE TO DRAIN, 0.5 PERCENT MINIMUM.
4. ALL EXCAVATION, BEDDING, AND BACKFILL SHALL MEET EARTHWORK SPECIFICATIONS FOR TRENCH
INSTALLATIONS UNDER BUILDINGS.
5. PROVIDE TRAP PRIMER AND COPPER WATER SUPPLY TO ALL FLOOR DRAINS AND TRENCH DRAIN
OUTLETS.
6. WATER DISTRIBUTION SHALL COMPLY WITH THE EDITION OF THE INTERNATIONAL BUILDING CODE.
7. ALL HORIZONTAL WASTE PIPING SHALL SLOPE IN COMPLIANCE WITH THE CURRENT EDITION OF THE
INTERNATIONAL BUILDING CODE.
8. INSTALL ALL HORIZONTAL WATER PIPING TO DRAIN BACK FROM NEW GREENHOUSE TO THE BASEMENT OF
THE EXISTING HEADHOUSE TO ALLOW FOR WINTERIZATION OF THE WATER LINES.
9. INCLUDE MOUNTING BRACKETS FOR FOR ALL MOUNTED FIXTURES.
10. ALL SANITARY PIPING SHALL COMPLY WITH THE CURRENT EDITION OF THE INTERNATIONAL BUILDING
CODE.
11. PROVIDE VACUUM BREAKERS, CHECK VALVES WHERE REQUIRED BY THE CURRENT ADDITION OF THE
INTERNATIONAL BUILDING CODE.
12. PROVIDE EPA APPROVED WATER SYSTEM BACKFLOW PREVENTER ON THE 1" WATER LINE FEED TO THE
NEW GREENHOUSE.
13. PIPE BACKFLOW PREVENTER RELIEF DRAIN LINES TO DRAIN IN BASEMENT, PROVIDE 2" AIR GAP.
14. UNDER FLOOR SLAB AND BURIED WATER LINE SHALL BE TYPE K COPPER.
15. ABOVE GRADE, INTERIOR WATER LINE SHALL BE TYPE L HARD DRAWN COPPER.
16. ALL ROOF DRAIN PIPING AND SANITARY WASTE PIPING UNDER SLAB SHALL SLOPE 1/8" PER FOOT.
PLUMBING NOTES
1. PROPOSED 6" WIDE X 24'-0" LONG PRE-SLOPED POLYPROPYLENE TRENCH DRAIN SYSTEM.
2. PROPOSED COMPATIBLE TRENCH DRAIN CATCH BASIN WITH REMOVABLE STRAINER.
3. PROPOSED 8" FLOOR DRAIN.
4. PROPOSED 3/4" MANUAL SHUT OFF VALVE
5. PROPOSED GAS FIRED HEATER.
6. PROPOSED EVAPORATIVE COOLING SYSTEM.
7. PROPOSED INCOMING WATER SERVICE (SEE SITE PLAN FOR CONTINUATION).
8. PROPOSED OUT GOING SANITARY LINE (SEE SITE PLAN FOR CONTINUATION).
9. PROPOSED 4" DIAMETER GREENHOUSE DOWNSPOUTS TO STORM TILE (SEE SITE PLAN FOR CONTINUATION).
10. PROPOSED INCOMING NATURAL GAS (SEE SITE PLAN FOR CONTINUATION).
11. PROPOSED GAS MANIFOLD/REULATOR (ABOVE GRADE)
12. PROPOSED GAS LINE THROUGH INSULATED PANEL.
13. PROPOSED GAS LINE RISE TO UNI-STRUT CEILING SUPPORT.
14. PROPOSED CONTROL JOINT. 15' MAXIMUM SPACING.
SANITARY AND WASTE DRAIN AND/OR SEWER
COLD WATER PIPING
PLUMBING PIPING LEGEND
C W
C W
C W
C W
S A N
S A N
SAN
CW
CW
GAS NATURAL GAS
GASGASGASGASGASGASGAS
G A S
G A S
G A S
8 9
SAN SAN
4" C.O.
C.O. CLEAN OUT
C.
O.
SE
E
SI
TE
P
LA
N
FO
R
CO
NT
IN
UA
TI
ON
T.
D.
THROUGH
FOUNDATION WALL, 2
FIXTURE UNITS
F.
D.
SANITARY ISOMETRIC DIAGRAM
SCALE: NONE
T.D. TRENCH DRAIN
F.D. FLOOR DRAIN
GAS ISOMETRIC DIAGRAM
SCALE: NONE
SE
E
SI
TE
P
LA
N
FO
R
CO
NT
IN
UA
TI
ON
THROUGH SLAB, FLOOR, WALL, ETC.
COPPER SHUT OFF VALVE, SIZED TO FIT LINE.
DRIP LEG
THROUGH GREENHOUSE
FLOOR
COLD WATER ISOMETRIC DIAGRAM
SCALE: NONE
1" K-COPPER
INCOMING WATER
BACKFLOW PREVENTER
150,000 BTU
NATURAL GAS FIRED
SUSPENDED UNIT
HEATER
GAS
GA
S
GAS
GA
S
C W
C W
C W
C W
C W
SAN
SA
N
INCOMING GAS
SLOPE - 3/16" PER 1'-0"
S
LO
P E
3/
" P
E R
'-0
S
LO
P
E
3/
" P E
R
'-0
947.75
947.75
947.75947.75947.75
947.45
947.75
947.75 947.45
TOP OF GRATE
946.70
4" INV.
946.54
4" INV.
SLOPE - 3/16" PER 1'-0"
1 1/4"
1"
3/4"4"
4"
4"
4"
THROUGH HEADHOUSE
BASEMENT FOUNDATION
WALL
TEE INTO EXISTING
WATER LINE INSIDE
HEADHOUSE
HOSE BIBB FOR FLEX LINE
FOR WATER SYSTEM
DRAIN DOWN FOR
WINTERIZATION
1"
1"
3/4"
1"
17'-0"26'-0"
NATURAL GAS REGULATOR/MANIFOLD
THROUGH
GREENHOUSE WALL
THROUGH CONCRETE
WALK
943.75
943.25
942.75
946.51" TYPE L COPPER
WATER (INSIDE)
COPPER HOSE BIBB, SIZED TO FIT LINE.
TRAP PRIMER DETAIL
ALL SUPPLY LINES TO
FLOOR DRAINS SHALL BE
1/4" COPPER
GRAVITY LINE TO
TRAP(S)
VACUUM BREAKER
TRAP - SEAL PRIMER
VALVE
COLD WATER BRANCH
LINE 1/2"
SCALE: NONE
15 15
150,000 BTU
NATURAL GAS FIRED
SUSPENDED UNIT
HEATER
1" TYPE L COPPER
WATER (INSIDE)
1. GAS PIPING INSTALLATION SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR.
2. ALL JOINTS IN THE PIPING SYSTEM, UNLESS WELDED, SHALL BE SCREWED WITH APPROVED STANDARD THREADS. THEY SHALL BE
MADE UP WITH APPROVED PIPE JOINT MATERIAL.
3. ALL GAS LINE MATERIALS AND INSTALLATION SHALL BE PROVIDED IN STRICT ACCORDANCE WITH THE LATEST VERSION OF THE
INTERNATIONAL FUEL GAS CODE.
4. PIPING SHALL BE THREADED IN COMPLIANCE WITH ASTM A120. JOINTS SHALL BE THREADED IN COMPLIANCE WITH ANSI B2.1.
UNDERGROUND PIPING SHALL BE C.P. AND BURIED AT LEAST 18" DEEP. BRANCH CONNECTIONS SHALL BE MADE ON THE TOP OR SIDES OF HORIZONTAL PIPE. PIPING SHALL BE SUPPORTED AT 10' INTERVALS. CONNECTION TO EACH APPLIANCE SHALL INCLUDE SHUTOFF VALVE AND UNION. GAS PIPING SHALL BE TESTED AT TWICE THE OPERATING PRESSURE WITH AIR OR INERT GAS. TEST SHALL LAST 15 MINUTES WITH NO PRESSURE DROP. PIPING SHALL BE PURGED TO A SAFE LOCATION.
5. ALL GAS PIPING WITHIN THE BUILDING SHALL BE STANDARD WEIGHT BLACK IRON PIPE PER ASTM A53, COPPER PIPE PER ASTM B42, OR COPPER TUBING TYPE K OR L ASTM B88. ALL COPPER PIPING SHALL BE PROTECTED FROM CORROSION.
6. PLASTIC PIPING, TUBING, AND FITTINGS SHALL BE USED OUTSIDE UNDERGROUND ONLY. SHALL CONFORM WITH ASTM D2513. PIPING
SHALL BE MARKED "GAS" AS ASTM D2513
7. ALL BRANCH PIPING SHALL BE SIZED PER PLUMBING FIXTURE ISOMETRIC DRAWING.
GAS PIPING NOTES
POWER EXHAUSTER
(WHERE REQUIRED BY
MANUFACTURER)
12" MIN.
GAS UNIT HEATER DETAIL
SCALE: NONE
ALUMINUM
PENETRATION PANEL
WITH SEALANT
4"Ø GAS TIGHT
GALVANIZED STEEL
UL LISTED APPLIANCE
VENT
GREENHOUSE WALL
UNIT
NATURAL
GAS
HEATER
3/4" NATURAL
GAS LINE
1. ALL VENTING SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURERS INSTALLATION INSTRUCTIONS AND THE
INTERNATIONAL MECHANICAL CODE.
2. SEAL ALL VENT JOINTS WITH A METALLIC TAPE OR SILASTIC
SUITABLE FOR TEMPERATURES UP TO 350°F.
3. PROVIDE CLEARANCES AS PER THE MANUFACTURER'S
WRITTEN INSTALLATION INSTRUCTIONS.
GAS HEATER GENERAL NOTES
1. GENERAL CONTRACTOR SHALL COORDINATE WITH THE PLUMBING, ELECTRICAL, AND HVAC CONTRACTORS PRIOR TO
CONSTRUCTION FOR PENETRATIONS THROUGH CONCRETE CONSTRUCTION.
2. ALL HVAC CONTRACTOR EQUIPMENT PROVIDED BY THE HVAC CONTRACTOR SHALL BE WIRED BY THE ELECTRICAL CONTRACTOR.
3. VENT SYSTEMS: VENTS SHALL BE UL OR FM LABELED. VENTS SHALL BE PROTECTED FROM DAMAGE. VENT CONNECTORS SHALL BE MINIMUM NO. 28 GALVANIZED SHEET GAUGE. STANDARD CONNECTORS SHALL MAINTAIN 9" CLEARANCE TO COMBUSTIBLES.
4. ALL APPLIANCES SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS.
5. PROVIDE CLEARANCE AS PER LISTED APPLIANCE FROM COMBUSTIBLE MATERIALS.
6. ALL GAS BURNING APPLIANCES SHALL HAVE AN APPROVED SHUT-OFF VALVE.
7. ALL APPLIANCES SHALL BEAR A LEGIBLE FACTORY APPLIED NAME PLATE.
8. ALL APPLIANCES SHALL BE PROPERLY VENTED WITH U.L. LISTED VENTING ASSEMBLIES.
9. PROVIDE ALL STRUCTURAL SUPPORTS FOR ALL EQUIPMENT AS RECOMMENDED BY THE EQUIPMENT MANUFACTURERS
10. FLASH AND SEAL ALL PENETRATIONS OF EXTERIOR WALLS AND ROOFS.
11. THERMOSTATS, AUTOMATIC DAMPERS, LOUVERS, CONTROL WIRING, ETC.. SHALL BE BY THE HVAC CONTRACTOR. CONDUIT AND BOXES FOR THE SAME ITEMS SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
MECHANICAL NOTES
3/4"
DRIP LEG
APPLIANCE SHUT-OFF VALVE
UNION
UNI-STRUT
2" VENT
VENT THROUGH ROOF
3" VENT
3" VENT
THROUGH ROOF
1 1/4"
1 1/4"
STAT E OF OH I O
MICHAEL
J.
BRUNS
#E-66091REG I S T ERED
PRO F ES S I ONA L E NG I N
EE
R
AMMENDED 01/14/16: R.SINDT
CAP FOR FUTURE EXPANSION
CAP FOR FUTURE EXPANSION
S
S
S
214 W. Fourth St., Greenville, OH 45331 937.548.7511 www.moteassociates.com
Mote& Associates Engineering, Land Surveying
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO: OF
MICHAEL J. BRUNS P.E. # 66091
ELECTRICAL PLAN
FSL DELAWARE GREENHOUSE REPLACEMENT
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH 8 9
1/4" = 1'-0"
4/28/15
DEL03081314 1D12982
POWER PLAN
SCALE: 1/4" = 1'-0" N
KEYNOTESID
ELECTRICAL LEGEND
30'-0"
60'-0"
12'-0" 12'-0" 12'-0" 12'-0" 12'-0"
A B C D E F
LIGHTING PLAN
SCALE: 1/4" = 1'-0" N
30'-0"
60'-0"
12'-0" 12'-0" 12'-0" 12'-0" 12'-0"
A B C D E F
S
S
115 VOLT, 20 AMP DUPLEX RECEPTACLE MOUNTED ON WALL 4'-6" ABOVE FLOOR (TO TOP OF BOX)
UNLESS NOTED OTHERWISE. ALL RECEPTACLES AND COMPONENTS MUST MEET UL LISTING
REQUIREMENTS FOR WET LOCATION.
ELECTRIC MOTOR PROVIDED WITH EQUIPMENT UNLESS NOTED OTHERWISE.
BRANCH CIRCUIT POWER WIRING.
POWER CIRCUIT WIRING TO PANEL AND CIRCUIT BREAKER NUMBER INDICATED.
SINGLE POLE 115 VOLT, 20 AMP SNAP SWITCH, 4'-0" ABOVE FLOOR (TOP OF BOX).
3 WAY 115 VOLT, 20 AMP SNAP SWITCH, 4'-0" ABOVE FLOOR (TOP OF BOX).
(9) GENERAL PURPOSE LIGHTS: LITHONIA SERIES CB WITH TWO 32 WATT, 115 VOLT, T-8 LAMPS.
FIXTURES DESIGNATED N-E SHALL HAVE EMERGENCY BATTERY BALLASTS TO OPERATE THE
FIXTURE 1-1/2 HOURS UPON LOSS OF NORMAL POWER. FIXTURES SHALL BE MOUNTED
APPROXIMATELY 11'-6" ABOVE THE FLOOR
20 AMP, 115 VOLT GROW LIGHT RECEPTACLE (TWO LIGHT PER RECEPTACLE), NEMA 5-20R
EXCEPT WHERE OTHER CONFIGURATION IS REQUESTED BY OWNER. CONTRACTOR SHALL
REQUEST DIRECTION ON CONFIGURATION FROM GROW LIGHT PROVIDER BEFORE PURCHASING
ANY LIGHTING RECEPTACLES.
EXTERIOR EGRESS LIGHT: LITHONIA TWA-CF 115 VOLT, 26 WATT, COMPACT FLUORESCENT WALL
PACK FIXTURE WITH PHOTOCELL. FIXTURE SHALL NOT BE SWITCHED. BALLASTS SHALL BE
RATED FOR USE AT AMBIENT TEMPERATURES DOWN TO 20° F. MOUNT FIXTURE A MINIMUM OF
10'-0" ABOVE FINISHED FLOOR.
1. PROPOSED SINGLE SPEED EXHAUST FAN.
2. PROPOSED TWO SPEED EXHAUST FAN.
3. PROPOSED NATURAL GAS FIRED UNIT HEATER WITH THERMOSTAT.
4. PROPOSED RIDGE VENT MOTOR
5. PROPOSED GABLE VENT MOTOR.
6. PROPOSED EVAPORATIVE COOLING PUMP & TANK.
7. PROPOSED HORIZONTAL AIR FLOW FAN.
8. PROPOSED UNI-STRUT HANGING SYSTEM. UNI-STRUT SYSTEM TO BE 6' ON
CENTER LENGTH WAYS AND ATTACHED BETWEEN EACH TRUSS BOTTOM
CHORD.
9. PROPOSED SHADE SYSTEM MOTOR.
10. PROPOSED 400 AMP 120/208V 3 PHASE POWER PANEL (P-1).
11. PROPOSED 200 AMP 120/208V 3 PHASE SUB PANEL (P-2).
12. PROPOSED CONTACTOR PANEL.
13. PROPOSED CONTROLS PANEL.
14. PROPOSED INCOMING POWER.
15. PROPOSED WEATHER STATION, LOCATION TO BE DETERMINED. WIRING FROM
CONTROLS PANEL.
16. EXISTING HEAHOUSE.
17. EXISTING DOOR LOCATED ON NORTH WALL OF HEADHOUSE.
18. PROPOSED 1" CONTROLS CONDUIT TO HEADHOUSE..
1. MINIMUM ACCEPTABLE CONDUCTOR SIZES PROTECTED BY PANELBOARD CIRCUIT BREAKERS
SHALL BE AS FOLLOWS:
BREAKER, CONDUCTOR, MIN. CONDUIT SIZE
TRIP RATING SIZE
[AMPS] [AWG CU.]
15 #12 -----------------------------3/4" 20 #12 -----------------------------3/4" 30 #10 -----------------------------3/4" 40 # 8 ------------------------------3/4" 50 # 6 ------------------------------1" 60 # 4 ------------------------------1 1/4" 75 # 3 ------------------------------1 1/2" 90 # 2 ------------------------------1 1/2"
PROVIDE LARGER CONDUCTORS WHERE INDICATED.
2. BRANCH CIRCUITS HAVING MORE THAN 75 FEET OF CONDUCTOR LENGTH BETWEEN THE
PANELBOARD AND THE FIRST UTILIZATION DEVICE OR OUTLET ON THE CIRCUIT SHALL HAVE
CONDUCTORS ONE SIZE LARGER THAN INDICATED IN THE ABOVE CONDUCTOR SIZING NOTE.
3. NO MORE THAN 9 CURRENT CARRYING CONDUCTORS MAY BE INSTALLED IN ANY ONE RACEWAY.
WHEN MORE THAN THREE CURRENT CARRYING CONDUCTORS ARE INSTALLED IN ONE RACEWAY,
CAPACITY OF CONDUCTORS MUST BE DERATED AS REQUIRED BY NEC. WHERE NECESSARY,
UPSIZE CONDUCTORS SUCH THAT DERATED CAPACITY IS NOT LOWER THAN THE OVERCURRENT
PROTECTION TRIP RATING.
4. BRANCH CIRCUITS SHALL HAVE ALL NEUTRAL CONDUCTORS COUNTED AS CURRENT CARRYING
CONDUCTORS. ALL 120 VOLT BRANCH CIRCUITS SHALL HAVE INDIVIDUAL DEDICATED NEUTRAL
CONDUCTORS. DO NOT SHARE NEUTRAL CONDUCTORS ON MULTIPLE CIRCUITS.
5. WHERE PHASE CONDUCTORS ARE UPSIZED FOR LENGTH OF RUN OR GROUPING IN RACEWAYS,
ALSO UPSIZE NEUTRAL AND GROUNDING CONDUCTORS TO MATCH.
6. ALL ELECTRICAL MATERIALS INSTALLED LOWER THAN 10 FEET ABOVE THE FLOOR IN
GREENHOUSE COMPARTMENTS SHALL BE UL LISTED FOR USE IN WET LOCATIONS.
7. ALL 120 VOLT RECEPTACLE CIRCUITS ON THIS PROJECT SHALL BE GFCI PROTECTED BY ONE OF
THE RECEPTACLES ON THE CIRCUIT.
8. ALL CIRCUITS IN GREENHOUSE SHALL BE SERVED FROM THE PANELBOARD IN THAT
GREENHOUSE.
9. ALL CONDUITS IN THE GREENHOUSE CONSTRUCTION SHALL BE SCHEDULE 80 PVC WITH
PROVISIONS FOR EXPANSION AT EACH COUPLING.
10. CONDUIT PENETRATION THROUGH CONCRETE SLABS SHALL BE RIGID STEEL.
11. HORIZONTAL CONDUITS SHALL NOT BE EMBEDDED IN CONCRETE FLOORS.
12. MINIMUM CONDUIT SIZE SHALL BE 3/4 INCH.
13. PROVIDE THHN/THWN COPPER.
14. ALL EQUIPMENT CONNECTIONS SHALL BE MADE USING LIQUID TIGHT FLEXIBLE METAL CONDUIT.
15. ALL CONDUIT ROUTING SHALL BE DETERMINED BY THE CONTRACTOR AND SHALL MEET ALL
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
16. MOUNT LIGHTING RECEPTACLE ON THE FRAMING SYSTEM PROVIDED TO SUPPORT THE GROWTH
LIGHTS, APPROXIMATELY 12'-0" ABOVE FINISHED FLOOR.
17. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MOUNTING THE GREENHOUSE
ENVIRONMENTAL CONTROLS AND MAKING THE CONNECTIONS BETWEEN THE BREAKER PANEL
AND THE CONTACTOR PANEL. ELECTRICAL CONTRACTOR SHALL RUN COMMUNICATION CABLE
FROM THE TEMPERATURE SENSOR TO THE CONTROL BOX,THE WEATHER STATION TO THE
CONTROL BOX AND THE COMPUTER (TO BE PROVIDED BY OWNER) TO THE CONTROL BOX.
CONTROLS CONDUCTORS SHALL BE RAN IN SEPARATE CONDUIT.
18. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MOUNTING POWER PANEL, ELECTRICAL
CONDUITS, FITTINGS, INSTALLING ALL BREAKERS AND WIRING.
ELECTRICAL NOTES
101112
SINGLE SPEED EXHAUST FAN
TWO SPEED EXHAUST FAN
VC2000 ROOF VENT MOTOR
VC2000 GABLE END VENT MOTOR
TF150 NATURAL GAS HEATER
VK12 H.A.F. FANS
EQUIPMENT DISCRIPTION QTY
VOLTAGE
PHASE
3/4
HP
7.8
AMPS
1 115 1 3/4 9.3 2 115 1 1/5 2.5 1 115
2 115 2 115
1/5
1/4 1/10
2.5
5.8 1.3
EVAPORATIVE COOLING PUMP 1 115 1 1/3 2.9
VC2000 ROOF SHADE MOTOR (OPT 2) 1 115 1 1/5 2.5
P-1
CCT-2
P-2
CCT-1
P-2
CCT-2
P-2
CCT-3
P-2
CCT-4
P-2
CCT-5
P-2
CCT-6
P-2
CCT-7
P-2
CCT-8
P-2
CCT-9
P-1
CCT-4
P-1
CCT-7
P-1
CCT-6
P-1
CCT-8
P-1
CCT-15
P-1
CCT-9
P-1
CCT-10
P-1
CCT-12
P-1
CCT-14
P-1
CCT-16
P-1
CCT-13
P-1
CCT-11
101112 14
P-1
CCT-1,2,3
STAT E OF OH I O
MICHAEL
J.
BRUNS
#E-66091REG I S T ERED
PRO F ES S I ONA L E NG I N
EE
AMMENDED 01/14/16: R. SINDT
Mote& Associates Engineering, Land Surveying
DATE
REVISIONS:
SCALE:
DATE:DRAWN: CHECKED:
PROJ. NO: DWG. NO:
SHEET NO: OF
MICHAEL J. BRUNS P.E. # 66091
ELECTRICAL PANELS & DETAILS
FSL DELAWARE GREENHOUSE REPLACEMENT
U.S. DEPARTMENT OF AGRICULTURE
FINAL DESIGN DRAWINGS
4/28/15
CRM MWH 9 9
NONE
4/28/15
DEL03081314 1D12983
PROPOSED 400 AMP PANEL
ONOFF
PANEL: P-1
NEC LOAD: 80.15A
VOLTS: 120/208
AMPS: 400A PHASE: 3
NO. LOAD DESCRIPTION
BRKR
AMPS
LEFT PHASE
LOADING (WATTS) NO.LOAD DESCRIPTION
BRKR
AMPS
POLE
A B C
RIGHT PHASE
LOADING (WATTS)
A B C
POLE
BRANCH BREAKERS
20 1 897
SPACE
SPACE
SINGLE SPEED EXHAUST FAN
20 1 20 1 20 1 20 1
13794 11597 11704 2877 1675 1937
SPACE
SPACE
TWO SPEED EXHAUST FAN
ROOF SHADE MOTOR288
288 GABLE VENT MOTOR
NATURAL GAS HEATER667
299HORIZONTAL AIR FLOW FANS
EVAP. PUMP-WEST WALL REC.
667NORTH WALL REC. 720
SOUTH WALL REC.
EAST WALL REC. 540
GENERAL PURPOSE LIGHTS 314
REMOVE EXISTING POWER
CONDUCTORS AND INSTALL NEW
FEEDER IN EXISTING CONDUIT
(2) SETS - #4/0 THHN/THWN
CU. AND (1) #3 GROUND
PANEL
P1
400A MCB
NEMA 3R
CIRCUITS
3PH-400
SPACE
3PH-100
ELECTRICAL SINGLE LINE DIAGRAM
3PH-100
3PH-100
EXISTING GREENHOUSE
EXISTING SPARE
EXISTING BASEMENT
WESTINGHOUSE 120/208 VOLT,
3 PH, 4-W 1200 AMP PANEL
MDP
SPACE3PH-225
EXISTING
EXISTING
KEYNOTESID
1. ALL WORK SHALL CONFORM TO THE NATIONAL ELECTRIC
CODE.
2. REMOVE AND DISPOSE OF ANY TEMPORARY WIRING AS
DIRECTED BY OWNER.
3. FINAL SHOP DRAWINGS OF THE POWER PANELS AND
CONTACTOR PANEL SHALL BE PROVIDED AND APPROVED BY
OWNER PRIOR TO CONSTRUCTION AND INSTALLATION. IT
SHALL BE THE ELECTRICAL CONTRACTORS RESPONSIBILITY
TO COORDINATE POWER WIRING AND CONTROL WIRING
SYSTEMS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
PREPARING SHOP DRAWINGS.
GENERAL NOTES:
UNI-STRUT PLAN VIEW DETAIL
SCALE: NONE
UNI-STRUT SIDE VIEW DETAIL
SCALE: NONE
1. UNI-STRUT P1000 SERIES, 0.20 MINIMUM MODULUS APPROXIMATELY 6' ON
CENTER, ATTACH TO TRUSS BOTTOM CHORD USING 3/8" BOLTS. (RUNNING THE
LENGTH OF THE GREENHOUSE).
2. UNI-STRUT P1000 SERIES, 0.20 MINIMUM MODULUS APPROXIMATELY 12' ON
CENTER (EQUALLY SPACED BETWEEN TRUSS BOTTOM CHORDS), ATTACH TO
UNI-STRUT USING 3/8" BOLTS.
3. ELECTRICAL CONDUIT.
4. ELECTRICAL JUNCTION BOX.
5. GROW LIGHT RECEPTACLE.
6. FUTURE GROW LIGHT ELECTRICAL DEMAND ASSUMPTIONS:
115 VOLT, 1 PH, 5.7 AMPS (OR) 208 VOLT 1 PH, 3.3 AMPS (CURRENTLY SHOWING)
NATURAL GAS HEATER
PROPOSED 200 AMP PANEL
ONOFF
PANEL: P-2
NEC LOAD: 59.4A
VOLTS: 120/208
AMPS: 200A PHASE: 3
NO. LOAD DESCRIPTION
BRKR
AMPS
LEFT PHASE
LOADING (WATTS) NO.LOAD DESCRIPTION
BRKR
AMPS
POLE
A B C
RIGHT PHASE
LOADING (WATTS)
A B C
POLE
BRANCH BREAKERS
20 1
SPACE
SPACE
20 1 20 1 20 1 20 1
2746 2746
SPACE
SPACE
GROW LIGHT RECEPTACLE
GROW LIGHT RECEPTACLE GROW LIGHT RECEPTACLE
GROW LIGHT RECEPTACLE GROW LIGHT RECEPTACLE
GROW LIGHT RECEPTACLE GROW LIGHT RECEPTACLE
GROW LIGHT RECEPTACLE GROW LIGHT RECEPTACLE1373
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE
1373 2746 1373 1373
P-2 P-2 P-2
200 3
3 ROOF VENT MOTORS575
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE
SPACE
12357 10984
10984
PANEL
P2
200A MCB
NEMA 3R
CIRCUITS
(4) #3/0 (1) #2
GROUND THHN/THWN
CU. IN 2" CONDUIT
GRADE
EXISTING POWER
FEED TO REMAIN
REMOVE AND REPLACE POWER WIRING
FROM MDP TO NEW PANEL P-1.
PROVIDE (2) SETS (4) - #4/0
THHN/THWN CU. AND (1) #2 GROUND
IN EXISTING 4" CONDUIT AND
PROPOSED EXTENDED CONDUIT
EXISTING HEADHOUSE INSIDE PROPOSED
GREENHOUSE
GRADE
EXISTING BUBBLE
HOUSE TO BE
REMOVED BY OWNER
CUT EXISTING 4" CONDUIT AND
EXTEND 4" CONDUIT TO PROPOSED
GREENHOUSE. PROVIDE PROTECTIVE
CONCRETE DUCT AND CONTINUE
TRACER WIRE. PROVIDE CAUTION
TAPE ABOVE CONDUIT
THE EXISTING ELECTRICAL EQUIPMENT INSIDE THE
HEAHOUSE WILL BE REMOVED BY OWNER. THE
CONTRACTOR SHALL COORDINATE ELECTRICAL SYSTEM
SWITCHGEAR TO NEW GREENHOUSE WITH OWNER. THE
CONTRACTOR SHALL PROVIDE TEMPORARY ELECTRIC
MEASURES TO THE EXISTING BUBBLE HOUSE UNTIL
NEW GREENHOUSE IS COMPLETED AND OWNER HAS
OCCUPANCY
RATING: NEMA 3R RATING: NEMA 3R
CONFIRM EXISTING
GROUNDING
6 6
PROVIDE (2) SETS (4) - #4/0
THHN/THWN CU. AND (1) #2
GROUND IN 4" CONDUIT
STAT E OF OH I O
MICHAEL
J.
BRUNS
#E-66091REG I S T ERED
PRO F ES S I ONA L E NG I N
EE
R
AMMENDED 01/14/16: R. SINDT
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE