a0002REVISED_Sheet_E001_-from_Y2_Drawings_FINAL_SUBMITTAL.pdf

PDF 614 KB Posted

Attached to
Y2K BLDG Federal contract opportunity
Solicitation number
AG-6197-S-17-0014
Issued by
Department of Agriculture Animal and Plant Health Inspection Service Veterinary Services

About this file

drawing

View the file

Other files for this federal contract opportunity

Other files attached to Y2K BLDG, newest first.
File Type Posted
SF30a00003.pdf PDF
SF30a00002.pdf PDF
a0002Bldg_22_and_Bldg_Y2_area_map.pdf PDF
A0001drawing.pdf PDF
A0001signin.pdf PDF
A0001Question.docx DOCX document
A0001bidsch.docx DOCX document
SF30a00001.pdf PDF
AG-6197-S-17-0014_Y2K.docx DOCX document
Y-2_Construction_Specifications.pdf PDF
Attch_J_General_Decision_NumberIA170145_07282017.docx DOCX document
Atth_J_SOW_for_Y-2_Building_Remodel.docx DOCX document
1442.pdf PDF
Y-2_Construction_Renovation_Drawings.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Scale: NONE

E001

PROPOSED SINGLE LINE DIAGRAM

Scale: NONE

E001

DEMOLITION SINGLE LINE DIAGRAM

SINGLE LINE NOTES:

No.

Description

A.

LIGHT COLORS DENOTE EXISTING CIRCUITRY AND EQUIPMENT, DARKER COLORS DENOTE NEW

CIRCUITRY AND EQUIPMENT.

Scale: NONE

E001

GROUNDING DETAIL

KEYED NOTES

Mark

Description

DEMOLISH EXISTING ELECTRICAL DEVICE, CIRCUITRY, AND ALL ASSOCIATED APPURTENANCES AS

REQUIRED.

Scale: NONE

E001

GROUNDING DETAIL

Scale: NONE

E001

A-A DUCTBANK DETAIL

Scale: NONE

E001

B-B DUCTBANK DETAIL

AutoCAD SHX Text EXISTING UTILITY TRANSFORMER SQUARE D #EE50S3H 50kVA, 480:240/120V,1 ,3W

AutoCAD SHX Text Y2 60/2/3R F-60

AutoCAD SHX Text Z2B 100/2/3R F-100

AutoCAD SHX Text Z2A 100/2/3R F-100

AutoCAD SHX Text

HOOP BARN 100/2/3R F-100

AutoCAD SHX Text Z3 100/2/3R F-100

AutoCAD SHX Text 3#6,#10(G),1"C.

AutoCAD SHX Text

EXISTING ELECTRICAL GUTTER

AutoCAD SHX Text

ETR

AutoCAD SHX Text

ETR

AutoCAD SHX Text

EXISTING 8 CKT LOADCENTER

AutoCAD SHX Text 20/1

AutoCAD SHX Text 20/1

AutoCAD SHX Text 20/1

AutoCAD SHX Text 15/1

AutoCAD SHX Text

TYPE 2A SPD

AutoCAD SHX Text

SEE PANEL SCHEDULE FOR EXACT INFORMATION.

AutoCAD SHX Text

SEE GROUNDING DETAIL 4/E001.

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text

PANEL A

AutoCAD SHX Text

#2/0(G), 1" PVC C.

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

8' MIN.

AutoCAD SHX Text

EXOTHERMIC WELD

AutoCAD SHX Text

8' MIN.

AutoCAD SHX Text

(TYPICAL OF ALL)

AutoCAD SHX Text

BOND TO BUILDING STEEL. USE EXOTHERMIC WELD.

AutoCAD SHX Text

BOND TO GROUND BUSHING ON ALL FEEDER CONDUITS.

AutoCAD SHX Text

GROUNDING AND BONDING SHALL COMPLY WITH NEC ARTICLE 250.

AutoCAD SHX Text

(3) 3/4"x10' COPPER CLAD DRIVEN GROUND RODS IN TRIANGULAR FORM. (TRIAD GROUNDING GRID)

AutoCAD SHX Text

GROUND BAR

AutoCAD SHX Text

NO N-G BOND.

AutoCAD SHX Text THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NEW 250/3, ELECTRONIC TRIP CIRCUIT BREAKER IN EXISTING PANEL OSMCC4-G1 IN BUILDING 21. MATCH EXISTING BREAKER TYPE AND AIC RATING.

AutoCAD SHX Text

3#250KCM, #4(G), 3"C. IN CONCRETE DUCTBANK. SEE DETAIL 5/E001.

AutoCAD SHX Text NEW 150kVA TRANSFORMER 480:208Y/120V,3 ,4WNEMA 3R RATED ENCLOSURE

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text

TWO RUNS OF: 4#350KCM, #2/0(G), 3-1/2"C.

AutoCAD SHX Text

#2/0 BARE COPPER GROUND, 1" PVC CONDUIT, BOND TO MAIN GROUND BAR IN PANEL DP

AutoCAD SHX Text

4#500KCM, #3(G), 3-1/2"C. IN CONCRETE DUCTBANK SEE DETAIL 6/E001

AutoCAD SHX Text

SEE 3/E001.

AutoCAD SHX Text 3#1, #8(G), 1-1/2"C.

AutoCAD SHX Text

EXISTING HOOP BARN CIRCUITRY

AutoCAD SHX Text

EXISTING Z3 CIRCUITRY

AutoCAD SHX Text 3#1, #8(G), 1-1/2"C.

AutoCAD SHX Text

PANEL DP:

AutoCAD SHX Text

CONNECTION TO EXISTING CIRCUITRY AS REQUIRED.

AutoCAD SHX Text #6(G)

AutoCAD SHX Text

#1(G), 1" PVC C.

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

8' MIN.

AutoCAD SHX Text

EXOTHERMIC WELD

AutoCAD SHX Text

8' MIN.

AutoCAD SHX Text

(TYPICAL OF ALL)

AutoCAD SHX Text

BOND TO GROUND BUSHING ON ALL FEEDER CONDUITS.

AutoCAD SHX Text

GROUNDING AND BONDING SHALL COMPLY WITH NEC ARTICLE 250.

AutoCAD SHX Text

(3) 3/4"x10' COPPER CLAD DRIVEN GROUND RODS IN TRIANGULAR FORM. (TRIAD GROUNDING GRID)

AutoCAD SHX Text

GROUND BAR

AutoCAD SHX Text #6(G)

AutoCAD SHX Text

TYPE 1 SPD

AutoCAD SHX Text

SEE PANEL SCHEDULE FOR EXACT INFORMATION.

AutoCAD SHX Text

400/3/3R DISCONNECT SWTICH

AutoCAD SHX Text

IT SHALL BE REPAIRED TO MATCH ITS PRE-

AutoCAD SHX Text

WHERE CONCRETE OR ASPHALT IS CUT,

AutoCAD SHX Text 66"

AutoCAD SHX Text 12"

AutoCAD SHX Text

CONSTRUCTION CONDITION

AutoCAD SHX Text

3000 PSI CONCRETE

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

MARKER TAPE

AutoCAD SHX Text A

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text COMPACTED EARTH FILL BACKFILL IN 6" LIFTS, COMPACT. FINAL COMPACTION SHALL BE 95% THAT OF ADJACENT EARTH.

AutoCAD SHX Text 6"

AutoCAD SHX Text 3"

AutoCAD SHX Text 6"

AutoCAD SHX Text 18"

AutoCAD SHX Text 21"

AutoCAD SHX Text

A. 3" FOR POWER. B. 3" SPARE

AutoCAD SHX Text B

AutoCAD SHX Text

IT SHALL BE REPAIRED TO MATCH ITS PRE-

AutoCAD SHX Text

WHERE CONCRETE OR ASPHALT IS CUT,

AutoCAD SHX Text 66"

AutoCAD SHX Text 12"

AutoCAD SHX Text

CONSTRUCTION CONDITION

AutoCAD SHX Text

3000 PSI CONCRETE

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

MARKER TAPE

AutoCAD SHX Text A

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text COMPACTED EARTH FILL BACKFILL IN 6" LIFTS, COMPACT. FINAL COMPACTION SHALL BE 95% THAT OF ADJACENT EARTH.

AutoCAD SHX Text 6"

AutoCAD SHX Text 3"

AutoCAD SHX Text 6"

AutoCAD SHX Text 18"

AutoCAD SHX Text 22"

AutoCAD SHX Text

A. 3" FOR POWER. B. 3" SPARE

AutoCAD SHX Text B

AutoCAD SHX Text

3#250KCM, #4(G), 3"C.

AutoCAD SHX Text

PPM

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text Agricultural

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

DATE

AutoCAD SHX Text c

AutoCAD SHX Text P.A.

AutoCAD SHX Text

FIRM

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text D

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text A

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text S

AutoCAD SHX Text

USDA

AutoCAD SHX Text

BY

AutoCAD SHX Text

AGRICULTURAL RESEARCH SERVICE

AutoCAD SHX Text

OF

AutoCAD SHX Text

THE

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

JOB #

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

A-E FIRM

AutoCAD SHX Text

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

AutoCAD SHX Text Johnson M Adams

AutoCAD SHX Text

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

AutoCAD SHX Text

USDA AGRICULTURAL RESEARCH SERVICE

AutoCAD SHX Text

NATIONAL CENTER FOR ANIMAL HEALTH

AutoCAD SHX Text

BUILDING Y2 RENOVATION

AutoCAD SHX Text

AMES, IOWA

AutoCAD SHX Text

LEGEND SHEET

AutoCAD SHX Text E001

AutoCAD SHX Text 23 25

AutoCAD SHX Text 3/1/17

AutoCAD SHX Text

REH

AutoCAD SHX Text

AMF

AutoCAD SHX Text

CNI

AutoCAD SHX Text

MIDWEST AREA

AutoCAD SHX Text

PEORIA, IL

AutoCAD SHX Text 1316-A

AutoCAD SHX Text

B. A' HEARN

AutoCAD SHX Text

L. FABER

AutoCAD SHX Text

D. MACE

AutoCAD SHX Text

P. BORDELON

David.Mace Typewritten Text Error and Correction

David.Mace Typewritten Text

David.Mace Typewritten Text

David.Mace Typewritten Text Existing panel OSMCC4-G1 is in Building 22 (twenty two) not 21.

David.Mace Typewritten Text

David.Mace Typewritten Text

David.Mace Line

David.Mace Text Box Building 22

David.Mace Rectangle

File details come from the government source that posted it. Updated .