D R
A I N
F I E
L D
GRAVITY FED SEWER LINES
(REMOVE)
DISTRIBUTION BOX
(REMOVE)
UTILITY BOX
(PRESERVE)
HOST SITE
R
A
M
P
T
R
A
I L
15 14 13 12 11 10
16 17 18 19 20
21 22
T
O
F
R
O
H
I G
H
W
Y
W W
W
W
W
W
WW
WW
W
W
W
E
E
W
E
EE
E
E
LEGEND:
Restrooms
Drinking Water
Campsite Number
Reserved for Handicapped
Trail
Underground Waterline
Underground Electrical
W
E
CONCRETE SEPTIC TANKS,
1500 GALLON CAPACITY EACH
(REMOVE)
Parking Bumper
RESTROOM BUILDING
2 5
H O
R S
F A
L
B
E A
C
S
P
T
S
T E
M
R
E P
L A
C E
M E
N T
L A
Y O
U T
O
F
E
X I S
T I N
G
F
A C
I L
I T
I E
S
BEACH ACCESS
BEACH ACCESS
LAYOUT OF EXISTING FACILITIES
NOTES:
LOCATION OF EXISTING UNDERGROUND UTILITIES SHOWN ARE APPROXIMATE. CONTRACTOR SHALL
BE RESPONSIBLE FOR LOCATING AND PRESERVING UTILITIES AND OTHER IMPROVEMENTS NOT
DESIGNATED TO BE REMOVED UNDER THE WORK OF THIS CONTRACT. MUST CALL 811 FOR ELECTRIC
SERVICE LOCATE PRIOR TO DIGGING.
PROPERLY DECOMMISSION THE EXISTING SEPTIC SYSTEM IN ACCORDANCE WITH OAR 340-071-0185.
REFER TO THE PROJECT SPECIFICATIONS AND STATEMENT OF WORK FOR ADDITIONAL DETAILS.
GRAVITY FED SEWER LINES
(REMOVE)
ELECTRICAL SERVICE ENTRANCE
(PRESERVE)
NOT TO SCALE
T R
A I L
RV SERVICE PIPE
(PRESERVE)
M a g
3000 GALLON PRIMARY SEPTIC TANK
a g
PROPOSED SITE PLAN
NOT TO SCALE
REPLACE EXISTING CLEANOUT;
MATCH EXISTING ELEVATION
ELECTRICAL SERVICE
ENTRANCE
RV SEWAGE DRAIN, CONNECT TO NEW PIPE
BOTTOMLESS SAND FILTER,
26' X 70' INTERIOR DIMENSIONS
UTILITY BOX (PRESERVE)
3000 GALLON "CLARIFIER"
SEPTIC TANK WITH BIOFILTER
PARKING LOT
" DIAMETER, SCHEDULE 40 PVC MANIFOLD
LINES BETWEEN THE ADV AND LATERALS
" SCHEDULE 80 PVC PIPE, PRESSURIZED EFFLUENT LINE
" DIAMETER, CLASS 200 PIPE LATERALS, SPACED 24" BETWEEN ROWS
ORIFICES SHALL BE SPACED 24" ON CENTER ALONG THE LATERALS.
2000 GALLON DOSING TANK WITH BIOTUBE PUMP VAULT;
REFER TO SHEET 5 FOR ADDITIONAL DETAILS
NOTES:
1. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL DISTANCES AND
SPACING OF COMPONENTS ON THE GROUND.
2. CONTRACTOR SHALL CAST A PIPE SECTION SLEEVE INTO THE CONCRETE WALL OF THE
SAND FILTER FOR THE PIPE PENETRATION, AS SHOWN ON SHEET 4.
3. ALLOW FIVE (5) FEET BETWEEN THE NEAREST POINTS OF ADJACENT SEPTIC TANKS, AND
STEP DOWN
" PER FOOT FROM THE OUTLET OF ONE TANK TO THE INLET OF THE NEXT.
4. AT A MINIMUM, CONTRACTOR SHALL PROVIDE AND INSTALL 780 LINEAR FEET OF PIPING
FOR THE LATERALS: SIX (6) ZONES WITH TWO (2) LATERALS EACH, EACH LATERAL AT
LEAST 65 FEET LONG.
5. ORIFICES IN DRAINFIELD LATERALS SHALL BE
" IN DIAMETER, AND EACH ORIFICE SHALL
BE FITTED WITH AN ORIFICE SHIELD. TO AVOID ERRORS AND INCONSISTENCY, AND TO
UPHOLD WARRANTY TERMS, CONTRACTOR SHALL PROVIDE PRE-MANUFACTURED
DRAINFIELD LATERALS. CONTRACTOR IS NOT PERMITTED TO DRILL THEIR OWN
ORIFICES.
6. PROVIDE LABOR AND MATERIALS NEEDED TO CONNECT THE CAMP HOST WASTEWATER
LINE TO THE NEW SEPTIC SYSTEM.
7. SAWCUT AND REMOVE CONCRETE PATHWAY ALONG THE EAST SIDE OF THE RESTROOM
BUILDING, AS SHOWN IN THE HATCH PATTERN. THE AREA OF THE SIDEWALK TO BE
REMOVED IS APPROXIMATELY 24' LONG BY 3' WIDE. THE EXISTING CONCRETE IS BADLY
DAMAGED AND CREATING A TRIPPING HAZARD. REPLACE THE REMOVED PORTION OF
CONCRETE WITH
"- MINUS CRUSHED AGGREGATE BASE MATERIAL, 6" COMPACTED
DEPTH, WITH GEOTEXTILE FILTER FABRIC UNDERNEATH. SLOPE 2% TO DRAIN.
8. REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL DETAILS ON COMPONENTS.
FLUSHING VALVE AND VALVE BOX,
ONE PER LATERAL, TWELVE TOTAL
3 5
H O
R S
F A
A
P
T
S
T E
M
R
E P
L A
C E
M E
N T
S I T
E
P
L A
N
O
F
P
R O
P O
S E
D
I M
P R
O V
E M
E N
T S
NEW 6" DIAMETER, SCHEDULE 80 PVC PIPE; GRAVITY FED AT MINIMUM SLOPE OF
" PER FOOT
CONTROL PANEL, MOUNTED INSIDE BUILDING
AUDIBLE AND VISUAL ALARMS MOUNTED OUTSIDE BUILDING
NEW ELECTRICAL LINE, IN CONDUIT; CONNECT TO DOSING TANK AND CONTROL PANEL
CONCRETE PATHWAY - SEE NOTE #7
6" GATE VALVE AND BOX
6" GATE VALVE AND BOX
CONTOUR LINES SHOWN IN
ONE-FOOT INTERVALS
AUTOMATIC DISTRIBUTION VALVE (ADV) IN
FIBERGLASS ENCLOSURE TO (6) SEPARATE ZONES
NEW 6" DIAMETER, SCHEDULE 80 PVC PIPE; GRAVITY FED AT MINIMUM SLOPE OF
" PER FOOT
NEW ELECTRICAL LINE, IN CONDUIT; CONNECT TO CLARIFIER TANK AND REMOTE ALARM PANEL
8"
2'
FILTER SAND (REFER TO SIEVE
GRADATION IN SPECIFICATIONS)
FILTER FABRIC, IN ACCORDANCE
WITH OAR 340-73-0041
LOAMY SAND
" PVC LATERAL LINES, INSTALL LEVEL,
ORIFICE SHIELDS 24" ON CENTER
FLUSHING VALVE AND VALVE
BOX, ONE PER LATERAL
REINFORCED CONCRETE WALL
(SEE DETAIL BELOW)
SELECT NATIVE SOIL BACKFILL;
SLOPE 3H:1V TO MEET WITH ADJACENT
GROUND, AS DESCRIBED IN NOTE #3
NOTES:
1. SIEVE ANALYSIS SHALL BE PROVIDED FOR THE FILTER SAND AND UNDERDRAIN MEDIA PROVIDED.
2. LATERAL LINES SHALL BE 1
" IN DIAMETER, AND COMPOSED OF POLYVINYL CHLORIDE WITH A
MINIMUM PRESSURE RATING OF 200 PSI.
3. EXISTING GROUND ELEVATION NOT SHOWN; CONTRACTOR SHALL FIT THE SAND FILTER TO THE
EXISTING TERRAIN. DUE TO THE SAND DUNE ALONG THE WEST EDGE, AND THE OVERALL SLOPE
TO THE EAST, IT IS EXPECTED THAT THE WEST WALL OF THE SAND FILTER WILL BE MOSTLY
BURIED AGAINST THE ADJACENT SAND DUNE, WHILE THE EAST WALL WILL BE MOSTLY EXPOSED.
4. "LOAMY SAND" ABOVE THE FILTER FABRIC SHALL MEET THE REQUIREMENTS OF OAR 340-071-0295, AS DESCRIBED IN SECTION 02530, SANITARY SEWAGE.
5. ALL PVC LATERALS SHALL HAVE AT LEAST 3" OF UNDER DRAIN MEDIA BELOW, AND SUFFICIENT
MEDIA ABOVE TO COVER THE ORIFICE SHIELDS.
6. MAINTAIN AT LEAST 3" OF CONCRETE BETWEEN THE STEEL REINFORCEMENT (REBAR) AND THE
EDGE OF CONCRETE. OVERLAP REBAR AND CONDUCT OTHER CONCRETE FRAMING,
REINFORCEMENT, PLACING, CURING, TESTING, ETC. IN ACCORDANCE WITH AMERICAN CONCRETE
INSTITUTE (ACI) STANDARDS AND SECTION 03300 OF THE PROJECT SPECIFICATIONS.
7. TOP EDGE OF CONCRETE WALL SHALL BE LEVEL ALONG ENTIRE PERIMETER OF THE SAND FILTER.
UNDERDRAIN MEDIA
6" MINIMUM - SEE NOTE #5
" PEA GRAVEL
(I.E. UNDERDRAIN MEDIA)
8"
NATIVE, UNDISTURBED SOIL
BOTTOMLESS SAND FILTER CROSS SECTION
NOT TO SCALE
8"
#5 VERTICAL REBAR,
24" ON CENTER
#5 HORIZONTAL REBAR,
3 ROWS SPACED EQUALLY
4'
1'-6"
PERIMETER CONCRETE FOOTING AND STEM WALL DETAIL
NOT TO SCALE
CAST 3" DIAMETER PVC PIPE
SLEEVE INTO CONCRETE
8"
#5 FOOTING DOWEL ("L"- BAR):
24" ON CENTER, ALTERNATE
DIRECTION OF LEGS
NATIVE, UNDISTURBED SOIL
4 5
H O
R S
F A
A
P
T C
I
S
Y S
T E
M
R
E P
L A
C E
M E
N T
B O
T T
O M
L E
N
D
F
I L
T E
R
D
E T
A I L
S
30 MIL PVC LINER
(AROUND ENTIRE PERIMETER)
NATIVE, UNDISTURBED SOIL
SELECT NATIVE SOIL BACKFILL;
SLOPE 3H:1V TO MEET WITH
ADJACENT GROUND, AS
DESCRIBED IN NOTE #3
3" MINIMUM CLEAR
COVER, ALL SIDES
4'
" - MINUS CRUSHED AGGREGATE
BASE, COMPACTED MEASURE
NATIVE, UNDISTURBED SOIL
1'
2'
90 DEGREE FITTING, THREADED FOR
INCREASED SERVICEABILITY
" SCHEDULE 80
PVC INFLUENT LINE
FROM DOSING TANK
70'
(NOT TO SCALE)
5 5
O
R S
F A
A
P
T
S
T E
M
R
E P
L A
C E
M E
N T
D O
S I N
G
T
A N
K
D
E T
A I
NOTES:
1. REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL DETAILS ON THE DOSING TANK, SEPTIC TANKS, EFFLUENT FILTER, CONTROL PANEL, PUMPS, ETC.
2. DOSING AND SEPTIC TANKS SHALL BE STANDARD DEQ APPROVED DESIGN.
3. EXISTING GROUND ELEVATION NOT SHOWN. CONTRACTOR SHALL FIT THE NEW TANKS AND PLUMBING CONNECTIONS TO THE EXISTING
TERRAIN AND PLUMBING. PIPE INLET / OULET ELEVATIONS SHALL BE SET TO MAINTAIN A CONTINUOUS 3% (MIN) SLOPE IN THE GRAVITY
SEWER LINES.
4. OUTER DIMENSIONS OF 2000 - GALLON PRECAST CONCRETE TANKS ARE APPROXIMATELY 13' LONG BY 6.25' WIDE BY 5.5' TALL.
5. OUTER DIMENSIONS OF 3000 - GALLON PRECAST CONCRETE TANKS ARE APPROXIMATELY 12.5' LONG BY 6.5' WIDE BY 7.5' TALL.