PLANT SCHEDULE
COMMON NAME SIZE QTY
QUAKING ASPEN
(SINGLE STEM)
6-8' TALL 8
SAGE
KINNIKINNICK
(GROUNDCOVER)
1 GAL 21
1 GAL 23
LANDSCAPE ELEMENTS
LANDSCAPE BOULDER (3'X2')
LANDSCAPE STONE (2-4" COBBLE) WITH WEED
BARRIER UNDERLAYMENT
NOTES:
1. SEE SHEET D2 FOR PLANTING DETAILS.
2. PLANT QUANTITIES PROVIDED ARE FOR CONVENIENCE ONLY. THE
DRAWING SHOWING PLANTING LAYOUT SUPERCEDES THE PLANT
SCHEDULE.
3. STRIP NATIVE TOPSOIL FROM ALL AREAS WHERE CONSTRUCTED
FEATURES ARE REMOVED. TOPSOIL SHALL BE USED FOR
LANDSCAPING AND GRADING AROUND BUILDING.
4. SPREAD NATIVE TOPSOIL TO A UNIFORM DEPTH OF 4-INCHES IN ALL
AREAS SHOWN AS KENTUCKY BLUEGRASS SOD PRIOR TO SODDING.
5. SEE SHEET I1 FOR SPRINKLER IRRIGATION DESIGN.
6. INTEGRATE EXISTING EVERGREEN SHRUBS INTO PLANTING PLAN.
7. IF OPTION "A" IS AWARDED SEE SHEET L2 FOR REVISED LANDSCAPE
PLAN.
KENTUCKY BLUEGRASS SOD
INSTALL LANDSCAPE BOULDER
(TYP.) (SEE SHEET D2)
CONSTRUCT DRAINAGE
STRUCTURE (TYP.)
(SEE SHEET D2)
BOTANICAL NAME
POPULUS TREMULOIDES
SALVIA NEMOROSA
'MAY NIGHT'
ARCTOSTAPHYLOS
UVA-URSI
WOOD MULCH (3" DEPTH) WITH WEED BARRIER
UNDERLAYMENT
KIOSK
EXISTING EVERGREENS (TYP.)
EXISTING EVERGREEN
SHRUBS (TYP.) (SEE NOTE #7)
EXISTING FENCE
EXISTING ASPEN (TYP.)
INSTALL LANDSCAPE EDGER
(TYP.) (SHEET D1)
INSTALL LANDSCAPE BOULDER
(TYP.) (SEE SHEET D2)
EXISTING DISTRICT
OFFICE SIGN
INSTALL SOD (TYP.)
INSTALL LANDSCAPE EDGER
(TYP.) (SEE SHEET D1)
EXISTING EVERGREEN (TYP.)
BUILDING ROOFLINE
BIGTOOTH MAPLE 2" CAL 1ACER GRANDIDENTATUM
GOLD FLAME SPIREA 5 GAL 18SPIREA X BUMALDA
'GOLDFLAME'
PARKING LOT
DISTRICT OFFICE BUILDING
BENDER BOARD LANDSCAPE EDGING
INSTALL LANDSCAPE EDGER
(TYP.) (SHEET D1)
SEE NOTE #5 (TYP.)
EXISTING ASPEN TREE (TYP.)
IF OPTION "A" IS AWARDED SEE SHEET L2
FOR REVISED ENTRY LANDSCAPE PLAN (TYP.)
OPTION A ADDITIONAL QUANTITIES
COMMON NAME SIZE QTY
QUAKING ASPEN
(SINGLE STEM)
6-8' TALL 1
SAGE
KINNIKINNICK
(GROUNDCOVER)
1 GAL 5
1 GAL 2
LANDSCAPE ELEMENTS
LANDSCAPE BOULDER (3'X2')
LANDSCAPE STONE (2-4" COBBLE) WITH WEED
BARRIER UNDERLAYMENT
KENTUCKY BLUEGRASS SOD
INSTALL LANDSCAPE BOULDER
(TYP.) (SEE SHEET D2)
CONSTRUCT DRAINAGE
STRUCTURE (TYP.)
(SEE SHEET D2)
BOTANICAL NAME
POPULUS TREMULOIDES
SALVIA NEMOROSA
'MAY NIGHT'
ARCTOSTAPHYLOS
UVA-URSI
WOOD MULCH (3" DEPTH) WITH WEED BARRIER
UNDERLAYMENT
EXISTING EVERGREEN
SHRUBS (TYP.)
(SEE NOTE #5)
EXISTING FENCE
EXISTING ASPEN (TYP.)
INSTALL LANDSCAPE EDGER
(TYP.) (SHEET D1)
EXISTING EVERGREEN (TYP.)
BUILDING ROOFLINE
GOLD FLAME SPIREA 5 GAL NO ADDITIONALSPIREA X BUMALDA
'GOLDFLAME'
BENDER BOARD LANDSCAPE EDGING
NOTES:
1. IF OPTION "A" IS AWARDED, PLANT SCHEDULE QUANTITIES ON THIS
SHEET ARE IN ADDITION TO PLANT SCHEDULE QUANTITIES ON SHEET L1.
2. PLANT QUANTITIES ARE FOR CONVENIENCE ONLY. THE DRAWING
SHOWING PLANTING LAYOUT SUPERCEDES THE PLANT SCHEDULE.
2. SEE SHEET D2 FOR PLANTING DETAILS.
3. STRIP NATIVE TOPSOIL FROM ALL AREAS WHERE CONSTRUCTED
FEATURES ARE REMOVED. TOPSOIL SHALL BE USED FOR LANDSCAPING
AND GRADING AROUND BUILDING.
4. SPREAD NATIVE TOPSOIL TO A UNIFORM DEPTH OF 4-INCHES IN ALL
AREAS SHOWN AS KENTUCKY BLUEGRASS SOD PRIOR TO SODDING.
5. INTEGRATE EXISTING EVERGREEN SHRUBS INTO PLANTING PLAN.
6. SEE SHEET I1 FOR SPRINKLER IRRIGATION DESIGN.
7. SEE A SHEETS FOR OPTION A GRADING INFORMATION.
DISTRICT OFFICE BUILDING
SEE NOTE #7
INSTALL RAILING (TYP.)
(SEE A SHEETS)
* IF OPTION "A" IS AWARDED, PLANT SCHEDULE QUANTITIES ON THIS
SHEET ARE IN ADDITION TO PLANT SCHEDULE QUANTITIES ON SHEET L1.
J R
J R
J R
J R
J R J
R
J R R
S
TO CAN LIGHTS
TO REMAIN
TO REMOVED
SWITCH
J R
J R
J R
J R
S
S
S
MOTORIZED CURTAINS MOTORIZED CURTAINS
JUNCTION BOX, REPRESENTS PIECE OF
EQUIPMENT INDICATED AND SHALL BE
REMOVED WITH ACCOMPANYING CIRCUITRY
FLUORESCENT LUMINAIRE TO REMAIN,
SURFACE MOUNT
REMOVE FLUORESCENT LUMINAIRE,
SURFACE MOUNT. TYPE "S" IS TO BE
SALVAGED FOR REUSE.
CAN LIGHT RECESSED LUMINAIRE TO REMAIN
REMOVE LUMINAIRE: RECESSED CAN AND
WALL MOUNT. TYPE "S" ARE TO BE
SALVAGED FOR REUSE.
EXISTING EXIT SIGN, CORRECT TO INCLUDE
DIRECTING ARROW
SINGLE POLE SWITCH TO REMAIN
REMOVE SWITCH, TYPE "3" INDICATES 3-WAY
DUPLEX RECEPTACLE TO REMAIN
REMOVE DUPLEX RECEPTACLE
REMOVE DATA/VOICE OUTLET AND CABLES
S
S
DEMOLITION NOTES
GENERAL
1. REMOVE UNUSED, ABANDONED CIRCUITS BACK TO PANEL L1 OR
L2. WHERE DOING SO WILL DAMAGE THE BUILDING FINISH IN
AREAS NOT AFFECTED BY CONSTRUCTION, CABLES AND
CONDUIT MAY REMAIN. UNUSED BREAKERS MAY REMAIN.
2. LOCATE AND PROPERLY LABEL ALL BREAKERS IN PANEL L1 AND
L2 (IN BASEMENT) AFFECTED BY CHANGES IN THIS CONTRACT
AND PROPERLY LABEL THEM FOR THE FINAL BUILDING
CONDITION.
a. FOR LIGHTING AND RECEPTACLE CIRCUITS KEEP TRACK OF
THE NUMBER OF DEVICES AND TYPES THAT ARE REMOVED
FOR PREVENTING OVERLOADING CIRCUIT EXTENSIONS
WHEN INSTALLING.
3. CUTTING WINDOWS INTO THE OLD COLLECTOR WALL SHOULD
NOT AFFECT ANY CIRCUITS NOT SHOWN.
BASE BID
1. REMOVE ALL ELECTRICAL FEEDING THE GREENHOUSE AND ALL
RELATED DEVICES INCLUDING THE CONTROLS AND RELATED
ELECTRICAL EQUIPMENT IN THE BASEMENT AND THERMOSTATS.
2. REMOVE LIGHTING, RECEPTACLES AND RELATED CIRCUITRY
SHOWN IN THE RECEPTION AREA, EXTENDED AREA, AND HALL.
SALVAGE ONE LUMINAIRE FROM THE GREENHOUSE FOR REUSE
AS INDICATED.
3. DEVICES SHOWN TO REMAIN SHALL REMAIN OPERATIONAL.
4. VERIFY AND PREPARE CIRCUITS FOR EXTENSION TO NEW
EQUIPMENT AND DEVICES. CIRCUITS SHALL NOT BE MIXED
BETWEEN LIGHTING AND NON-SWITCHED RECEPTACLES.
5. REMOVE TELECOMMUNICATIONS OUTLETS SHOWN WITH
CABLES, INCLUDING CONNECTIONS TO THE CATEGORY 3 PATCH
PANELS AND CORRECT PATCH PANEL LABELING AND ANY
EXISTING DATA OUTLET MAP LOCATED IN THE
TELECOMMUNICATIONS CLOSET IN THE BASEMENT.
OPTION A
1. REMOVE AND SALVAGE HPS WALL PACK LUMINAIRE, IF EQUIPPED
WITH A PHOTOCONTROL REMOVE PHOTOCONTROL.
2. REMOVE RELATED WALL PACKS SWITCH AND ENSURE CIRCUIT
POWER TO OLD WALL PACK LOCATION. IF THE POWER IS
ROUTED THROUGH THE SWITCH LOCATION, INSTALL A BLANK
COVER WHERE THE SWITCH WAS LOCATED, OTHERWISE
REMOVE THE SWITCH LEG CIRCUIT.
a. CUTTING IN THE NEW DOORWAY MAY AFFECT THE ROUTING
OF THIS CIRCUIT WHICH SHALL BE REROUTED AS NEEDED
TO AVOID ISSUES.
3. REMOVE CAN LIGHTS AND SWITCHED RECEPTACLES SHOWN
AND PREPARE CIRCUIT FOR RECONNECTION TO EQUIPMENT
SHOWN TO REMAIN.
4. REMOVE THE COVER PLATE FOR THE "WP" RECEPTACLE TO
REMAIN AND REROUTE ANY PORTION OF THE FEEDING CIRCUIT
NEEDFUL FOR CUTTING IN THE NEW DOORWAY. PREPARE
RECEPTACLE FOR FEEDING NEW RECEPTACLE.
R E
C E
P
TI
O N
A R
E A
TO NEW
SWITCH
LOCATION
A A
A
AA
S
S
S
S
S
J
AA
M M
REMAINS ON
EXISTING
CIRCUITS
TO CAN LIGHTS TO REMAIN
ON EXISTING CIRCUIT
REWORK HOME RUN
TO THIS LOCATION
OR TO NEW LIGHT
LOCATIONS
E M
INSTALLATION NOTES
GENERAL
1. REPAIR DAMAGE TO WALLS AND CEILING EXPOSED OR CAUSED
BY REMOVAL AND RELOCATIONS.
2. FUNCTIONAL WIRING SHOWN, ACTUAL WIRING MAY DIFFER AS TO
POWER LOCATIONS AND MAY ALSO INCLUDE EXISTING FEED
THROUGH WIRING FOR OTHER DEVICES FED BY THE SAME
CIRCUIT OR OTHER EXISTING FEEDS.
3. FINAL PANEL LABELING OF ALL IMPACTED CIRCUITS SHALL
ACCURATELY AND UNDERSTANDABLY INDICATE ALL LOADS
SERVED BY THOSE INDIVIDUAL BREAKERS. IF MULTIWIRE
BRANCH CIRCUITS ARE FOUND, CLEARLY INDICATE WHICH
CIRCUITS ARE SHARING THE COMMON NEUTRAL.
BASE BID
1. INSTALL NEW RECEPTION AREA LIGHTING WITH SWITCHES ON
THE EXISTING LEAST LOADED LIGHTING CIRCUIT IMPACTED BY
DEMOLITION.
a. LABEL UNDER EACH LAMP "USE T-8 LAMPS ONLY."
b. LIGHTING LOCATIONS MAY NEED TO BE ADJUSTED TO
ACCOMMODATE EXISTING HVAC.
2. INSTALL SALVAGED LUMINAIRE IN HALL WITH NEW HALL
LIGHTING CONTROLS AS CALLED FOR.
3. INSTALL NEW RECEPTACLES IN RECEPTION DESK WITH THE TWO
SINGLE DUPLEX RECEPTACLES ON ONE RECEPTACLE CIRCUIT
IMPACTED BY THE DEMOLITION AND THE QUAD ON A SEPARATE
RECEPTACLE CIRCUIT IMPACTED BY THE DEMOLITION.
a. LOCATIONS OF RECEPTACLES TELECOMMUNICATIONS
OUTLETS IN DESK ARE SHOWN AS POSSIBLE, ACTUAL
LOCATIONS TO BE DETERMINED AND APPROVED BY THE
CONTRACTING OFFICER.
4. 3-INCH ACCESS DESKTOP ROUND ACCESS GROMMET DIRECTLY
ABOVE THE RECEPTACLE ARE REQUIRED.
5. INSTALL TELECOMMUNICATIONS OUTLETS (2 JACKS EACH) WITH
CABLING TO A 12 PORT MINIMUM, RACK MOUNTED, PATCH PANEL.
CATEGORY 6 IS REQUIRED. SEE REQUIREMENTS IN THE
SPECIFICATIONS.
a. FOLLOW AND USE EXISTING PATHWAYS FOR
TELECOMMUNICATIONS CABLING WHEN EVER POSSIBLE.
b. REUSE OF PORTS WITHIN AND THE EXISTING PATCH PANEL
NOT ALLOWED.
OPTION A
1. INSTALL SALVAGED HPS WALL PACK LUMINAIRE,WITH NEW
PHOTOCONTROL WITHIN FIXTURE KNOCKOUT AND INSTALL IN
NEW LOCATION SHOWN.
2. INSTALL SALVAGED CAN LIGHTS IN NEW LOCATIONS WITH
PHOTOCONTROL AS SHOWN.
3. INSTALL NEW EXIT SIGN WITH REMOTE HEAD CAPABILITY AND
REMOTE EMERGENCY HEAD.
4. RECONNECTION CAN LIGHTS AND SWITCHED RECEPTACLES
CIRCUIT FOR PROPER OPERATION OF EQUIPMENT TO REMAIN.
5. EXTEND CIRCUIT FROM EXISTING RECEPTACLE TO NEW
EXTERIOR RECEPTACLE, INSTALL EXISTING WITH NE W COVER
PLATE.
JUNCTION BOX AND CIRCUIT FROM REMOVAL OF
WALL PACK
FLUORESCENT LUMINAIRE, TYPE "X" SURFACE
MOUNT
FLUORESCENT LUMINAIRE TO REMAIN, SURFACE
MOUNT
LUMINAIRE, TYPE "X": RECESSED CAN LIGHT AND
WALL MOUNT
CAN LIGHT RECESSED LUMINAIRE TO REMAIN
EXIT SIGN, SINGLE FACE, TYPE "X": BACK MOUNT,
PROVIDES EMERGENCY REMOTE POWER TO
REMOTE HEAD
OCCUPANCY SENSOR, CEILING MOUNT,
WATTSTOPPER CI-355: SET FOR 5 MINUTE,
WALK-THROUGH ENABLED, AMBIENT LIGHT SETTING
NOT REQUIRED, CONNECT IN PARALLEL
PHOTO CONTROL, BUTTON TYPE, HUBBELL PBT-1
SINGLE POLE SWITCH
RECEPTACLE, DUPLEX OR TYPE SHOWN: NEW,
REPLACE, REMAIN, AND REMOVE
RECEPTACLE, GFCI W/WEATHER PROOF COVER
DUPLEX RECEPTACLE TO REMAIN
GFCI RECEPTACLE TO REMAIN, REPLACE COVER
PLATE WITH INTERIOR IVORY PLATE
RECEPTACLE, TWO DUPLEX IN A SINGLE DEVICE BOX
TELECOMMUNICATIONS WORKSTATION OUTLET, SEE
SPECIFICATION IN DIVISION 27
BRANCH CIRCUIT: o - INDICATES GROUND, LONG LINE
- "NUETRAL" OR "GROUNDED CONDUCTOR" AND THE
SHORT LINE - "HOT" OR "LINE" CONDUCTORS
M
S
TYPE DESCRIPTION MANUFACTURER MODEL # LAMPS MOUNTING Qty NOTES:
A 1X4 FLUORESCENT LITHONIA AVSM 2 32 SBL DLS MVOLT (2) 32W T8 CW SURFACE/CEILING 7 IN BASE BID S SALVAGED 1X4 FLUORESCENT LITHONIA CB 140 EXISTING SURFACE/CEILING 1 IN BASE BID E EXIT SIGN DUAL LITE HCXUGW-RC12-O3L LED SURFACE/WALL OR CEILING 1 IN BID OPTION A
EM REMOTE EMERGENCY HEAD DUAL LITE PGRZ LED SURFACE/WALL 1 IN BID OPTION A
S SALVAGED CAN LIGHT LUMINAIRE PROGRESS? EXISTING EXISTING R-20 50W RECESSED/CEILING 2 IN BID OPTION A S SALVAGED HPS WALL PACK LUMINAIRE HUBBELL PVL 0070S EXISTING HPS 70W SURFACE/WALL 1 IN BID OPTION A, INSTALL WITH NEW HUBBELL PBT-1 PHOTOCONTROL
TOTAL 13
R
E C
E P
TI
O
N A
R
A
AS-BUILT ACCURACY NOTES:
1. THERE HAS BEEN ADDITIONAL WORK DONE ON THE
BUILDING SINCE ORIGINALLY BUILT, MOST HAS
BEEN ON THE SOLAR HEATING AND HVAC SYSTEMS.
2. THESE PLANS WERE DECLARED BY CONTRACTORS
AS AS-BUILTS, BUT THAT DOES NOT MEAN MUCH
ELECTRICALLY. THEY DO NOT SHOW SIGNS OF
CORRECTIONS OR EDITING.
3. EXISTING CIRCUIT LABELING IN THE TWO EXISTING
LOAD CENTERS DO NOT HELP OR CLARIFY MUCH.
THEY DO INDICATE THAT LOADS ARE WIRED
SIGNIFICANTLY DIFFERENT THAN THE CIRCUITRY
SHOWN ON THESE AS-BUILTS ABOVE.
SECTION