TAMPER SWITCH

AND FLOW SENSOR

ACTIVATE BELL ONLY

SPRINKLER FLOW

ALARM BELL

GENERAL ELECTRICAL NOTES

THE WORK AT THE SITE INCLUDES:

1. COORDINATING ALL CUSTOMER REQUIRED WORK AND EQUIPMENT TO

COMPLY WITH ROCKY MOUNTAIN POWER REQUIREMENTS AND PROJECT

SPECIFICATIONS TO PROVIDE FOR UNDERGROUND ELECTRICAL

SERVICES AND WITH FREEMONT TELCOM AND CABLEONE FOR PHONE

AND CABLE TV SERVICES. VERIFY SERVICE ENTRANCE LOCATIONS WITH

BUILDING SITING, IN COORDINATION WITH UTILITY PROVIDERS.

2. VERIFY SERVICE FROM ROCKY MOUNTAIN AS 120/208 VAC OR 120/240 VAC

AND INSTALL SERVICE AND PANELS BASED ON SERVICE TO BE PROVIDED.

METERING EQUIPMENT SHALL MEET ROCKY MOUNTAIN POWER

REQUIREMENTS FOR SAFETY SOCKET.

3. PROVIDE AND INSTALL SERVICE LATERAL CONDUIT IN A 36-INCH MINIMUM

TRENCH DEPTH WITH A MINIMUM BURIAL DEPTH OF 30-INCHES PER

POWER COMPANY BEDDING AND BACKFILL REQUIREMENTS. SERVICE

SHALL BE KEPT 36-INCHES FROM WATER OR GAS SERVICES. LOCATE

SERVICE LATERAL TO AVOID FUTURE BUNKHOUSE FOUNDATION BY

5-FEET MINIMUM.

4. PROVIDE AND INSTALL A 3-INCH CONDUIT LATERAL FROM THE SERVICE

POLE TO DIRECTLY BELOW THE EXISTING WAREHOUSE SERVICE

(CURRENTLY OVERHEAD). STUB ABOVE GRADE AT BOTH ENDS AND CAP

ENDS. MEET ALL ROCKY MOUNTAIN POWER REQUIREMENTS.

5. ELECTRICAL SERVICE METERBASE SHALL BE INSTALLED WITH IMC AND

SWEEP PER FOREST SERVICE SPECIFICATIONS, WITH CENTER OF METER

LOCATED BETWEEN 5 AND 6-FEET ABOVE FINISHED GRADE.

6. ELECTRICAL SERVICE EQUIPMENT SHALL BE RATED AS SHOWN IN

CALCULATIONS THIS SHEET, MINIMUM, AND 22,000 SHORT CIRCUIT

CURRENT RATED (MAY BE SERIES RATED), EQUIVALENT TO SQUARE D QO

OR BETTER, NO TANDEM OR HALF SIZED BREAKERS ALLOWED.

7. PROVIDE A 2-INCH CONDUIT FROM POLE FOR PHONE AND CABLE TV

SERVICES. DIRECT BURIED CABLE(S) THAT WILL MEET REQUIREMENTS

FOR BOTH SERVICE INSTALLED BEFORE CONTRACT IS COMPLETE MAY

SUBSTITUTE FOR THE CONDUIT. CONDUIT OR CABLES SHALL BE BURIED

24-INCHES MINIMUM AND KEPT 5-FEET FROM FUTURE BUNKHOUSE FOOT

PRINT. IT MAY BE INSTALLED IN THE SAME TRENCH AS THE ELECTRICAL

SERVICE AT 30-INCHES MINIMUM. KEEP SEPARATE FROM POWER

COMPANY INSTALLED SECONDARY A MINIMUM OF 12-INCHES

HORIZONTALLY.

8. HOME RUN INTERNAL PHONE TO THIS LOCATION INTO COMBINER/SERVICE

BOX. GROUND PER CODE AND SPECIFICATIONS.

9. HOME RUN TELEVISION INTERNAL CABLE TO SURGE ARRESTOR MOUNTED

IN THE SAME GENERAL AREA FOR CABLE TV SERVICE. GROUND PER

CODE, SPECIFICATIONS, AND AS SHOWN.

10. ELECTRICAL IN HOUSING SHOWN IS A MINIMUM AND MAY VARY BASED ON

SUBMITTED FLOOR PLANS. IF ALTERNATIVE SIZED BUILDING IS

APPROVED, ELECTRICIAN SHALL SUBMIT MODIFIED ELECTRICAL PLAN.

ADDITIONAL LUMINAIRES AND OR TYPE CHANGES MAY BE REQUIRED AT

NO ADDITIONAL COST TO PROVIDE THE SAME LEVEL OF SERVICE.

ADDITIONAL RECEPTACLES MAY ALSO BE REQUIRED TO MEET INTENT AS

SHOWN.

11. SMOKE, CARBON DIOXIDE, AND VISUAL ALARMS SHALL ALL BE

INTERCONNECTED.

S

S

C

M

CRAWL SPACES AND ATTIC SPACES LIGHTING AND RECEPTACLES

1- AT CRAWL AND ATTIC ACCESS, INSTALL ONE GFCI RECEPTACLE AND SINGLE POLE PILOT SWITCH ON THE

CIRCUIT SERVING THE ROOM WITH THE ACCESS ONLY ACCESSIBLE FROM WITHIN THE SPACE.

2- SWITCH SHALL CONTROL 2 TYPE "N" LUMINAIRES LOCATED TO LIGHT THE SPACE. LOCATIONS SHALL BE

APPROVED BY THE CONTRACTING OFFICER BEFORE INSTALLATION.

A

A-1

A-1

A-1

S

A

A-1

A-1

A-1

S

B

B

B B

C

C

SERVICE CALCULATIONS

NEC 220.82

(3VA/FT2)(1300FT2)= 3,900

(1.5KW)(3 SMALL APPL)= 4,500

(1.5KW)(1 LAUNDRY)= 1,500

TOTAL= 9,900

2 REFRIGERATORS= 1,200

DRYER= 5,000

2 RANGES DEMAND LOAD= 10,000

TOTAL VA= 26,100

OTHER LOADS THAT SHALL BE INCLUDED:

FURNACE MOTOR @ 100%

A/C CONDENSERS @ 100%

SERVICE, MAIN BREAKER AND PANEL SHALL BE 200 AMP MINIMUM 120/240

VAC SINGLE PHASE, OR, 150 AMP 120/208 VAC THREE PHASE TO ALLOW FEED

TO THE FUTURE BUNKHOUSE.

PANEL SHALL BE LARGE ENOUGH TO ACCOMMODATE 5 BLANK BREAKER

SPACES BEYOND INSTALLED BREAKERS FOR FUTURE FEEDER AND OTHER

POSSIBLE LOADS.

LOAD CENTER DISTRIBUTION

THE FOLLOWING IS A LIST OF COMMON CIRCUITS MINIMUM:

# AMPS DESCRIPTION

A-1 20 BEDROOMS LIGHTS AND RECEPTACLES

AND EXTERIOR RECEPTACLES

A-2 20 RECEPTACLE-SMALL BATHROOM

A-3 20 ALL LIGHTS AND FANS EXCEPT BEDROOMS

A-4 20 RECEPTACLE-LARGE BATHROOM

A-5 20 SOUTH FRIDGE AND RANGE HOOD

A-6 20 RECEPTACLES-KITCHEN WEST WALL

A-7 20 NORTH FRIDGE AND RANGE HOOD

A-8 20 RECEPTACLES-KITCHEN NORTH WALL

A-9 20 RECEPTACLES-LIVING ROOM AND HALL

A-10 20 RECEPTACLES-KITCHEN DINING

PENINSULA AND DINING AREAS

A-11 20 RECEPTACLE-WASHER

A-12,14 30 RECEPTACLE-DRYER

A-13 15 SMOKE ALARMS, ALARM BELL CIRCUIT

A-15,17 50 SOUTH RANGE

A-16,18 50 NORTH RANGE

OTHER CIRCUITS THAT ARE NOT SHOWN INCLUDE BUT ARE

NOT LIMITED TO:

FURNACE AND SINGLE POLE SWITCH DISCONNECTS

AIR CONDITIONER AND GENERAL DUTY DISCONNECTS

WATER HEATER - GAS WATER HEATERS WITH SMALL LOADS

MAY BE PLACED ON OTHER CIRCUITS.

REQUIRED CRAWL SPACE AND ATTIC SPACE LIGHTING AND

RECEPTACLES AS DESCRIBED MAY BE PLACED ON OTHER

CIRCUITS.

M M

A-3

A-3

A-4

A-1

A- 11

A-17,19

A-3

A-3

J

A-7

A-10

A-8 A-8A-8

A-6

A-7

A-5

A-9

C

S

A-5

SEE LEGEND FOR

MORE INFORMATION

G

MOUNT BOTH TV AND

RECEPTACLE AT 48" TO

CENTER ABOVE

FINISHED FLOOR.

SURGE SUPPRESSION FOR CABLE

TV ENTRANCE WITH BOND BACK

TO ELECTRICAL SERVICE.A-1

A-1

A-1

A

A-1

S

A

A-1

A-1

A-1

A-1

S

A-1

A-1

A-1

A-1

A-1

A-1

A-1

A-1

A-1

C

A-3

A-2

G

A-3

A-9

A-9

A-9

B

J

A-16,18

A-6

A-15,17

A-6

C

C C

A-3

A-3

C

A-10

A-3 A-3

A-10

A-9 A-9

S

G1.G2
01_G01_Cover
G1
G2
01_G1
C0_C4
C1_C_SITE
C0
C1
C2
C3
C4
D1_D4
D1_D4
D1
D2
D3
D4
A1
A2
StAnthonyBHElec