TAMPER SWITCH
AND FLOW SENSOR
ACTIVATE BELL ONLY
SPRINKLER FLOW
ALARM BELL
GENERAL ELECTRICAL NOTES
THE WORK AT THE SITE INCLUDES:
1. COORDINATING ALL CUSTOMER REQUIRED WORK AND EQUIPMENT TO
COMPLY WITH ROCKY MOUNTAIN POWER REQUIREMENTS AND PROJECT
SPECIFICATIONS TO PROVIDE FOR UNDERGROUND ELECTRICAL
SERVICES AND WITH FREEMONT TELCOM AND CABLEONE FOR PHONE
AND CABLE TV SERVICES. VERIFY SERVICE ENTRANCE LOCATIONS WITH
BUILDING SITING, IN COORDINATION WITH UTILITY PROVIDERS.
2. VERIFY SERVICE FROM ROCKY MOUNTAIN AS 120/208 VAC OR 120/240 VAC
AND INSTALL SERVICE AND PANELS BASED ON SERVICE TO BE PROVIDED.
METERING EQUIPMENT SHALL MEET ROCKY MOUNTAIN POWER
REQUIREMENTS FOR SAFETY SOCKET.
3. PROVIDE AND INSTALL SERVICE LATERAL CONDUIT IN A 36-INCH MINIMUM
TRENCH DEPTH WITH A MINIMUM BURIAL DEPTH OF 30-INCHES PER
POWER COMPANY BEDDING AND BACKFILL REQUIREMENTS. SERVICE
SHALL BE KEPT 36-INCHES FROM WATER OR GAS SERVICES. LOCATE
SERVICE LATERAL TO AVOID FUTURE BUNKHOUSE FOUNDATION BY
5-FEET MINIMUM.
4. PROVIDE AND INSTALL A 3-INCH CONDUIT LATERAL FROM THE SERVICE
POLE TO DIRECTLY BELOW THE EXISTING WAREHOUSE SERVICE
(CURRENTLY OVERHEAD). STUB ABOVE GRADE AT BOTH ENDS AND CAP
ENDS. MEET ALL ROCKY MOUNTAIN POWER REQUIREMENTS.
5. ELECTRICAL SERVICE METERBASE SHALL BE INSTALLED WITH IMC AND
SWEEP PER FOREST SERVICE SPECIFICATIONS, WITH CENTER OF METER
LOCATED BETWEEN 5 AND 6-FEET ABOVE FINISHED GRADE.
6. ELECTRICAL SERVICE EQUIPMENT SHALL BE RATED AS SHOWN IN
CALCULATIONS THIS SHEET, MINIMUM, AND 22,000 SHORT CIRCUIT
CURRENT RATED (MAY BE SERIES RATED), EQUIVALENT TO SQUARE D QO
OR BETTER, NO TANDEM OR HALF SIZED BREAKERS ALLOWED.
7. PROVIDE A 2-INCH CONDUIT FROM POLE FOR PHONE AND CABLE TV
SERVICES. DIRECT BURIED CABLE(S) THAT WILL MEET REQUIREMENTS
FOR BOTH SERVICE INSTALLED BEFORE CONTRACT IS COMPLETE MAY
SUBSTITUTE FOR THE CONDUIT. CONDUIT OR CABLES SHALL BE BURIED
24-INCHES MINIMUM AND KEPT 5-FEET FROM FUTURE BUNKHOUSE FOOT
PRINT. IT MAY BE INSTALLED IN THE SAME TRENCH AS THE ELECTRICAL
SERVICE AT 30-INCHES MINIMUM. KEEP SEPARATE FROM POWER
COMPANY INSTALLED SECONDARY A MINIMUM OF 12-INCHES
HORIZONTALLY.
8. HOME RUN INTERNAL PHONE TO THIS LOCATION INTO COMBINER/SERVICE
BOX. GROUND PER CODE AND SPECIFICATIONS.
9. HOME RUN TELEVISION INTERNAL CABLE TO SURGE ARRESTOR MOUNTED
IN THE SAME GENERAL AREA FOR CABLE TV SERVICE. GROUND PER
CODE, SPECIFICATIONS, AND AS SHOWN.
10. ELECTRICAL IN HOUSING SHOWN IS A MINIMUM AND MAY VARY BASED ON
SUBMITTED FLOOR PLANS. IF ALTERNATIVE SIZED BUILDING IS
APPROVED, ELECTRICIAN SHALL SUBMIT MODIFIED ELECTRICAL PLAN.
ADDITIONAL LUMINAIRES AND OR TYPE CHANGES MAY BE REQUIRED AT
NO ADDITIONAL COST TO PROVIDE THE SAME LEVEL OF SERVICE.
ADDITIONAL RECEPTACLES MAY ALSO BE REQUIRED TO MEET INTENT AS
SHOWN.
11. SMOKE, CARBON DIOXIDE, AND VISUAL ALARMS SHALL ALL BE
INTERCONNECTED.
S
S
C
M
CRAWL SPACES AND ATTIC SPACES LIGHTING AND RECEPTACLES
1- AT CRAWL AND ATTIC ACCESS, INSTALL ONE GFCI RECEPTACLE AND SINGLE POLE PILOT SWITCH ON THE
CIRCUIT SERVING THE ROOM WITH THE ACCESS ONLY ACCESSIBLE FROM WITHIN THE SPACE.
2- SWITCH SHALL CONTROL 2 TYPE "N" LUMINAIRES LOCATED TO LIGHT THE SPACE. LOCATIONS SHALL BE
APPROVED BY THE CONTRACTING OFFICER BEFORE INSTALLATION.
A
A-1
A-1
A-1
S
A
A-1
A-1
A-1
S
B
B
B B
C
C
SERVICE CALCULATIONS
NEC 220.82
(3VA/FT2)(1300FT2)= 3,900
(1.5KW)(3 SMALL APPL)= 4,500
(1.5KW)(1 LAUNDRY)= 1,500
TOTAL= 9,900
2 REFRIGERATORS= 1,200
DRYER= 5,000
2 RANGES DEMAND LOAD= 10,000
TOTAL VA= 26,100
OTHER LOADS THAT SHALL BE INCLUDED:
FURNACE MOTOR @ 100%
A/C CONDENSERS @ 100%
SERVICE, MAIN BREAKER AND PANEL SHALL BE 200 AMP MINIMUM 120/240
VAC SINGLE PHASE, OR, 150 AMP 120/208 VAC THREE PHASE TO ALLOW FEED
TO THE FUTURE BUNKHOUSE.
PANEL SHALL BE LARGE ENOUGH TO ACCOMMODATE 5 BLANK BREAKER
SPACES BEYOND INSTALLED BREAKERS FOR FUTURE FEEDER AND OTHER
POSSIBLE LOADS.
LOAD CENTER DISTRIBUTION
THE FOLLOWING IS A LIST OF COMMON CIRCUITS MINIMUM:
# AMPS DESCRIPTION
A-1 20 BEDROOMS LIGHTS AND RECEPTACLES
AND EXTERIOR RECEPTACLES
A-2 20 RECEPTACLE-SMALL BATHROOM
A-3 20 ALL LIGHTS AND FANS EXCEPT BEDROOMS
A-4 20 RECEPTACLE-LARGE BATHROOM
A-5 20 SOUTH FRIDGE AND RANGE HOOD
A-6 20 RECEPTACLES-KITCHEN WEST WALL
A-7 20 NORTH FRIDGE AND RANGE HOOD
A-8 20 RECEPTACLES-KITCHEN NORTH WALL
A-9 20 RECEPTACLES-LIVING ROOM AND HALL
A-10 20 RECEPTACLES-KITCHEN DINING
PENINSULA AND DINING AREAS
A-11 20 RECEPTACLE-WASHER
A-12,14 30 RECEPTACLE-DRYER
A-13 15 SMOKE ALARMS, ALARM BELL CIRCUIT
A-15,17 50 SOUTH RANGE
A-16,18 50 NORTH RANGE
OTHER CIRCUITS THAT ARE NOT SHOWN INCLUDE BUT ARE
NOT LIMITED TO:
FURNACE AND SINGLE POLE SWITCH DISCONNECTS
AIR CONDITIONER AND GENERAL DUTY DISCONNECTS
WATER HEATER - GAS WATER HEATERS WITH SMALL LOADS
MAY BE PLACED ON OTHER CIRCUITS.
REQUIRED CRAWL SPACE AND ATTIC SPACE LIGHTING AND
RECEPTACLES AS DESCRIBED MAY BE PLACED ON OTHER
CIRCUITS.
M M
A-3
A-3
A-4
A-1
A- 11
A-17,19
A-3
A-3
J
A-7
A-10
A-8 A-8A-8
A-6
A-7
A-5
A-9
C
S
A-5
SEE LEGEND FOR
MORE INFORMATION
G
MOUNT BOTH TV AND
RECEPTACLE AT 48" TO
CENTER ABOVE
FINISHED FLOOR.
SURGE SUPPRESSION FOR CABLE
TV ENTRANCE WITH BOND BACK
TO ELECTRICAL SERVICE.A-1
A-1
A-1
A
A-1
S
A
A-1
A-1
A-1
A-1
S
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
C
A-3
A-2
G
A-3
A-9
A-9
A-9
B
J
A-16,18
A-6
A-15,17
A-6
C
C C
A-3
A-3
C
A-10
A-3 A-3
A-10
A-9 A-9
S
| G1.G2 |
| 01_G01_Cover |
| G1 |
| G2 |
| 01_G1 |
| C0_C4 |
| C1_C_SITE |
| C0 |
| C1 |
| C2 |
| C3 |
| C4 |
| D1_D4 |
| D1_D4 |
| D1 |
| D2 |
| D3 |
| D4 |
| A1 |
| A2 |
| StAnthonyBHElec |