Technicall Exibit 3: Preventative Maintenance
Frequency
QuarterlySemiannualAnnualBiennial5 Years
Sprinkler Wet Pipe (NFPA 25)
1. Notify proper authorities prior to testing alarm systemXXXX
2. Open and close post indicator valve (PIV) to check operation; makeXX
minor adjustments such as lubricating valve stem, cleaning and/or
replacing target windows as required.
3. Open and close OS&Y (outside stem and yoke) cut-off valve to checkXX
operation; make minor repairs such as lubricating stems and tightening
packing glands as required.
4. Perform operational test of water flow detectors; make minorXX
adjustments and restore system to proper operational condition
5. Check to ensure that alarm drain is open; clean drain line if needed.X
6. Open water motor alarm test valve and ensure that outside alarmXX
operates; lubricate alarm, make adjustments as needed.
7. Conduct main drain test by opening 2" test valve; maintain aX
continuous record of drain tests; make minor adjustments if needed;
restore system to proper operating condition.
8. Check general condition of sprinklers and sprinkler system; makeX
minor adjustments as required.
9. Check equipment gaskets, piping, packing glands, and valves forX
leaks; tighten flange bolts and loose connections to stop all leaks.
10. Check condition of fire department connections; replace missing orXX
broken covers as needed.
11. Trip test wet pipe system using test valve (control valve); makeXX
minor adjustments as needed and restore system to proper operation
condition.
12. Inspect OS&Y and PIV cut-off valves for OPEN position.XX
13. Back Flow Prevention AssembliesX
14. Obstruction, internal inspection of pipingX
Fire Alarm (NFPA 72)
1.Visually inspect all alarm equipment for obstructions or physical damage, clean dirt and dust from interior and exterior of panel/pull boxes, tighten loose connectionsXX
2.Notify facility manager and facility occupants prior to testing any alarm systemsXX
3.Notify fire department/coordinate testing with alarm shop (when applicable)
4.Conduct operational test of initiating and signal transmitting devices in populated buildings by building zone/area; for those circuits which do not operate properly, check detectors, control units and annunciators for dust on defective components; makeX
5.Perform battery load tests (voltage) on backup batteries in both FACP, Radio Transmitter (RT) AND Mass Notification System if installed.X
Visually inspect panel wiring and connections for tightnessX
6.Test monitored Control Panel/Annunciator Equipment to verify proper receipt of alarm, supervisory, trouble signals (inputs).X
7.Test monitored Control Panel/Annunciator Equipment to verify proper operation of notification appliances & auxiliary functions (outputs).X
8.Verify monitored Control Panel & Annunciator Equipment that all lamps and LEDs are illuminated.X
9.Load test Control Panel & Annunciator Equipment backup batteries (when provided).X
10.Initiating Devices-Manual Fire Alarm Stations verify station is accessibleX
11.Test Initiating Devices-Radiant Energy Detectors (Optical Detectors) to verify alarm initiation & receipt.X
13."Initiating Devices-Gas Detectors 1. Test to verify alarm initiation and receipt. 2. Verify no facility change that affects performance.X
14.Notification Appliances and Voice Communication (telephone, speakers, horns, and strobe lights) Test to verify operability.X
15.Digital Alarm Transmitters and Receivers. Test to verify operabilityX
16."Visually check entire system: Detectors unblocked & uncovered, Manual stations in place & unobstructed.X
17."Visually check entire system: Panels secured & indicator lamps functional, Notification appliances in place,X
18."Entire System: Exercise evacuation notification appliances for audibility, clarity, and visibility.X
19.Check all air handler and exhaust fan shut down circuit for proper operation (for HVAC Systems of 2000 cfm and greater)X
20.Check binary transmitter (BT) (radio control box) to ensure all alarm activations, tampers & AC power fails transmit to the fire dept. alarm monitoring deskX
21.Perform battery load tests on backup batteries in both fire control panel & (BT) (radio control box).X
22.Inspect Fire Alarm Control Panel (FACP) for proper labelingX
23.Restore system to proper operating conditionXX
24.Notify facility manager/facility occupants of test completionXX
25.Notify fire department of test completionXX
26.Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s) and provide to CORXX
27.Only Trained or Qualified Personnel shall perform Inspection, Testing & Maintenance (ITM) tasks on Fire Suppression Systems.XX
Foam Systems Bldg 3170, 3181 (UFC 3-601-02)
1. Notify proper authorities prior to testing alarm systemXX
2. Foam Concentrate - Inspect to verify adequate supplyX
3. Foam Generator - Take sample and test in accordance with manufacturer's instructions.X
4. Foam Generator - Conduct test to verify operability. (Water-powered may be done with water only.)X
5. Actuators - Verify that all manual and automatic actuators function.X
6. Foam Proportioning Systems - Conduct full flow test to ensure proper system function. (Test may be done through a test connection or through foam generators. Only discharge until full foam flow appears from each generator; then end foam injection.)X
7. Foam Proportion Systems - Verify proper concentration.X
8. Control Valve - Operate valve through entire travel to verify function.X
9. Control Vlave - Lubricate stem.X
10. Mainline Water Strainer - inspect for damaged or corroded partsX
11. Louvers - test louvers to ensure operabilityX
12.Restore system to proper operating conditionXX
13. Inspect OS&Y and PIV cut-off valves for OPEN position.XX
14.Notify facility manager/facility occupants of test completionXX
15.Notify fire department of test completionXX
16.Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s) and provide to CORXX
17.Only Trained or Qualified Personnel shall perform Inspection, Testing & Maintenance (ITM) tasks on Fire Suppression Systems.XX
Fire Pumps (NFPA 25)
1. Ensure all valves relating to water system are in correct positionXX
2. Open and close OS&Y (outside stem and yoke) cut-off valve to checkX
operation; make minor repairs such as lubricating stems and
tightening packing glands as required.
3. CONTROL PANELS: check controller panel for each pump forXX
proper operation IAW standard procedures for the type of panel installed
replace burned out bulbs and fuses; make other repairs as needed.
4. Check wiring for loose connections and fraying; tighten or replace.X
5. Diesel engines Blds 3173 and 3182:
A) check battery terminals for corrosion; clean if neededX
B) check belts for tension and wear; adjust or replace if needed.X
C) check electrical wiring, connections, switches, etc.; adjust as neededX
D) perform 10 min pump check for proper operation and adjust as req.X
piping, seals, packing glands, etc.
E) check pump operations; vibration, noise, overheating, etc.X
F) check alignment, clearances, and rotation of shaft and couplerX
(includes removing and reinstalling safety cover)
G) tighten or replace loose, missing or damaged nuts, bolts, or screw.X
Have not been damaged.X
H) check suction or discharge pressure gauge readings and flow rate.X
I) check packing glands and tighten or repack as required: note thatX
slight dripping is required for proper lubrication of shaft.
6. Electric Fire Pumps in Bldgs 131 and 3172:
A) Perform 10 min pump test run, check for proper operation andX
adjust as needed.
B) test start pump without foam discharger.X
C) check for leaks on suction and discharge piping, seals, packing, glands.X
D) check for excessive vibration, noise, overheating, etc.X
E) check alignment, clearances, rotation of shaft and couplerX
(includes removing and reinstalling safety cover)X
F) tighten or replace loose, missing or damaged nuts, bolts, or screws.X
G) lubricate pump and motor as required.X
(H) check suction or discharge pressure gauge readings and flow rate.X
(I) check packing glands and tighten or repack as required; note thatX
slight dripping is required for proper lubrication of shaft.
7. Inspect and clean strainers after each use and flow test.X
8. Check water supply pressure; adjust as needed.X
9. Open and close OS&Y (outside stem and yoke)cut-off valve to checkX
operation; make minor repairs such as lubricating stems and
tightening packing glands as required.
Dry Chemical/Ansul (NFPA 17)
1. Check nozzles, heads, and fusible links or heat detectors to ensureX
that they are clean, have adequate clearance from obstructions and
have not been damaged.
2. Check hand hose lines, if applicable, to ensure that they are clear, inX
proper position and in good condition.
3. Check to ensure that all operating controls are properly set.X
4. Observe pressure on system to ensure that sufficient gas is available.X
5. Check expellant gas cylinders of gas cartridge systems for properX
pressure or weight to ensure that sufficient gas is available.
6. Test all actuating and operating devices; turn valve on dry chemicalX
bottle or cylinder to off position IAW manufacturers specs, and test
operation of control head by removing fusible link, activating heat
detectors or pulling test control. Restore system to normal operations.
7. Open and check dry chemical in cylinder and stored pressure systemsX
to ensure it is free flowing and without lumps.
8. When an alarm system is reactivated, ensure that it functions IAWX
manufacturers specifications.
9.Check dry chemical containers, auxiliary containers, and hose assemblies for hydrostatic date (date stamp must be within 12 years), if within one year of expiration notify and provide quote to COR for hydrostatic testing.X
Carbon Dioxide (NFPA 12)
1. Check and test the carbon dioxide system for operation.X
2. Check that there have been no changes to the size, type, and configuration of the hazard systemX
3. Check and test all time delays for operationX
4. Check and test all audible alarms for operationX
5. Check and test all visible signals for operationX
6. Check that all warning signs are installedX
7. Check to ensure that the procedures are appropriate and alarms are operable.X
8. Check and test each detectorX
9. Test hosesX
9. High-pressure cylinders - weigh and make sure date of last hydrostatic test is notedX
10. High-pressure cylinders - replace/refill any cylinder showing a loss in net content of more than 10 percentX
Portable Fire Extinguishers (NFPA 10)
1. Ensure that the extinguisher is the proper size and type for the hazard presentX
2. Ensure that the extinguisher is located in its designated locationX
3. Ensure that the hangar is properly secured and that the extinguisher is hung and not resting on the floorX
4. Ensure that there are no obstructions to limit the extinguisher’s access or visibilityX
5. Ensure that the operating instructions on the nameplate are legible and facing outwardX
6. Check and replace the safety seals and tamper indicatorsX
7. Determine the fullness of the extinguisher by weighing itX
8. Fluff dry chemical extinguishers with a rubber malletX
9. Examine the extinguisher for obvious physical damage to the shell or any component, corrosion, leakage, or clogged nozzleX
10. Ensure the pressure gauge indicates that the extinguisher is within operating rangeX
12. Ensure the Hazardous Material Identification System (HMIS) label is in placeX
13. Perform a conductivity test of all carbon dioxide fire extinguishersX
14. Check hydrostatic testing of carbon dioxide, wet chemical, dry chemical, foam, and portable fire extinguishersX
15. Check hydrostatic testing of all cartridges associated with portable fire extinguishersX
16. Check hydrostatic testing of all dry chemical hose equipped units with a shut off valveX
17. Attach and inspection stickers to all portable fire extinguishers. Stickers shall be designed to stay onX
18. Notify COR of any extinguishers that are non-compliant for hydrostatic testing or are in need of replacement due to physical damageX
19. Stored pressure fire extinguishers that require a 12-year hydrostatic test must be empied and proper maintenance precedures performed in accordance with 6-year maintenance requirementsX

&CFire Protection Performance Work Statement

Sheet2

INSPECTION REQUIREMENTS
HYDROMAINTHYDRO
LABOR-HRSWMQSA12 YEARS6 YEARS12 YEARS
AUTOMATIC SUPPRESION SYSTEMS
WETX
DRYX
PREACTION DELUGEX
ANSULX
HALONX
FLOW TESTX
Flight Line
PORTABLE FIRE EXTINGUISHERSXXX
Flight LineXXxX
DETECTION DEVICES
HEATX
SMOKEX
INITATING DEVICES/AUDIBLES
PULL STATIONSX
HORN/STROBESX
BATTERIESX
EXIT LIGHTSX

&CFIRE DETECTION AND

SUPPRESION INSPECTIONS

Sheet5