A06_NIFC_Campus_Storm_Drain_Piping_Replacement_Drawings_01DEC2022.pdf
PDF 5 MB Posted
- Attached to
- NIFC Campus Storm Drain Federal contract opportunity
- Solicitation number
- 140L3723R0001
About this file
This document package includes construction drawings and specifications for a federal contract opportunity to replace storm drain piping at the National Interagency Fire Center campus in Boise, Idaho. The project involves demolishing existing water lines, fencing, and pavements; installing new 2-inch water service lines, yard hydrants, gate valves, security fencing, bollards, a 12-inch HDPE drain line, a precast concrete catch basin, and a headwall; and paving surfaces. Drawings provide plans, profiles, demolition plans, details, notes and legends for civil site work, plumbing, and architectural elements. Specifications include requirements for trenching, backfilling, concrete, asphalt paving and fencing. The related solicitation is for the NIFC Campus Storm Drain project issued by the Bureau of Land Management Idaho Region.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L3723R0001_Amd_0001.pdf | ||
| SF1442_Example_Completion-Instructions.pdf | ||
| A06_PROLOGUE_REV1_NIFC_Campus_Storm_Drain_Piping_Replacement_27FEB2023.pdf | ||
| A06_NIFC_Campus_Storm_Drain_Piping_Replacement_-_Bid_Schedule.pdf | ||
| A06_NIFC_Campus_Storm_Drain_Piping_Replacement_Specs_01DEC2022.pdf | ||
| B03_Wage_Determination_ID20230025_02-03-2023.pdf | ||
| Sol_140L3723R0001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROBINSON ROAD
SIDEWALK
KR
U
M M
R O
AD
BOLLARD
HVAC
PIPES
D
EV
EL
O
PM
EN
T
AV
E
MCP
Gravel Area
NO PARKING
REFUSE
STOPSTOP
TRUCKS
MCP
M
CP
MCP
MCP
MCP
M C
P
MCP
MCP
MCP
CONCRETE
SI
D
EW
AL
K
MCP
MCP
MCP
MCP
MCP
MCP
MCP
MCP
MCP
MCP
MCP
MCP
MOBILIZATION AREA
NIFC CAMPUS
215 405 410B
0C 420
PROJECT LOCATION SITE ACCESS - NIFC CAMPUS
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE
YOU DIG, GRADE, OR EXCAVATE FOR THE
MARKING OF UNDERGROUND MEMBER
UTILITIES
Call before you dig.
Know what's below .
PROJECT VICINITY
PROJECT VICINITY - BOISE, IDAHO
PROJECT
LOCATION
PROJECT LOCATION
DESIGNERS
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NIFC CAMPUS STORM PIPE AND WATERLINE
REPLACEMENT
INDEX OF DRAWINGS
GENERAL
G001 COVER SHEET
CIVIL
C101 EXISTING CONDITIONS PLAN
C102 DEMOLITION AND SITE SECURITY PLAN
C103 SITE PLAN
C201 PROFILES
C501 DETAILS
C502 DETAILS
ARCHITECTURAL
A101 FIRST FLOOR PLAN AND DETAILS - 410C-RWS
A102 FIRST FLOOR PLAN AND DETAILS - 430 EQS
PLUMBING
P001 PLUMBING LEGEND AND ABBREVIATIONS
PD101 PLUMBING DEMOLITION PLAN / ELEVATION
P101 PLUMBING PLAN / ELEVATION / SCHEDULE
P501 PLUMBING DETAILS
5'20' 0 20'10'
NOTES:
1. SURVEY SUPPLIED BY J-U-B ENGINEERS, LLC DURING THE
DEVELOPMENT OF "NIFC CAMPUS STORM DRAIN PIPING
INVESTIGATION, JAN 2022" AND SUPPLEMENTED BY J-U-B IN
MARCH 2022 FOR THIS EFFORT.
2. HORIZONTAL DATUM IS NAD 83 (NSRS2007), MODIFIED
IDAHO STATE PLANE COORDINATE SYSTEM (WEST ZONE
1103). ANY BEARINGS SHOWN ARE AT GRID AZIMUTH. ANY
DISTANCES SHOWN REPRESENT GROUND DISTANCES.
3. MODIFIED IDAHO STATE PLANE COORDINATES,
REPRESENTING GROUND DISTANCES, WERE CALCULATED
BY USING A COMBINED FACTOR OF 1.0001799589 DERIVED
FROM THE ADA COUNTY GIS SYSTEM.
4. VERTICAL DATUM IS NORTH AMERICAN VERTICAL DATUM
1988 (NAVD88). NGS BENCH MARK'S - (IDA 80 35, PID #
OH0133) AND (T 86, PID # OH0127) WERE USED TO CONTROL
ELEVATION FOR THE PROJECT.
5. LOCATIONS OF EXISTING UTILITIES ARE SHOWN IN
APPROXIMATE WAY ONLY. CONTRACTOR SHALL
DETERMINE LOCATIONS OF ALL EXISTING UTILITIES BEFORE
WORK.
LEGEND:
UTILITY
WATER
METER
EXISTING
2" WATER
SERVICE
EXISTING FROST FREE
YARD HYDRANTS
EXISTING VALVES AND
STAND PIPE WITH
BACKFLOW PREVENTER
EXISTING
2" WATER
SERVICE
EXISTING
COMMUNICATIONS
TOWER AND GROUNDING
RING
1.5" AND 34" FROST FREE
YARD HYDRANTS AND 2'-6"
X 5'-9" PROTECTIVE
RACKING
EXISTING
WATER SERVICE
CONNECTION TO
410C
UNDERGROUND POWER
SANITARY SEWER
UNDERGROUND TELECOM
WATERLINE
EDGE OF PAVEMENT
CHAIN LINK FENCE
STORM DRAIN
GAS LINE
PERCEIVED RIGHT OF WAY
BUILDING
ASPHALT PAVEMENT
CONCRETE PAVEMENT
SANITARY SEWER MANHOLE
TELECOM MANHOLE
LIGHTPOLE
ELECTRICAL POLE
BOLLARD
YARD HYDRANT
GAS METER
ELECTRICAL JUNCTION BOX
EXISTING COMMUNICATIONS
VAULT
EXISTING
DEGRADED
CURB
STOPS
EXISTING
JERSEY
BARRIERS (8)
Ben L Carter Digitally signed by Ben L Carter Date: 2022.10.21 09:14:11 -06'00'
XX
X X
X X
X X
X X
X
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
N:692280.89 E:2503838.81
N:692262.43 E:2503837.54
N:692050.77 E:2503841.53
N:692263.95 E:2503819.93
N:692270.23 E:2503816.85
N:692265.12 E:2503806.32
N:692240.91 E:2503772.48
N:692247.91 E:2503770.87
N:692240.93 E:2503756.38
N:692225.36 E:2503756.36
N:692225.88 E:2503738.24
N:692240.96 E:2503738.62N:692241.02
E:2503697.55
N:692241.02 E:2503692.55
N:692245.92 E:2503526.86
N:692240.92 E:2503526.80
N:692326.45 E:2503502.56
N:692326.52 E:2503519.17
N:692351.05 E:2503506.64
N:692332.37 E:2503498.46
N:692405.82 E:2503518.83
N:692405.82 E:2503524.75
N:692421.09 E:2503524.75
N:692421.09 E:2503518.73
N:692438.91 E:2503518.67
N:692443.47 E:2503513.65
N:692443.83 E:2503530.11
N:692438.98 E:2503530.01
N:692331.16 E:2503514.15
N:692284.82 E:2503614.18
X X X
5'20' 0 20'10'
NOTES:
1. CONTRACTOR SHALL DEMOLISH WATER LINE, FENCING AND
PAVEMENTS TO FULL DEPTH. CONTRACTOR SHALL REMOVE
AND SALVAGE ALL VALVES AND STANDPIPES AND SHALL
RETURN TO OWNER.
2. WHERE CONCRETE OR ASPHALT PAVEMENT IS TO BE
REMOVED, CLEAN, PERPENDICULAR SAWCUTS SHALL BE
MADE. WHERE CONCRETE IS TO BE REPLACED, EXPANSION
JOINT SHALL BE USED AROUND PROPOSED CONCRETE.
WHERE ASPHALT IS BEING SAWCUT AN REPLACED,
CONTRACTOR SHALL MILL THE TOP HALF INCH OF THE 6
INCHES OF ADJACENT ASPHALT PAVEMENT AND PAVE TO
MILLING LIMITS.
KEY NOTES:
1. DEMOLISH 2' WATER SERVICE, TYP.
2. DEMOLISH ASPHALT PAVEMENT, TYP.
3. DEMOLISH CONCRETE PAVEMENT, TYP.
4. DEMOLISH YARD HYDRANT / STAND PIPE, TYP.
5. DEMOLISH GATE VALVE, TYP.
6. DEMOLISH SECURITY FENCING, TYP. PRIOR TO
FENCE DEMOLITION, REMOVE AND PROTECT FIBER
OPTIC SECURITY WIRE. DEMOLITION NEAR FIBER
OPTIC WIRE SHALL BE UNDERTAKEN WITH EXTREME
CARE, WIRE SHALL NOT BE SEVERED.
7. REMOVE PROTECTIVE RACKING FOR
RE-INSTALLATION.
8. DEMOLISH BOLLARD, TYP.
9. PROVIDE 8' TALL LOCKABLE TEMPORARY SECURITY
FENCING WITH 2" MESH, AS SHOWN, THROUGHOUT
CONSTRUCTION. CONTRACTOR SHALL MAINTAIN
PERIMETER SECURITY AT ALL TIMES.
10. PROTECT / RESET BOLLARDS, TYP.
11. BACKFLOW PREVENTION DEVICE LOCATION, SEE
ARCHITECTURAL SHEETS.
12. WATER METER TO REMAIN.
13. DEMOLISH DEGRADED WHEELSTOPS, TYP.
14. REMOVE AND SALVAGE (8) JERSEY BARRIERS. MOVE
TO GOVERNMENT LAYDOWN AREA ON NE CORNER
OF CAMPUS (APPROXIMATELY 2000 LF DRIVE
DISTANCE) FOR GOVERNMENTS CONTINUED USE.
LEGEND:
SECURED AREA, NO
UNACCOMPANIED ACCESS
DEMOLISH ITEM, SEE KEY NOTES
TEMPORARY SECURITY FENCING
2 2
6 9
Ben L Carter Digitally signed by Ben L Carter Date: 2022.10.21 09:14:44 -06'00'
X
X X
X X
X X
X X
X X
X X
X
0+00.00
1+00.00
2+00.002+22.68
0+50.00
1+50.00
W
W W
W W
W W
W W
W W
W
W W
W W
W
W
W W W W W W W W W W W W W W W W W W W W W
W
W
W
W
W
W
WW
WWWW
W
W W
5+49.75
0+00.00
1+00.002+00.003+00.00
4+
.0
5+
.0
0+50.00
1+50.002+50.00
3+50.00
4+
.0
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
N:692414.43 E:2503518.47
N:692412.43 E:2503518.47
N:692284.25 E:2503619.73
N:692265.11 E:2503841.59
N:692227.12 E:2503743.51
N:692233.51 E:2503695.05
N:692050.77 E:2503841.53
N:692063.86 E:2503855.85
N:692283.78 E:2503855.06
W W W W
UP UP UP UP
5'20' 0 20'10'
NOTES:
1. CONTRACTOR SHALL COORDINATE WITH SUEZ/VEOLIA WATER FOR CONNECTION
TO EXISTING WATER METER. ALL WATER SERVICE SHALL BE 2" AND PIPING,
FITTINGS, AND VALVES SHALL MEET REQUIREMENTS OF MOST RECENT IDAHO
STANDARDS FOR PUBLIC WORKS CONSTRUCTION, SECTION 404.
2. VERTICAL SEPARATION OF 18" MINIMUM SHALL BE MAINTAINED FROM EXISTING
AND PROPOSED UTILITIES.
3. WATER SERVICE SHALL BE INSTALLED WITH 42" MINIMUM COVER.
4. LABEL EXPOSED WATERLINES TO YARD HYDRANTS AS NON-POTABLE WATER.
KEY NOTES:
1. FURNISH AND INSTALL 2" PE WATER SERVICE, TYP. SEE TRENCH DETAIL
1/C501.
2. FURNISH AND INSTALL ASPHALT PAVEMENT, TYP.
3. FURNISH AND INSTALL CONCRETE PAVEMENT, TYP. SEE DETAIL 2/C501.
4. FURNISH AND INSTALL 34" HOSE THREAD YARD HYDRANT, TYP. ORIENTATION
PER GOVERNMENT.
5. FURNISH AND INSTALL GATE VALVE, TYP.
6. FURNISH AND INSTALL SECURITY FENCING, TYP. SEE DETAIL 7/C502.
7. RE-INSTALL PROTECTIVE RACKING. PAINT SAFETY YELLOW AND INSTALL 4"
REFLECTIVE TAPE 2' FROM TOP OF EACH VERTICAL CORNER POST.
PROVIDE A MINIMUM OF 10' OF CLEAR SPACE FROM B410C RWS.
8. FURNISH AND INSTALL BOLLARD, TYP. SEE DETAIL 4/C501.
9. FURNISH AND INSTALL 12" HDPE DRAIN LINE. SEE TRENCH DETAIL 1/C501.
10. FURNISH AND INSTALL 4' DIAMETER PRECAST CONCRETE DOGHOUSE
CATCH BASIN. SEE DETAIL 5/C501.
11. FURNISH AND INSTALL HEADWALL, SEE DETAIL 6/C502.
12. STORMWATER SWALE, GRADE AS SHOWN. SEE A/C201.
13. FURNISH AND INSTALL PIPING AND 2" DOUBLE CHECK VALVE ASSEMBLY
BACKFLOW PREVENTION DEVICE WITHIN INSULATED ENCLOSURE IN BLDG
430, SEE ARCHITECTURAL SHEETS FOR EXACT LOCATION.
14. FURNISH AND INSTALL PIPING AND TWO (2) X 2" DOUBLE CHECK VALVE
ASSEMBLY BACKFLOW PREVENTION DEVICE (BFD) WITHIN INSULATED
ENCLOSURE IN BLDG 410W, SEE ARCHITECTURAL SHEETS FOR EXACT
LOCATION. CONNECT THE DOWNSTREAM PIPING OF ONE BFD TO EXISTING
BUILDING 410W WATER SERVICE.
15. RECONNECT EXISTING WATER SERVICE TO PROPOSED, SEE DETAIL 9/C502.
16. FURNISH AND INSTALL 1.5" HOSE THREAD YARD HYDRANT, TYP.
ORIENTATION PER GOVERNMENT.
17. FURNISH AND INSTALL 6' CURB STOP, TYP. SEE DETAIL 8/C502.
18. FURNISH AND INSTALL 2 X 2" SCHEDULE 40 PVC ELECTRICAL CONDUITS
(SOLVENT WELDED) WITH STUB UPS AND TERMINATION CAPS. END INSIDE
BLDG 430 BESIDE BFP ENCLOSURE AND AS SHOWN IN THE YARD NEAR
PROPOSED MAN GATE.
19. 2' IN EACH DIRECTION FROM CENTERLINE OF NORTH FACING FENCE ALONG
DRIVEWAY, PROVIDE 4" POST (2 TOTAL) PER CORNER POST IN DETAIL
7/C502.
LEGEND:
UNDERGROUND CONDUITS
2" WATER SERVICE
12' DRAIN LINE
ASPHALT
CONCRETE
GATE VALVE
YARD HYDRANT
BOLLARD
CB-1
RIM: 2866.84'
INV IN (EXISTING): 2863.91'
INV OUT (EXISTING): 2863.90'
INV IN (PROPOSED): 2863.92'
HW-1
INV IN: 2864.15'
Date: 2022.10.21 09:15:18 -06'00'
SCALE:A STORMWATER SWALE
NTS
+/- 0.5'
2' BOTTOM WIDTH
2' D
EP
TH
+/- 0.5'14' TOP WIDTH
6" LIFT OF 2" - 6" RIP RAP MATERIAL
COMPLYING WITH ITD STANDARD
SPECIFICATIONS SECTION 711
PERCEIVED RIGHT OF WAY
SLOPE EVENLY AND RETURN
TO PRE-EXISTING CONDITIONS
WITH NATIVE SOIL
EXISTING PAVED ROAD
+/- 30'
+/- 14' +/- 16'
EXISTING CONCRETE PAD
PARKING STOP
3' M
IN
. S
EP
AR
AT
IO
N T
O
SE
AS
O
N
AL
H
IG
H G
R O
U N
D W
AT
ER
RELOCATED FENCE
MAX 3:1 SLOPE EACH SIDE
OVEREXCAVATE A MINIMUM OF 12"
INTO NATIVE SOILS. BACKFILL WITH
NATIVE FREE-DRAINING MATERIAL.
ESTIMATED HIGH
GROUNDWATER
4'
Date: 2022.10.21 09:15:43 -06'00'
SCALE:1 TYPICAL WET UTILITY TRENCH
NTS
MATCH ADJACENT
SURFACE TREATMENT,
SEE 2/C501 FOR
ASPHALT AND 3/C501
FOR CONCRETE
SIZE OF UTILITY
MAY VARY
SUITABLE SOIL
BACKFILL
WIDTH AS NOTED ON PLANS
4' OR 2xØ MIN, WHICHEVER IS LARGER
PIPE ZONE BEDDING
COURSE
TRENCH WIDTH - 1/2Ø, TYP
NOTE: BACKFILL MATERIALS COMPACTION
- 95% STD PROCTOR UNDER SLABS AND ROADS
- 90% STANDARD PROCTOR MIN ALL OTHER AREAS
PIPE ZONE MATERIAL TO
SURROUND PIPE 3" MIN
DEPTH PER PLAN
WATERLINE - 42" MIN
STORM - 24" MIN
UTILITY MARKING TAPE
12 AWG TRACING WIRE
SCALE:2 TYPICAL ASPHALT PAVING
NTS
HMA - 3" MIN OR MATCH EXISTING,
WHICHEVER IS THICKER. HMA
SHALL MATCH SUPERPAVE MIX
SP-2 OR APPROVED EQUAL PER
ITD STANDARD SPECIFICATIONS
FOR HIGHWAY CONSTRUCTION
(2018) - SECTION 405.
8" MIN OF 34" MINUS COMPACTED
AGGREGATE BASE COURSE
SUBGRADE COMPACT
PER TRENCH DETAIL
1/C501.
FRAME AND GRATED INLET COVER PER
SPECIFICATIONS
48" BARREL SECTIONS
MANHOLE STEP
NON-SHRINK GROUT
4'-0"
VA
R
IE
S
PE
R
P
LA
N
SLOPE FINISH GRADE
FRAME AND COVER,
PROVIDE 2' RADIUS OF
CONCRETE PAVING
CAST IN PLACE BASE
6"
MIN.
INVERT PER PLAN
NON-SHRINK GROUT
SURROUNDING
RUBBER GASKET
6" APPROVED
ENGINEERING FILL OVER 6"
OF SCARIFIED, MOISTURE
CONDITIONED AND
COMPACTED SUBGRADE
SCALE:5 TYPICAL PRECAST DOGHOUSE CATCHBASIN
NTS
SCALE:3 TYPICAL CONCRETE PAVING
NTS
3/8 " M
IN
SE
AL
AN
T
TH
IC
KN
ES
S
CONTROL JOINT - TYP.
1/4" RADIUS
SILICONE JOINT SEALER
JOINT SEALER - AT POUR BREAKS AND ADJACENT TO EXISTING HARDSCAPES
3/4"
1/4" WIDE X 1 1/2" DEEP
GROOVE (SEE NOTE 4)
JOINT SANDBLAST TOP 1" OF
BEFORE SEALING
1" OVAL BACKER ROD3/4" PREFORMED
JOINT FILLER
NOTES:
1. CONTRACTOR SHALL INSTALL 4" OF CRUSHED AGGREGATE BASE COURSE UNDER
ALL CONCRETE PAVING PER ISPWC SECTION 802.
2. CONCRETE SHALL BE CLASS 3000 PER ISPWC SECTION 703.
3. CONTRACTOR SHALL INSTALL CONTROL JOINTS IN CONCRETE PAVING AT 12' MAX
SPACING BOTH WAYS. COORDINATE WITH ARCHITECTURAL PLANS FOR SCORING
PATTERN.
4. CONTROL JOINT TO BE 1/4 OF THE SLAB THICKNESS TYPICALLY.
5. COORDINATE WITH CONTROL JOINTS. WHERE CONCRETE PAVING ABUTS BUILDING
STRUCTURES, COLUMNS, FOOTINGS, POLE BASES, INLETS AND OTHER SIMILAR
IMMOVABLE OBJECTS, CONTRACTOR SHALL PROVIDE EXPANSION JOINT WITH
FILLER MATERIAL. CONTRACTOR SHALL ALSO PROVIDE CONTROL JOINTS TO
MINIMIZE POTENTIAL FOR CRACKING. COORDINATE WITH ENGINEER FOR
LOCATIONS. EXISTING CONCRETE PAVEMENT MUST HAVE PAVING DEPTH OF 4" OR
MORE FOR INSTALLATION OF EXPANSION JOINT WITH A DOWEL.
6. IN LIEU OF REINFORCEMENT SHOWN, CONTRACTOR MAY USE 6x6 W1.4/W1.4
WELDED WIRE FABRIC.
7. CONSTRUCTION JOINTS & CONTROL JOINT SHALL DIVIDE SLAB INTO AREAS NOT
EXCEEDING 225 SQFT WITHOUT REENTRANT CORNERS AND WITH LENGTH TO WIDTH
RATIOS NOT EXCEEDING 1 1/2 TO 1. CONTRACTOR SHALL SUBMIT LAYOUT PLAN
SHOWING PROPOSED CONTROL AND CONSTRUCTION JOINT LOCATIONS. JOINT
SPACING SHALL NOT EXCEED 20 FEET IN EITHER DIRECTION. FOR SIDEWALKS,
CONTRACTOR SHALL HAVE CONTROL JOINTS EVERY 5 FEET AND EXPANSION JOINTS
EVERY 50 FEET MINIMUM.
#3 @ 15" O.C.E.W.
CONCRETE PAVING BUILD-UP (TYP.)
4"
PLACE REINFORCING
AT MID-DEPTH
4"
4" MINUS COMPACTED AGGREGATE
BASE COURSE PER ISPWC SECTION 802
#3 @ 15" O.C.E.W.
5/8" SMOOTH BAR @ 15" C.T.C.
DOWEL BASKET
EXPANSION JOINT - DOWELED AT JOINTS WITH EXISTING CONCRETE
6"
EPOXY
EMBEDMENT
6"
5/8" PREFORMED JOINT SEALER
JOINT SEALER (DETAIL BELOW) GREASE ONE END FOR BOND BREAK
PLACE REINFORCING
AT MID-DEPTH
SUBGRADE COMPACTED PER TRENCHING DETAIL
EXISTING
CONCRETE
4" REFLECTIVE STRIP
FIRM NATIVE SOILS OR
ENGINEERED COMPACTED FILL
1" CONCRETE CROWN TOP
6" SCH. 40 STEEL PIPE PAINTED
SAFETY YELLOW AND FILLED
WITH CONCRETE
1" CONCRETE CROWNTOP OF NEW GRADE
4' -0
3'
-0
1'-6" Ø CONCRETE BASE
SCALE:4 TYPICAL BOLLARD
NTS
Ben L Carter Digitally signed by Ben L Carter Date: 2022.10.21 09:17:10 -06'00'
1 1/4" CORNER
BRACE WITH TIE
WIRES 24" OC
1'-4" DIA CONC
CORNER BASE
ADJ GRADE
TOP OF
1/4" X 3/4"
7' -0
4'
1" CROWN
TYP
4' -0
TY
P
OC AND FLAT BAR
BAR BANDS 12"
WITH STRETCHER
4" CORNER POST
3/8" ROUND ROD 10'-0" MAX (TYP)
CONNECTION AND
PRESSED STEEL
TURN BUCKLE, TYP
LINE BASE
1'-0" DIA CONC
WOVEN WIRE
FABRIC FENCE
ABOVE SURFACE
1 1/4" BOTTOM
3' -6
TY
P
24" OC
WITH TIE WIRES
RAIL 2" MAX
2" LINE POST
WITH TIE WIRES
14" OC
CAP, TYP
ALL POSTS
7 GAUGE COIL SPRING WIRE
45° EXTENSION ARM
(TYP EA POST EXCEPT AT GATE)
x x x x x x x x x x x x xx x x x x x x x x x x x xx x x x x x x x x x x x x
BARBED WIRE
1' -0
PRIVACY SLATS,
COLOR PER GOVERNMENT
FIBER OPTIC
SECURITY WIRE
SEE NOTE 5
IN LIEU OF TOP RAIL
FENCING NOTES:
1. FOOTINGS SHALL BE CYLINDRICAL OF THE DIAMETERS INDICATED.
2. FENCE FABRIC SHALL BE #9 GA. HOT GALVANIZED WIRE WOVEN IN A 2" MESH,
CHAIN LINK FABRIC AND SHALL BE TWISTED SELVAGE.
3. ALL POSTS, RAILS AND FITTINGS GALVANIZED BY HOT DIP PROCESS.
4. ALL PIPE (RAILS AND POSTS) TO BE NOMINAL STD. WEIGHT.
5. REINSTALL SENSTAR FIBER PATROL FP1150 SERIES OPTIC SECURITY WIRE ALONG
INSIDE OF PROPOSED FENCING PER MANUFACTURER'S RECOMMENDATIONS. WIRE
SHALL NOT BE SEVERED DURING DEMOLITION OF EXISTING FENCE OR
CONSTRUCTION OF NEW FENCE.
SCALE:7 TYPICAL PERIMETER FENCE AND CORNER
NTS
A
A
0'-6"0'-6"1'-0"2'-0"0'-9"2'-4"
KJIH
12" 3'-0" 5'-0" 0'-6" 3'-0"
GFECBADIA.
DIMENSIONS FOR HEADWALL
DIA.
A
6" 6"
B
#4 BARS @
12" O.C.
PLAN ELEVATION
SECTION A-A
#4 BARS
C
F
D I
6" J
6" E
H
K
1'- 6"
G
#4 BARS @
12" O.C.
1 1 /2"
SCALE:6 VERTICAL HEADWALL
NTS
METAL GRATING / TRASH
SCREEN SHALL BE INSTALLED
AT INLET WITH MAXIMUM 2"
DIAMETER OPENINGS
SCALE:8 CURB STOP DETAIL
NTS
6'
1' 1'
5/8" Ø HOLE
5/8" Ø HOLE
ELEVATION
7"
2"2"
3"5"
PAVEMENT
BOLT WHEEL STOP TO PAVEMENT WITH 1/2" Ø
ANCHOR DRIVEN TO MANUFACTURERS
RECOMMENDED DEPTH OR 24", WHICHEVER
IS DEEPER.
SECTION
SCALE:9 STANDPIPE LAYOUT
NTS
WW
W W
PROTECT
EXISTING
BOLLARD,
TYP.
PROPOSED 2"
WATERLINE, SEE
SHEET C-103
EXISTING STANDPIPE,
REMOVE BACKFLOW
PREVENTER
CONNECT PROPOSED
WATERLINE AT
EXISTING GATE VALVE
EXISTING GATE VALVE, TYP
PROTECT
EXISTING
BOLLARD,
TYP.
W
SCALE:9A STANDPIPE
NTS
REPOSITION EXISTING
HOSE COUPLINGS AND
STANDPIPE SUPPORT
STRUCTURE AFTER
REMOVAL OF
BACKFLOW
PREVENTER.
Date: 2022.10.21 09:17:45 -06'00'
4'-0" V.I.F.
" V
.I.
F.
5'-0" V.I.F. 4'-6"
1' -6
A
AV
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRC.
NON POTABLE COLD WATER
SANITARY SEWER
VENT
FLOOR CLEAN OUT
GRADE CLEAN OUT
WALL CLEAN OUT
CONDENSATE DRAIN
NONPOTABLE WATER
RAIN WATER LEADER
OVERFLOW RAIN LEADER
PUMPED CONDENSATE RETURN
CONDENSATE RETURN
SLOPE DOWN IN DIRECTION OF FLOW
DCW
HWC
NPCW
DHW
SS
VT
FCO
GCO
WCO
CD
CR
NPCW
RWL
OFL
PCR
S=.XXX
A
P
T
DE
X
S
GATE VALVE
BALL VALVE
BUTTERFLY VALVE
GLOBE VALVE
GAS SHUT-OFF COCK
SWING CHECK VALVE
SPRING CHECK VALVE
Y-TYPE STRAINER
WATER OUTLET (TYPE INDICATED)
BACKFLOW PREVENTER
SLEEVE (PIPE) THRU WALL OR FLOOR
FLEX CONNECTOR (TYPE INDICATED)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
TEMP. & PRESSURE RELIEF VALVE
AUTOMATIC AIR VENT
DIELECTRIC UNION
UNION
AUTOMATIC FLOW BALANCING VA
DIAL THERMOMETER
PRESSURE GAUGE - PROVIDE WITH
PIGTAIL FOR STEAM
PIPE ANCHOR
SOLENOID VALVE
L.P. VALVE
ECCENTRIC PLUG BALANCING VA.
VALVE IN RISER
INLINE PUMP
TEE DOWN
ELBOW UP
ELBOW DOWN
PIPE CAP
PIPE DRAIN & CAP
CONNECT TO EXISTING
NEW PIPING
CENTRIFUGAL PUMP
LINE SIZE CHANGE
TURBINE WATER METER
CHLORINE ANALYZER
CHLORINATOR
T-TYPE STRAINER
ALTITUDE VALVE
SUMP PUMP
HOSE BIB
DRAIN
INSTRUMENT WIRE
AIR/VACUUM VALVE
INSTRUMENT
WBG - WATER BOARD GAGE
LE - LEVEL ELEMENT
LT - LEVEL TRANSMITTER
LD - LEVEL DISPLAY
P - ANALOG PRESSURE
GAUGE
PG - PRESSURE GAUGE,
DIGITAL
WM - WATER METER
TRANSMITTER
PS - PRESSURE SWITCH
LS - LEVEL SWITCH
BREAK LINE
Cl
AB
REVISION NUMBER
DETAIL BUBBLE
SECTION CUT
M102
SHEET NO. - WHERE
SECTION
IS SHOWN
SECTION LETTER
SHEET NO. - WHERE
DETAIL
IS SHOWN
DETAIL NUMBER
DESCRIPTION SYMBOL DESCRIPTION - ABBREVIATIONS -
NORTH ARROW
MECHANICAL EQUIPMENT TAG
KEY NOTE
(NOTE: NOT ALL SYMBOLS SHOWN ARE USED ON THESE DRAWINGS)PLUMBING LEGEND
SYMBOL -GRAPHIC SYMBOLS-
EF-1
HATCHING
INDICATES
ITEM(S) TO BE
REMOVED
PRESSURE RELIEF VALVE
A M102
UNDERGROUND PIPING
ABOVE CEILING
ABOVE FINISHED FLOOR
ACID VENT
ACID WASTE
BELOW FINISHED FLOOR
BACK FLOW PREVENTER
BELOW GRADE
BOOSTER PUMP
COMPRESSED AIR
CONDENSATE DRAIN
CAST IRON NO HUB
CLEANOUT
CHECK VALVE
CHLORINATED POLYVINYL CHLORIDE
COLD WATER
CONNECT TO EXISTING
PIPE DROP
DOMESTIC COLD WATER
DRINKING FOUNTAIN
DOMESTIC HOT WATER
PIPE DROP TO NEXT LEVEL
DETAIL
EXISTING
EXPANSION TANK
FIRE SERVICE
FLOOR CLEANOUT
FLOOR DRAIN
FILTER
FOUNDATION DRAIN
FLOW METER
FEMALE RESTROOM
GRADE CLEANOUT
HOSE BIB
HOT WATER
HOT WATER CIRCULATION
INDIRECT WASTE
INVERT ELEVATION IRRIGATION
LAVATORY
LIQUEFIED PETROLEUM GAS
LOW WATER CUTOFF
MAXIMUM
MINIMUM
MALE RESTROOM
MOP SINK BASIN
NATURAL GAS
NEW
NORMALLY OPEN (VALVE)
NORMALLY CLOSED (VALVE)
NOT TO SCALE
OVERFLOW DRAIN
OVER HEAD
OVERFLOW RAIN LEADER
PUMP
CROSS LINKED POLYETHYLENE
PIPE RISE
ROOF DRAIN
RECIRCULATION PUMP
REST ROOM
POLYVINYL CHLORIDE
ROUGH-IN ONLY
RECIRCULATED WATER
RAIN WATER LEADER
SINK
SHEET
SOFT COLD WATER
SHUT OFF COCK (GAS)
SHUT OFF VALVE
SANITARY SEWER
SAMPLE TAP
TYPICAL
TRAP PRIMER LINE
URINAL
UNDERGROUND
PIPE RISE TO NEXT LEVEL
UNDER SLAB
UP THRU ROOF
VALVE
VENT
VENT THRU ROOF
WASTE
WATER CLOSET
WATER HEATER
WALL CLEANOUT
WATER HAMMER ARRESTOR
WATER HEATER
WATER METER
AB.C.
AFF
AV
AW
BFF
BFP
BG
BP
CA
CD
C.I.N.H
CO
CKV
CPVC
CW
CX
(D)
DCW
DF
DHW
DN
DTL
(E)
ET
F
FCO
FD
FIL
FND
FM
F.R.R.
GCO
HB
HW
HWC
IDW
IRR
LAV
LPG
LWCO
MAX
MIN
M.R.R.
MSB
NG
(N)
NO
NC
NTS
OD
OH
OFL
(P)
PEX
(R)
RD
RP
R.R.
PVC
RIO
RW
RWL
(S)
SHT
SCW
SOC
SOV
S.S.
ST
TYP
TPL
(U)
UG
UP
US
UTR
VA
VT
VTR
(W)
WC
WH
WCO
WHA
WH
WM
NEW (SHADED) / EXISTING
FLAG
DEMO (SHADED) / EXISTING
FLAG
GENERAL NOTES:
NORTH REF
GAS REGULATOR
COMPRESSED AIRCA
S
Hb
BFP
TEE FITTING
VALVE IN RISER
1. COORDINATE PLUMBING FIXTURES AND RELATED PIPING WITH ALL OTHER
TRADES AS REQUIRED.
2. CONTRACTOR TO PROTECT AND MAINTAIN EXISTING UTILITIES AS INDICATED.
REFERENCE, PLUMBING, ELECTRICAL DRAWINGS. FIELD LOCATE
UNDERGROUND LINES, MARK, AND PROTECT AS NECESSARY. COORDINATE
PROTECTION AND ANY AND ALL TEMPORARY DISRUPTIONS OF SERVICE WITH
GOVERNMENT AS NECESSARY. PROVIDE ANY REQUIRED SHORING AND
STRUCTURAL SUPPORTS OF PIPING AND CONDUITS AS REQUIRED.
SCHEDULE WORK AND ANY REQUIRED INSPECTIONS TO MINIMIZE
DISRUPTION OF SERVICE AS NECESSARY.
3. REFER TO ARCHITECTURAL FLOOR PLANS FOR EXACT FIXTURE MOUNTING
HEIGHTS AND LOCATIONS.
4. LOCATE WATER PIPING IN HEATED AREAS ONLY. DO NOT LOCATE PIPING IN
NON-INSULATED ATTIC, CEILING OR WALL SPACES. DO NOT LOCATE WATER
PIPING IN ANY EXTERIOR WALLS UNLESS NOTED ON DESIGN DRAWINGS.
5. COORDINATE WITH ALL OTHER TRADES INCLUDING MECHANICAL FOR
EQUIPMENT, FIXTURES AND RELATED PIPING.
6. REFER TO PLUMBING FIXTURE SCHEDULE FOR CONNECTION SIZES. FIELD
VERIFY FOR TRANSITIONS REQUIRED FOR CONNECTING TO EXISTING PIPING.
7. PROJECT DESIGNED TO MEET CODE OF CONSTRUCTION IPC - 2018.
Juan L Rodriguez
Digitally signed by Juan L Rodriguez DN: CN=Juan L Rodriguez, dnQualifier=A01410C0000017D390FBB550001FB2C, O=CIRI DEVELOPMENT CORPORATION DBA
NORTH WIND GROUP, C=US
Location: NorthWind, Knoxville TN Reason: I am approving this document Contact Info: 7863518681 Date: 2022.10.21 09:12:00-04'00'
PD101
SCALE: 3/8" : 1'-0"
BLDG 410C - ROOM 100 DEMOLITION PLAN1
GENERAL NOTES:
1. DEMOLISH PIPE, ACCESSORIES AND PIPE SLEEVE
OF THE RISER.
2. RE-ROUTE THE PIPE UNDERGROUND TO
PENETRATE IN THE WALL NEAR THE WINDOW. SEE
P101 DRAWING FOR LOCATION.
3. CUT, CAP AND PROTECT THE EXISTING PIPE FOR
FUTURE RECONNECTION.
EXISTING
SUPPLY RISER
SCALE: 3/8" : 1'-0"
BLDG 410C - ROOM 100 DEMOLITION ELEVATION2
CUT AND CAP
ABOVE
CEILING IN
PREPARATION
FOR FUTURE
CONNECTION
REMOVE PIPE
SUPPORT
DEMOLISH RISER AND
SLEEVE. RE-ROUTE TO WALL
AREA NEXT TO WINDOW. (SEE
P101 FOR LOCATION)
CUT AND CAP PIPE
ABOVE CEILING. SEE
P101 FOR
RECONNECTION.
CEILING
WALL
EXISTING
WINDOW
EXISTING FILE
CABINET TO BE
RELOCATED BY
GOVERNMENT
EXISTING PIPE
EXISTING FILE
CABINET REPAIR SLAB WITH
CONCRETE AND
MATCH EXISTING
CARPET
Juan L Rodriguez
Digitally signed by Juan L Rodriguez DN: CN=Juan L Rodriguez, dnQualifier=A01410C0000017D390FBB550001FB2C, O=CIRI DEVELOPMENT CORPORATION DBA NORTH
WIND GROUP, C=US
Location: NorthWind, Knoxville TN Reason: I am approving this document
Date: 2022.10.21 09:13:18-04'00'
BF
P
BFP
BFP
P101
SCALE: 3/8" : 1'-0"
BLDG 410C - ROOM 100 PLAN1
EXISTING
WINDOW CONTINUE TO
BUILDING SUPPLY
14" X 24"
ACCESS PANEL
30" X 30"
ACCESS PANEL
BFP-1
BFP-1
ISOLATION
VALVE
ST-1
WITH UNIONS
TEE
SUPPLY RISER
(RE-ROUTED FROM DEMOLITION) TO YARD HYDRANTS
SCALE: 1" : 1'-0"
BLDG 410C - ROOM 100 ELEVATION2
EXISTING WALL
CEILING
FINISHED FLOOR
ELEVATION 12
" M
IN
SCALE: 1 1/2" : 1'-0"
BLDG 430 - ROOM 101 ELEVATION4
P101
PLUMBING CHASE
SEE ARCHITECTURAL
DRAWINGS
24" X 24"
ACCESS PANEL
TO YARD HYDRANTS
SUPPLY RISER
BFP-2 UNION
ISOLATION
VALVE
BACKFLOW PREVENTER SCHEDULE
SYMBOL NAME DESCRIPTION QTY MODEL #
BFP-1 WATTS 2" DOUBLE CHECK VALVE, SERIES LF-007 2 LF007M1QT
BFP-2 WATTS 2" DOUBLE CHECK VALVE WITH STRAINER, SERIES LF-007 1 LF007M1QT-S
ST-1 WATTS 2" WYE PATTERN LEAD FREE CAST COPPER SILICON ALLOY STRAINER 1 LF777
SCALE: 3/8" : 1'-0"
BLDG 430 - ROOM 101 PLAN3
GENERAL NOTES:
1. ALL PIPES ARE 2"
2. ENGRAVED, LAMINATED PHENOLIC NAMEPLATES
(BLACK LETTERS ON A WHITE BACKGROUND).
NAMEPLATES ARE TO HAVE AT LEAST 1/2-INCH-
(6-MM-) HIGH LETTERING. NAMEPLATES TO INCLUDE
BFP TAG AND TO BE INSTALLED ON BOTH THE BFP
AND THE ACCESS PANEL
3. POSITION ACCESS PANELS TO ENABLE SERVICING
AND MAINTENANCE OF THE BACKFLOW
PREVENTERS AND STRAINERS.
4. ACCESS PANELS SHALL HAVE HINGES AND
NON-KEYED CLOSURES.
ROUTE ABOVE CEILING
TIE INTO
EXISTING
PIPE ABOVE
CEILING
FINISHED FLOOR
ELEVATION
PIPE SLEEVE SEE DETAIL 1/P501 (TYP)
PIPE SLEEVE (TYP)
EXTENDED WALL SECTION
PIPE SLEEVE SEE DETAIL 1/P501 (TYP)
PIPE SLEEVE
TIE INTO EXISTING
BELOW GRADE
PIPE INSULATION
INSTALLED BETWEEN
BACKFLOW AND
EXTERIOR WALL
PIPE INSULATION
INSTALLED BETWEEN
BACKFLOW AND
EXTERIOR WALL
8" X 16"
ACCESS PANEL
Juan L Rodriguez
Digitally signed by Juan L Rodriguez DN: CN=Juan L Rodriguez, dnQualifier=A01410C0000017D390FBB550001FB2C, O=CIRI DEVELOPMENT CORPORATION DBA
NORTH WIND GROUP, C=US
Location: NorthWind, Knoxville TN Reason: I am approving this document
Date: 2022.10.21 09:10:48-04'00'
TOP OF SLAB
PIPE PER PLANFILL ANNULAR SPACE WITH
NON-SHRINK GROUT FOR
WATER PROOF SEAL
STANDARD WEIGHT HOT
DIPPED GALVANIZED
STEEL PIPE SLEEVE.
SIZE AT LEAST 2
PIPE SIZES LARGER
THAN UTILITY O.D.
SCALE: NTS
TYPICAL PIPE PENETRATION THROUGH SLAB1
Juan L Rodriguez
Digitally signed by Juan L Rodriguez DN: CN=Juan L Rodriguez, dnQualifier=A01410C0000017D390FBB550001FB2C, O=CIRI DEVELOPMENT CORPORATION DBA
NORTH WIND GROUP, C=US
Location: NorthWind, Knoxville TN Reason: I am approving this document
Date: 2022.10.21 09:09:04-04'00'