A06_Drawings.pdf

PDF 1 MB Posted

Attached to
LIGHTING PANEL REPLACEMENT Federal contract opportunity
Solicitation number
140L3924Q0146
Issued by
Department of the Interior Bureau of Land Management Nevada Region

About this file

This document appears to be a set of drawings related to a federal contract opportunity for LIGHTING PANEL REPLACEMENT. The key details are:

The federal contract opportunity has a Solicitation Number of 140L3924Q0146 and is posted by the Department of the Interior Bureau of Land Management Nevada Region. The drawings provide details on the relay panels to be replaced, including the circuit controls, schedules, and related electrical information. While the document does not directly specify the required products or services, it appears to be providing technical details in support of the contract opportunity. No additional details on response dates, award information, or set asides are provided in this document.

View the file

Other files for this federal contract opportunity

Other files attached to LIGHTING PANEL REPLACEMENT, newest first.
File Type Posted
Sol_140L3924Q0146.pdf PDF
RFQ_Provisions.docx DOCX document
A04_SOW.doc DOC document
A06_Panel_Information.pdf PDF
Bid_Sheet.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

H

JO

B S E 1.

d w g

:1 :1

P M rg ri m es

MooreM Text Box 226 233 dwelch Callout

RELAY PANEL RP1 TO BE REPLACED

dwelch Callout

PANEL LOCATION(SEE BELOW FOR DETAILS)

JO

B S E .d w g

:1 :4

P M rg ri m es

RP2 RELAY PANEL SCHEDULE

RELAY CIRCUIT CONTROLS NOTES:

1 L143 TC, Sc TRACK LTG. A/V ROOM 2 L145 TC, Sd TRACK LTG. A/V ROOM 3 L147 TC, Se TRACK LTG. A/V ROOM 4 L149 TC, Sh TRACK LTG. MULTIPURPOSE 5 L151 TC, Si TRACK LTG. MULTIPURPOSE 6 L153 TC, Sj TRACK LTG. MULTIPURPOSE

7 L155 TC, SL LOBBY LIGHTING

8 L157 TC, LOCAL SWITCH REST RMS., RETAIL OFFICE

9 L159 TC, LOCAL SWITCH A/V, MULTIPUROPSE DN. LTS.

10 L161 TC, LOCAL SWITCH OPEN OFFICE

11 L163 TC, LOCAL SWITCH LIBRARY

12 L165 TC, LOCAL SWITCH MECHANICAL, EQUIP. ROOMS

13 L164 (PART) TC, SE CANOPY UP LTG.

14 L164 (PART) TC, SE PATIO UP LTG.

15 L164 (PART) PE CELL EXTERIOR DN. LTS.

16 L176 TC, SE SITE ENTRY LTG.

17 L178 (PART) TC, SE PLAZA WALL LTS.

18 L178 (PART) TC, SE PLAZA WALL LTS.

19 L180 TC, SE PLAZA BOLLARDS

20 L177,79 (2POLE)TC FLAGPOLE LTG.

21 L182,84 (2POLE)TC, SE PARKING LOT LTG.

22 SPARE

23 SPARE

24 SPARE

25 SPARE

26 SPARE

27 SPARE

28 SPARE

29 SPARE

30 SPARE

31 SPACE

32 SPACE

33 SPACE

34 SPACE

35 SPACE

36 SPACE

37 SPACE

38 SPACE

39 SPACE

40 SPACE

41 SPACE

42 SPACE

43 SPACE

44 SPACE

45 SPACE

46 SPACE

47 SPACE

48 SPACE

L181 CONTROL POWER

RP1 RELAY PANEL SCHEDULE

RELAY CIRCUIT CONTROLS NOTES:

1 L11 TC, Sn TRACK LTG. NORTH EXHIBIT 2 L13 TC, Sn TRACK LTG. NORTH EXHIBIT 3 L15 TC, Sn TRACK LTG. NORTH EXHIBIT 4 L17 TC, Sn TRACK LTG. NORTH EXHIBIT 5 L19 TC, Sn TRACK LTG. NORTH EXHIBIT 6 L111 TC, Sn TRACK LTG. NORTH EXHIBIT 7 L113 TC, Sn TRACK LTG. NORTH EXHIBIT 8 L115 TC, Sn TRACK LTG. NORTH EXHIBIT 9 L117 TC, Sn TRACK LTG. NORTH EXHIBIT 10 L119 TC, Sn TRACK LTG. NORTH EXHIBIT 11 L121 TC, Sn TRACK LTG. NORTH EXHIBIT 12 L123 TC, Sn TRACK LTG. NORTH EXHIBIT 13 L125 TC, Sn TRACK LTG. NORTH EXHIBIT 14 L127 TC, Sn TRACK LTG. NORTH EXHIBIT 15 L129 TC, Sn TRACK LTG. NORTH EXHIBIT 16 L131 TC, Sn TRACK LTG. NORTH EXHIBIT 17 L12 TC, Ss TRACK LTG. SOUTH EXHIBIT 18 L14 TC, Ss TRACK LTG. SOUTH EXHIBIT 19 L16 TC, Ss TRACK LTG. SOUTH EXHIBIT 20 L18 TC, Ss TRACK LTG. SOUTH EXHIBIT 21 L110 TC, Ss TRACK LTG. SOUTH EXHIBIT 22 L112 TC, Ss TRACK LTG. SOUTH EXHIBIT 23 L114 TC, Ss TRACK LTG. SOUTH EXHIBIT 24 L116 TC, Ss TRACK LTG. SOUTH EXHIBIT 25 L118 TC, Ss TRACK LTG. SOUTH EXHIBIT 26 L120 TC, Ss TRACK LTG. SOUTH EXHIBIT 27 L122 TC, Ss TRACK LTG. SOUTH EXHIBIT 28 L124 TC, Ss TRACK LTG. SOUTH EXHIBIT 29 L126 TC, Ss TRACK LTG. SOUTH EXHIBIT 30 L128 TC, Ss TRACK LTG. SOUTH EXHIBIT 31 L130 TC, Ss TRACK LTG. SOUTH EXHIBIT 32 L132 TC, Ss TRACK LTG. SOUTH EXHIBIT 33 L134 TC, Ss TRACK LTG. SOUTH EXHIBIT 34 L136 TC, Ss TRACK LTG. SOUTH EXHIBIT 35 L138 TC, Ss TRACK LTG. SOUTH EXHIBIT 36 L140 TC, Ss TRACK LTG. SOUTH EXHIBIT 37 L142 TC, Ss TRACK LTG. SOUTH EXHIBIT 38 L144 TC, Sw TRACK LTG. WEST EXHIBIT 39 L146 TC, Sw TRACK LTG. WEST EXHIBIT 40 L148 TC, Sw TRACK LTG. WEST EXHIBIT 41 L150 TC, Sw TRACK LTG. WEST EXHIBIT 42 L152 TC, Sw TRACK LTG. WEST EXHIBIT 43 L154 TC, Sr TRACK LTG. RETAIL 44 L156 TC, Sr TRACK LTG. RETAIL 45 L158 TC, Sr TRACK LTG. RETAIL 46 L160 TC, Sr TRACK LTG. RETAIL 47 L162 TC, Sr TRACK LTG., DN. LTS. RETAIL

48 SPARE

L181 CONTROL POWER

KEY CIRCUIT NUMBER RELAY NUMBER TRACK LENGTH

1 L11 RP11 25'

2 L13 RP12 25'

3 L15 RP13 12'

4 L17 RP14 16'

5 L19 RP15 24'

6 L111 RP16 24'

7 L113 RP17 24'

8 L115 RP18 16'

9 L117 RP19 25'

10 L119 RP110 25'

11 L121 RP111 24'

12 L123 RP112 24'

13 L125 RP113 24'

14 L127 RP114 24'

15 L129 RP115 16'

16 L131 RP116 12'

17 L12 RP117 22'

18 L14 RP118 22'

19 L16 RP119 20'

20 L18 RP120 16'

21 L110 RP121 16'

22 L112 RP122 16'

23 L114 RP123 12'

24 L116 RP124 20'

25 L118 RP125 20'

26 L120 RP126 25'

27 L122 RP127 20'

28 L124 RP128 25'

29 L126 RP129 20'

30 L128 RP130 16'

31 L130 RP131 16'

32 L132 RP132 16'

33 L134 RP133 16'

34 L136 RP134 24'

35 L138 RP135 24'

36 L140 RP136 22'

37 L142 RP137 22'

38 L144 RP138 20'

39 L146 RP139 20'

40 L148 RP140 16'

41 L150 RP141 16'

42 L152 RP142 16'

43 L154 RP143 12'

44 L156 RP144 18'6"

45 L158 RP145 12'

46 L160 RP146 18'6"

47 L162 RP147 8'

48 L143 RP21 16'

49 L145 RP22 16'

50 L147 RP23 16'

51 L149 RP24 16'

52 L151 RP25 16'

53 L153 RP26 16'

TRACK LIGHTING CIRCUITING SCHEDULE

MooreM Text Box 232 233

JO

B S E 1.

d w g

:1 :1

P M rg ri m es

NAME: MDC VOLTAGE: 120/208 V. TYPE: SWITCHGEAR FIXED MOLDED CASE BREAKER

3 PH MOUNTING: (SEE SPECIFICATIONS)

FED FROM: 4 W. ENCLOSURE FRONT: (SEE SPECIFICATIONS)

1200 AMP MAIN RATED @ 60 HZ NEUTRAL BUS: YES

N/A AMP MAIN LUGS GROUND BUS: YES ISOLATED GND: NO

1200 AMP BUS NOTE: 1.

COPPER BUSING 2.

100000 SYMMETRICAL RMS AMPS 3.

COMBINED PANEL SHORT CIRCUIT RATING 4.

CCT BREAKER BREAKER CCT

NOTE DESCRIPTION VA AMP / P CCT PH CCT AMP / P VA DESCRIPTION NOTE

PANEL M1 22100 400 1 A 2 175 13248 GHSP1

" 22100 B 13248 " 23200 3 C 3 13248

PANEL M2 10850 225 3 A 4 225 6400 PANEL P1

" 12360 B 6900 " " 11050 3 C 3 4900 "

PANEL L1SECT 1 31440 400 5 A 6 225 9576 PANEL P2

" 30434 B 9000 " " 30145 3 C 3 8750 "

TVSS 0 60 7 A 8 100 5800 WELL PUMP

0 B 5800 0 3 C 3 5800

SPACE 0 9 A 10 100 0 FUTURE PANEL S

0 B 0 0 3 C 3 0

SPACE 0 11 A 12 0 SPACE

0 B 0 0 3 C 3 0

NEC DEMAND LOAD SUMMARY

PANEL LOADING SUMMARY POWER DEMAND CALCULATED

LOAD TYPE PH A PH B PH C TOTAL kW kVA FACTOR LOAD INCANDESCENT 27.8 24.8 25.1 77.7 kVA INCANDESCENT 77.7 @ 100% = 77.7 @ 125% = 97.1 kVA FLUORESCENT 3.665 5.109 5.045 13.8 kVA FLUORESCENT 13.1 @ 95% = 13.8 @ 125% = 17.3 kVA RECEPTACLES 7.6 6.9 6.7 21.2 kVA RECEPTACLES MOTORS 51.7 51 50 152.7 kVA FIRST 10 kVA 9.5 @ 95% = 10 @ 100% = 10 kVA APPLIANCE 2.376 2 0.7 5.1 kVA REMAINDER 10.6 @ 95% = 11.2 @ 50% = 5.6 kVA HEAT 0 1.5 3 4.5 kVA MOTORS COMPUTER 0 0 0 0 kVA LARGEST 31.8 @ 80% = 39.7 @ 125% = 49.6 kVA MISC. 6.25 8.46 6.5 21.2 kVA REMAINDER 90.5 @ 80% = 113.1 @ 100% = 113.1 kVA OTHER 0 0 0 0 kVA APPLIANCES 4.1 @ 80% = 5.1 @ 100% = 5.1 kVA TOTAL 99 100 97 296 kVA HEAT 4.5 @ 100% = 4.5 @ 125% = 5.6 kVA

COMPUTER 0 @ 75% = 0 @ 100% = 0 kVA PHASE BALANCE (%) AB BC CA PF MISC. 18 @ 85% = 21.2 @ 100% = 21.2 kVA

99 97 98 88 OTHER 0 @ 95% = 0 @ 100% = 0 kVA 25 66.7 @ 90% = 74.1 @ 100% = 74.1 kVA

MIN PANEL AMPACITY 1108 AMPERES TOTAL 327 kW 370 kVA 399 kVA

UTILITY

% SPARE

80%

LOAD TYPE FACT

PointtoPoint * Feeder Summary

From To Phase Length Isc Avail # Runs C V(LL) Wire Isc Utility Xfmr to MDC 3 70 58,900 4 22736 208 350 42772 MDC to Panel L1 3 10 42,772 2 12843 208 3/0 37569 MDC to Panel M1 3 15 42772 2 12843 208 3/0 35415 MDC to Panel M2 3 20 42772 1 15082 208 4/0 29062 MDC to Panel P1 3 20 42772 1 15082 208 4/0 29062 MDC to Panel P2 3 20 42772 1 15082 208 4/0 29062 MDC to Panel S (Future) 3 275 42772 1 9317 208 1/0 3719

Short Circuit Summary MDC F E E D E R S C H E D U L E

KEY CONDUIT & CONDUCTORS REMARKS

[SEE NOTE 1]

30A2G 3/4" C 2#10, 1#10G 50A4G 1" C 4#6, 1#10G

70A2GM 3/4" C 2#8, 1#8G 2C W/G USE CABLE

90A4G 11/4" C 4#2, 1#8G 225A4G 21/2" C 4#4/0, 1#4G

350A3GM 2" C 3#2/0, 1#3G

400A4G 2 [ 2" C 4#3/0, 1#3G ] 1200A4 4 [ 21/2" C 4#350 ]

3/0G 3/4" C 1#3/0G 6G 3/4" C 1#6G 8G 3/4" C 1#8G

225A4IG 21/2" C 4#4/0, 1#4G, 1#4IG

SCHEDULE NOTES:

1. THIS FEEDER SCHEDULE IS BASED ON 60 DEGREE CENTIGRADE

(TYPE THW) WIRE AND TERMINATIONS FOR SIZES #14 TO #1,

AND 75 DEGREE CENTIGRADE (TYPE THHN) WIRE AND

TERMINATIONS FOR SIZES #1/0 AND LARGER.

UNLESS NOTED OTHERWISE, CONDUIT IS SIZED

BASED ON TYPE EMT CONDUIT. USE OF OTHER CONDUIT

TYPES REQUIRES EVALUATION OF CONDUIT SIZE.

MooreM Text Box 233 233

File details come from the government source that posted it. Updated .