26 05 00 - COMMON WORK RESULTS FOR ELECTRICAL
A. SCOPE OF WORK: FURNISH AND INSTALL ALL MATERIAL AND EQUIPMENT FOR AN EXTENSION TO THE
EXISTING ELECTRICAL SYSTEM AS INDICATED ON THE DRAWINGS AND IN THESE SPECIFICATIONS.
B. STANDARDS, CODES AND REGULATIONS: COMPLY WITH THE LATEST ADOPTED EDITION OF THE NATIONAL
ELECTRICAL CODE, INTERNATIONAL BUILDING CODE, AND INTERNATIONAL FIRE CODE INCLUDING ALL STATE AND LOCAL AMENDMENTS TO THESE CODES. COMPLY WITH THE LATEST PUBLISHED VERSION OF
THE NECA STANDARD OF INSTALLATION.
C. DRAWINGS: THE DRAWINGS ARE DIAGRAMMATIC, NOT NECESSARILY SHOWING ALL OFFSETS OR EXACT LOCATIONS OF FIXTURES, EQUIPMENT, ETC. UNLESS SPECIFICALLY DIMENSIONED. REVIEW THE DRAWINGS AND SPECIFICATIONS FOR EQUIPMENT FURNISHED BY OTHER CRAFTS BUT INSTALLED IN ACCORDANCE WITH THIS SECTION. BRING QUESTIONABLE OR OBSCURE ITEMS, APPARENT CONFLICTS BETWEEN PLANS AND SPECIFICATIONS, GOVERNING CODES OR UTILITIES REGULATIONS TO THE ATTENTION OF THE OWNER.
CODES, ORDINANCES, REGULATIONS, MANUFACTURER'S INSTRUCTIONS OR STANDARDS TAKE
PRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH THE DRAWINGS AND
SPECIFICATIONS.
D. RECORD DRAWINGS: MARK UP A CLEAN SET OF DRAWINGS AS THE WORK PROGRESSES TO SHOW THE DIMENSIONED LOCATION AND ROUTING OF ALL ELECTRICAL WORK WHICH WILL BECOME PERMANENTLY
CONCEALED. SHOW ROUTING OF WORK IN PERMANENTLY CONCEALED BLIND SPACES WITHIN THE
BUILDING. SHOW COMPLETE ROUTING AND SIZING OF ANY SIGNIFICANT REVISIONS TO THE SYSTEMS
SHOWN.
E. WORKMANSHIP: INSTALLATION OF ALL WORK SHALL BE MADE SO THAT ITS SEVERAL COMPONENT PARTS SHALL FUNCTION AS A WORKABLE SYSTEM COMPLETE WITH ALL ACCESSORIES NECESSARY FOR ITS
OPERATION. ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS, INSTRUCTIONS AND/OR INSTALLATION DRAWINGS AND IN
ACCORDANCE WITH NECA STANDARDS. MATERIALS AND EQUIPMENT SHALL BE NEW AND SHALL CONFORM
WITH APPLICABLE INDUSTRY STANDARDS, NEMA STANDARDS AND UNDERWRITERS LABORATORIES
STANDARDS WHERE APPLICABLE.
F. WARRANTY: THE CONTRACTOR SHALL GUARANTEE ALL WORK EXECUTED UNDER THIS CONTRACT TO BE FREE FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM BENEFICIAL OCCUPANCY. ANY FAULTY MATERIALS OR WORKMANSHIP SHALL BE REPAIRED OR REPLACED TO THE
SATISFACTION OF THE OWNER DURING THE GUARANTEE PERIOD.
G. PERMITS: SECURE AND PAY FOR ALL FEES, PERMITS, ETC. REQUIRED BY LOCAL AND STATE AGENCIES AND
ALL LOCAL UTILITY COMPANIES.
H. REFERENCE SYMBOLS: THE ELECTRICAL "LEGEND" ON THE DRAWINGS IS A STANDARDIZED VERSION, AND ALL SYMBOLS SHOWN MAY NOT BE USED. USE THE "LEGEND" AS A REFERENCE FOR THE SYMBOLS USED
ON THE DRAWINGS.
I. PENETRATION OF FIRE BARRIERS: ALL ELECTRICAL PENETRATIONS THROUGH FIRE RATED BARRIERS
SHALL BE SEALED IN ACCORDANCE WITH NEC ARTICLE 300.21 AND THE FOLLOWING:
1. ALL HOLES OR VOIDS CREATED TO EXTEND ELECTRICAL SYSTEMS THROUGH FIRE RATED FLOORS, WALLS OR CEILING SHALL BE SEALED WITH AN ASBESTOS-FREE INTUMESCENT FIRE STOPPING
MATERIAL CAPABLE OF EXPANDING 8 TO 10 TIMES WHEN EXPOSED TO TEMPERATURES 250 DEGREES F
OR HIGHER.
2. MATERIALS SHALL BE SUITABLE FOR THE FIRE STOPPING OF PENETRATIONS MADE BY STEEL, GLASS, PLASTIC AND SHALL BE CAPABLE OF MAINTAINING AN EFFECTIVE BARRIER AGAINST FLAME, SMOKE AND GASES IN COMPLIANCE WITH THE REQUIREMENTS OF ASTM E814, UL 1479 AND THE UL FIRE RESISTANCE
DIRECTORY REQUIREMENTS FOR THROUGH-PENETRATION FIRESTOP DEVICES (XHCR).
3. THE RATING OF THE FIRE STOPS SHALL BE THE SAME AS THE TIME-RATED FLOOR, WALL OR CEILING
ASSEMBLY.
4. INSTALL FIRE STOPPING MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
26 05 05 - SELECTIVE DEMOLITION FOR ELECTRICAL
A. DEMOLITION DRAWINGS ARE BASED ON AS-BUILTS AND NON-DESTRUCTIVE FIELD OBSERVATION. REPORT
DISCREPANCIES TO OWNER BEFORE DISTURBING THE EXISTING INSTALLATION. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN ALL EXISTING ELECTRICAL SYSTEMS (TELEPHONE, FIRE ALARM, LIGHTING, ELECTRICAL SERVICE, ETC.) IN SERVICE DURING CONSTRUCTION. DISABLE SYSTEMS ONLY TO
MAKE SWITCHOVERS AND CONNECTIONS.
B. OBTAIN PERMISSION FROM OWNER AT LEAST 24 HOURS BEFORE PARTIALLY OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION AND MAKE TEMPORARY CONNECTIONS TO MAINTAIN SERVICE IN AREAS ADJACENT TO WORK AREA. WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR
CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS.
C. REMOVE, RELOCATE AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION.
REMOVE ABANDONED WIRING TO SOURCE OF SUPPLY. REMOVE EXPOSED ABANDONED CONDUIT,
INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. WHERE ABANDONED CONDUIT ENTERS EXISTING SURFACES TO REMAIN, CUT CONDUIT FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES. DISCONNECT ABANDONED OUTLETS AND REMOVE DEVICES. REMOVE ABANDONED OUTLETS IF CONDUIT SERVICING THEM IS ABANDONED AND REMOVED. PROVIDE BLANK COVER FOR ABANDONED
OUTLETS WHICH ARE NOT REMOVED.
D. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS BEEN REMOVED. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN
ACTIVE.
E. CONTRACTOR TO FIELD VERIFY CONDUITS AND ELECTRICAL ITEMS IN WALLS TO BE DEMOLISHED PRIOR TO START OF WORK. DEMOLISH CONDUITS, BOXES, DEVICES, EQUIPMENT, ETC. IN WALLS THAT ARE SCHEDULED FOR DEMOLITION. WHERE CONDUITS PASS THROUGH THE WALLS OR CIRCUITS ARE SHARED WITH EQUIPMENT THAT IS EXISTING TO REMAIN, PROVIDE ALL WORK NECESSARY (INCLUDING EXTENDING AND RE-ROUTING CONDUITS) TO MAINTAIN ACCESS AND PROVIDE ELECTRICAL CONTINUITY TO EXISTING
SYSTEMS AND CIRCUITRY.
26 05 19 - WIRE AND CABLE
A. SUBMITTALS: NONE REQUIRED FOR THIS SECTION.
B. MATERIALS:
1. ALL CONDUCTORS SHALL BE COPPER WITH TYPE XHHW, THWN, THW OR THHN INSULATION. MINIMUM BRANCH CIRCUIT CONDUCTOR SIZE SHALL BE #12 AWG. MINIMUM CONTROL CIRCUIT CONDUCTOR SIZE
SHALL BE #18 AWG.
2. CONTROL CIRCUITS SHALL BE COPPER, STRANDED CONDUCTOR, 600V INSULATION, THHN/THWN, MINIMUM SIZE 18 AWG.
3. TYPE MC CABLE: SOLID COPPER CONDUCTOR, 600 VOLT THERMOPLASTIC INSULATION, RATED 90º C, INSULATED GREEN GROUNDING CONDUCTOR, AND GALVANIZED STEEL ARMOR OVER MYLAR.
C. INSTALLATION:
1. COLOR CODE WIRES BY LINE OR PHASE. COLOR CODE THE 120/240V CONDUCTORS BLACK, RED AND
WHITE.
2. DO NOT SHARE NEUTRAL CONDUCTORS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH
BRANCH CIRCUIT THAT REQUIRES A NEUTRAL.
3. USE PROPERLY SIZED INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR ALL
CONDUCTORS #8 AWG AND SMALLER. TERMINATE #6 AWG AND LARGER CONDUCTORS WITH CRIMP OR
COMPRESSION TYPE CONNECTORS INSTALLED WITH TOOL RECOMMENDED BY CONNECTION
MANUFACTURER AND INSULATE WITH PROPERLY SIZED 600 VOLT RATED HEAT SHRINK TUBING.
4. INSTALLATION SCHEDULE: BUILDING WIRE IN RACEWAYS AT ALL LOCATIONS UNLESS OTHERWISE NOTED. PROVIDE XHHW-2 FOR FEEDERS AND IN EXTERIOR LOCATIONS. TYPE MC CABLE MAY BE USED FOR BRANCH CIRCUIT WIRING IN DRY, INTERIOR LOCATIONS OTHER THAN HOMERUNS. HOMERUNS SHALL BE BUILDING WIRE IN RACEWAY. METAL CLAD CABLE USED FOR BRANCH CIRCUIT WIRING FROM A LIGHT SWITCH OR LIGHTING CONTROL STATION TO THE LIGHT FIXTURE SHALL INCLUDE A NEUTRAL
CONDUCTOR.
26 05 26 - GROUNDING AND BONDING
A. SUBMITTALS: SUBMIT PRODUCT DATA FOR GROUND RODS.
B. MATERIAL: SOLID GROUND RODS: COPPER-ENCASED STEEL, 3/4 INCH DIAMETER, MINIMUM LENGTH 10
FEET.
C. INSTALLATION:
1. PROVIDE A SEPARATE, INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL NEW BRANCH CIRCUITS
AND FEEDERS. TERMINATE EACH END ON A GROUNDING LUG, BUS, OR BUSHING.
2. PROVIDE GROUNDING FOR NEW BUILDING FEED PER NEC 250.32
3. MECHANICAL CONNECTORS: NON-REVERSIBLE CRIMP TYPE LUGS ONLY. USE FACTORY MADE
COMPRESSION LUG FOR ALL TERMINATIONS. FOR TELECOMMUNICATION SYSTEMS USE COPPER,
COPPER ALLOY, OR TIN-PLATED COPPER, NON-REVERSIBLE LONG BARREL CRIMP TYPE BOLT LUGS
WITH TWO BOLT TONGUES FOR 6 AWG OR LARGER CONDUCTORS. CRIMP TYPE ONE HOLE FOR
CONDUCTORS SMALLER THAN 6 AWG.
4. BOND TOGETHER SYSTEM NEUTRALS, SERVICE EQUIPMENT ENCLOSURES, EXPOSED NON-CURRENT
CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT, METAL RACEWAY SYSTEMS, GROUNDING
CONDUCTOR IN RACEWAYS AND CABLES, RECEPTACLE GROUND CONNECTORS, AND PLUMBING AND
FUEL SYSTEMS
26 05 29 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
A. SUBMITTALS: NONE REQUIRED FOR THIS SECTION.
B. MATERIAL: SUPPORT CHANNEL SHALL BE GALVANIZED OR PAINTED STEEL. HARDWARE SHALL BE
CORROSION RESISTANT.
C. INSTALLATION: EQUIPMENT WEIGHING MORE THAN 50 POUNDS SHALL BE ADEQUATELY ANCHORED TO THE
BUILDING STRUCTURE TO RESIST LATERAL EARTHQUAKE FORCES.
26 05 33 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
A. SUBMITTALS: NONE REQUIRED FOR THIS SECTION.
B. MATERIALS
1. RIGID STEEL CONDUIT: ANSI C80.1. FITTINGS AND CONDUIT BODIES: ANSI/NEMA FB 1; THREADED TYPE
WITH INSULATED THROAT BUSHINGS, MATERIAL TO MATCH CONDUIT.
2. INTERMEDIATE METAL CONDUIT (IMC): GALVANIZED STEEL. FITTINGS AND CONDUIT BODIES: ANSI/NEMA
FB 1; USE FITTINGS AND CONDUIT BODIES SPECIFIED ABOVE FOR RIGID STEEL CONDUIT.
3. ELECTRICAL METALLIC TUBING CONDUIT (EMT): ANSI C80.3. GALVANIZED TUBING. FITTINGS AND CONDUIT BODIES: ANSI/NEMA FB 1; STEEL OR MALLEABLE IRON, COMPRESSION TYPE OR SET SCREW FITTINGS WITH INSULATED THROAT BUSHINGS. DIE-CAST FITTINGS ARE NOT ACCEPTABLE. MAXIMUM
SIZE SHALL BE 2". PROVIDE FACTORY ELBOWS ON SIZES 1-1/2" AND LARGER.
4. FLEXIBLE METAL CONDUIT: FS WW-C-566; STEEL, FULL WALL OR REDUCED WALL THICKNESS. FITTINGS AND CONDUIT BODIES: ANSI/NEMA FB 1; STEEL OR MALLEABLE IRON WITH INSULATED THROAT
BUSHINGS. DIE CAST FITTINGS ARE NOT ACCEPTABLE.
5. LIQUIDTIGHT FLEXIBLE CONDUIT: FLEXIBLE METAL CONDUIT WITH PVC JACKET. FITTINGS AND CONDUIT BODIES: ANSI/NEMA FB 1; STEEL OR MALLEABLE IRON WITH INSULATED THROAT BUSHINGS. DIE CAST
FITTINGS ARE NOT ACCEPTABLE.
6. PROVIDE GALVANIZED OR CADMIUM PLATED, ONE PIECE PRESSED STEEL OUTLET BOXES 4 INCH
SQUARE OR OCTAGONAL, 1-1/2 INCHES DEEP MINIMUM SIZE FOR USE IN INTERIOR AREAS.
C. INSTALLATION:
1. INSTALL CONDUIT FOR ALL SYSTEMS UNLESS OTHERWISE NOTED, 1/2 INCH MINIMUM SIZE, EXCEPT
CONDUIT FOR SPECIAL SYSTEMS SHALL BE 3/4” MINIMUM AND BELOW GRADE SHALL BE MINIMUM 1”.
FEEDERS SHALL BE RIGID STEEL CONDUIT OR INTERMEDIATE METAL CONDUIT.
2. EXPOSED DRY INTERIOR LOCATIONS SHALL BE RIGID STEEL CONDUIT OR INTERMEDIATE METAL CONDUIT. ELECTRICAL METALLIC TUBING MAY BE USED EXPOSED WHEN INSTALLED ON THE CEILING, A MINIMUM OF TEN FEET ABOVE THE FLOOR OR WHERE NOT SUBJECT TO PHYSICAL DAMAGE. EMT MAY
ALSO BE USED FOR CONCEALED, DRY, INTERIOR LOCATIONS.
3. MOTOR AND EQUIPMENT CONNECTIONS SHALL BE SHORT EXTENSIONS OF FLEXIBLE METAL CONDUIT TO ALLOW FOR VIBRATION. LIQUIDTIGHT FLEXIBLE CONDUIT AND FITTINGS SHALL BE USED FOR THESE
CONNECTIONS IN DAMP OR WET LOCATIONS.
4. INSTALL RACEWAYS PER THE LATEST NECA (NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION)
STANDARDS.
5. PAINT ALL EXPOSED CONDUIT IN FINISHED AREAS TO MATCH SURFACE TO WHICH IT IS ATTACHED OR CROSSES. CLEAN GREASY OR DIRTY CONDUIT PRIOR TO PAINTING IN ACCORDANCE WITH PAINT
MANUFACTURER'S INSTRUCTIONS.
6. INSTALL RACEWAYS LEVEL AND SQUARE TO A TOLERANCE OF 1/8 INCH PER 10 FEET. ROUTE EXPOSED RACEWAYS AND RACEWAYS ABOVE ACCESSIBLE CEILINGS PARALLEL AND PERPENDICULAR TO WALLS, CEILING, STRUCTURAL MEMBERS AND ADJACENT PIPING.
7. PROVIDE OUTLET BOXES AS SHOWN ON THE DRAWINGS, AND AS REQUIRED FOR SPLICES, TAPS, WIRE
PULLING, EQUIPMENT CONNECTIONS, DEVICE INSTALLATION AND CODE COMPLIANCE.
8. DO NOT INSTALL BOXES BACK-TO-BACK IN WALLS. PROVIDE A MINIMUM 6 INCH SEPARATION FOR
MINIMUM SOUND TRANSMISSION.
9. USE MULTIPLE-GANG BOXES WHERE MORE THAN ONE DEVICE ARE MOUNTED TOGETHER; DO NOT USE
SECTIONAL BOXES.
10. SUPPORT BOXES INDEPENDENTLY OF CONDUIT.
11.COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS MOUNTED ABOVE COUNTERS,
BENCHES AND BACKSPLASHES.
26 05 53 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
A. SUBMITTALS: NONE REQUIRED FOR THIS SECTION.
B. MATERIALS:
1. NAMEPLATES: ENGRAVED THREE-LAYER LAMINATED PLASTIC, WHITE LETTERS ON A BLACK
BACKGROUND. NAMEPLATES SHALL BE PROVIDED TO IDENTIFY ALL ELECTRICAL DISTRIBUTION AND
CONTROL EQUIPMENT AND LOADS SERVED.
2. TAPE LABELS: ADHESIVE TAPE LABELS, WITH 3/16 INCH BOLD BLACK LETTERS ON CLEAR BACKGROUND
MADE USING DYMO RHINOPRO 5000 OR EQUAL LABEL PRINTER.
3. WIRE AND CABLE MARKERS: CLOTH MARKERS, SPLIT SLEEVE OR TUBING TYPE.
C. INSTALLATION:
1. CONDUITS: MARK ALL CONDUITS ENTERING OR LEAVING PANELBOARDS WITH INDELIBLE BLACK MAGIC MARKER WITH THE CIRCUIT NUMBERS OF THE CIRCUITS CONTAINED INSIDE. LABEL FEEDER CONDUITS
AND SPARE CONDUITS AT EACH END WITH SOURCE AND TERMINATION POINT.
2. JUNCTION BOXES: MARK ALL CIRCUIT NUMBERS OF WIRING ON ALL JUNCTION BOXES WITH SHEET STEEL COVERS. MARK WITH INDELIBLE BLACK MARKER. ON EXPOSED JUNCTION BOXES IN PUBLIC
AREAS, MARK ON INSIDE OF COVER.
3. WIRE IDENTIFICATION: PROVIDE WIRE MARKERS ON EACH CONDUCTOR IN PANELBOARD GUTTERS, PULL BOXES, OUTLET AND JUNCTION BOXES, AND AT LOAD CONNECTION. MARKERS SHALL BE LOCATED WITHIN ONE INCH OF EACH CABLE END, EXCEPT AT PANELBOARDS, WHERE MARKERS FOR BRANCH
CIRCUIT CONDUCTORS SHALL BE VISIBLE WITHOUT REMOVING PANEL DEADFRONT.
4. DEVICE PLATES: LABEL EACH RECEPTACLE DEVICE PLATE OR POINT OF CONNECTION DENOTING THE
PANELBOARD NAME AND CIRCUIT NUMBER. INSTALL LABEL ON THE TOP OF EACH PLATE.
26 21 00 - LOW-VOLTAGE ELECTRICAL SERVICE ENTRANCE
A. SUMMARY: THIS SECTION INCLUDES EQUIPMENT AND COORDINATION WITH LOCAL UTILITY TO OBTAIN
PERMANENT ELECTRICAL SERVICE FOR THE FACILITY. THIS WILL INVOLVE COORDINATING WITH THE UTILITY TO INSTALL A NEW UTILITY METER. SEE POWER ONE-LINE DIAGRAM FOR CONFIGURATION.
B. SUBMITTALS: SUBMIT PRODUCT DATA FOR APPROVAL.
C. MATERIALS:
1. METER: FURNISHED AND INSTALLED BY THE UTILITY COMPANY.
D. INSTALLATION:
1. MAKE ARRANGEMENTS WITH UTILITY COMPANY TO OBTAIN PERMANENT ELECTRIC SERVICE TO THE
PROJECT.
2. ALL SERVICE ENTRANCE EQUIPMENT SHALL HAVE SIGNAGE FOR ARC HAZARD INSTALLED. THE
MARKING SHALL BE LOCATED TO BE CLEARLY VISIBLE TO QUALIFIED PERSONNEL BEFORE
EXAMINATION, ADJUSTMENT, SERVICING OR MAINTENANCE OF THE EQUIPMENT. AT A MINIMUM THE
3-LINE SIGNAGE SHALL STATE THE FOLLOWING:
WARNING - ARC FLASH AND SHOCK HAZARD - APPROPRIATE PPE REQUIRED.
26 24 16 - PANELBOARDS
A. SUBMITTALS: SUBMIT PRODUCT DATA FOR APPROVAL.
B. MATERIAL:
1. MANUFACTURERS: SQUARE D, GE, EATON, OR EQUAL.
2. NEW BREAKERS IN EXISTING PANELS: NEMA AB 1; UL LISTED FOR USE IN THE PANEL, AMPERE RATING
AND NUMBER OF POLES AS INDICATED ON PLANS. AIC RATING SHALL MATCH THE LOWEST RATED
DEVICE IN THE PANEL.
C. INSTALLATION:
1. PROVIDE TYPED CIRCUIT DIRECTORIES FOR EACH PANELBOARD.
2. ALL PANELBOARDS SHALL HAVE SIGNAGE FOR ARC HAZARD INSTALLED. THE MARKING SHALL BE
LOCATED TO BE CLEARLY VISIBLE TO QUALIFIED PERSONNEL BEFORE EXAMINATION, ADJUSTMENT, SERVICING OR MAINTENANCE OF THE EQUIPMENT. AT A MINIMUM THE 3-LINE SIGNAGE SHALL STATE
THE FOLLOWING:
WARNING
ARC FLASH AND SHOCK HAZARD
APPROPRIATE PPE REQUIRED
3. INSTALL NEW BREAKER(S) IN EXISTING PANEL(S) AND TEST FOR PROPER OPERATION. UPDATE CIRCUIT
DIRECTORY TO REFLECT ALL CHANGES.
26 28 19 - ENCLOSED SWITCHES
A. SUBMITTALS: SUBMIT PRODUCT DATA FOR APPROVAL.
B. MATERIALS:
1. MANUFACTURERS: SQUARE D, GE, EATON, OR EQUAL
2. NONFUSIBLE SWITCH ASSEMBLIES: SAME CRITERIA AS ABOVE WITHOUT THE FUSES.
C. INSTALLATION
1. INSTALL DISCONNECT SWITCHES IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD LOCATE FINAL LOCATION OF DISCONNECTS TO ALLOW READY ACCESS AND NEC
110.26 WORKING CLEARANCES WHERE APPLICABLE.
2. ALL FUSED DISCONNECTS SHALL HAVE SIGNAGE FOR ARC HAZARD INSTALLED. THE MARKING SHALL BE LOCATED TO BE CLEARLY VISIBLE TO QUALIFIED PERSONNEL BEFORE EXAMINATION, ADJUSTMENT, SERVICING OR MAINTENANCE OF THE EQUIPMENT. AT A MINIMUM THE 3-LINE SIGNAGE SHALL STATE
THE FOLLOWING:
WARNING
ARC FLASH AND SHOCK HAZARD
APPROPRIATE PPE REQUIRED
05-05-2023
SHEET
PMIS/PKG NO.
DRAWING NO.
188281
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
BOAS-TAILOR HVAC SYSTEM UPGRADE
OF 11
319209B
KLONDIKE GOLD RUSH NATIONAL
HISTORIC PARK
5/5/23
LEGEND
E001
NVF
NVF
SB, PCC
ELECTRICAL
SPECIFICATIONS
Not in Contract
05-05-2023
SHEET
PMIS/PKG NO.
DRAWING NO.
188281
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
BOAS-TAILOR HVAC SYSTEM UPGRADE
OF 11
319209B
KLONDIKE GOLD RUSH NATIONAL
HISTORIC PARK
5/5/23
2 FIRST FLOOR ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"
GENERAL NOTES:
SHEET NOTES:
4 FIRST FLOOR ELECTRICAL REMODEL PLAN
1/4" = 1'-0"
3 SECOND FLOOR ELECTRICAL PLAN
1/4" = 1'-0"1 ELECTRICAL SITE PLAN
1/8" = 1'-0"
5 TRENCHING DETAIL
NONE
E101
NVF
NVF
SB, PCC
ELECTRICAL FLOOR LAN
Contractor shall schedule with the COR a review and pickup by NPS of the salvaged materials from the site
05-05-2023
SHEET
PMIS/PKG NO.
DRAWING NO.
188281
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
BOAS-TAILOR HVAC SYSTEM UPGRADE
OF 11
319209B
KLONDIKE GOLD RUSH NATIONAL
HISTORIC PARK
5/5/23
1 ADDITIVE ALTERNATE #1 - ELECTRICAL POWER ONE-LINE DEMOLITION PLAN
NOT TO SCALE
2 ADDITIVE ALTERNATE #1 - ELECTRICAL POWER ONE-LINE REMODEL PLAN
NOT TO SCALE
SHEET NOTES
NVF
NVF
SB, PCC
ADDITIVE ALTERNATE #1,
ONE-LINES & PANEL
SCHEDULES