This statement of work describes requirements for an intrusion detection system for the Fish and Wildlife Service Dulles Airport OLE Office in Dulles, Virginia. The system must include an Underwriters Laboratory listed panel with the capability for expansion and remote monitoring via analog, digital, ethernet, or cellular communications. Authorized panel manufacturers include Honeywell, Radionics/Bosch, and Digital Monitoring Products. The system must provide coverage of the storage room, offices, interior doors, and common areas through devices including a keypad, door contacts, panic buttons, and motion detectors. The contractor must provide training and the system must be capable of auto-arming daily. Installation is required by an unspecified deadline.

View the file

Other files for this federal contract opportunity

Other files attached to INSTRUSION DETECTION SYSTEM (IDS) - DULLES, VA, newest first.
File Type Posted
Sol_140F1G24Q0004_Amd_0003.pdf PDF
B08_Instructions_to_Offerors_and_Clauses_Update_1_19_24_0003.pdf PDF
Sol_140F1G24Q0004_Amd_0002.pdf PDF
B08_Instructions_to_Offerors_and_Clauses_0001.pdf PDF
Q_A_140F1G24Q0004_0001.pdf PDF
Sol_140F1G24Q0004_Amd_0001.pdf PDF
Sol_140F1G24Q0004.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INTRUSION DETECTION SYSTEM (IDS) – Dulles Airport OLE Office, Dulles, VA

This Intrusion Detection System (IDS) is specified for the Fish and Wildlife Service Dulles Airport OLE Office in Dulles, VA.

The contractor shall install, and make fully functional, an Underwriters Laboratory (UL) listed Intrusion Detection System (IDS) with panic buttons. The system hardware (panel) shall be of a manufacturer listed below (unless equivalent is approved) and shall have the capability of expansion with expansion modules, panel tamper notification, remote monitoring, and remote annunciation using standard analog, digital, ethernet, or approved cellular communications (backup only).

MONITORING SOLUTIONS:

The Government will provide additional connection/monitoring information to the vendor once the vendor has offered an approved panel.

▪ The Government may choose to contract with the U.S. Department of Homeland Security (DHS) - Federal Protective Service (FPS) for monitoring services. All systems monitored by DHS will require the completion of the DHS Mega Center Alarm Requirements (MAR) package (Instructions are associated with the MAR package).

▪ If the vendor is to provide monitoring services, the station will provide FWS-OEMPS an alarm zone data sheet obtained from the commercial monitoring company prior to acceptance of the system.

The Government may request the system be programmed to auto-arm on a daily basis (TBD).

The IDS control panel and associated power distribution hardware will be located on the wall within the storage closet in Suite 200. This area must be properly ventilated to ensure appropriate cooling of electronics. The system must have an analog phone connection (Plain Old Telephone System—POTS) or an ethernet connection as part of the panel board using one of the panels listed below. POTS connection is preferred for this location and POTS line is available. The installer must coordinate with FWS-Information Resources & Technology Management (IRTM) for porting access of any ethernet connection. There must be a keypad located on the panel door for maintenance purposes.

A battery backup shall be incorporated into the IDS panel that will allow for a minimum of 8 hours of backup power, from initial commercial power failure.

System Panels Authorized (POTS Connection)

A. Honeywell (Ademco) B. Radionics/Bosch C. Digital Monitoring Products Note: Proprietary panels (TYCO, ADT, etc.) will not be accepted due to the inability to provide adequate support.

System Panels Authorized (Ethernet Connection) A. Radionics/Bosch (9512 series)

a. Port Security 7700 B. Digital Monitoring Products (XR150 or XR550 series)

a. Port Security 2001 Note: Proprietary panels (TYCO, ADT, etc.) will not be accepted due to the inability to provide adequate support.

https://doimspp.sharepoint.com/sites/fws-FF09R00000/SiteAssets/SitePages/Office-of-Emergency-Management-and-Physical-Security/MegaCenter-Alarm-Requirements-2020.docx?web=1 https://doimspp.sharepoint.com/sites/fws-FF09R00000/SiteAssets/SitePages/Office-of-Emergency-Management-and-Physical-Security/MegaCenter-Alarm-Requirements-2020.docx?web=1

The doors/area as listed in table below, shall be alarmed using appropriate methods for the types of doors and areas. All wood, metal, or solid core doors are to be fitted with recessed magnetic contacts, where appropriate. If a recessed magnetic contact is not preferred or not the preferred method of installation by the contractor, then approval from the Contracting Officer must be granted, unless already identified below.

The contractor must provide a minimum of 2 hours of end-user training to facility staff and 4 hours of training to agency system administrators prior to facility acceptance.

DEVICE LOCATION DEVICE TYPE

Storage room inside Suite

PANEL - in enclosure shall be mounted to a ¾“ plywood backer board that is affixed to the room wall, and connected to an analog POTS line for transmission.

Inside Suite 200

Inside Office 211

On Panel enclosure (inside storage closet in suite 200)– for system programming & testing

KEYPAD (KP) - Alphanumeric or Touchscreen Keypad(s)- wall mounted.

6 Interior Doors – Offices 200 (2 doors), 210, 211, 214, 216

WIRED MAGNETIC CONTACT - Frame or mortise installed device (if aluminum frame door(s) are utilized here, surface mount contacts are allowed)

Inside Suite 200 and Office

PANIC BUTTON - United Security Products HUB2S Hold Up Button - Momentary, SPDT panic button - Wired/wireless (or equivalent).

Offices 200, 210, 211, 214, WIRED PHOTO INFRARED MOTION DETECTOR(S) –

Ceiling/wall mounted - Honeywell brand Hardwired PIR Motion Detector (or equivalent), Installed as per industry standards for coverage with no gaps in coverage. Devices should be placed on ceiling and spaced appropriately.

Suite 200 ALARM ANNUNCIATION HORN: Install a minimum of 96 Decibel alarm annunciation horn inside each building where IDS is present.

Devices:

1 Alarm panel with enclosure and battery backup 3 keypads 6 door contacts 2 panic buttons 5 motion detectors 1 alarm annunciation horn

File details come from the government source that posted it. Updated .