A04_ATTACHMENT_2_Scope_of_Repairs_by_Building_Number.pdf
PDF 246 KB Posted
- Attached to
- Fire Suppression System Inspection, Testing and Ma Federal contract opportunity
- Solicitation number
- 140P8123Q0056
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A04_ATTACHMENT_7_2021_Wet_Pipe_Inspection_Report.pdf | ||
| A04_ATTACHMENT_3_Fire_Alarm_Systems_List_for_ITM.pdf | ||
| Sol_140P8123Q0056.pdf | ||
| A04_ATTACHMENT_11_Statement_of_Work_-_Fires_Suppression_ITM.pdf | ||
| A04_ATTACHMENT_10_NPS_RM_58_Structural_Fire_Management.pdf | ||
| A04_ATTACHMENT_8_2021_Dry_Pipe_Inspection_Report.pdf | ||
| A04_ATTACHMENT_6_NPS_Standard_ITM_Forms.pdf | ||
| A04_ATTACHMENT_9_2021_Alarm_System_Inspection_Report.pdf | ||
| A04_ATTACHMENT_12_SCA_Wage_Rates_-_Inyo_County_12-27-2022.pdf | ||
| A04_ATTACHMENT_5_Residential_Sprinkler_Systems_List_for_ITM.pdf | ||
| A04_ATTACHMENT_4_Commercial_Sprinkler_Systems_List_for_ITM.pdf | ||
| A04_ATTACHMENT_1_Maps.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT 2 ‐ SCOPE OF REPAIRS BY BUILDING NUMBER
ALARM SYSTEM REPAIRS ‐ DEVA 330756
Bldg. # Bldg. Name description of deficiencies repair scope
CC54 Trade Shop Upgrade AES radio battery to new size as currently recommeded by the manufacturer Install 12V 10 Ah battery
CC345 Curatorial bldg Upgrade AES radio battery to new size as currently recommeded by the manufacturer Install 12V 10 Ah battery
FC270 Visitors center
Replace the batteries on the Booster Power Supply, the Fire Alarm Control Panel and the AES Radior that all failed the load test. Install(2) 12V 7 Ah batteries, (2) 12V 18 Ah batteries and (1) 12V 10 Ah battery
FC271 HQ
Upgrade AES radio battery to new size as currently recommeded by the manufacturer. Verify proper antenna installation and grounding. Re‐send signal
Install 12V 10 Ah battery. Verify proper antenna installation and grounding. Re‐send signal.Install 12V 10 Ah battery. Verify proper antenna installation and grounding. Re‐send signal.
SP351 Ranger Station Replace the batteries on the Fire Alarm Control Panel and the AES Radior that all failed the load test. Install (2) 12V 7 Ah batteries and (1) 12V 10 Ah battery
CC62 warehouse Replace the batteries on the Fire Alarm Control Panel and the AES Radior that all failed the load test. Install (2) 12V 7 Ah batteries and (1) 12V 10 Ah battery
CC316 MAINT. ADMIN
Upgrade AES radio battery to new size as currently recommeded by the manufacturer. Verify proper antenna installation and grounding. Re‐send signal Install 12V 10 Ah battery. Verify proper antenna installation and grounding. Re‐send signal.
CC348 AUTO SHOP
Upgrade AES radio battery to new size as currently recommeded by the manufacturer Install 12V 10 Ah battery
CC350 International Hall
Upgrade AES radio battery to new size as currently recommeded by the manufacturer. Verify proper antenna installation and grounding. Re‐send signal Install 12V 10 Ah battery. Verify proper antenna installation and grounding. Re‐send signal.
Dorms
Upgrade AES radio battery to new size as currently recommeded by the manufacturer. Verify proper antenna installation and grounding. Re‐send signal
Install 12V 10 Ah batteryInstall 12V 10 Ah battery. Verify proper antenna installation and grounding. Re‐send signal.
ATTACHMENT 2 - SCOPE OF REPAIRS BY BUILDING NUMBER
NON‐RESIDENTIAL SPRINKLER SYSTEM REPAIRS ‐ DEVA 330756
Bldg. # Bldg. Name description of deficiencies repair scope
CCQ354 Salt Pan 4" Butterfly Valve is Broken Replace Supply Side Butterfly Valve CC54 Trades Shop OS&Y is Corroded and Leaking Replace OS&Y SC5 Gas House) Air Compressor Failed Replace Air Compressor SC5 Gas House) 1/2" Check is not Closing. Replace 1/2" Check Valve SC2 Annex 1/2" Check is not Closing. Replace 1/2" Check Valve FC271 HQ OS&Y Tamper Has Rotted Off Replace Tamper ‐ A&D Tech FC270 Visitor's Center Excessive Water Pressure Add Riser Pressure Relief Valve FC270 Visitor's Center Replace 7 heads at hard lid Replace 7 heads utilizing new NPS‐installed access points
ATTACHMENT 2 - SCOPE OF REPAIRS BY BUILDING NUMBER
RESIDENTIAL SPRINKLER SYSTEM REPAIRS ‐ DEVA 330756
Bldg. # Bldg. Name description of deficiencies repair scope
CQ328B SkyLine Riser is Corroded Rebuild Riser CQ329 SkyLine Bell Failed Replace Bell ‐ A&D Tech CCQ330 SkyLine Riser is Corroded, Flow Switch Siezed Rebuild Riser CCQ340 Coyote Loop Drain is Disassembled Reassemble Drain SPQ332 Dunes View Control Valve Siezed, HSW Head Siezed Rebuild Riser, Replace 1" Control Valve and Siezed Head in Master Bedroom