FB-0751 FB-1001 FB-1251 FB-1501 FB-1751 FB-2001

WATER

GALLON CAPACITY 73 77 87 94 106 111

HEATING SURFACE (SQ. FT.) 87 114.7 140.5 162.3 186 197.8

INLET WATER CONNECTION 3" Flanged 3" Flanged 3" Flanged 4" Flanged 4" Flanged 4" Flanged OUTLET WATER CONNECTION 3" Flanged 3" Flanged 3" Flanged 4" Flanged 4" Flanged 4" Flanged

DRAIN 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2

MAXIMUM FLOW RATE (GPM) 350 350 350 350 350 350

ABSOLUTE MINIMUM FLOW RATE (GPM) 18 18 18 25 25 25

20°F ΔT WATER FLOW (GPM) 72 96 120 144 168 192

HEAD LOSS (FT. OF HD.) 4.8 8.3 9.2 12.3 13.8 14.5

40°F ΔT WATER FLOW (GPM) 36 48 60 72 84 96

HEAD LOSS (FT. OF HD.) 3.0 6.0 6.0 7.3 8.1 8.1

MAX. WORKING PRESSURE (PSI) 160 160 160 160 160 160

# OF RELIEF VALVES 1 1 1 1 1 1

RELIEF VALVE SIZE 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2

RELIEF VALVE RATING (MBH) 1,954 1,954 1,954 1,954 1,954 3,075

RELIEF VALVE PRESSURE RATING (PSI) 50 50 50 50 50 50

GAS

BTU/HR INPUT 750,000 999,000 1,250,000 1,500,000 1,750,000 1,999,000

BTU/HR OUTPUT (HIGH FIRE) 722,000 961,000 1,203,000 1,443,000 1,684,000 1,923,000

BTU/HR OUTPUT (LOW FIRE) 48,100 48,100 60,150 57,720 67,360 76,920

HORSE POWER (INPUT) 22 30 37 45 52 60

INLET CONNECTION 1 1/4 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2

MAX. INLET PRESSURE, NAT 14" w.c 14" w.c 14" w.c 14" w.c 14" w.c 14" w.c MIN. INLET PRESSURE, NAT 4" w.c. 4" w.c. 4" w.c. 4" w.c. 4" w.c. 4" w.c.

MAX. INLET PRESSURE, LP 14" w.c 14" w.c 14" w.c 14" w.c 14" w.c 14" w.c MIN. INLET PRESSURE, LP 8" w.c. 8" w.c. 8" w.c. 8" w.c. 8" w.c. 8" w.c.

ELECTRICAL *

VOLTAGE/HEATER (VAC) 120V/1PH/60Hz 120V/1PH/60Hz 120V/1PH/60Hz 120V/1PH/60Hz 120V/1PH/60Hz 120V/1PH/60Hz

VOLTAGE/CONTROL (VAC) 24 24 24 24 24 24

TOTAL AMPS (FLA) 5 6 7 10 10 13

MINIMUM CIRCUIT AMPS (MCA) 6 8 9 13 13 16

# OF ELECTRICAL CONNECTIONS 1 1 1 1 1 1

DIMENSIONS

HEIGHT 78 78 78 78 78 78

WIDTH 30 30 30 30 30 30

DEPTH 57 5/8 57 5/8 57 3/4 68 68 68

SHIPPING WEIGHT (lbs.) 1,560 1,596 1,648 1,961 2,017 2,087 OPERATING WEIGHT (lbs.) 1,768 1,838 1,975 2,307 2,458 2,570

SERVICE CLEARANCES (RECOMMENDED)

FRONT 30 30 30 30 30 30

REAR 24 24 24 24 24 24

RIGHT SIDE 24 24 24 24 24 24

LEFT SIDE 24 24 24 24 24 24

TOP 24 24 24 24 24 24

DIRECT VENTING

VENT SIZE 6 6 8 8 8 8

AIR INLET SIZE 6 6 6 8 8 8

VENT CATEGORY II or IV II or IV II or IV II or IV II or IV II or IV VENT MATERIAL SS, CPVC, PVC, Polypro SS, CPVC, PVC, Polypro SS, CPVC, PVC, Polypro SS, CPVC, PVC, Polypro SS, CPVC, PVC, Polypro SS, CPVC, PVC, Polypro

Unless otherwise specified dimensions are in inches.

FBNT-PS-07 (Replaces FBNT-PS-06) 07/20 - Printed in U.S.A.

Lochinvar LLC • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000 www.Lochinvar.com

* Electrical - For alternate voltages and amp draws, please consult the factory or the installation and operation manual.

CREST BOILER PRODUCT SUMMARY

(FB) 750,000 - 2,000,000 BTU/HR

http://www.lochinvar.com/ http://www.lochinvar.com/ http://www.lochinvar.com/ http://www.lochinvar.com/ http://www.lochinvar.com/ http://www.lochinvar.com/ http://www.lochinvar.com/ KWBarnes Rectangle

Table 1

File details come from the government source that posted it. Updated .