Attachment III- VendorQuestions_70RCSA20Q00000041.pdf

PDF 415 KB Posted

Attached to
CCTV Equipment and Installation Services - DHS/CISA/CSD Federal contract opportunity
Solicitation number
70RCSA20Q00000041
Issued by
Department of Homeland Security Office of Procurement Operations

View the file

Other files for this federal contract opportunity

Other files attached to CCTV Equipment and Installation Services - DHS/CISA/CSD, newest first.
File Type Posted
VendorQuestions_70RCSA20Q00000041_070920.pdf PDF
VendorQuestions_70RCSA20Q00000041_070120.pdf PDF
Attachment I - SOW_70RCSA20Q00000041_Updated060320.pdf PDF
Attachment I - SOW_70RCSA20Q00000041.pdf PDF
Attachment II - Clauses_70RCSA20Q00000041.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question Question Government Response

Can you provide some additional information about the VideoNEXT Platform. Is it a hardware product or a cloud VMS product?

VideoNEXT is a cloud-based system.

2 Is this a new requirement. Is there a incumbument or prior contract?

This is a new requirement. There is no prior incumbent or contract that performed this requirement.

3 Are Scaled Drawings available, if so please post. Due to OPSEC Requirements, we cannot provide drawings of the office locations.

4 Are Ceilings Suspended? Or Hard Lid? It is a mix of both, depending on the specific location.

5 Are there existing Cable Trays for wiring above ceilings? No, but conduit available.

6 Can Existing Wiring be utilized? Depends on location. There is no existing wiring on Floor 3, 4, and 5.

7 Is a “UPS” required? If so, What Time/Power Duration is required? Typically yes for 2 hours. But would need to confirm with Physical Security Services.

8 Are “Or Equal” Equipment substitutions allowed?

Per the SOW, CCTV equipment with AXIS brand name (or equal) that is compatible with the VideoNEXT system and meets all the restrictions and guidance outlined in the SOW/RFQ are allowed.

9 Is “Plenum Wire” acceptable? Depends on the location.

Is “After Hours Access” for said work, available to contractor at no add’l cost to the Gov’t?

Not at this time, but can be situational if necessary. All contractors would require Federal Personnel to act as Security Escorts while work is performed onsite, which would require additional Federal employee schedule coordination if done outside typical working hours.

11 What is the height of Exterior Cameras? (If any) Cameras are between 8-10ft. Garage height is currently unknown.

12 Please provide a list of equipment to be installed.

Please see Section 2.0 of the SOW (Attachment I - AMD 0001) for a complete list of equipment requirements. Please note, the Section 2 Equipment List requirements have been updated under AMD 0001 of the SOW.

13 Are there any abilities for a brief on-site visit to provide more accurate pricing?

Unfortunately due to the COVID-19 situation, we are unable to offer site visits for this requirement at this time.

14 Please provide/post other “Q&A” requests. All submitted questions and Government responses are captured in this attachment.

15 Are you able to extend the submission deadline.

The Government is extending the submission deadline to Thursday June 11th, 2020 at

11AM EST.