7-ROSE CREEK ES 100% CD combined.pdf

PDF 3 MB Posted

Attached to
IFB - Rose Creek Elementary make-Up-Air Replacement State and local contract opportunity
Solicitation number
26DB03
Issued by
Utah

About this file

This file comprises the complete construction design documents for the Make-Up-Air Replacement project at Rose Creek Elementary School in Riverton, Utah, issued by Jordan School District in January 2026. The project involves replacing the kitchen HVAC system at 12812 South 3600 West, Riverton, Utah 84065, with mechanical and electrical upgrades designed by Olsen & Peterson Consulting Engineers and Resolut Group. The scope includes installation of a new make-up air unit (MAU-1), with two alternates: Alternate 01 features a rooftop packaged unit (RT-1) with natural gas heating, while Alternate 02 specifies a wall-mounted mini-split air conditioning system (AC-1) with an outdoor condensing unit. The design documents include mechanical demolition and installation plans, plumbing connections for water and gas supply, electrical power distribution schedules, and detailed equipment specifications. Key mechanical equipment includes the ECON-AIR EA3-D500-24D make-up air unit rated at 6,600 MBH with 27.0 CFM at project altitude, the Mitsubishi PKA-AL18NL/PUZ-AK18NL mini-split system for Alternate 02, and the Carrier 48FEDM08 rooftop unit for Alternate 01. Electrical work requires 208/3/60 volt, three-phase power distribution with circuit breakers ranging from 20 to 60 amperes for various components, coordination with existing fire alarm systems, and installation of control panels and thermostats.

The design calls for comprehensive mechanical, plumbing, and electrical coordination involving demolition of existing equipment, rework of ductwork and piping connections, and installation of new roof-mounted equipment bases with proper flashing and seismic restraints. Electrical contractors must verify existing panelboard capacity, extend circuiting from the nearest distribution panel, and integrate new equipment with the building's fire alarm and control systems. The project requires field verification of exact equipment locations, coordination with the mechanical contractor for unit placement and utility connections, and compliance with current code standards for all installations. Rooftop equipment includes proper curbing, weather protection, disconnects, and service receptacles, while interior work encompasses control panel installation, thermostat wiring, and condensate drain routing. All work must maintain continuity of existing building systems outside the renovation area, with abandoned circuits labeled as spare and panelboard directories updated accordingly.

View the file

Other files for this state and local contract opportunity

Other files attached to IFB - Rose Creek Elementary make-Up-Air Replacement, newest first.
File Type Posted
1-Vendor Information Sheet - 02.26.2025.pdf PDF
2-Attachment B - Boycott Statement - 09.pdf PDF
6-Rose Creek ES Kitchen HVAC Bid Specifications (1).pdf PDF
5-26DB03 - IFB - Rose Creek Elementary Make Up Air Replacement.docx DOCX document
4-Attachment A - JSD Standard Terms Conditions.pdf PDF
3-Attachment F - URS Post-Retired Verification Form.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TS

TI

TL

E

SH

EE

T

N

JANUARY 9, 2026

SITE ADDRESS

DRAWING INDEXVICINITY MAPCONSULTANTS

OLSEN & PETERSON CONSULTING ENGINEERS - MECHANICAL

14 East 2700 South Salt Lake City, Utah 84115 Phone: (801) 486-4646

GENERAL

TS TITLE SHEET

MECHANICAL

MD101

M101 M501 M601 P101 P601

MECHANICAL DEMOLITION PLAN

MECHANICAL PLAN

MECHANICAL SCHEDULES

MECHANICAL DETAILS

PLUMBING PLAN

PLUMBING DETAILS

ROSE CREEK

ELEMENTARY

SCHOOL

ROSE CREEK ELEMENTARY SCHOOL

KITCHEN HVAC UPGRADE

12812 SOUTH 3600 WEST

RIVERTON, Utah 84065

Sheet No.

Sh ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

RESOLUT GROUP - ELECTRICAL

181 East 5600 South Suite 200 Murray, Utah 84107 Phone: (801) 530-3148

ELECTRICAL

E001 E002

ED101

E111

ELECTRICAL TITLE SHEET

ELECTRICAL SCHEDULES AND DETAILS

FIRST FLOOR ELECTRICAL DEMOLITION PLAN

FIRST FLOOR ELECTRICAL POWER PLAN

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i

AutoCAD SHX Text

T

Sheet No.

Sh ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

MECHANICAL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

MD101

N

M

EC

HA

NI

CA

L

DE

M

O

LI

TI

O

N

PL

AN

REFERENCE NOTES

1 REMOVE EXISTING GAS FIRED/EVAP. MAKE-UP AIR UNIT & CURB

COMPLETE. COORDINATE WITH NEW WORK.

REMOVE EXISTING MAKE-UP AIR DUCT & DUCT INSULATION COMPLETE TO

BELOW ROOF DECK. COORDINATE WITH NEW WORK.

EXISTING MAKE-UP AIR DUCT TO HOOD TO REMAIN.

EXISTING ROOFTOP UNIT & CURB TO BE REMOVED UNDER ALTERNATE 01.

EXISTING EXHAUST FAN TO REMAIN.

REMOVE EXISTING MAKE-UP AIR UNIT CONTROL PANEL. COORDINATE

WITH NEW WORK.

EXISTING DUCTWORK TO REMAIN. (TYPICAL)

EXISTING DIFFUSERS & GRILLES TO REMAIN. (TYPICAL)

EXISTING HEATING/COOLING THERMOSTAT TO BE REMOVED & REPLACED

UNDER ALTERNATE 01.

EXISTING HOOD TO REMAIN.

AREA OF REQUIRED ROOF SYSTEM DEMOLITION & REPAIR. BUILT-UP ROOF

SYSTEM & INSULATION DEMOLITION & REPLACEMENT REQUIRED. SEE

SPECIFICATIONS 230100-8.2.2.2

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EF-5

AutoCAD SHX Text

EF-3

AutoCAD SHX Text

(ON ROOF)

AutoCAD SHX Text D-3

AutoCAD SHX Text

AutoCAD SHX Text

(9-REQ'D)

AutoCAD SHX Text

EF-4

AutoCAD SHX Text

DH-1

AutoCAD SHX Text

MUA-1

AutoCAD SHX Text

(ON ROOF)

AutoCAD SHX Text

EF-1

AutoCAD SHX Text

(ON ROOF)

AutoCAD SHX Text

KH-1

AutoCAD SHX Text

RT-1

AutoCAD SHX Text

(ON ROOF)

AutoCAD SHX Text 24"x16"(E)

AutoCAD SHX Text 24"x16"(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 6"%%C(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 42"x24"(E)

AutoCAD SHX Text 12"x12"(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 32"x24"(E)

AutoCAD SHX Text 16"x12"(E)

AutoCAD SHX Text 14"x12"(E)

AutoCAD SHX Text 6"x10"(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text D-2

AutoCAD SHX Text

AutoCAD SHX Text D-2

AutoCAD SHX Text

AutoCAD SHX Text G-1

AutoCAD SHX Text

(4-REQ'D.)

AutoCAD SHX Text D-2

AutoCAD SHX Text

AutoCAD SHX Text 46"x18"(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"x12"(E)

AutoCAD SHX Text 16"x12"(E)

AutoCAD SHX Text 8"x12"(E)

AutoCAD SHX Text 16"x12"

AutoCAD SHX Text 18"x14"(E)

AutoCAD SHX Text 30"%%C(E)

AutoCAD SHX Text 4" (E)

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text

CUST/RECIEVING

AutoCAD SHX Text B20

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text B22

AutoCAD SHX Text

CAN WASH

AutoCAD SHX Text B21

AutoCAD SHX Text

TOILET ROOM

AutoCAD SHX Text B27

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text B25

AutoCAD SHX Text

LAUNDRY

AutoCAD SHX Text B26

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text B24

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text B28

AutoCAD SHX Text

DW

AutoCAD SHX Text B23

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i

T

MUA-1

(ON ROOF)

M501

AC-1

(INDOOR)

(ALT. 02)

AC-1

(OUTDOOR)

M601

(ALT. 02)

M601

T

RT-1

(ON ROOF)

M601

(ALT. 01)

RT-1

Sheet No.

Sh ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

MECHANICAL PLAN

SCALE: 1/4" = 1'-0"

M101

N

M

EC

HA

NI

CA

L

P

LA

N

REFERENCE NOTES

1 CONNECT NEW MAKE-UP AIR DUCT TO EXISTING BELOW ROOF DECK.

REPAIR DUCT INSULATION AT TIE-IN.

COORDINATE NEW MAU-1 & CURB WITH EXISTING EXHAUST FAN & CURB.

NEW DUCT THRU ROOF. COORDINATE WITH EXISTING CONDITIONS.

4'-0" MAXIMUM LENGTH MAU-1 INLET HOOD.

EXISTING HOOD CONNECTIONS.

NEW MAU-1 CONTROL PANELS. SEE DETAIL 2/M501. COORDINATE WITH

EXISTING PANEL LOCATION.

WALL MOUNTED HARD WIRED HEATING/COOLING THERMOSTAT.

(ALTERNATE 02)

REFRIGERANT LINES UP THRU ROOF. COORDINATE WITH OUTDOOR UNIT

LOCATION. (ALTERNATE 02)

REFRIGERANT LINES TO RUN ABOVE EXISTING CEILING. COORDINATE

WITH EXISTING CONDITIONS. (ALTERNATE 02)

CONNECT NEW RT-1 SUPPLY & RETURN DUCT TO EXISTING BELOW ROOF

DECK UNDER ALTERNATE 01. COORDINATE WITH EXISTING CONDITIONS &

UNIT PROVIDED.

RE-BALANCE EXISTING SUPPLY AIR DIFFUSERS TO CFM LISTED UNDER

ALTERNATE 01.

PROVIDE NEW WALL MOUNTED HEATING/COOLING THERMOSTAT UNDER

ALTERNATE 01.

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EF-5

AutoCAD SHX Text

EF-3

AutoCAD SHX Text

(ON ROOF)

AutoCAD SHX Text D-3

AutoCAD SHX Text

AutoCAD SHX Text

(9-REQ'D)

AutoCAD SHX Text

EF-4

AutoCAD SHX Text

DH-1

AutoCAD SHX Text

EF-1

AutoCAD SHX Text

(ON ROOF)

AutoCAD SHX Text

KH-1

AutoCAD SHX Text 24"x16"(E)

AutoCAD SHX Text 24"x16"(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 6"%%C(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 42"x24"(E)

AutoCAD SHX Text 12"x12"(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 8"%%C(E)

AutoCAD SHX Text 32"x24"(E)

AutoCAD SHX Text 16"x12"(E)

AutoCAD SHX Text 14"x12"(E)

AutoCAD SHX Text 6"x10"(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text D-2

AutoCAD SHX Text

AutoCAD SHX Text D-2

AutoCAD SHX Text

AutoCAD SHX Text G-1

AutoCAD SHX Text

(4-REQ'D.)

AutoCAD SHX Text D-2

AutoCAD SHX Text

AutoCAD SHX Text 46"x18"(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"%%C(E)

AutoCAD SHX Text 10"x12"(E)

AutoCAD SHX Text 16"x12"(E)

AutoCAD SHX Text 8"x12"(E)

AutoCAD SHX Text 16"x12"

AutoCAD SHX Text 18"x14"(E)

AutoCAD SHX Text 30"%%C(E)

AutoCAD SHX Text 4" (E)

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text

CUST/RECIEVING

AutoCAD SHX Text B20

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text B22

AutoCAD SHX Text

CAN WASH

AutoCAD SHX Text B21

AutoCAD SHX Text

TOILET ROOM

AutoCAD SHX Text B27

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text B25

AutoCAD SHX Text

LAUNDRY

AutoCAD SHX Text B26

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text B24

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text B28

AutoCAD SHX Text

DW

AutoCAD SHX Text B23

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i

Sheet No.

Sh ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

M501

M

EC

HA

NI

CA

L

S

CH

ED

UL

ES

AC-1

MECHANICAL EQUIPMENT SCHEDULE

INDOOR UNIT: HEATING/COOLING, WALL MOUNTED, HORIZONTAL DISCHARGE, 265-310-375-450 CFM, 4,300-18,000 BTUH TOTAL COOLING CAPACITY AT 95° F O.A. TEMP, 80° F D.B. & 67° F W.B., 11,700 BTUH TOTAL HEATING CAPACITY AT 17° F.O.A.

TEMP, 70° F D.B. & 60° F W.B., MCA=1.0, 208/230/1/60 MOTOR TO BE UL LISTED. UNIT TO BE COMPLETE WITH CELANABLE FILTER, CONDENSATE PUMP, CHECK & EXPANSION VALVE KIT, PRE-CHARGED LINE SET, DRIP PAN AND DRAIN CONNECTION.

PROVIDE WALL MOUNTED THERMOSTAT WITH NIGHT SET BACK. THERMOSTAT SHALL BE HARD WIRED TO UNIT.

UNIT DIM: 35 11/32" LENGTHX11 25/32" HEIGHT X 9 11/32" DEPTH.

WEIGHT: 28 LBS.

SEER2: 19.5

HSPF2: 8.9

MANUFACTURER: MITSUBISHI

MODEL: PKA-AL18NL

OUTDOOR UNIT: AIR COOLED, HORIZONTAL DISCHARGE, INVERTER COMPRESSOR, UNIT TO BE MOUNTED ON ROOF.

4,300-18,000 BTUH TOTAL CAPACITY AT 95° F O.A. TEMP, 80° F D.B. & 67° F W.B., 11,700 BTUH TOTAL HEATING CAPACITY AT 17° F O.A. TEMP, 70° F D.B. & 60° F W.B., MCA=16, 208/230/1/60. UNIT TO BE COMPLETE WITH CRANKCASE HEATER, AMBIENT CONTROL KIT TO 0° F, AND ALL CONTROLS FOR AUTOMATIC OPERATION. CONTRACTOR TO PROVIDE A ROOF CURB 18"

ABOVE FINISHED ROOF LEVEL. R454B REFRIGERANT.

UNIT DIM: 35 19/64" LENGTH X 24 13/16" X HEIGHT X 11 13/16" WIDTH.

WEIGHT: 99.2 LBS.

MANUFACTURER: MITSUBISHI

MODEL: PUZ-AK18NL

6600 .60" YES DOWN 554.9 510.5 10 H.P. ECON-AIR EA3-D500-24D

MAKE-UP AIR UNIT SCHEDULE

MODEL & MANUFACTURER

MBH OUTPUTMBH INPUT EFFICIENCY

NATURAL GAS - HEATING CAPACITY

ESPCFMSYMBOL EVAP

SECTION

FLOW

CONFIG

MOTOR HP/

VOLTAGE

SIZE L"xW"xH"

WEIGHT/ LBS

NOTES:

(1) DIRECT NATURAL GAS FIRED.

(2) FAN CFM AT PROJECT ALTITUDE

(3) 14" FACTORY ROOF CURB, FACTORY DISCONNECT, RAIN HOOD, AND HAIL GUARDS.

(4) FACTORY UN-POWERED 20 AMP@ 120/1/60 CONVENIENCE OUTLET.

(1)(2)(3)(4)

EXISTING KITCHEN HOOD

AREA SERVED

MAU-1 80% 208/3/60

139-3/4"L x 41-3/8"W x 43-7/8"H

1500 LBS27.0 35 A 60 A

MCAFLA MOCP

(ALT. 02)

ROOFTOP UNIT SCHEDULE - ALT. 01

MODEL & MANUFACTURERPOWEROATEATTEMP RISETYPE

HEATING CAPACITY GROSS COOLING CAPACITY

ESPCFMSYMBOL

FAN

MOTOR

B.H.P. STAGES

MOPIEER WEIGHT

LBS.UNIT DIMENSIONSROOM

MBH

SENSIBLE

MBH

TOTAL

OUTPUT

MBH

INPUT

MBHO.A.

MIN

208/3/60

MCA

208/3/60

RT-1 3000 .75"KITCHEN -- 2

NATURAL

GAS 37.0 45.015.079.6 78.12 120029.7 88.1 L x 59.5 W x 41.3 H968082.4100450 CARRIER 48FEDM08

(1)(2)(3)(4)(5)

& 120/1/60 208/3/60

NOTES:

(1) PROVIDE HINGED ACCESS DOORS, 100% OUTDOOR AIR ECONOMIZER PACKAGE WITH BUILT-IN 100% RELIEF AIR, 18" HIGH FACTORY ROOF CURB, UNPOWERED WEATHERPROOF GFI CONVENIENCE OUTLET, AND ALL CONTROLS FOR AUTOMATIC OPERATION (WITH ABILITY FOR BMS ENABLE/DISABLE AND MONITORING WITH BACNET). UNIT SHALL BE U.L. LISTED, ARI CERTIFIED AND AGA APPROVED. DOWN DISCHARGE.

(2) COOLING CAPACITY BASED ON 45 DEG. F. S.S.T., 80 DEG. F. db TEMP, 67 DEG. F. wb TEMP. AND 96 DEG. F. O.A. TEMP; HEATING BASED ON 0 DEGREES AMBIENT.

(3) UNITS SHALL BE COMPLETE WITH 2" MERV 8 FILTERS, ABLE TO UPGRADE TO MERV 8 WITH NO CHANGES TO FILTER RACK.

(4) UNITS SHALL USE R-454B REFRIGERANT.

(5) CAPACITIES BASED ON 4250 FT. ELEVATION.

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

M601

M

EC

HA

NI

CA

L

D

ET

AI

LS

NOTE:

NEW MAKE-UP AIR UNIT MAU-1 DETAIL

D G

MAKE-UP AIR UNIT

12" MIN.

GAS INLET

12" MIN.

ROOF MOUNTING

FRAME TO BE

ANCHORED SECURELY

TO ROOF JOISTS

NOT TO SCALE

DISCONNECT SWITCH

AIRFLOW

WATER INLET. PROVIDE

NEW BALL VALVE WITH

DRAIN DOWNSTREAM

OF ISOLATION VALVE

NEW WATER SOLENOID

IN HEATED

CEILING SPACE

M601

1. CONNECT TO WATER,

GAS AND DRAIN.

2. CURB SHALL BE

CONTINUOUS UNDER ALL

SECTIONS OF UNIT.

NEW ROOF

SYSTEM

CONNECT TO EXISTING WATER

DRAIN TO EXISTING

STOP & WASTE

CONNECT TO EXISTING

MAKE-UP AIR DUCT BELOW

ROOF DECK. FIELD VERIFY

PROVIDE NEW GAS

RATED BALL VALVE.

PROVIDE NEW GAS

PRESSURE REGULATOR

GAS RISE ON ROOF CURB.

FLASH AT PENETRATION.

PROVIDE VALVE & REGULATOR

EXISTING DIMENSION

NEW DUCT INSULATION WRAP.

NOT TO SCALE

NEW MAKE-UP AIR UNIT AND

KITCHEN EXHAUST CONTROL PANEL DETAIL

STAINLESS STEEL, FLUSH

MOUNTED BOX FOR SYSTEM

CONTROLS

OFF ON

INDICATOR LIGHT (TYP)

FAN ON

OFF ON

FAN ON

MAKE-UP AIR UNIT MAU-1 CONTROLS

ON

OFF

HEAT

ON

OFF

COOL HEATING

AIR TEMP

MAU ON

COOKING HOOD

EXHAUST SYSTEM

(E) EF-1

DISHWASHER HOOD

EXHAUST FAN

(E) EF-3

M601

ROOFTOP EQUIPMENT BASE DETAIL

NOT TO SCALE

TREATED WOOD RAILS

TO FORM A CONTINUOUS

CURB. BOLT EACH

SECTION TO ROOF IN 3

PLACES

CANT STRIP & ROOF

FLASHING

24" CLEAR MIN.

ROOF LINE

ROOF STRUCTURE

DRILL THRU ROOF

STRUCTURE & BOLT

DOWN EQUIPMENT

RAIL

3/4" NUT & 3" DIA.

WASHER

ROOF INSULATION

3/4" STEEL STOVE

BOLT IN RECESS W/

2" WASHER

3/4" TREATED PLYWOOD

ON TOP OF RAILS

22 GAUGE GALV.

SHEET METAL PAN

OVER TOP OF BASE

FLOOD RECESS WITH

PITCH

NOTE:

PROVIDE EQUIPMENT BASE AT MAKE-UP AIR UNIT. ANCHOR BASE

SECURELY TO STRUCTURE & EQUIPMENT TO BASE. BASE SHALL BE

LARGE ENOUGH FOR ALL UTILITIES TO RISE THRU BASE. COVER OVER

BASE SHALL BE ONE PIECE WATER TIGHT TURNED OVER EDGES,

FLASH AT UTILITIES.

M601

AC-1 CONDENSING UNIT DISCONNECT INSTALLATION DETAIL - ALT. 02

NOT TO SCALE

M601

12" MIN1'-0" MIN

1'-0" MIN

2'-0" MIN

POWER DISCONNECT

UNISTRUT RISER FOR

POWER DISCONNECT. USE

2" CONDUIT FOR LINE SETS TO

EXTEND 8' ABOVE DECK AND 1"

CONDUIT FOR POWER TO BE 24"

MIN. FROM DECK. OF 1'-0" APART

(NOTE: SPLIT LINE SET TO UNIT)

PROVIDE PIPE FLASHING (72 MIL)

AS PER MANUFACTURERS

RECOMENDATIONS (12" MIN FROM

FINISHED ROOF)

PIPE CLAMP MEMBRANE TO

COPPER SET LINE

ANGLE BRACKETS TO

SECURLY ATTACH TO CURB

MAKE UP WATER AND

LOUVERED INTAKE

SUPPLY CONNECTION

FIELD LOCATED

MEDIA

3/4" NPT DRAIN

3/4" NPT OVERFLOW

12.192 5.748

2" ALUMINUM FILTER

7.377

DRAIN CONNECTION DETAIL

AIRFLOW

M601NOT TO SCALE

ANCHOR C.U. SECURELY

TO CURB. (4-PLACES)

NOTE:

PROVIDE EQUIPMENT BASE AT OUTDOOR CONDENSING

UNITS. ANCHOR BASE SECURELY TO STRUCTURE AND

EQUIPMENT TO BASE. BASE SHALL BE LARGE ENOUGH FOR

ALL UTILITIES TO RISE THRU BASE. COVER OVER BASE

SHALL BE ONE PIECE WATER TIGHT TURNED OVER EDGES,

FLASH AT UTILITIES.

DRILL THRU ROOF

STRUCTURE & BOLT

DOWN EQUIPMENT RAIL

INDIVIDUAL REFRIGERANT

PIPING AND CONDUIT FLASHING.

1 PIECE 22 GAUGE GALV. SHEET

METAL PANS OVER TOP OF BASE.

ALL JOINTS, SEAMS AND

FLASHINGS SHALL BE SOLDERED

3/4" TREATED PLYWOOD ON TOP

OF RAILS

EXISTING ROOF INSULATION

PROVIDE NEOPRENE PADS WHERE

UNIT SITS ON PLATFORM

A/C OUTDOOR UNIT DETAIL - ALT. 02

NOT TO SCALE

3/4" STEEL STOVE BOLT IN

RECESS W/ 2" WASHER

3/4" NUT & 3" DIA.

WASHER

TREATED WOOD RAILS TO

FORM A CONTINUOUS CURB.

BOLT EACH SECTION TO

ROOF IN 3 PLACES

ROOF FLASHING

24" CLEAR MIN.

EXISTING ROOF LINE

ROOF STRUCTURE

OUTDOOR

CONDENSING

UNIT

M601

(ALTERNATE 01)

(ALTERNATE 02)

(ALTERNATE 02)

AC-1

MAU-1

ABOVE CEILING CONNECT TO EXISTING GAS

LINE ABOVE CEILING

P501

CONNECT TO EXISTING

DRAIN ABOVE CEILING

PACKAGED ROOF-TOP UNIT DETAIL - ALT. 01

UNIT TO BE INSTALLED LEVEL.

SHIM UNDER ROOF CURB

MOUNTING AS NECESSARY

INSTALL NEOPRENE

GASKET BETWEEN UNIT &

ROOF CURB FRAME

ROOF FLASHING BY

GENERAL CONT

18" CLEAR MINIMUMEXISTING ROOF LINE

24" HIGH MANUFACTURERS

INSULATED AND PRE-FABRICATED

ROOF CURB

ROOF OPENINGS TO BE SIZED FOR DUCT

PENETRATIONS. COORDINATE OPENINGS WITH

STRUCTURAL ENGINEER (TYP)

CONDENSATE DRAIN LINE

W/ P-TRAP TO ROOF

OUTSIDE AIR INTAKE W/

WEATHER HOOD

LOCKING ACCESS

DOOR (TYP)

R.A. S.A.

INSTALL SEISMIC RESTRAINT

BRACKETS PER MFGR

INSTRUCTIONS (TYP)

RELIEF AIR OPENING

W/ WEATHER HOOD

SUPPLY AIR DUCTWORK. SEE PLAN FOR SIZE

ATC CONTROL

WIRING CONDUIT

POWER WIRING

CONDUIT

THROUGH THE

BASE RTU UTILITY

PLATE

RETURN AIR DUCTWORK. SEE PLAN FOR SIZE

THROUGH THE

BASE UTILITIES

WATER TIGHT

FITTINGS (TYP)

THROUGH THE BASE

UTILITY PLATE - PLAN VIEW

CONSISTENT AND LEVEL 4"

CONCRETE REQUIRED IN CURB BASE

M601NOT TO SCALE

GAS LINE THRU ROOF

G

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 65%%D

85%%D

AC-1

(ALT. 02)

G

2"

1/2"

7 88

MUA-1

D D

SLOPE

3/4"10

RT-1

(ALT. 01)

141-1/4"

Sheet No.

Sh ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

PLUMBING PLAN

SCALE: 1/4" = 1'-0"

P101

N

PL

UM

BI

NG

P

LA

N

REFERENCE NOTES

1 APPROXIMATE LOCATION OF EXISTING WATER ABOVE CEILING.

APPROXIMATE LOCATION OF EXISTING DRAIN ABOVE CEILING.

APPROXIMATE LOCATION OF EXISTING 4OZ GAS ABOVE CEILING.

EXISTING GAS/EVAP MAKE-UP AIR UNIT TO BE REMOVED. DISCONNECT

EXISTING WATER, DRAIN & GAS. REMOVE COMPLETE TO BELOW ROOF

DECK. COORDINATE WITH NEW WORK FOR NEW CONNECTIONS.

NEW DRAIN CONNECTION. COORDINATE WITH UNIT PROVIDED SEE DETAIL

2/P601.

NEW WATER CONNECTION. COORDINATE WITH UNIT PROVIDED. SEE

DETAIL 2/P601.

NEW 2"/4OZ GAS CONNECTION. COORDINATE WITH UNIT PROVIDED SEE

DETAIL 1/P601.

CONNECT TO EXISTING PIPING ABOVE CEILING.

EXISTING MAU STOP & WASTE.

3/4" CONDENSATE DRAIN FROM AC-1. CORE OR SLEEVE PENETRATION AT

EXISTING WALL. (ALT. 02)

RUN PIPING ABOVE EXISTING CEILING. (ALT. 02)

TERMINATE CONDENSATE INDIRECT AT CAN WASH. (ALT. 02)

NEW 1-1/4" 4OZ GAS TO RT-1. (ALT. 01) SEE DETAIL 1/P601.

REMOVE EXISTING GAS TO RT-1 BACK TO MAIN. (ALT. 01)

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"(E)

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text 1-1/2"(E)

AutoCAD SHX Text 160%%D

AutoCAD SHX Text 160%%D

AutoCAD SHX Text 160%%D

AutoCAD SHX Text 160%%d

AutoCAD SHX Text 1/2"(E)

AutoCAD SHX Text 1/2"(E)

AutoCAD SHX Text 2"(E)

AutoCAD SHX Text 1"(E)

AutoCAD SHX Text 2"(E)

AutoCAD SHX Text 140%%D

AutoCAD SHX Text 1-1/4"(E)

AutoCAD SHX Text 4oz

AutoCAD SHX Text 4oz

AutoCAD SHX Text 1-1/2"(E)

AutoCAD SHX Text 2-1/2"(E)

AutoCAD SHX Text

MUA-1

AutoCAD SHX Text (E)

AutoCAD SHX Text

CUST/RECIEVING

AutoCAD SHX Text B20

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text B22

AutoCAD SHX Text

CAN WASH

AutoCAD SHX Text B21

AutoCAD SHX Text

TOILET ROOM

AutoCAD SHX Text B27

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text B25

AutoCAD SHX Text

LAUNDRY

AutoCAD SHX Text B26

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text B24

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text B28

AutoCAD SHX Text

DW

AutoCAD SHX Text B23

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i ee t T itl e

D at e:

JA

N . 2

Pr oj ec t N o.

C he ck ed

D ra w n:

ST

AF

F

M

FT

PR

O

PO

SE

D M

EC

H

A N

IC

A

L U

PG

R

A D

E

FO

R

S.

W

. R

IV

ER

TO

N , U

TA

H

R O

SE

C

R

EE

K

EL

EM

EN

TA

R

Y

SC

H O

O L

KI

TC

H

EN

H

VA

C U

PG

R

AD

E

P601

PL

UM

BI

NG

D

ET

AI

LS

NEW PIPE

FLASHING RAIN

ROOFING CONTRACTOR

FLASHING BY

COLLAR WITH CLAMP

BY ROOFING CONTRACTOR.

EXISTING ROOF

CAULKING (TYPICAL)

PIPE THRU ROOF PENETRATION DETAIL

M

IN

NOT TO SCALE

SQUARE FLASHING

FLANGE BY ROOFING

CONTRACTOR

P601

6" V

ER

TI

C

AL

NOTE: VERIFY EXACT

REQUIREMENTS WITH

ROOFING CONTRACTOR

KEEP AS SHORT

AS POSSIBLE

(3 FEET MAX)

EXISTING PIPE RISE FROM

MAIN. SEE PLAN

FOR SIZE

EXISTING ROOF

FLASHING FLANGE

VENT FLASHING RIAN

COLLAR WITH CLAMP

CAULKING (TYPICAL)

MANUAL MAIN

SHUT-OFF VALVE

PLUGGED TEE

GROUND JOINT UNION

PIPING TO BE SAME SIZE

AS APPLIANCE INLET.

CONNECT TO

ROOFOP

EQUIPMENT

FLEXIBLE GAS

CONNECTOR

18" MAX

NEW GAS REGULATOR

SEDIMENT TRAP-

SAME SIZE AS DROP

NEW FLASHING

CONNECT TO

NEW UNIT

ROOFTOP GAS LINE CONNECTION DETAIL

NEW 5# GAS PIPING

PAINT ALL EXPOSED

GAS PIPING

(1) OR (2)

CONNECTIONS

AS REQUIRED

NOTE: SOLENOID POSITIONS SHOWN ARE FOR WINTER DRAIN DOWN.

SUPPLY LINE

SUMP OVERFLOW 3/4"

SUMP DRAIN 3/4"

SUMP DRAIN SOLENOID

(NORMALLY OPEN)

SUPPLY LINE DRAIN SOLENOID

(NORMALLY OPEN)

SUPPLY SOLENOID

(NORMALLY CLOSED)

TRAP

DRAIN TO BUILDING

MAU-1

FLASH PIPE

PENETRATIONS

SEPERATELY

NEW ROOFING

SEAL COLD WATER PENETRATION WATER TIGHT.

MAKE UP WATER AND DRAIN SOLENOID DETAIL

P601

P601

NOT TO SCALE

NOT TO SCALE

AutoCAD SHX Text 14 East 2700 South, Salt Lake City, UT 84115

AutoCAD SHX Text Phone: (801) 486-4646 Fax: (801) 467-2531

AutoCAD SHX Text s

AutoCAD SHX Text c

AutoCAD SHX Text o

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text u

AutoCAD SHX Text l

AutoCAD SHX Text t

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text n

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text

AutoCAD SHX Text n

AutoCAD SHX Text c

AutoCAD SHX Text i

EV EV

DO

M

TV

J

FB PT

#-a

LC

CO

0 cd

0 cd

0 cd

0 cd

0 cd

DH

DCL

F S

D

R

0 cd

XXX

XXXX

XX

F

X X

X W

A P

W A

P X

X

J

#-a

X##

TC

T

0 cd

CR

D

VFD

F

XX

EXIT SIGNAGE

SHADING & ARROWS INDICATE FACES &

DIRECTIONAL CHEVRONS

WALL-MOUNTED FIXTURES, TYPICAL

(VARIOUS SYMBOLS)

LINEAR, CEILING MOUNTED LIGHT FIXTURE

(VARIOUS DIMENSIONS, DOTS INDICATE PENDANT

MOUNT)

RECESSED DOWNLIGHT FIXTURE

CHEVRON INDICATES WALL WASH

DIRECTIONAL LIGHT, TRACK OR FLOOD LIGHT

LINEAR LIGHT, TAPE LIGHT

LIGHTING FIXTURE SYMBOLS LEGEND

NOTE:

1. SWITCH IDS ARE UNIQUE PER SPACE.

2. A SWITCH WITHOUT A TAGGED ID CONTROLS ALL LIGHTING FIXTURES WITHIN A SPACE.

3. ID TAGS MAY BE USED ON CONTROL DEVICES OTHER THAN SWITCHES, SUCH AS OCCUPANCY

SENSORS OR CONTACTORS.

4. ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING FIXTURE INDICATES FIXTURE IS

CONTROLLED BY THE ONLY SWITCH IN THE SPACE.

5. AN "x" IN PLACE OF THE SWITCH DESIGNATION INDICATES UNSWITCHED.

a

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

CEILING 1, 2, 4

CEILING

AS NOTED

AS NOTED

WALL/CEILING

WALL/CEILING

1, 2

POWER SYMBOLS LEGEND

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

S

WALL MOUNTED RECEPTACLE

SWITCHED RECEPTACLE

EMERGENCY RECEPTACLE

GROUND FAULT RECEPTACLE

RECEPTACLE MODIFIERS:

##": HEIGHT AFF OC

WP: WEATHERPROOF IN-USE

COVER

T: TAMPER-PROOF

U: RECEPTACLE WITH USB OUTLET

G: GROUND FAULT

18"

18"

D Q SP

18"

18"

RECEPTACLE (SPECIFIC HEIGHT)

ISOLATED GROUND RECEPTACLE

GENERAL NOTE

B

18"

SWITCH MODIFIERS:

K: KEYED

T: TIMER

M: MANUAL STARTER THERMAL

OVERLOAD SWITCH

EMERGENCY POWER OFF PUSH BUTTON

DOOR OPENER PUSH PLATE

ELECTRICAL POWER METER

FUSED DISCONNECT SWITCH

TOMBSTONE RECEPTACLE*

CORD REEL, DEVICE VARIES

CORD DROP, DEVICE VARIES

MULTI-OUTLET ASSEMBLY

FILLED SQUARES INDICATE 120V OUTLET

OPEN SQUARES INDICATE WITH USB

SINGLE / DUAL PORT ELECTRICAL VEHICLE

CHARGER

POWER POLE

NON-FUSED DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC STARTER WITH FUSED DISCONNECT

PUSHBUTTON

VARIABLE FREQUENCY DRIVE

TRANSFORMER:

SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &

REQUIREMENTS.

TX

7, 25

EMERGENCY EGRESS LIGHT FIXTURE CEILING 1, 2, 4

CRITICAL EGRESS LIGHT FIXTURE CEILING 1, 2, 4

GENERAL LEGEND

SYMBOL DESCRIPTION NOTES

SOLID ARCHED LINES INDICATE UNSWITCHED

POWER CIRCUITING

DASHED ARCHED LINES INDICATE SWITCHED

POWER CIRCUITING

ONE CIRCUIT, HOME RUN TO PANEL

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

4" CONCRETE

BASE

MAIN DISTRIBUTION PANEL 6'-6" TO TOP

FLUSH PANELBOARD 6'-6" TO TOP

SURFACE PANELBOARD 6'-6" TO TOP

TWO CIRCUITS, HOME RUN TO PANEL -

THREE CIRCUITS, HOME RUN TO PANEL -

CONDUIT RUN CONCEALED IN FLOOR OR GROUND -

CONDUIT RUN CONCEALED IN WALL OR CEILING -

CONDUIT UP -

CONDUIT DOWN -

CONDUIT STUB LOCATION CAP CONDUIT

CONDUIT / CIRCUIT CONTINUATION -

GROUND BUS BAR

CABLE TRAY

SOLID BOTTOM

LADDER

BASKET

MOUNTING

AS NOTED

8+18"

EQUIPMENT CEILING RACK

EQUIPMENT CABINET/RACK

EQUIPMENT 2-POST CABINET/RACK

TELEPHONE DEMARCATION BOARD +18" 25

AS NOTED 18, 25

SEE SPEC.

AS NOTED 18, 25

SEE SPEC.

CEILING

EXISTING --

DEMO --

TEMPORARY --

NEW --

CONDUIT

OHP: OVERHEAD POWER SERVICE

UGP: UNDERGROUND POWER

SERVICE

UGF: UNDERGROUND FIBER

SERVICE

TEL: TELEPHONE SERVICE

POWER DISTRIBUTION EQUIPMENT SYMBOLS

CIRCULAR, CEILING MOUNTED LIGHT FIXTURE

CENTER DOT INDICATES PENDANT

CEILING 1, 2, 4

CONTROLLED RECEPTACLE +18" OR AS

NOTED

SPD PROTECTED RECEPTACLE +18" OR AS

NOTED

TIME CLOCK +60" -

NOT IN CONTRACT --

MAGNETIC STARTER WITH BREAKER DISCONNECT

MOTOR

CEILING MOUNTED RECEPTACLE CEILING

TV BACKBOX FLAT PANEL

HEIGHT +12"

EMERGENCY LIGHTING UNIT, INTEGRAL BATTERY WALL/CEILING

CW W: WALL C: CEILING

LIGHTING TAGS LEGEND

NOTES:

1. HATCHED FILL INDICATES DISTRIBUTION PANEL OR

SWITCHBOARD.

2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.

3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE

(WIDTH & DEPTH).

4. DOOR INDICATES FRONT OF RECESSED PANEL.

H P

1A

LP

1A

M D

P

SB1

POWER TAGS LEGEND

GENERAL LEGEND

SYMBOL DESCRIPTION NOTESMOUNTING

KEYNOTE

ROOM NAME & NUMBER

DIAGRAM TAG

MATCH LINE TAG

ROOM NAME & NUMBER W/ ZONE I.D.

JUNCTION BOX

x

EXIT SIGNAGE WITH AUXILIARY HEAD

SHADING & ARROWS INDICATE FACES &

DIRECTIONAL CHEVRONS

AS NOTED

S: SIMPLEX D: DUPLEX

Q: FOURPLEX SP: SPECIAL PURPOSE

FLOOR BOX / POKE-THRU

- SEE SCHEDULE FOR TYPE INFORMATION

AREA LIGHT POLE & FIXTURE

POST-TOP LIGHT POLE & FIXTURE

BOLLARD LIGHT

ARROWS INDICATE DIRECTION

SWITCH

SWITCH MODIFIERS:

3: 3-WAY

4: 4-WAY

K: KEYED

D: DIMMING

T: TIMER

P: SWITCH W/ PILOT LIGHT

CONCRETE

BASE

CONCRETE

BASE

CONCRETE

BASE

LIGHTING CONTROL SYMBOLS

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

46" 6

STEP LIGHT FIXTURE AS NOTED

IN-GRADE LIGHT FIXTURE AS NOTED

MOMENTARY CONTACT SWITCH 46" 6

LOW VOLTAGE WALL STATION

(SUBSCRIPT INDICATES CONFIGURATION)

46" 6

CEILING FAN CEILING

LIGHTING CONTACTOR

LIGHTING CONTROL TOUCH SCREEN

WALL

46"

SENSORS/SWITCHES:

PC: PHOTO-ELECTRIC CONTROL

OS: OCCUPANCY SENSOR SWITCH

DL: DAYLIGHT HARVESTING SENSOR

AS NOTED 6, 28

SWITCH PACKS:

AP: AUXILIARY PACK

PP: POWER PACK

ABOVE

CEILING

6, 28

CONTROL:

RC: DIGITAL ROOM CONTROLLER

(SUBSCRIPT = NUMBER OF RELAYS)

EP: EMERGENCY LIGHTING CONTROL

UNIT

ABOVE

CEILING

REFER TO DIA

AND SPEC

FIRE ALARM SYMBOLS LEGEND

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

+94" WALL /

CEILING OR AS

NOTED

AUDIBLE ANNUNCIATION

(BLANK): HORN

LF: LOW FREQUENCY HORN

SP: SPEAKER

FB: FIRE BELL

+48" 8, 29MANUAL PULL STATION

+94" WALL /

CEILING OR AS

NOTED

VISIBLE ANNUNCIATION, CANDELA AS INDICATED

(BLANK): CLEAR STROBE

B: BLUE STROBE

A: AMBER STROBE

+94" WALL /

CEILING OR AS

NOTED

AUDIBLE/VISIBLE ANNUNCIATION, CANDELA AS

INDICATED

(BLANK): CLEAR STROBE

B: BLUE STROBE

A: AMBER STROBE

LF: LOW FREQUENCY HORN

SP: SPEAKER

+94" WALL /

CEILING OR AS

NOTED

29REMOTE INDICATOR w/ TEST SWITCH

CEILING 29SMOKE DETECTOR

CEILING 29HEAT DETECTOR

CEILING 29CARBON MONOXIDE DETECTOR

CEILING 29BEAM DETECTOR

T: TRANSMITTER

R: RECEIVER

CEILING 29COMBINATION DETECTOR (UP TO THREE)

CEILING 29DUCT SMOKE DETECTOR

DUCT 29FIRE/SMOKE DAMPER

AS INDICATEDDOOR HOLDER

AS INDICATED 29DOOR CLOSER

+48" 8, 29FIRE SERVICE PHONE

29ADDRESSABLE MODULE

AIM: ADDRESSABLE INPUT MODULE

AOM: ADDRESSABLE OUTPUT MODULE

AIO: ADDRESSABLE INPUT/OUTPUT

+48" 8, 29FIRE ALARM CONTROL UNIT

EVAC: VOICE EVACUATION CONTROL

PANEL

FAA: FIRE ALARM ANNUNCIATOR

FACP: FIRE ALARM CONTROL PANEL

FATC: FIRE ALARM TERMINAL CABINET

NACP: NOTIFICATION APPLIANCE

CIRCUIT PANEL

FAMN: FIRE ALARM MASS

NOTIFICATION PANEL

TW: TWO WAY COMMUNICATION

INTERCOM

TWZ: TWO WAY COMMUNICATION

CONTROLLER

8, 29SUPERVISORY or INTERFACE DEVICE

PIV: POST INDICATOR VALVE

PS: PRESSURE SWITCH

R: NON-ADDRESSABLE RELAY

VS: VALVE SUPERVISORY SWITCH

FS: FLOW SWITCH

TS: TAMPER SWITCH

WF: WATER FLOOD SENSOR

CW W: WALL C: CEILING

DATA NETWORK SYMBOLS LEGEND

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

DATA OUTLET (SINGLE CABLE) 18" WALL/

FLOOR/CEILING

DATA OUTLET (TWO CABLES) 18" WALL/

FLOOR/CEILING

DATA OUTLET (THREE CABLES) 18" WALL/

FLOOR/CEILING

SERIES-X COAXIAL CABLE OUTLET

DISTRIBUTED ANTENNA SYSTEM (DAS)

PUBLIC SAFETY AND/OR

CELLULAR/COMMERCIAL

ANT: ANTENNA

BDA: BI-DIRECTIONAL AMPLIFIER

SPL: SPLITTER

VIA: VIA

108" WALL,

CEILING,

ABOVE

CEILING, OR AS

NOTED

WIRELESS ACCESS POINT* 96" WALL/

CEILING

W F C W: WALL F: FLOOR C: CEILING

18" WALL/

FLOOR/CEILING

CW W: WALL C: CEILING

EQUIPMENT SYSTEM PANELS

ACS: ACCESS CONTROL PANEL

IDS: INTRUSION DETECTION PANEL

PSP: POWER SUPPLY PANEL

RP#: LIGHTING PANEL

DAS: DISTRIBUTED ANTENNA SYSTEM

ERCCS: FIRST RESPONDERS RADIO SYSTEM

CATV: CABLE TV CONTENT EQUIPMENT

CEILING

CEILING

+46"

+46"

+46"

+72"

+60"

+60"

+60"

+60"

AS NOTED

18, 25

SEE SPEC.

7, 22

7, 25

7, 25

7, 25

7, 25

7, 25

Space

Space

XX

A a

FIXTURE ID (UPPERCASE UNDERLINED LETTER)

PANEL ID (NUMBERS & UPPERCASE LETTERS) - CIRCUIT NUMBER

RELAY ID (UPPERCASE LETTERS)

FIXTURE CONTROL ZONE ID (LOWERCASE LETTER)

#: INDICATES SWITCH TYPE

LOWERCASE LETTER: INDICATES SWITCH ID

DEVICES WITH A CHEVRON INDICATE TO

COORDINATE WITH MILLWORK PRIOR TO ROUGH-IN.

B

ELEVATION TAG. HATCHED AREA INDICATES

WHICH WALL, NUMBER INDICATES VIEW, AND

CENTER NUMBER INDICATES WHICH SHEET.

REVISION CLOUD DELTA. SHOWN WITH CLOUD

AND INDICATES A CHANGE PER THE TITLE BLOCK.

TAG FOR MECHANICAL, KITCHEN, AND SHOP

DEVICES. REFER TO SCHEDULES FOR INFO.

HICKS

BRIAN

No. 7709037-2202

G

IN

E E R

ONA

O F

E

SS

I

R

UT

AH

TE OF

S T A

P

L EN

Project #: 251089

PROJECT

NO:DRAWN BY:

CHK'D BY:

DATE:

T H

IS

P

R

IN

T

IS

IN

C

O L

O R

A

BCDEFGHIJKLMN

ABCDEFGHIJKLMN

01/09/2026

/9

/2

:2 :4

A

M A u to d e s k D o c s /J

S D

R o s e

C re e k E

S M

A U

R e p la c e m e n t/

J

S D

R o s e C re e k E

S M

A U

R e p la c e m e n t_

E L E

C v

.r v t

01/09/2026

251089

BR

FK

ELECTRICAL

TITLE SHEET

E001

J S

D R o s e

C re e k E

S M

A U

R e p la c e m e n t

S

W

R iv e rt o n

U

T

JS

D

R os e C re ek

E S

M A

U R ep la ce m en t

ELECTRICAL ABBREVIATIONS INDEX

ABBREV. DESCRIPTION

A AMPS

AC ALTERNATING CURRENT

ACLG ABOVE CEILING

ADC ANALOG-TO-DIGITAL

CONVERTER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT

AFCI ARC FAULT CIRCUIT

INTERRUPTER

AFF / A.F.F. ABOVE FINISH FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPS INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AM AMPS METER

AMP AMPERE

AMPL AMPLIFIER

ANN ANNUNCIATOR

AOE AUDIO-OVER-ETHERNET

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIOVISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BC BARE COPPER

BD BOARD

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BLDG BUILDING

BMS BUILDING MANAGEMENT

SYSTEM

BPM BEATS-PER-MINUTE

C, CND CONDUIT

C.O. CONDUIT ONLY

C/W COMPLETE WITH

CAB CABINET

CAT CATEGORY CABLE

CAT# CATALOG

CATB COMMUNITY ANTENNA

TELEVISION

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CF CREST FACTOR

CKT CIRCUIT

CLG CEILING

CMPR COMPRESSOR

CNTR CONTRACTOR

CO CONDUIT ONLY

CODEC CODER-DECORDER

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONV CONVECTOR

CP CIRCULATING PUMP

CRT COMPUTER TERMINAL

CT CURRENT TRANSFORMER

CU COPPER

CV CONSTANT VOLTAGE

DAC DIGITAL-TO-ANALOG

CONVERTER

DB DECIBEL

DBFS DB REF. FULL SCALE

DBM DB REF. 0.001 WATT

DBU DB REF. 0.775 V

DBV DB REF. 1 V

DC DIRECT CURRENT

DCP DOMESTIC CIRCULATING PUMP

DED DEDICATED

DEPT DEPARTMENT

DET DETAIL

DFA DROP FROM ABOVE

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DR DYNAMIC RANGE

DS DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EG EMERGENCY GENERATOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY/EGRESS BATTERY

EMI ELECTRO-MAGNETIC

INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

ENT ELEC. NON-METAL. TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

ER EXISTING TO BE RELOCATED

ES SOURCE VOLTAGE

EWC ELECTRIC WATER COOLER

FA FIRE ALARM

FABP FIRE ALARM BOOSTER PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOT CANDLE

FCU FAN COIL UNIT

FIR FINITE IMPULSE RESPONSE

FILTER

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FMC FLEXIBLE METAL CONDUIT

FU FUSE

FUDS FUSE SAFETY DISCONNECT

SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEC GRND. ELEC. COND. AT SES

GEN GENERATOR

GFCI GROUND FAULT CURRENT

INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

ABBREV. DESCRIPTION

GRC GALVANIZED RIGID CONDUIT

GYP BD GYPSUM BOARD

HOA HAND-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSE POWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING & AIR

CONDITIONING

HZ HERTZ

I/W INTERLOCK WITH

IC INTERRUPTING CAPACITY

IFC INTERNATIONAL FIRE CODE

IG ISOLATED GROUND

IIR INFINITE IMPULSE RESPONSE

FILTER

IMC INTERMEDIATE METALLIC

CONDUIT

INCAND INCANDESCENT

IR INFRARED

IT TOTAL CURRENT

J-BOX JUNCTION BOX

KCMIL 1000 CIRCULAR MILS (MCM)

KHZ THOUSANDS OF HZ

KV KILOVOLT

KVA KILOVOLT AMPERES

KVAR KILOVARS

KW KILOWATT

KWH KILOWATT HOUR

LCS C-WEIGHTED SLOW SOUND

LEVEL

LEQ EQUIVALENT SOUND LEVEL

LFMC LIQUID-TIGHT FLEX.

METAL. COND.

LFNC LIQUID-TIGHT FLEX. NON-METAL.

COND.

LOC LOCATE OR LOCATION

LP, SPL SOUND PRESSURE LEVEL

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LU LOUDNESS UNIT METERING

LUFS LOUDNESS UNIT FULL SCALE

LV LOW VOLTAGE

M/C MOMENTARY CONTACT

MAC MEDIA ACCESS CONTROL

MAG.S MAGNETIC STARTER

MAX MAXIMUM

MB MAIN BUS

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCM 1000 CIRCULAR MILLS

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MEP MECHANICAL, ELECTRICAL, AND

PLUMBING

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT

SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MNF MANUFACTURER

MOA MULTI-OUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MSP MOTOR STARTER PANELBOARD

MSS MOTOR STARTER SWITCH

MTG MOUNTING

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

N NEW

N.I.C. NOT IN CONTRACT

N/A NOT APPLICABLE

N1 NEMA 1

N3R NEMA 3R

NAC NOTIFICATION APPLIANCE

CIRCUIT PANEL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECT.

MANUFAC. ASSOC.

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NFPA NATIONAL FIRE PROTECTION

ASSOC.

NL NIGHT LIGHT, BYPASS LOCAL

SWITCHING

NO NORMALLY OPENED

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

OC ON CENTER

OH OVERHEAD

OL OVERLOADS

OS & Y OUTSIDE SCREW & YOKE

OSI OPEN SYSTEM INTEGRATION

PA PASCAL

PB PUSHBUTTON

PBB PRIMARY BONDING BUSBAR

PC PLUMBING CONTRACTOR

PCM PULSE CODE MODULATION

PDU POWER DISTRIBUTION UNIT

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PFR PHASE FAILURE RELAY

PIV POST INDICATING VALVE

PLEN PLENUM

PNL PANEL

POC POINT OF CONNECTION

POE POWER OVER ETHERNET

POS POINT OF SALE

PP POWER POLE

PPM PEAK PROGRAM METER

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PSI POUNDS-PER-SQUARE-INCH

PT POTENTIAL TRANSFORMER

PTP POINT TO POINT

PTZ PAN, TILT, AND ZOOM

ABBREV. DESCRIPTION

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

QUAN QUANTITY

R RESISTANCE

RECEP, RECPT RECEPTACLE

REQ,REQD REQUIRED

REX REQUEST TO EXIT

RF RADIO FREQUENCY

RFM ROOF MOUNTED

RL LOAD RESISTANCE

RLA RATED LOAD AMPS

RM ROOM

RMC RIGID METALLIC CONDUIT

RMP ROCKY MOUNTAIN POWER

RMS ROOT MEAN SQUARE

RNC RIGID NON-METALLIC COND.

RPM ROTATIONS-PER-MINUTE

RS SOURCE RESISTANCE

RT TOTAL RESISTANCE

RTU ROOF TOP UNIT

RX RECEIVER

S/N SOLID NEUTRAL

S/S STOP/START PUSHBUTTONS

SBB SECONDARY BONDING BUSBAR

SBG SUPPLEMENTARY BONDING

GRID

SBJ SYSTEM BONDING JUMPER

SC SURFACE CONDUIT

SCA SHORT CIRCUIT AMPERES

SDI SERIAL DIGITAL INTERFACE

SE SERVICE ENTRANCE

SEC SECONDARY

SES SMOKE EVACUATION SYSTEM

SHT SHEET

SIM SIMILAR

SLD SINGLE-LINE DIAGRAM

SNR SIGNAL-TO-NOISE RATIO

SP SPARE

SPDIF SONY PHILLIPS DIGITAL

INTERFACE

SPEC SPECIFICATIONS

SPKR LOUDSPEAKER

SPL SOUND PRESSURE LEVEL

SPP SINGLE-POINT POWER

SR SURFACE RACEWAY

SS SELECTOR SWITCH

SSW SELECTOR SWITCH

STA STATION

STD STANDARD

STP SHIELDED TWISTED PAIR

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

SYS SYSTEM

TBB TELECOMMUNICATIONS

BONDING BACKBONE

TBC TELECOMMUNICATIONS

BONDING CONDUCTOR

TC TEMP. CONTROL CONTR.

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL

TX TRANSMITTER

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTED POWER

SUPPLY

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UTP UNSHIELDED TWISTED PAIR

UV ULTRAVIOLET

V VOLT (KV-KILOVOLT)

VA VOLT/AMPS

VA/R, VAR VOLT-AMPS/REACTIVE

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DC CURRENT

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VI VOLUME INDICATOR

VIF VERIFY IN FIELD

VM VOLT METER

VOL VOLUME

VU VOLUME UNIT

W WATTS

W/ WITH

W/O WITHOUT

WG WIRE GUARD

WH WATTHOUR METER

WP WEATHERPROOF/NEMA 3R

XFMR TRANSFORMER

XFMR SW SW TRANSFER SWITCH

XFR TRANSFER

XL X-CONNECTOR LOCKING

XLR X-CONNECTOR LOCKING

RUBBERIZED

XP EXPLOSION PROOF

XR EXISTING TO BE REMOVED

1P ONE-POLE

2P TWO-POLE

3P THREE-POLE

4P FOUR-POLE

∠ ANGLE

& AND

@ AT

° DEGREE

▲ DELTA

', FT FOOT, FEET

", IN INCH, INCHES

# NUMBER

Ω, OHM UNIT OF ELECTRICAL

RESISTANCE

Ø, PH PHASE

℄, CTR CENTER LINE, CENTER

P PLATE

SYMBOL LEGEND GENERAL NOTES

1. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE

INDICATES INSTALLED IN CEILING.

2. WALL DEVICES NOTED WITH A CHEVRON INDICATE TO COORDINATE WITH MILLWORK SHOP

DRAWINGS & ELEVATIONS FOR HEIGHT.

3. TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN THIS SET OF DRAWINGS.

4. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE

& DETAILS.

5. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.

6. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.

7. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.

8. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.

9. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.

10. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.

11. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.

12. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR

480 VOLT.

13. SIZE TO THE EQUIPMENT BEING CONTROLLED.

14. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.

15. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.

16. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,

MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.

17. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.

18. COORDINATE WITH DOOR HARDWARE SUPPLIER.

19. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS

A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.

20. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

21. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.

22. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.

23. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.

24. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.

25. ROUGH-IN TO BE HORIZONTAL.

26. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE

REQUIRED.

27. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.

28. SUBSCRIPT INDICATES NEMA CONFIGURATION.

29. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.

30. USE WITH POWER PACK.

31. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.

32. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.

GENERAL SYMBOLS LEGEND

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

EQUIPMENT CEILING RACK CEILING 18, 25, SEE

SPEC.

EQUIPMENT CABINET/RACK AS NOTED 18, 25, SEE

SPEC.

EQUIPMENT 2-POST CABINET/RACK AS NOTED 18, 25, SEE

SPEC.

TELEPHONE DEMARCATION BOARD +18" 25

ELECTRICAL SHEET LIST

E001 ELECTRICAL TITLE SHEET

E002 ELECTRICAL SCHEDULES & NOTES

ED101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

E111 FIRST FLOOR ELECTRICAL POWER PLAN

E501 PANEL SCHEDULES

EXISTING SYSTEMS INFORMATION AND VENDOR CONTRACTS

(INCLUDE WITHIN BID)

FIRE ALARM SYSTEM - FIELD VERIFY

COMPANY

CONTACT

CELL PHONE NO.

OFFICE PHONE NO.

EMAIL

EXTEND EXISTING FIRE ALARM INTIATION/NOTIFICATION CIRCUITS TO ACCOMMODATE NEW FIRE ALARM DEVICES AS REQUIRED. MATCH SYSTEM WIRING. UPDATE

PROGRAMMING.

FIELD VERIFY

REVISIONS

MARK DATE DESCRIPTION

FIELD VERIFY

FIELD VERIFY

FIELD VERIFY

FIELD VERIFY

R

INITIATION LOOP

DAMPER

FACP

(2) #12 FOR FIRE/SMOKE

DAMPER CONTROL (120V)

D

CM

J J

M

5'-0" MAX.

NOTES

1. REFER TO MECHANICAL DRAWINGS FOR LOCATION OF

ALL FIRE/SMOKE DAMPERS.

2. PROVIDE 120V FROM NEAREST POWER PANEL.

PROVIDE A MAXIMUM OF 6 DAMPERS ON ONE CIRCUIT.

HICKS

BRIAN

No. 7709037-2202

G

IN

E E R

ONA

O F

E

SS

I

R

UT

AH

TE OF

S T A

P

L EN

Project #: 251089

PROJECT

NO:DRAWN BY:

CHK'D BY:

DATE:

T H

IS

P

R

IN

T

IS

IN

C

O L

O R

A

BCDEFGHIJKLMN

ABCDEFGHIJKLMN

01/09/2026

/9

/2

:2 :4

A

M A u to d e s k D o c s /J

S D

R o s e

C re e k E

S M

A U

R e p la c e m e n t/

J

S D

R o s e C re e k E

S M

A U

R e p la c e m e n t_

E L E

C v

.r v t

01/09/2026

251089

BR

FK

ELECTRICAL

SCHEDULES &

NOTES

E002

J S

D R o s e

C re e k E

S M

A U

R e p la c e m e n t

S

W

R iv e rt o n

U

T

JS

D

R os e C re ek

E S

M A

U R ep la ce m en t

NOTE 4: EC TO VERIFY BREAKER AMPACITY. PROVIDE NEW BREAKERS AS NEEDED TO MATCH OCP SHOWN IN SCHEDULE BELOW.

NOTE 3: ALL EQUIPMENT TO BE RATED FOR THE ENVIRONMENT FOR WHICH IT IS INSTALLED.

NOTE 2: OVERCURRENT PROTECTION DEVICE (OCPD) SHOWN IS LOCATED AT POWER PANEL. ALL FUSING TO BE SIZED IN ACCORDANCE WITH FUSE MFR RECOMMENDATION FOR MOTOR NAME PLATE RATING.

NOTE 1: PER 250.122(A), EQUIPMENT GROUND IS NOT REQUIRED TO BE LARGER THAN THE PHASE CONDUCTOR

GENERAL NOTES

CC - CONTROL CONTRACTOR

MC - MECHANICAL CONTRACTOR (DIVISION 23)

EC - ELECTRICAL CONTRACTOR (DIVISION 26)

RESPONSIBILTY LEGEND:

MECHANICAL EQUIPMENT SCHEDULE

IDENTITY INFORMATION ELECTRICAL LOAD INFORMATION OCP CIRCUIT INFORMATION STARTER CONTROL DISCONNECT

INTERLOCK NOTES

TYPE

ID

INSTANCE

ID

DESCRIPTION VOLTAGE PHASE

MOTOR

POWER

APPARENT

POWER

REAL

POWER

FLA MCA TYPE OCP

PHASE CONDUCTORS NEUTRAL CONDUCTOR GROUND CONDUCTOR

CONDUIT

SIZE TYPE FURNISH INSTALL TYPE FURNISH INSTALL TYPE FURNISH INSTALL

SETS NO. SIZE TYPE NEUTRAL SIZE TYPE SIZE TYPE SIZE

AC - 1 AIR CONDITIONER- INDOOR 208 V 1 0.00 hp 0.2 kVA 0.1 kW 0.8 A 1 A (Motor) Inverse Time Breaker N/A 1 2 12 Cu Yes 12 Cu 12 Cu 3/4" CC EC FUSED EC EC PROVIDE WIRING FROM

OUTDOOR TO INDOOR UNIT

PER MANUFACTURER

REQUIREMENTS

AC - 1 AIR CONDITIONER-OUTDOOR 208 V 1 0.00 hp 2.7 kVA 2.4 kW 12.8 A 16 A (Motor) Inverse Time Breaker 20 A 1 2 12 Cu Yes 12 Cu 12 Cu 3/4" CC EC FUSED EC EC PROVIDE WIRING FROM

OUTDOOR TO INDOOR UNIT

PER MANUFACTURER

REQUIREMENTS

MAU - 1 MAKE-UP AIR UNIT 208 V 3 0.00 hp 10.1 kVA 9.1 kW 28 A 35 A (Motor) Inverse Time Breaker 60 A 1 3 8 Cu Yes 8 Cu 10 Cu 1" MAGNETIC

STARTER

CC CC CC EC FUSED EC EC PROVIDE 120V POWER TO

MANUFACTURER PROVIDED

GFCI SERVICE RECEPTACLE

RT - 1 ROOFTOP UNIT 208 V 3 0.00 hp 10.7 kVA 9.6 kW 29.6 A 37 A (Motor) Inverse Time Breaker 45 A 1 3 8 Cu Yes 8 Cu 10 Cu 1" CC EC FUSED EC EC PROVIDE UNDER ALT 1.

PROVIDE 120V POWER TO

MANUFACTURER PROVIDED

GFCI SERVICE RECEPTACLE

ELECTRICAL DEMOLITION NOTES

1. REFERENCE & COORDINATION

A. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DEMOLITION AND

CONSTRUCTION PHASES. COORDINATE ALL ELECTRICAL WORK WITH GENERAL

CONSTRUCTION REQUIREMENTS, DOOR RELOCATIONS, AND WALL MODIFICATIONS.

2. DEVICE & FIXTURE REMOVAL

A. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES, SWITCHES, AND LIGHTING

FIXTURES IN DEMOLITION AREAS UNLESS NOTED OTHERWISE.

B. REMOVE ALL CONDUIT/WIRING IN WALLS SCHEDULED FOR DEMOLITION (SHOWN

DASHED) BACK TO THE LAST ACTIVE DEVICE.

C. WHERE NEW WALLS INTERSECT EXISTING ONES, REMOVE ANY AFFECTED DEVICES,

BOXES, OR BACK BOXES.

3. CIRCUIT CONTINUITY & SYSTEM MODIFICATIONS

A. FURNISH AND INSTALL CONDUIT, WIRING, AND/OR COMMUNICATIONS/DATA CABLING AS

NECESSARY TO MAINTAIN CONTINUITY OF FEEDERS, BRANCH CIRCUITS, AND SYSTEMS

SERVING DEVICES OR EQUIPMENT TO REMAIN.

B. RECONNECT, RELOCATE, AND/OR REWIRE EXISTING DEVICES, FIXTURES, OR EQUIPMENT

AS REQUIRED TO AVOID CONSTRUCTION CONFLICTS AND ENSURE PROPER OPERATION.

4. EQUIPMENT OUTSIDE WORK AREA

A. LEAVE ALL EQUIPMENT IN NON-REMODELED AREAS IN WORKING CONDITION. RESTORE

ANY INTERRUPTED FEEDERS, BRANCH CIRCUITS, OR SYSTEMS TO FULL OPERATION.

5. RACEWAYS & WIRING

A. EXISTING RACEWAYS MAY BE REUSED IF THEY MEET CURRENT CODE, SPECIFICATIONS,

AND PROJECT INTENT. VERIFY THEIR INTEGRITY BEFORE REUSE.

B. CONCEAL RACEWAYS AND WIRING IN EXISTING WALLS, CEILINGS, AND FLOORS UNLESS

OTHERWISE INDICATED. USE SURFACE METAL RACEWAY ONLY WHERE EXPLICITLY

NOTED.

C. REMOVE ALL UNUSED RACEWAYS, CONDUCTORS, BOXES, DEVICES, AND EQUIPMENT

NOT INTENDED FOR REUSE.

6. LIGHTING FIXTURE HANDLING

A. REMOVE FIXTURES NOT TO BE REUSED AND EITHER RETAIN FOR THE OWNER OR

DISPOSE OF PROPERLY. STORE REUSABLE FIXTURES IN CARTONS AND LABEL CLEARLY.

7. COVER PLATES

A. PROVIDE BLANK COVER PLATES ON ALL UNUSED OPENINGS.

8. PENETRATIONS

A. DO NOT PENETRATE STRUCTURAL ELEMENTS (FLOORS, WALLS, CEILINGS, ROOFS, ETC.)

UNLESS SPECIFICALLY PERMITTED IN THE CONSTRUCTION DOCUMENTS.

12" = 1'-0"

FIRE/SMOKE DAMPERS CONNECTION

REVISIONS

MARK DATE DESCRIPTION

WD

FG

CUST/RECIEVING

B20

OFFICE

B22

CAN WASH

B21

TOILET ROOM

B27

STORAGE

B25

LAUNDRY

B26

KITCHEN

B24

STORAGE

B28

DW

B23

F

F

T

T

T

T

AIM

CO

CO

AIM

EXISTING EXHAUST FAN TO REMAIN

EXISTING EXHAUST FAN TO REMAIN

EXISTING EXHAUST FAN TO REMAIN

EXISTING MAU TO BE REMOVED

D5

EXISTING ROOFTOP UNIT

(ALT 01)

EXISTING EXHAUST

FAN TO REMAIN

D5

EXISTING MAU CONTROL PANEL

TO BE REMOVED

D1

D2

D3

D3

D3

D3

D4

D4 D

D6

HICKS

BRIAN

No. 7709037-2202

G

IN

E E R

ONA

O F

E

SS

I

R

UT

AH

TE OF

S T A

P

L EN

Project #: 251089

PROJECT

NO:DRAWN BY:

CHK'D BY:

DATE:

T H

IS

P

R

IN

T

IS

IN

C

O L

O R

A

BCDEFGHIJKLMN

ABCDEFGHIJKLMN

01/09/2026

/9

/2

:2 :4

A

M A u to d e s k D o c s /J

S D

R o s e

C re e k E

S M

A U

R e p la c e m e n t/

J

S D

R o s e C re e k E

S M

A U

R e p la c e m e n t_

E L E

C v

.r v t

01/09/2026

251089

BR

FK

FIRST FLOOR

ELECTRICAL

DEMOLITION

PLAN

ED101

J S

D R o s e

C re e k E

S M

A U

R e p la c e m e n t

S

W

R iv e rt o n

U

T

JS

D

R os e C re ek

E S

M A

U R ep la ce m en t

KEYNOTES

D1 EXISTING MAU TO BE REMOVED. DIV. 26 IS TO DISCONNECT CONDUIT AND WIRING FROM UNIT

BACK TO THE PANEL.

D2 DISCONNECT POWER AND DATA TO EXISTING MAU CONTROL PANEL. PULL CONDUIT AND/OR

CABLING BACK TO AN ACCESSIBLE CEILING. CONTROL PANEL REMOVAL BY OTHERS.

D3 APPROXIMATE LOCATION OF EXISTING EXHAUST FAN. EXHAUST FAN TO REMAIN.

D4 REMOVE CO DETECTOR, DUCT DETECTOR AND CONTROL MODULE AS REQUIRED.

D5 DIV. 26 IS TO REMOVE & STORE EXISTING LIGHT FIXTURES AND FIRE ALARM DEVICE FROM

CEILING AS NECESSARY. COORDINATE WITH MECHANICAL CONTRACTOR. REWORK ANY

CONDUIT AND WIRING IN THE CEILING AS NECESSARY.

D6 DISCONNECT EXISTING POWER TO RT-1. PULL BACK CONDUIT AND WIRE BACK TO THE PANEL.

SCALE = 1/4" = 1'-0"

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN

DEMOLITION GENERAL NOTES

1. DIVISION 26 SHALL CONFIRM EXACT LOCATION OF EXISTING AND NEW EQUIPMENT WITH

OWNERS. FIXTURE LOCATIONS ARE DIAGRAMMATICALLY SHOWN ON THE DRAWINGS.

EXISTING ELECTRICAL FIXTURES, DEVICES, EQUIPMENT, CIRCUITING AND/OR CIRCUITING

AND/OR CONDUITS ARE NOT SPECIFIED UNLESS NOTED ON DRAWINGS. FINAL ROUTING OF

THE CONDUITS, CIRCUITING AND CABLING SHALL BE DETERMINED BY THE CONTRACTOR AND

CLOSELY COORDINATED WITH OWNER. ALL EXISTING CONDITIONS MUST BE VERIFIED

WITHOUT EXCEPTION.

2. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING DEMOLITION DRAWINGS

FOR ADDITIONAL DEMOLITION INFORMATION.

3. DURING DEMOLITION AND NEW CONSTRUCTION, THE CONTINUATION OF BUILDING SYSTEMS

MAY BE NECESSARY, TRACE AND IDENTIFY EXISTING ELECTRICAL SYSTEM (POWER,

LIGHTING, FIRE ALARM AND SECURITY) WIRING IN AREAS PRIOR TO DEMOLITION. ELECTRICAL

CONTRACTOR SHALL DISCONNECT ALL NECESSARY EQUIPMENT TO MAKE IT SAFE FOR

DEMOLITION, WHERE LIVE CIRCUITS OR FEEDERS PASS THROUGH A REMODEL AREA,

CONTRACTOR SHALL MAINTAIN ELECTRIC CONTINUITY TO AND PROTECT BRANCH CIRCUITS

AND/OR FEEDERS PASSING THROUGH. WHERE FEEDERS AND/OR BRANCH CIRCUITS FEED

BOTH LOADS IN A REMODELED AREA AND OUTSIDE OF A REMODELED AREA, CONTRACTOR

SHALL DISCONNECT AND REMOVE PORTIONS OF THE ELECTRICAL BRANCH CIRCUITS AND/OR

FEEDERS WITHIN THE REMODELED AREA AND REWORK BRANCH CIRCUITS AND/OR FEEDERS

TO MAINTAIN ELECTRICAL CONTINUITY TO LOADS O UTSIDE OF THE REMODELED AREA.

4. DEVICES AND EQUIPMENT TO BE DEMOLISHED SHALL BE REMOVED, INCLUDING ALL RELATED

CONDUCTORS,RACEWAY, JUNCTION AND SPLICE BOXES UP TO THE

PANELBOARD/SWITCHBOARD. ALL CONDUITS AND BOXES THAT ARE SURFACE MOUNTED AND

NO LONGER REQUIRE ACTIVE CIRCUITS SHALL BE COMPLETELY REMOVED. DEVICES TO BE

REMOVED ON DRYWALL OR PLASTERTYPE WALLS THAT ARE TO REMAIN SHALL HAVE THE

WALL SURFACE PATCHED TO MATCH THE EXISTING FINISH. THE CONTRACTOR SHALL

IDENTIFY ALL DEMOLISHED AND ABANDONED BRANCH CIRCUITS. THESE SHALL BE NOTED AS

SPARE ON PANELBOARD SCHEDULES. THIS INCLUDES IDENTIFYING EXISTING ABANDONED

AND SPARE CIRCUITS THAT ARE CURRENTLY IDENTIFIED AS USED. THE CONTRACTOR SHALL

FURNISH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS.

5. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL. ANY MATERIAL THE

OWNER CHOOSES NOT TO ACCEPT SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY

THECONTRACTOR.

6. FULLY COORDINATE MECHANICAL EQUIPMENT ELECTRICAL CONNECTION REMOVAL AND

RELOCATION WITH THE MECHANICAL CONTRACTOR.

7. CONTRACTOR TO VERIFY THAT ALL EXISTING EQUIPMENT THAT IS TO REMAIN, BE REMOVED

AND RE-INSTALLED ARE IN WORKING CONDITIONS, CONTRACTOR IS TO PROVIDE OWNER

WRITTEN DOCUMENTATION OF ANY ITEMS NOT IN WORKING CONDITION

PRIORTOCOMMENCING WORK IN AN AREA.

8. CONTRACTOR IS TO PROTECT IN PLACE ALL MECHANICAL, PLUMBING, ELECTRICAL

ABOVECEILINGS. THIS MAY INCLUDE BUT NOT LIMITED TO: NETWORK CABLING, COAX

CABLING, CONDUITS, PIPING, DUCTWORK, ETC.PROVIDE ADDITIONAL CABLING SUPPORTS AS

REQUIRED FOR ANY UNSUPPORTED CABLING, RACEWAY, ETC.

9. WHERE DEVICES OR EQUIPMENT IS TO BE RELOCATED, CONTRACTOR SHALL EXTEND

EXISTING CIRCUITING TO NEW…