Liberty Star November 2012 Thermography Report.pdf

PDF 537 KB Posted

Attached to
TS FREEDOM STAR Fall Package Federal contract opportunity
Solicitation number
6933A219Q000023
Issued by
Department of Transportation Maritime Administration

About this file

Liberty Star November 2012 Thermography Report.pdf

View the file

Other files for this federal contract opportunity

Other files attached to TS FREEDOM STAR Fall Package, newest first.
File Type Posted
IMG_20181226_145225753.jpg JPG image
IMG_20181226_145208558.jpg JPG image
Amdmt_0004.pdf PDF
Amdmt_3.pdf PDF
Amdmt_0002.pdf PDF
ABS_Recognized_Service_Providers.pdf PDF
Amdmt_1_6933A219000023.pdf PDF
workboat.PNG PNG image
ExternalSpecialist_SEARCH_RESULT.pdf PDF
IMG_2144.JPG JPG image
ISIS Est_1200_from_AL_T._MARINE_ELECTRONICS Redacted.pdf PDF
1427-555, Rev -, TV FREEDOM STAR, FIRE AND SAFETY PLAN.pdf PDF
Wartsila PC and 4-3 valve quote redacted.pdf PDF
TVFS LIPS CPP INFO.pdf PDF
Liferaft Certificates 2018.pdf PDF
WD_TSFS_Fall_Pkg.pdf PDF
MARAD AM550 Collar Quote - Redacted.pdf PDF
Attmt_1_SOW_TSFS_Fall_2019_Items_3.pdf PDF
OD Box Photo.pdf PDF
THERMOGRAPHY LIST 2012.pdf PDF
6933A219Q000023_combined_syn_sol.pdf PDF
7 remaining 2018 gauge calibration certs.pdf PDF
Fast Rescue Boat 1.jpg JPG image
Fast Rescue Boat 2.jpg JPG image
Fast Rescue Boat 3.jpg JPG image
2018 Annual Firefighting Equipment.pdf PDF
Attmt_2_Vendor_Price_Sheet.xlsx XLSX spreadsheet
ISIS700B.pdf PDF
2018 Gauge calibration certs.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMERICAN OVERSEAS MARINE CORPORATION

THERMOGRAPHY REPORT

M/V Liberty Star (King’s Pointer)

5 November, 2012

EMPRISE CORPORATION

P.O. Box 129

Ledyard, CT 06339

(860) 464-8555/FAX (860) 464-1366

THERMOGRAPHY REPORT M/V LIBERTY STAR (KING’S POINTER)

P.O. Box 129, Ledyard, CT 06339

(860)464-8555/(860)464-1366 FAX

Page i

TABLE OF CONTENTS

SECTION PAGE

1.0 INTRODUCTION

2.0 THERMOGRAPHY LIST

3.0 LIST OF DISCREPANCIES

4.0 THERMOGRAPHY SETS

(860)464-8555/(860)464-1366 FAX

1.0 INTRODUCTION

BACKGROUND

The purpose of an Electrical Equipment Thermographic Survey is to find, localize and characterize electrical equipment deficiencies. Heat generated by poor electrical connections, loose wiring, faulty contacts, etc., is detected via infrared radiation which it emits in proportion to the amount of heat generated. The FLIR ThermaCam E4, used by Emprise Corporation in the completion of this survey, is a thermographic device which utilizes an uncooled Focal Plane Array (FPA) technology and special filters which are only sensitive to energy in the infrared spectrum. This device allows viewing of the equipment to be surveyed on a 3 inch LCD display. The actual temperatures are read directly from the calibrated images.

Anomalies can then be identified and actual temperatures quantified. Data is stored in a radiometric calibrated JPEG.

RESULTS

The results of the survey are presented in the form of thermograms of the image displayed by the FLIR ThermaCam E4. A corresponding natural light image of the area concerned is also presented beside the thermogram constituting a Thermographic Set. Red arrows point to the fault on both the thermogram and the natural light image so that a repair technician can positively localize the fault on board the ship.

Severity judgment, tempered with normal operational characteristics of the equipment, is assigned on the following scale:

Temperature Rise in 0F Recommendation

1.0 – 25.0 Low

25.1 – 50.0 Moderate

50.1 - 75.0 High

Above 75.1 Severe

Preceding the List of Discrepancies is a record of the electrical equipment inspected during the performance of the survey.

The last section of this report contains the thermographic sets accompanied by a detailed description of the problem, its location, fault and (if applicable) ambient temperatures, temperature rise, probable cause, and repair recommendation.

(860)464-8555/(860)464-1366 FAX

2.0 THERMOGRAPHY LIST

EQUIPMENT/LOCATION TESTED OFF COMMENTS

Main Deck Shore Power Junction Box xxx Emergency Diesel Generator Room 2 HP Supply Fan Controller xxx Emergency Power Transfer Switch xxx Emergency Breaker Panel xxx Breaker Panel L212 xxx Engine Room Entry, Main Deck Port ER Exhaust Fan Controller xxx ER Supply Fan #1 Controller xxx Fault Page 6 ER Supply Fan #2 Controller xxx Breaker Panel L211 xxx Pump Flat, Engine Room Forward Port Sanitary Pump Controller xxx Fire Pump Controller xxx Keel Cooler Circ. Pump Controller xxx A/C Circ. Pump Controller #1 xxx A/C Circ. Pump Controller #2 xxx Engine Shop Breaker Panel P141 xxx Fault Page 8 Lower Deck Breaker Panel L112 xxx Breaker Panel L113 xxx Engine Room Forward Starboard Breaker Panel L111 xxx Fault Page 15 Deck Hydraulic Pump Controller xxx MSD Controller xxx Sewage Transfer Pump Controller xxx Engine Room Center Line Ballast Pump Controller xxx Purifier Controller xxx D.O. Transfer Pump #1 Controller xxx D.O. Transfer Pump #2 Controller xxx L.O. Transfer Pump xxx Dirty Oil Transfer Pump xxx Cannot run Tow Winch Control Panel xxx 120v portion only Engine Room Port Aft Ship service Air Compressor #2 xxx Port C.P.P. Pump #1 Controller xxx Port C.P.P. Pump #2 Controller xxx Fault Page 18 Engine Room Stbd Aft Ship service Air Compressor #1 xxx Stbd C.P.P. Pump #1 Controller xxx Stbd C.P.P. Pump #2 Controller xxx

(860)464-8555/(860)464-1366 FAX

EQUIPMENT/LOCATION TESTED OFF COMMENTS

Main Switchboard Main Buss xxx Gen #1 Breaker xxx Gen #2 Breaker xxx Shore Power Breaker xxx Breaker Panel 115V Dist xxx Breaker Panel 460V Dist xxx Other breakers xxx Fault Page 10 Stern Thruster Space Stern Thruster Rotation Controller xxx Steering Gear Controller #1 xxx Steering Gear Controller #2 xxx Main Deck Shop Breaker Panel P213 xxx Breaker Panel P242 xxx Fault Page 17 Mess Deck Breaker Panel P211 xxx Breaker Panel L211 xxx Bosun Stores Anchor HPU Controller xxx Bow Thruster HPU Controller xxx Dry Stores Breaker Panel P223 xxx Breaker Panel P241 xxx Fault Pages 9, 11 Breaker Panel P212 xxx Fault Pages 16, 19 01 Level ½ HP Exhaust Fan Controller xxx Breaker Panel P341 xxx Fault Pages12, 13, 14 Breaker Panel L311 xxx Rescue Boat HPU Controller xxx Hydraulic Leak Captains Office Main and Lower Deck Supply Fan xxx Exhaust Hood Galley xxx Bridge Breaker Panel EP411 xxx Breaker Panel EP401 xxx Breaker Panel L411 xxx Could not remove cover Breaker Panel P411 xxx Nav. Light Panel N411 xxx Fault Page 7

(860)464-8555/(860)464-1366 FAX

3.0 LIST OF DISCREPANCIES

1. Engine Room Supply Fan 1 Controller, fast speed overloads left side.

Fault Temperature: 179.0 ºF Temperature Rise: 135.7 ºF Severity: SEVERE

2. N411 Navigation Light Panel, bottom terminal board, right lead.

Fault Temperature: 149.8 ºF Temperature Rise: 37.5 ºF Severity: MODERATE

3. Engine Room Workshop Panel P141, breaker 2, top contact set.

Fault Temperature: 89.2 ºF Temperature Rise: 34.6 ºF Severity: MODERATE

4. Galley Stores Panel P241, breaker 7, center output lead.

Fault Temperature: 109.0 ºF Temperature Rise: 32.6 ºF Severity: MODERATE

5. Main Switchboard, Generator Room Supply Fan Breaker, top and bottom input connections.

Fault Temperature: 89.3 ºF Temperature Rise: 31.9 ºF Severity: MODERATE

6. Galley Stores Panel P241, breaker 3, bottom output lead.

Fault Temperature: 106.5 ºF Temperature Rise: 30.8 ºF Severity: MODERATE

7. 01 Deck Panel P341, breaker 1, top contact set.

Fault Temperature: 113.0 ºF Temperature Rise: 30.5 ºF Severity: MODERATE

8. 01 Deck Panel P341, breaker 2, bottom output lead.

Fault Temperature: 149.0 ºF Temperature Rise: 28.4 ºF Severity: MODERATE

9. 01 Deck Panel P341, breaker 7, bottom contact set.

Fault Temperature: 108.1 ºF Temperature Rise: 27.3 ºF Severity: MODERATE

10. Engine Room Panel L111, breaker 6.

Fault Temperature: 94.5 ºF Temperature Rise: 25.1 ºF Severity: MODERATE

(860)464-8555/(860)464-1366 FAX

11. Galley Stores Panel P212 Breaker 6, top contact set.

Fault Temperature: 106.3 ºF Temperature Rise: 24.6 ºF Severity: LOW

12. Main Deck Workshop Panel P242, breaker 6, bottom contact set.

Fault Temperature: 114.5 ºF Temperature Rise: 22.3 ºF Severity: LOW

13. Port #2 CPP Pump controller, overload output, center lead.

Fault Temperature: 97.4 ºF Temperature Rise: 22.0 ºF Severity: LOW

14. Galley Stores Panel P212, breaker 5 bottom contact set.

Fault Temperature: 103.4 ºF Temperature Rise: 19.6 ºF Severity: LOW

(860)464-8555/(860)464-1366 FAX

4.0 THERMOGRAPHY SETS

VESSEL: M/V Liberty Star (King’s Pointer)

THERMOGRAPHY SET 1 of 14 DATE: 5 November, 2012

EQUIPMENT: Engine Room Supply Fan 1 Controller

FAULT TEMP: 179.0 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 135.7 ºF.

FAULT LOCATION: Fast speed overloads left side.

PROBABLE CAUSE: Loose or corroded connection.

RECOMMENDATION: Check all connections for tightness.

NOTES: Top screw on the left Fast Speed overload was tightened approximately 1 turn which appeared to correct this fault.

SEVERITY: SEVERE

THERMOGRAPHIC IMAGE VISIBLE LIGHT IMAGE

EQUIPMENT: Engine Room Supply Fan 1 Controller

VESSEL: M/V Liberty Star (King’s Pointer)

THERMOGRAPHY SET 2 of 14 DATE: 5 November, 2012

EQUIPMENT: N411 Navigation Light Panel

FAULT TEMP: 149.8 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 37.5 ºF.

FAULT LOCATION: Bottom terminal board, right lead.

RECOMMENDATION: Replace bottom right lug, clean and tighten all connections.

NOTES: None.

SEVERITY: MODERATE

EQUIPMENT: N411 Navigation Light Panel

THERMOGRAPHY SET 3 of 14 DATE: 5 November, 2012

EQUIPMENT: Engine Room Workshop Panel P141

FAULT TEMP: 89.2 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 34.6 ºF.

FAULT LOCATION: Breaker 2, top contact set.

PROBABLE CAUSE: Loose or corroded connection; damaged contact set.

RECOMMENDATION: Replace breaker; check condition of bus work prior to re-installation.

EQUIPMENT: Engine Room Workshop Panel P141

THERMOGRAPHY SET 4 of 14 DATE: 5 November, 2012

EQUIPMENT: Galley Stores Panel P241

FAULT TEMP: 109.0 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 32.6 ºF.

FAULT LOCATION: Breaker 7, center output lead.

RECOMMENDATION: Clean and tighten all connections.

EQUIPMENT: Galley Stores Panel P241

THERMOGRAPHY SET 5 of 14 DATE: 5 November, 2012

EQUIPMENT: Main Switchboard, Generator Room Supply Fan Breaker

FAULT TEMP: 89.3 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 31.9 ºF.

FAULT LOCATION: Top and bottom input connections.

RECOMMENDATION: Clean switchboard, check all connections for tightness.

EQUIPMENT: Main Switchboard, Generator Room Supply Fan Breaker

THERMOGRAPHY SET 6 of 14 DATE: 5 November, 2012

EQUIPMENT: Galley Stores Panel P241

FAULT TEMP: 106.5 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 30.8 ºF.

FAULT LOCATION: Breaker 3, bottom output lead.

EQUIPMENT: Galley Stores Panel P241

THERMOGRAPHY SET 7 of 14 DATE: 5 November, 2012

EQUIPMENT: 01 Deck Panel P341

FAULT TEMP: 113.0 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 30.5 ºF.

FAULT LOCATION: Breaker 1, top contact set.

EQUIPMENT: 01 Deck Panel P341

THERMOGRAPHY SET 8 of 14 DATE: 5 November, 2012

EQUIPMENT: 01 Deck Panel P341

FAULT TEMP: 149.0 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 28.4 ºF.

FAULT LOCATION: Breaker 2, bottom output lead.

THERMOGRAPHY SET 9 of 14 DATE: 5 November, 2012

EQUIPMENT: 01 Deck Panel P341

FAULT TEMP: 108.1 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 27.3 ºF.

FAULT LOCATION: Breaker 7, bottom contact set.

THERMOGRAPHY SET 10 of 14 DATE: 5 November, 2012

EQUIPMENT: Engine Room Panel L111

FAULT TEMP: 94.5 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 25.1 ºF.

FAULT LOCATION: Breaker 6.

PROBABLE CAUSE: Internal phase to phase connection or ground.

RECOMMENDATION: Remove breaker and blank panel cover.

NOTES: This breaker exhibits a phase temperature variance with no output leads attached. Breaker is internally damaged as evidenced by its inability to be switched to off.

EQUIPMENT: Engine Room Panel L111

THERMOGRAPHY SET 11 of 14 DATE: 5 November, 2012

EQUIPMENT: Galley Stores Panel P212

FAULT TEMP: 106.3 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 24.6 ºF.

FAULT LOCATION: Breaker 6, top contact set.

SEVERITY: LOW

EQUIPMENT: Galley Stores Panel P212

THERMOGRAPHY SET 12 of 14 DATE: 5 November, 2012

EQUIPMENT: Main Deck Workshop Panel P242

FAULT TEMP: 114.5 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 22.3 ºF.

FAULT LOCATION: Breaker 6, bottom contact set.

EQUIPMENT: Main Deck Workshop Panel P242

THERMOGRAPHY SET 13 of 14 DATE: 5 November, 2012

EQUIPMENT: Port #2 CPP Pump controller

FAULT TEMP: 97.4 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 22.0 ºF.

FAULT LOCATION: Overload output, center lead.

EQUIPMENT: Port #2 CPP Pump controller

THERMOGRAPHY SET 14 of 14 DATE: 5 November, 2012

EQUIPMENT: Galley Stores Panel P212

FAULT TEMP: 103.4 ºF. AMBIENT TEMP: N/A ºF. TEMP RISE: 19.6 ºF.

FAULT LOCATION: Breaker 5 bottom contact set.

EQUIPMENT: Galley Stores Panel P212