654-20-117.12.Drawings.Delta2.pdf

PDF 7 MB Posted

Attached to
Y1DA--Mental Health EOC Compliance Federal contract opportunity
Solicitation number
36C26121R0072-0002
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

This solicitation package includes drawings and specifications for an inpatient mental health facility renovation project. The scope of work involves removing existing lighting, devices, and fixtures in patient rooms and corridors and replacing them with anti-ligature, vandal-resistant LED alternatives. It also requires upgrades to electrical systems and infrastructure to support the new fixtures and equipment. The project is located at a Department of Veterans Affairs medical center in Reno, Nevada. Responses to contractor questions are included to amend the solicitation and extend the closing date. Relevant construction disciplines involved include electrical, lighting, and infrastructure work. The level of detail in the drawings and specifications suggests this is a design-bid-build project intended for competitive bids.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--Mental Health EOC Compliance, newest first.
File Type Posted
26 27 26 - Wiring Devices.pdf PDF
36C26121R0072 0002.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C P

E

N

E N

NNNNN

N

N

N

N

N

N

E N

E

N

E

N

E

N

E

N

E

N

E N

E N

E

N

E N

E

N

E N

J

J

J

J J

J

F

7.6

9.4

G4

RECEIVING

B6127

BATH

B6131A

BATH

B6127A

TWO BED

B6131

ONE BED

B6135

HAC

B6133

BATH

B6137A

BATH

B6135A

BATH

B6192A

BATH

B6194A

TWO BED

B6192

SUN DECK

B6188

SECLUSION

B6134A

ANTE RM

B6134

TOILET

B6134B

TOILET

B6193B

SECLUSION

B6193A ANTE RM

B6193

NURSE STATION

B6128

MEDICATION

B6128A

WORK RM HOUSE

STAFF

B6104

STAFF TOILET

B6125

COPY

B6124

HAC

B6184A

DAY RM

RECREATION

B6184

NON-FOOD STRG

5C139

TOILET

5C138

TOILET

5C137

GOLD ELEVATOR

SILVER

ELEVATOR

PSYCHIATRIST

OFFICE

5C144

HEAD NURSE

5C143

TELE

B6184C

ADL KITCHEN

5C133C

CORRIDOR

B6C06

ELEVATOR

LOBBY

B6EGD

CORRIDOR

B6C01

SOCIAL WORK

OFFICE

5C147

PSYCHIATRIST

OFFICE

5C146

NURSE CLINICIAN

PHYSICIAN

ASSISTANT

5C142

REHABILITATION

THERAPIST

OFFICE

5C141

DEMOSTRATION

CLASSROOM

5C158

CORRIDOR

5C-C11

CORRIDOR

5C-C9

HYDRO TANK

5C140

TRAY CART

STORAGE

5C133B

DINING

5C133A

BMS

5C159

CORRIDOR

B6C02

SALLY PORT

B6C02A

ANTE RM

B6134

ANTE RM

B6193

CORRIDOR

B6C05

33 3

5NLC- 42

5NLC- 42

5NLC- 405NLC- 40

5NLC- 40

5NLC- 40

5NLC- 42

5NLC- 42

5NLB- 36

5NLB- 1

5ECA- 16

5ECA- 16

5NLB- 32

5NLB- 32 5NLB- 34

5ECA- 40 5ECA- 42

5NLB- 41

5NLD- 8

5NLD- 12

5NLD- 12

5NLD- 12

5NLB- 4

5ECA- 22

5NLB- 4

5NLA- 26

5NLA- 26

5NLA- 8

5NLA- 8

5NLA- 8

5NLA- 175NLA- 17

5NLA- 6

5NLA- 6

5NLA- 6

5NLA- 8

5NLD- 65NLD- 6

5NLD- 6

5NLD- 6

5NLD- 6

5NLD- 8

5NLD- 6

5NLD- 6

5NLA- 10

5NLA- 26

5NLD- 8

5NLD- 8

5NLD- 8

5NLD- 14

5NLD- 16

5NLC

5NLC

5NLC- 3

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLD- 10

5NLD- 10

5NLD

5NLD

5NLD

5NLD- 10

5NLD- 10

5NLD

5NLD

5NLD

5ECA- 18

5ECA- 18

5ECA- 18

5NLD- 8

5NLD- 8

5NLB- 27

5NLC- 19

5NLC- 19

5NLD

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5ECB

5NLC

5NLD

5EHEB

5NHB

5ELB

5NLA- 8

5NLA- 8

5NLA- 26

5NLD- 40

5ECA-15

5NLA-2

5NLA-2

5ECA-15

5ECA-15

5NLA-2

5NLA-2

ECA-14

ECA-14

ECA-14

ECA-14

5NLA-10

5NLA-10

5ECA-16

5ECA-16

5NLA-6

5NLA-6

5ECA-15

5E C

A -1

5E C

A -1

5N L A

-4

5N L A

-4

5E C

A -1

5E C

A -1

5N

LA

-1

5E C

A -1

5E C

A -1

5N

LB

-3

5N

LB

-3

5N L

B -5

5N L

B -5

5N

LB

-2

5N

LB

-2

5NLA- 17

(A)(B)(C)

(A)

(A)

(B)

(C)

TYP. OF 3

(A)

TYP. OF 3

(B)(C)

(A)

(B)

(C)

(A)

TYP. OF 3

(B)(C)

(A)

(A)

(B)

(C)

(A)

TYP. OF 3

(B)(C)

(A)

(B)

(C)

(A)(B)

(C)

TYP. OF 3

(A) (B)

(C) 9

TYP. OF 3

(C)

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12 /20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/2

/2

:3

:2

P

M

E-106A

ELECTRICAL PLAN - LEVEL 6 - AREA A - NEW 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F5

ELECTRICAL PLAN - LEVEL 6 - AREA A

- NEW

1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH

PUSHBUTTON NURSE CALL STATION AT EACH LOCATION

2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE

REMAINING EMERGENCY POWER OUTLET AND ONE NORMAL POWER OUTLET PER BED IN EACH

PATIENT ROOM AND PROVIDE ONE GFCI OUTLET IN PATIENT TOILET ROOM, COORDINATE ROUGH-IN

LOCATIONS WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED

ON/OFF CONTROL.

3. PROVIDE NEW ANTI-LIGATURE DOOR SENSOR ON BOTTOM OF DOOR. INTEGRATE WITH EXISTING

SENSOR LOCATED ON TOP OF DOOR. WIRE TO EXISTING POWER SUPPLY AND CONTROLS. MAIN

PANEL LOCATED IN THE NURSES STATION. SEE SPECIFICATION 08 71 00 FOR ADDITIONAL

REQUIRMENTS.

4. PROVIDE NEW POWER, DATA AND COAXIAL CONNECTIONS FOR NEW TV MONITOR AT 84" ABOVE

FINISHED FLOOR, COORDINATE ROUGH-IN LOCATIONS WITH NURSE MANAGER.

5. PROVIDE NEW POWER AND DATA AS SHOWN IN RENOVATED NURSES STATION.

6. PROVIDE NEW CAT 6A CABLING FOR ALL NEW DEVICES. PROVIDE NEW CAT 6A PATCH PANEL AND

LOCATE ON EXISTING RACK, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. PROVIDE NEW HARD-WIRED 120V/24V CONNECTION AND TRANSFORMER FOR INFRARED FLUSH

VALVE OPERATION.

8. TEMPORARY WALL OPENING FOR ACCESS TO MEDICAL ROOM DURING PHASING. CONTRACTOR

SHALL COORDINATE TEMPORARY RELOCATION OF ELECTRICAL UTILITIES AS NECESSARY. RETURN

TO EXISTING CONDITIONS AFTER INFILL.

9. RECONFIGURE RECEPTACLE LAYOUT IN MEDICATION ROOM. RELOCATE ONE NORMAL POWER

RECEPTACLE TO NORTH WALL AND ONE EMERGENCY POWER RECEPTACLE TO SOUTH WALL.

10. PROVIDE NEW ANTI-LIGATURE CAMERA (BASIS OF DESIGN AXIS Q92160-SLV)AND CONNECT TO EXISTING HEAD END EQUIPMENT. CONFIRM FINAL LOCATION WITH OWNER TO ENSURE ADQQUATE

COVERAGE.

11. PROVIDE BARREL-KEY WALL SWITCH (20A,120-277V) TO CONTROL INDICATED POWER RECEPTACLE(S)

IN PATIENT ROOM. PROVIDE BARREL KEY SWITCH COVER PLATE AND INSTALL WITH TAMPER-

RESISTANT SCREWS.

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

Revisions: Date:

2 - ELECTRICAL RFI'S 04.20.2021

2 2 2

N

NNNN

N N N

N N

N

E N

E

N

E N

E N

E

N

E

N

E

N

E NE N

E

N

E N

E

N

E

N

E

N

E

N

E

N

E N

E

N

J J

J

J

J

J

J

J

J

J

J

J

7.6

9.4

H I K L

BATH

B6137A

BATH

B6135A

RED BAG

STORAGE

B6138

SOILED UTILITY

B6136

LOCKER ROOM

B6195

TWO BED

B6194

BATH

B6192A

BATH

B6194A

CORRIDOR

B6C06

ONE BED

B6137

CORRIDOR

B6C03

ELEC EQUIP

B6139

GROUP THERAPY

B6143

ONE BED

B6147

ONE BED

B6149

BATH

B6147A

BATH

B6149A

ONE BED

B6150

BATH

B6150A

TWO BED

B6208

QUIET

B6146

TWO BED

B6206

BATH

B6206A

BATH

B6208A

WASHER DRYER

B6205

NOURISH

KITCHEN

B6203

CLEAN UTILITY

B6201

CLEAN LINEN

B6199

OFFICE

B6140

TELE

B6142

TELE EQUIP

B6197

TWO BED

B6204

TWO BED

B6200

BATH

B6200A

BATH

B6204A

STAIR 2

BS2

CORRIDOR

B6C04

5ELA

5ECA

5NLA

5NLB

5NHA

5EHEA

5 5 5 5

5NLA- 85NLA- 8

5NLA- 8

5NLA- 26

5NLB- 28

5ECA- 38

5NLB- 7

5NLB- 5

5NLB- 26

5ECA- 36

5NLB- 26

5ECA- 36

5E C

A

5N L B

5N L B

5N L B

5E C

A

5N L B

5N L B

5E C

A

305NLA- 24

5NLA- 24

5NLB- 14

5ECA- 28

5NLB- 14

5NLB- 10

5ECA- 26

5NLB- 10

5ECA- 24

5NLB- 8

5NLB- 8

5NLA- 24 5NLA- 24

5NLA- 24

5NLA- 24

5NLA- 20

5NLA- 20

5NLA- 20

5NLA- 20

5NLA- 22

5NLA- 22

5NLB- 19

5NLB- 19

5NLB- 21

5NLA- 22

5NLB- 17

5NLA- 26

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 12

5NLA- 26

5ECA- 7

5NLA- 12 5ECA- 9

5ECA- 9

5E C

A

5E C

A

5E

LA

5E

LA

5ELA- 4

5ECA- 13

5NLA- 12

5NLA- 24

5NLA- 22

5NLA- 22

5ECA- 20

5ECA- 20

5ECA- 20

5ECA- 7

2 2

5NLA- 39

5N L

B -5

5N

LB

-2

5N

LB

-2

5N

LB

-2

5N

LB

-1

5N

LB

-1

5NLB-12

5NLB-13

5NLB-13

2 2

2 2

2 2

DEDUCT #1

5ECA- 38

(A)(B)(C)

(A)

(B)

(A)

(C)

(A)(B)(C)

(A)

(B)

(A)

(C)

TYP. OF 3 TYP. OF 3

(A)(B)(C)

TYP. OF 3

(A)

(B)

(A)

(C)

(A) (B) (C)

TYP. OF 3

(A) (A)(B)

(C)

(A) (B) (C)

TYP. OF 3

(A) (B) (A)

(C)

(A) (B) (C)

TYP. OF 3

(A)(B)

(C)

(A) (B) (C)

TYP. OF 3

(A)

(B)

(C)

(A) (B) (C)

TYP. OF 3

(A)

(B)

(C)

(A)

(B)

(C) 9

TYP. OF 3

(C)

(B)

(A)

2 2

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA B

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12 /20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/2

/2

:3

:2

P

M

E-106B

ELECTRICAL PLAN - LEVEL 6 - AREA B - NEW 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F3

ELECTRICAL PLAN - LEVEL 6 - AREA B

- NEW

1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH

PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.

2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE

REMAINING EMERGENCY POWER OUTLET AND ONE NORMAL POWER OUTLET PER BED IN EACH

PATIENT ROOM AND PROVIDE ONE GFCI OUTLET IN PATIENT TOILET ROOM, COORDINATE ROUGH-IN

LOCATIONS WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED

ON/OFF CONTROL.

3. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT GROUP THERAPY ROOM. COORDINATE 1

REMAINING OUTLET FOR TV WITH NURSE MANAGER.

4. REMOVE CONVENIENCE OUTLETS, BLANK FACES JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) IN PROCEDURE ROOM AS NECESSARY.

COORDINATE WITH NURSE MANAGER OUTLETS TO REMAIN FOR EQUIPMENT.

5. PROVIDE NEW ANTI-LIGATURE DOOR SENSOR ON BOTTOM OF DOOR. INTEGRATE WITH EXISTING

SENSOR LOCATED ON TOP OF DOOR. WIRE TO EXISTING POWER SUPPLY AND CONTROLS. MAIN

PANEL LOCATED IN THE NURSES STATION. SEE SPECIFICATION 08 71 00 FOR ADDITIONAL

REQUIRMENTS.

6. PROVIDE NEW CAT 6A CABLING FOR ALL NEW DEVICES. PROVIDE NEW CAT 6A PATCH PANEL AND

LOCATE ON EXISTING RACK, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. PROVIDE NEW HARD-WIRED 120V/24V CONNECTION AND TRANSFORMER FOR INFRARED FLUSH

VALVE OPERATION.

8. NEW EMERGENCY POWER OUTLET WIRED TO PANEL AND CIRCUIT SHOWN, COORDINATE ROUGH-IN

LOCATION WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED

ON/OFF CONTROL.

9. PROVIDE BARREL-KEY WALL SWITCH (20A,120-277V) TO CONTROL INDICATED POWER RECEPTACLE(S)

IN PATIENT ROOM. PROVIDE BARREL KEY SWITCH COVER PLATE AND INSTALL WITH TAMPER-

RESISTANT SCREWS.

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

Revisions: Date:

2 - ELECTRICAL RFI'S 04.20.2021

F

7.6

9.4

G

RECEIVING

B6127

BATH

B6131A

BATH

B6127A

TWO BED

B6131

ONE BED

B6135

HAC

B6133

BATH

B6137A

BATH

B6135A

BATH

B6192A

BATH

B6194A

TWO BED

B6192

SUN DECK

B6188

SECLUSION

B6134A

ANTE RM

B6134

TOILET

B6134B

TOILET

B6193B

SECLUSION

B6193A

ANTE RM

B6193

NURSE STATION

B6128

MEDICATION

B6128A

WORK RM HOUSE

STAFF

B6104

STAFF TOILET

B6125

COPY

B6124

HAC

B6184A

DAY RM

RECREATION

B6184

NON-FOOD STRG

5C139

TELE

B6184C

ADL KITCHEN

5C133C

CORRIDOR

B6C06

DINING

5C133A

CORRIDOR

B6C05

CORRIDOR

B6C02

SALLY PORT

B6C02A

CORRIDOR

B6C03

3 3

L1

L1

L1

L2

L2

L2

L2

L2

L2

L2 L2

L2

L4

L4

L4

L4

L4

L4

L4

L4

L4 L4 L4

L2

L2

L2

L2L2

L2

L1 L1 L1 L1

L4

L4 L4

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1A

L1 L1

L1A

L1

L1

L1

L2

L2

L2

L1A

L1A

L1A

L1A

L1A

L1

L3 L3

L3

L3

L3 L3

L3

L3

L3

L3 L3

L3L3

L3 L3

5 5

4 4

L5 L5

L3

L3 L3

L1 L1

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12 /20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/2

/2

:3

:3

P

M

EL106A

LIGHTING PLAN - LEVEL 6 - AREA A - NEW 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F2

LIGHTING PLAN - LEVEL 6 - AREA A -

NEW

1 RELOCATE SECLUSION LIGHT SWITCHES TO NURSE’S

STATION, PROVIDE DIMMABLE SWITCHES (TOTAL 4).

2 REPLACE EXISTING CORRIDOR LIGHT SWITCHES WITH

DIMMABLE SWITCHES.

3 REMOVE ALL EXISTING INTERIOR 2 X 4 RECESSED LIGHT

FIXTURES AND RECESSED CAN LIGHTS IN MENTAL HEALTH

UNIT. IN PATIENT ROOM AND SECURE AREAS, REPLACE WITH

VANDAL-RESISTANT, NON-LIGATURE 2X4 RECESSED LED

LIGHTING. IN STAFF ONLY SPACES, REPLACE WITH STANDARD

LED LIGHT FIXTURES.

4 REMOVE ALL PATIENT ROOM ABOVE SINK LIGHT SURFACE

FIXTURES AND RECESSED SHOWER LIGHTS. REPLACE WITH

VANDAL-RESISTANT, NON-LIGATURE LED LIGHTING.

5 REMOVE ALL EXIT LIGHTING, REPLACE WITH

VANDAL-RESISTANT, NON-LIGATURE LED EXIT LIGHTING.

6 REMOVE TWO (2) WALL-MOUNTED EXTERIOR LIGHT FIXTURES.

REPLACE WITH VANDAL RESISTANT, NON-LIGATURE LED

LIGHTING AT OUTDOOR DECK.

7 REPLACE ALL BACK-OF-HOUSE FLUORESCENT FIXTURES WITH

LED FIXTURES.

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

Revisions: Date:

7.6

9.4

H I K L

ELEC EQUIP

B6139

GROUP THERAPY

B6143

ONE BED

B6147

ONE BED

B6149

BATH

B6147A

BATH

B6149A

ONE BED

B6150

BATH

B6150A

TWO BED

B6208

QUIET

B6146

TWO BED

B6206

BATH

B6206A

BATH

B6208A

WASHER DRYER

B6205

NOURISH

KITCHEN

B6203

CLEAN UTILITY

B6201

CLEAN LINEN

B6199

OFFICE

B6140

TELE

B6142

RED BAG

STORAGE

B6138

SOILED UTILITY

B6136

LOCKER ROOM

B6195

TELE EQUIP

B6197

TWO BED

B6204

TWO BED

B6200

BATH

B6200A

BATH

B6204A

STAIR 2

BS2

TWO BED

B6194

ONE BED

B6137

CORRIDOR

B6C03

CORRIDOR

B6C04

TYP.

L1 L1

L1 L1 L1 L1

L1

L1 L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1

L1L1

L1L1

L1

L1A

L1

L1

L1

L1A L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1A

L1

L1

L1

L1

L1

L1

L1L1

L3

L3

L3

L3 L3

L3

L3 L3

L3

L3

L3

L3

L3

L3

L3L3

L3

L3

L3L3

L3

L3

L3

L3

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

3 3

DEDUCT #1

L3

L3

L3

TYP.

L1 L1 L1 L1 L1

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA B

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12 /20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/2

/2

:3

:3

P

M

EL106B

LIGHTING PLAN - LEVEL 6 - AREA B - NEW 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F3

LIGHTING PLAN - LEVEL 6 - AREA B -

NEW

1 REPLACE EXISTING CORRIDOR LIGHT SWITCHES WITH

DIMMABLE SWITCHES.

2 REMOVE ALL EXISTING INTERIOR 2 X 4 RECESSED LIGHT

FIXTURES AND RECESSED CAN LIGHTS IN MENTAL HEALTH

UNIT. IN PATIENT ROOM AND SECURE AREAS, REPLACE WITH

VANDAL-RESISTANT, NON-LIGATURE 2X4 RECESSED LED

LIGHTING. IN STAFF ONLY SPACES, REPLACE WITH STANDARD

2X4 LED LIGHT FIXTURES.

3 REMOVE ALL PATIENT ROOM ABOVE SINK LIGHT SURFACE

FIXTURES AND RECESSED SHOWER LIGHTS. REPLACE WITH

VANDAL-RESISTANT, NON-LIGATURE LED LIGHTING.

4 REMOVE ALL EXIT LIGHTING, REPLACE WITH

VANDAL-RESISTANT, NON-LIGATURE LED EXIT LIGHTING.

5 REPLACE ALL BACK-OF-HOUSE FLUORESCENT FIXTURES WITH

LED FIXTURES.

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12 /20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/2

/2

:3

:3

P

M

E-500

ELECTRICAL DETAILS 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL LOAD LAMP BALLAST

L1

L2

L3

L4

2X4 RECESSED LED DIRECT-INDIRECT TROFFER, 6" DEEP, HIGH ABUSE,

LIGATURE RESISTANT (OWNER TO CONFIRM DECORATIVE PANEL OPTIONS)

VISA CM1924-L35K-L-MVOLT-L-90CRI-ESS-NAF 72 VA LED 0-10V DIMMABLE

RECESSED SEALED 6" LED DOWNLIGHT FOR BEHAVIORAL HEALTH KURTZON VL-PBD-4-8-DLM20-940-UNV-WB-TPWHT

37 VA LED 0-10V DIMMABLE

6" APERTURE, LED DOWNLIGHT, FLAT CLEAR LENS, IP66 RATED GOTHAM EVO SERIES

12 VA LED 0-10V DIMMABLE

37 VA LED 0-10V DIMMABLE

2x2 RECESSED LED DIRECT-INDIRECT TROFFER, 3-1/2" DEEP, SNAP-IN FROSTED

ACRYLIC DIFFUSER

FOCAL POINT FARL 22 AC 4000L 35K 1C UNVL11 G1

SM WH

EX VRES SERIES OF ACTIVELED® ANTI LIGATURE AND HIGH ABUSE

LIGHTING EXIT SIGN

ACTIVELED VRES-UE SERIES

18 VA LED

VAN

RECESSED MIRROR WITH LED LIGHTING (SEE ARCHITECTURE FOR VANITY

LOCATIONS AND FINISH SELECTIONS)

VISA CB1850-L40K-H-MVOLT-NGT-AMC-RB 37 VA LED 0-10V DIMMABLE

L5 WALL MOUNTED, LED DOWNLIGHT, IP65 & IK10 RATED VANDALITE WHARFEDALE SERIES 24 VA LED 0-10V DIMMABLE

Revisions: Date:

2 - ELECTRICAL RFI'S 04.20.2021

L1A

2X4 RECESSED LED DIRECT-INDIRECT TROFFER, 6" DEEP, (OWNER TO

CONFIRM DECORATIVE PANEL OPTIONS)

VISA CM1946-L35K-L-MVOLT-L-90CRI-ESS-NAF 72 VA LED 0-10V DIMMABLE

Sheets
E-106A - ELECTRICAL PLAN - LEVEL 6 - AREA A - NEW
E-106B - ELECTRICAL PLAN - LEVEL 6 - AREA B - NEW
EL106A - LIGHTING PLAN - LEVEL 6 - AREA A - NEW
EL106B - LIGHTING PLAN - LEVEL 6 - AREA B - NEW
E-500 - ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .