Question_and_Answer_A003_63095201024A.pdf

PDF 20 KB Posted

Attached to
Sypply & Install New Annunciators Federal contract opportunity
Solicitation number
63095201024A
Issued by
International Boundary and Water Commission U.S.-Mexico

View the file

Other files for this federal contract opportunity

Other files attached to Sypply & Install New Annunciators, newest first.
File Type Posted
Schematic_alarms1.pdf PDF
Schematic_ARS1557.pdf PDF
Schematic_ASR1554.pdf PDF
Schematic_Annunciator_Teminal_Block.pdf PDF
Schematic_ASR1555.pdf PDF
Schematic_ASR1556.pdf PDF
Question_and_Answer_A002_63095201024A.pdf PDF
PRS_Annunciator_Project_Upgrade_Table.pdf PDF
Compensation_and_Liability_Insurance_--_IBWC.pdf PDF
Wage_Determination_15-5301_Rev._-1.pdf PDF
PWS_Annunciator_Project_Upgrade.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question and Answer Amendment A003

Solicitation Number 63095201024A Supply and Install New Annunciators

Q) We have been quoted 35-40 week delivery for all Tray Rated Fiber Optic Cable.

This does not fit within the allotted schedule of 150 days. We can do the same job cheaper and faster with Cat-5 cable. This is a shelve stocked item.

A) The Government requires fiber optic type of communication cable based on new equipment specified in the scope of work, plus the amount of fiber optic required for this project is not more than 200 ft.

Q) I did have one technical question. In the bid package you detail that you want the mechanical relays of your existing alarm system to be replaced with PLC IO cards. What is the coil voltage of the existing mechanical relays so that we can spec in the right PLC IO card?

A) The coil voltage of the existing mechanical relay is 125 V DC.