528-21-110 - PICTURES - Service - E-Wing AHU Repairs 25MAR22 02.pdf
PDF 3 MB Posted
- Attached to
- Z1DA--528-21-110 BUFFALO E-WING AHU REPAIRS Federal contract opportunity
- Solicitation number
- 36C24222B0049
About this file
This document outlines a federal contract opportunity for repair services on air handling units at the Veterans Affairs Western New York Healthcare System facility in Buffalo, New York. The scope of work includes replacing exhaust fans and steam humidifiers on two air handling units serving the emergency department and intensive care units, replacing preheat coils, duct silencers, and piping insulation. It also involves demolishing and replacing the fan wall on the air handling unit for the surgical intensive care unit. The contractor must provide all necessary labor, equipment, and materials except for certain components that will be government furnished. The work must be completed within 180 days of contract award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Pre Bid Attendance 528-21-110 E-Wing AHU.pdf | ||
| 36C24222B0049 0001.docx | DOCX document | |
| WAGE DETERMINATION.pdf | ||
| 528-21-110 E-Wing AHU Repair Specifications.pdf | ||
| 36C24222B0049.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA WESTERN NEW YORK HEALTHCARE SYSTEM
FACILITIES ENGINEERING
BUFFALO VA MEDICAL CENTER | 3495 BAILEY AVENUE, BUFFALO, NY 14215 | (716) 834‐9200
Exhaust Fan 1
The exhaust fan is a Chicago Blower:
Unit Serial Number: 347925
Unit Size: 36 ½
Motor is Baldor Super-E EM4110T-G
Combined weight is approximately 1425 lbs.
New fan to be installed.
New motor to be installed.
Existing fan to be removed.
Existing fan is approximately 8 feet from deck.
Steam Humidification
AHU 1
Existing steam humidifier to be removed
Existing steam piping
Location for new humidifier.
Approximately 8’ from existing steam pipe to center of door for new location.
AHU 1 Steam relocation.
Interior view of new humidifier location.
AHU 2
Existing Steam Humidifier to be replaced.
BUFFALO VA MEDICAL CENTER | 3495 BAILEY AVENUE, BUFFALO, NY 14215 | (716) 834‐9200
Insulation to be replaced. L.P Steam, replace vertical run to elbow in overhead.
AHU 1 Other Services
Replace fiberglass insulation on Chill Water Supply Piping up to yellow line and provide labels.
Replace all fiberglass insulation on return line pictured and provide labels.
RETURN
SUPPLY
BUFFALO VA MEDICAL CENTER | 3495 BAILEY AVENUE, BUFFALO, NY 14215 | (716) 834‐9200
Replace fiberglass insulation on Chill Water Supply Piping up to yellow line and provide labels.
Replace fiberglass insulation on return line up to yellow lines and provide labels.
AHU 2 Other Services
Demo and Replace filter frames.
SUPPLY
RETURN
VHAWNYHERBYC
Line
Filter bank locks
Clean Flow Duct Silencers to be replaced
Clean Flow Duct Silencers to be replaces
Floor section to be replace with Clean Flow Silencers
Floor section to be replace with Clean Flow Silencers
Preheat coils to be replaced. Break at unions, piping to remain. New coils supplied by VAMC. Glycol in coils to be reclaimed by contractor.
Preheat coils to be replaced. Break at unions, piping to remain. New coils to be supplied by VAMC. Glycol in coils to be reclaimed by contractor.
Replace 3-way valve. Valve supplied by VAMC, contractor to include new fittings.
SICU AHU Fans
Fan and Motor to be demolished and disposed of.
Fan and Motor to be demolished and disposed of. Clean and prep surfaces for new fan cubes.
New fan cube to be installed
New fan and motor to be installed
Backdraft dampers to be installed (we have missing slat).