Site Drawings.pdf
PDF 4 MB Posted
- Attached to
- Z1DZ--657-21-711JB EHRM Cerner Admin Space Construction Support - Jefferson Barracks Federal contract opportunity
- Solicitation number
- 36C77621B0012
About this file
This notice announces an upcoming solicitation for the EHRM Cerner Admin Space Construction Support project at the Jefferson Barracks VA Medical Center. The Department of Veterans Affairs, through its Veterans Health Administration Program Contracting Activity Central, intends to issue a solicitation and subsequently award a firm-fixed-price contract to provide design-build construction services. The solicitation is expected to be released in early July 2021 under solicitation number 36C77621B0012. Questions regarding this pre-solicitation notice must be submitted in writing by the deadline.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C77621B0012 0005.docx | DOCX document | |
| 36C77621B0012 0004.docx | DOCX document | |
| 36C77621B0012 0003.docx | DOCX document | |
| 36C77621B0012 0002.docx | DOCX document | |
| 36C77621B0012 0001.docx | DOCX document | |
| ATTACHMENT 3 - Contractor Safety - Environmental Form.docx | DOCX document | |
| ATTACHMENT 2 - Limitations on Subcontracting - Construction.docx | DOCX document | |
| ATTACHMENT 4 - DBA Wage Rates.pdf | ||
| ATTACHMENT 1 - Specifications Final 6-4-21.pdf | ||
| 36C77621B0012_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
AREA OF
WORK
APPLICABLE CODES & DESIGN STANDARDS
CODES / REGULATIONS (LATEST EDITION UNLESS NOTED OTHERWISE):
A. Building Classification – JB Building 1
1. Occupancy Classification – JB Bldg. 1:
a. Existing Building: I-2 Institutional, Hospital (IBC), Health Care (New & Existing) (NFPA)
b. Occupancy separation:
1) Healthcare requires a 1-hour smoke barrier every 22,500sf, 200ft travel, 30sf net on each side.
2) If entire building healthcare, then:
i. Corridor wall can be smoke partition.
c. Common Path Limit: 100ft.
d. Dead End Limit: 30ft.
e. Travel Distance Limit: 200ft.
g. 8ft corridors for gurney traffic. 44” clear for remainder.
h. Doors required to be 3’0” wide minimum, with openings to be sized appropriate to accommodate room functions.
2. Construction Type:
a. Construction Type (IBC/NFPA): Type I-A/Type I (332) (Assumed based on 1922 construction).
3. Seismic Design:
a. VA H-18-8 / July 2008 / Design Category = Table 1: Critical Facility (Hospital)
1) Spectral Response Accelerations:
i. SS (VA H-18-8) – Table 3 0.596
ii. SI (VA H-18-8) – Table 3 0.171
b. IBC Seismic (Chpt. 1613):
1) Hospital with Emergency Room - Seismic Risk Category IV (Table T1604.5)
2) Seismic Design Category – Short Period (0.2-second) Response Acceleration based on IBC SDS @ 0.183g = C (1613.3.4,Table T1613.3.5(1))
3) Seismic Design Category- 1-Second Period Response Acceleration based on IBC SD01 @ 0.596g = D (1613.3.4, Table T1613.3.5(2))
c. Renovation project will require seismic design considerations for installation of new suspended acoustical ceilings and MPFE items. Campuses are located in Zone 1. Need to review with VASTLHCS Engineering for current methods use in renovations.
Approximate Project Area JB – Bldg. 1 (Abatement + Renovation) 3,600sf
CODE INFORMATION
A. Building Codes and Regulations (Latest Editions)
1. Guidance on the Technical Information Library (TIL) (http://www.cfm.va.gov/til/).
a. Master Construction Specifications, Program Guide, PG‐18‐1
b. Design and Construction Procedures, PG‐18‐3
c. Standard Details, PG‐18‐4
d. Equipment Guide List, PG‐18‐5
e. Equipment Reference Manual, PG‐18‐6
f. Design Manuals for applicable disciplines, PG-18-10
g. Design Guides for graphics, PG-18-12
h. Barrier Free Design Guide, PG-18-13 (See item A.11 below)
i. Environmental Compliance Manual, PG-18-17
j. VA Sustainable Design Guide
k. VA Directives, Design Manuals and Design Guides
1) VHA Directive 1116(2) – Sterile Processing Services (SPS)
2) VHA Directive 1761(1) – Supply Chain Management (SCM)
l. VA Design Alerts
m. VA Quality Alerts
n. VA National CAD Standard Application Guide and BIM Guide
o. VA Drawing Title Box Layout
p. VA AE Design Submission Requirements
q. VA Design Review Checklists
r. Minimum Requirements for A/E Submissions for Minor and Minor Miscellaneous projects, Handbook
H‐18‐15 Volume C
s. Office of Construction & Facilities Management Design Manual, Architectural Design Manual
t. VA Medical Center Memorandums (MCM) (request from COR)
u. Manual for Preparation and Issuance of Construction Solicitation and Contract Documents
v. Technical Summaries
w. National Codes and Standards (NFPA, NEC, Natl.
Plumbing Code, EPA, OSHA, etc.)
x. Uniform Accessibility Standards
y. Asbestos Abatement Design Manual
z. Electrical Design Manual for Hospital Project
aa. Fire Protection Design Manual
bb. Estimating Manual
cc. Seismic Requirements
dd. VA Form 10-6238 Estimate Worksheet.
2. NFPA and VA Fire Projection Manual for fire protection.
3. NFPA 101 Life Safety Code: addresses life safety and fire protection features.
a. International Building Code (IBC): Items not addressed in NFPA 101, including structural strength, seismic stability, sanitation, adequate light and ventilation, and energy conservation.
4. NFPA National Fire Codes with the exception of NFPA 5000 and NFPA 900
5. Occupational, Safety and Health Administratio (OSHA) Standards.
6. Joint Commission on Accreditation of Healthcare Organizations (JCAHO) Requirements.
7. National Electrical Code (NEC)
8. International Plumbing Code (IPC)
9. ASME Boiler and Pressure Vessel Code
10. ASME Code for Pressure Piping
11. American with Disabilities Act (ADA), Architectural Barriers Act Accessibility Standards (ABAAS) including VA supplement, Barrier Free Design Guide (PG-18-13)
12. State of Missouri Department of Health and Senior Services
13. The Provisions for Construction and Safety Signs.
Stated in the General Requirements Section 01010 of the VA Master Construction Specification.
14. Ventilation for Acceptable Indoor Air Quality - ASHRAE Standard 62.1- 2004.
15. Safety Standard for Refrigeration Systems – ASHRAE Standard 15 – 2007.
16. American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Standard 90.1 2010, except where 90.1-2004 or 90.1-2007 are referenced or adopted by specific Veterans Affairs Design and Construction Procedures.
17. Energy Policy Act of 2005 (EPAct) and American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Standard 90.1-2004 Appendix G.
18. Extended Industry- Standard Architecture (EISA) 2007 for new facility fossil fuel generated energy consumption reduction.
B. Authorities Having Jurisdiction:
1. VA must function as the Authority Having Jurisdiction (AHJ). VA is not subject to local imposition of code enforcement procedures.
2. Joint Commission on the Accreditation of Healthcare Organizations (JCAHO)
3. US Department of Health & Human Services (H&HS) th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
##-XX-###
DISCIPLINE DESIGNATORS EXAMPLES
GI = GENERAL INFORMATION
CS = CIVIL SITE
AD = ARCHITECTURAL DEMOLITION
AS = ARCHITECTURAL SITE
AE = ARCHITECTURAL ELEMENTS
GENERAL & FLOOR PLANS
AI = ARCHITECTURAL INTERIORS
AG = ARCHITECTURAL GRAPHICS
AF = ARCHITECTURAL FINISHES
AC = ARCHITECTURAL CEILING PLAN
AW = ARCHITECTURAL WAYFINDING
AP = ARCHITECTURAL SPACE PLANNING
FLOOR PLANS & SCHEDULES
AL = ARCHITECTURAL LIFE SAFETY
DRAWINGS
SF = STRUCTURAL FRAMING
MH = MECHANICAL HVAC
PL = PLUMBING FIXTURES
EL = ELECTRICAL LIGHTING
DRAWING INDEX LEGEND
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
VA PROJECT NUMBER: 657-21-711JB
JEFFERSON BARRACKS
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
DRAWING INDEX
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
SHEET TYPE DESIGNATORS
0 = GENERAL
1 = PLANS
2 = ELEVATIONS
3 = SECTIONS
4 = LARGE-SCALE VIEWS
5 = DETAILS
6 = SCHEDULES & DIAGRAMS
7 = USER DEFINED
8 = USER DEFINED
9 = 3D REPRESENTATIONS
BUILDING NUMBER
FLOOR NUMBER ON PLAN SHEETS
SHEET NUMBER
/2
/2
:5 :1
P
M
01-G1-000
COVER SHEET
HT
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
Sheet List
Sheet Number Sheet Name
01-G1-000 COVER SHEET
01-GI-001 ICRA PLAN
01-HA-011 HAZARDOUS ABATEMENT
01-AD-100 DEMO PLANS
01-AE-100 FLOOR PLANS
01-AE-101 CEILING PLANS
01-E-100 ELECTRICAL PLAN
01-AI-100 FURNITURE & FINISHES
VICINITY MAP
PROJECT
LOCATION
TRUE
NORTH
1" = 100'-0"
KEYPLAN
PLAN
NORTH
HARD WALL
CONSTRUCTION BARRIER.
MANOMETER LOCATION
LOCK DOOR
NEGATIVE AIR
EXHAUSTED
TO EXTERIOR
CONTRACTOR
ENTRY/EXIT
ANTE ROOM
NEGATIVE AIR
EXHAUSTED
TO EXTERIOR
EXTERIOR
EXIT - 95'
ANTE ROOM
85' TO
EXIT
116'
TO
EXIT
120' TO
EXTERIOR
EXIT
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-GI-001
ICRA PLAN
HT
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
ICRA PLAN
1/8" = 1'-0"
LIFE SAFETY PLAN
IMG
A
IMG
B
BREAK
GW05A
OPEN WORK
GW04
CONFERENCE
GW07
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
WAITING
GW10
37' - 4 7/8"
CORRIDOR
H0011
ABATEMENT KEYNOTES/LEGEND
SCRAPE AND STABILIZE LEAD PAINTED SURFACES AT CONCRETE
DECK INSIDE GROSS REMOVAL NEGATIVE PRESSURE
CONTAINTMENT
REMOVE EXISTING ASBESTOS CONTAMINATED EXHAUST FAN,
DUCT AND HORIZONTAL SHAFT. STABILIZE EXITING FRAMING TO
REMAIN
3884 SF
SCRAPE AND STABLIZE LEAD PAINTED WALLS FROM FLOOR TO
DECK 170 LF
DEMOLISH EXISTING LEAD-BASED PAINT CONTAMINATED CEILING
TILE / GRID / LIGHTS - PROTECT/SUSPEND ALL EXISTING CEILING
MOUNTED DEVICES FOR REINSTALLATION IN THE SAME PLACE AT
NEW CEILING - SEE RCP FOR LIGHTS TO PROTECT/REINSTALL
3576 SF
QUANTITY GRAPHIC
SYMBOL
REMOVING NON-ACM TILE LAID IN ACM MASTIC
19 LF
NOT IN CONTRACT
REMOVE EXTERIOR ASBESTOS CONTAINING STUCCO TO 6'-0"
AFF. ENCAPUSLATE/STABILIZE ACM AT CUT EDGE
6 115 SF
CLEAN EXPOSED VAULT SURFACES OF POTENTIAL LEAD PAINT
DUST/CHIPS
9' - 0"
11' - 8"
8' - 8"
7' - 8"
9' - 0"
7' - 8"
8' - 3"
9' - 0"
7' - 7"
8' - 7"
7' - 7"
6' - 6"
8' - 9"
8' - 0"
8' - 9"
7' - 3" 11' - 3"
8' - 0"
SD
FAS
FAS
SD
SD
SD
FAS
SM
ME
ME
MEME
SD
FASFAS
FAS
SD
ME
SCSD
FAS
FAS
OS
OS
FAS
FASOS
ME
7' - 5"
FAS
TYP
BREAK
GW05A
OPEN WORK
GW04
CONFERENCE
GW07
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
WAITING
GW10
1 1
2 2
CORRIDOR
H0011
EXISTING PARTITION OR WALL
TO REMAIN
NEW PARTITION
NORTH ARROW
SYMBOLS
EXISTING PARTITION OR
CONSTRUCTION TO BE
REMOVED
EXISTING DOOR TO
REMAIN
NEW DOOR
ROOM NAME AND NUMBER
SECTION - BUILDING
CEILING HEIGHT
EXISTING DOOR TO BE REMOVED
PARTITION TYPE01
KEYNOTE#
AD888
AD888
SIM
SECTION - WALL
SECTION - CASEWORK
PLAN
NORTH
TRUE
NORTH
ARCHITECTURAL ANNOTATION
ARCHITECTURAL MODELING
Room Name
10'-0"
NOT ALL SYMBOLS ARE USED
NOT ALL SYMBOLS ARE USED
AD888
SECTION - DETAIL
NOT IN
CONTRACT
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-HA-011
HAZARDOUS ABATEMENT
HT
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
HAZARDOUS ABATEMENT PLAN
ASBESTOS AND LEAD ABATEMENT GENERAL NOTES
1. THE SCOPE OF THE ASBESTOS RELATED WORK CONSISTS OF REMOVING
APPROXIMATELY 3600 SF OF NON-ACM TILE LAID IN ACM MASTIC AND
APPROXIMATELY 115 SF OF EXTERIOR ASBESTOS CONTAINING STUCCO. LEAD
RELATED WORK CONSISTS OF THE DEMOLITION OF LEAD CONTAMINATED CEILINGS
AND STABILIZING LEAD-BASED PAINT ON THE CONCRETE CEILINGS
2. WIPE DOWN ALL EXPOSED SURFACES AND EXISTING COMPONENTS TO REMAIN THAT
WERE POSSIBLEY EXPOSED TO LEAD CONTAINING DUST OR PAINT CHIPS.
(DIFFUSERS, FCU'S ETC.)
3. THE ABATEMENT, DEMOLITION AND STABLIZATION WILL BE CONDUCTED INSIDE
NEGATIVE PRESSURE GROSS REMOVAL CONTAINMENTS AND ALL WORK SHALL BE
CONDUCTED IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL REGULATIONS
AND THE CONTRACT SPECIFICATIONS.
4. ALL ABATEMENT WORK SHALL BE CONDUCTED IN MULTIPLE PHASES DURING
ADMINISTRATIVE HOURS (8:00 AM TO 4:30 PM) MONDAY - FRIDAY
5. WORK SCHEDULES AND LIMITS OF ABATEMENT SHALL BE COORDINATED WITH THE
VA COR AND VPIH FOR APPROVALS, UNLESS OTHERWISE INDICATED ON THE
KEYNOTES.
6. THE ABATEMENT CONTRACTOR SHALL SUBMIT A DETAILED WORK PLAN AND
ABATEMENT SCHEDULE WITH THE REQUIRED SUBMITTALS. ANY CHANGES TO THE
PROCEDURES, CONTAINMENT LIMITS AND PHASING SHALL BE SUBMITTED TO THE VA
COR AND VPIH FOR APPROVALS.
7. THE LOCATIONS AND QUANTITIES SHALL BE FIELD VERIFIED BY THE ABATEMENT
CONTRACTOR.
8. THE LIMITS OF REMOVAL AND EXTENT OF THE CONTAINMENTS SHALL BE VERIFIED
WITH THE VA COR AND VPIH. FOR CLARITY, THE DRAWINGS ONLY SHOW
REPRESENTATIVE LOCATIONS.
9. ALL LOADOUT PROCEDURES SHALL BE COORDINATED WITH THE VA COR AND VPIH.
10. ALL POLYETHYLENE SHEETING USED FOR THE ABATEMENT PROJECT SHALL FIRE
RETARDANT.
11. THE LOCATIONS OF ABATEMENT DECONTAMINATION UNITS AND WASTE DISPOSAL
CONTAINERS SHALL BE FIELD VERIFIED WITH THE VA COR AND VPIH.
12. SEE DEMOLITION ICREA PLAN FOR TEMPORARY PARTITION AND INFECTION
CONTROL DETAILS.
13. ALL PERIMETER AIR MONITORING AND CLEARANCE SAMPLING WILL BE CONDUCTED
BY THE VPIH.
14. ALL LEAD WASTE SHALL BE TESTED BY THE ABATEMENT CONTRACTOR USING TCLP
ANALYTICAL METHODS TO DETERMINE PROPER WASTE DISPOSAL METHODS.
15. CPIH TO PROVIDE ALL SAMPLING & MONITORING NEEDED FOR LEAD
ABATEMENT/REMOVAL
16. TRACE AMOUNTS OF LEAD BELOW THE EPA HUD DEFINITION OF LEAD-BASED PAINT
WERE IDENTIFIED IN THE PROJECT AREAS. IT SHOULD BE NOTED THAT OSHA DOES
NOT RECOGNIZE THIS AS A THRESHOLD VALUE FOR LEAD EXPOSURE. ALTHOUGH
THE POTENTIAL LEAD HAZARD FOR NORMAL DEMOLITION OR CONSTRUCTION
ACTIVITIES IS LOW, ACTUAL LEAD EXPOSURE MAY VARY SIGNIFICANTLY DEPENDING
UPON THE SPECIFIC TASK, PROCEDURE AND OTHER WORK AREA CONDITIONS.
PROPER OSHA COMPLIANCE IS CONSIDERED PERFORMANCE BASED AND INCLUDES
EVALUATING POTENTIAL WORK EXPOSURES WITH AIR MONITORING OR BIOLOGICAL
EXPOSURE MONITORING (BLOOD LEAD TESTING), IF REQUIRED. UNLESS THE
DEMOLITION CONTRACTOR HAS HISTORICAL DATA DOCUMENTING THIS POTENTIAL
EXPOSURE, PERSONAL AIR SAMPLING SHALL BE CONDUCTED BY THE CPIH ON
REPRESENTATIVE TASKS TO DOCUMENT A NEGATIVE EXPOSURE FOR LEAD.
17. TEMPORARY LIGHTING OF SUFFICIENT LUMINOSITY SHALL BE PROVIDED FOR AND
USED BY THE ABATEMENT CONTRACTOR DURING THE ABATEMENT PROCESS
18. FIBERGLASS PIPE INSULATION WILL BE PRESENT IN ABATEMENT CONTAINMENTS.
PROPERLY WRAP AND PROTECT AS REQUIRED.
IMG A - INSIDE SHAFT LOOKING
NORTH
IMG B - INSIDE SHAFT LOOKING SOUTH
1/8" = 1'-0"
HAZARDOUS ABATEMENT CEILING PLAN
REMOVE ACM
CONTAINING
EIFS/PLASTER
REMOVE
CONTAMINATED
DUCT & GYP. BD.
REMOVE ACM
CONTAINING
EIFS/PLASTER
REMOVE
CONTAMINATED
DUCT
STABLIZE
CONTAMINATED
FRAMING
STABLIZE
CONTAMINATED
FRAMING
FE
FAP
FAP
UP
EQUIP.
PIT
EXIST.
EP
TYP
OPEN WORK
GW04
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
WAITING
GW10
CONFERENCE
GW07
BREAK
GW05A
OPEN WORK
GW04
A. EXISTING CONDITIONS ARE BASED ON INFORMATION OBTAINED
FROM EXISTING DRAWINGS AND FIELD SURVEY, AND WILL NOT
BE CONSTRUED AS "AS BUILT." THE CONTRACTOR WILL FIELD
VERIFY EXISTING CONDITIONS PRIOR TO ONSET OF
CONSTRUCTION.
B. CONTRACTOR WILL COMPLY WITH ALL INFECTIOUS CONTROL
REQUIREMENTS OF THE FACILITY. REVIEW REQUIREMENTS
PRIOR TO THE START OF CONSTRUCTION.
C. NOTES WHICH DO NOT HAVE ARROWS TO SPECIFIC ITEMS
INDICATE MATERIAL TO BE REMOVED FOR ENTIRE ROOM IN
WHICH NOTE OCCURS.
D. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER
SUITABLE FOR NEW FINISHES AND SURFACES.
E. WHEN DEMOLITION CAUSES OR EXPOSES DAMAGE TO FLOOR
SLAB, WALL, OR CEILING SURFACES WHICH WILL REMAIN IN THE
FINISHED WORK, SUCH CONDITIONS WILL BE REPAIRED AND
LEVELED AS REQUIRED TO RECEIVE NEW FINISHES. REPAIRS
MUST BE ACCEPTABLE TO OWNER.
F. THE CONTRACTOR WILL CLEAN, PATCH, AND REPAIR EXISTING
SURFACES AFFECTED DURING DEMOLITION AND CONSTRUCTION
TO MATCH EXISTING ADJACENT SURFACES. REPAIRS WILL BE
MADE AS TO MATCH EXISTING CONSTRUCTION IN MATERIAL,
METHOD, TECHNOLOGY, COLOR PATTERNS, ETC.
G. ALL DOORS SHOWN DASHED ARE TO BE REMOVED. ASSOCIATED
DOOR FRAME TO REMAIN UNLESS NOTED OTHERWISE.
H. THE CONTRACTOR WILL PROTECT THE EXISTING FLOOR FINISHES
TO REMAIN FROM DAMAGE THROUGHOUT CONSTRUCTION.
I. REMOVE EXISTING FLOOR BASE WHERE NEW FINISHES ARE
REQUIRED. CLEAN AND PREPARE SUBSTRATES AS REQUIRED TO
PRODUCE A FLAT, EVEN SURFACE IN A MANNER SUITABLE TO
ACCEPT NEW FINISHES.
J. PATCH FLOOR PENETRATIONS RESULTING FROM REMOVAL OF
EXISTING DUCTWORK, PIPING, AND ELECTRICAL RACEWAYS. FILL
PENETRATIONS WITH CONCRETE, FULL FLOOR THICKNESS AND
MAINTAIN FIRE-RESISTIVE RATING OF FLOOR SYSTEM. FINISH
SUBSTRATE IN A MANNER SUITABLE FOR NEW FLOOR FINISHES.
K. THE CONTRACTOR WILL FILL ALL WALL PENETRATIONS
RESULTING FROM THE REMOVAL OF EXISTING MEP DEVICES IN
THE INTERIOR WALLS TO REMAIN. THE PENETRATIONS WILL BE
FILLED FLUSH WITH, AND OF THE SAME MATERIALS AS, THE
SURROUNDING WALLS, THIS INCLUDES WORK ABOVE ALL
CEILINGS. THE CONTRACTOR WILL IN-FILL ALL OPENINGS IN
EXTERIOR WALLS RESULTING FROM THE REMOVAL OF LOUVERS,
EXHAUST FANS, ETC. THE OPENINGS WILL BE FILLED FLUSH
WITH, AND OF THE SAME MATERIALS AS, THE SURROUNDING
WALLS.
L. FOR ALL EXISTING ELECTRICAL DEVICES TO BE REMOVED FROM
WALLS WHICH REMAIN, CONTRACTOR SHALL DISCONNECT
POWER, REMOVE CONDUCTORS AND REMOVE DEVICE. WHERE
FIXTURES, EQUIPMENT OR DEVICES ARE REMOVED, PATCH THE
SURFACE AS REQUIRED TO MATCH THE EXISTING WALL
CONSTRUCTION.
M. ALL EXISTING ELECTRICAL EQUIPMENT, MISCELLANEOUS CABLES,
CONDUITS, WIRING DEVICES, ETC. TO BE REMOVED SHALL
BECOME THE PROPERTY OF THE CONTRACTOR, UNLESS
OTHERWISE NOTED. THE CONTRACTOR SHALL REMOVE THESE
ITEMS FROM THE PREMISES.
N. NOISE PRODUCING WORK ABOVE 85 DB WILL NOT BE ALLOWED
DURING NORMAL WORKING HOURS AND MUST BE SCHEDULED
WITH THE VA PROJECT ENGINEER FOR OTHER TIMES. THIS
INCLUDES JACKHAMMERING CONCRETE, SAW CUTTING
CONCRETE, FREQUENT HAMMER DRILLING OF CONCRETE, ETC.
GENERAL DEMOLITION NOTES
1. REMOVE EXTERIOR VENT AND PATCH W/ MTL PLATE TO MATCH ADJACENT
2. REMOVE EXISTING DEMOUNTABLE METAL WALLS INCLUDING TRACK. PREP
AS REQUIRED TO RECIEVE NEW FINISHES. REMOVE SURFACE MOUNTED
POWER AND DATA OUTLETS & WIRING BACK TO SOURCE.
3. SCRAPE & SKIM EXISTING WALL SURFACES TO RECIEVE NEW PAINT. TYP- @
ALL EXITING WALLS
4. REMOVE EXISTING AHU AND ASSOCIATED ELEC. REMOVE ASSOCIATED
PIPING BACK TO MAIN AND CAP.
5. NOT USED
6. REMOVE AND DISCARD EXISTING CASEWORK TYP. THROUGHOUT WORK
AREA U.N.O. REMOVE ANY ASSOCIATED ELECTRIC BACK TO JUNCTION BOX.
7. REMOVE EXISTING SINK/EYEWASH. REMOVE & CAP ASSOCIATED
PLUMBING BACK TO MAIN. TURN OVER EYEWASH TO MEDICAL CENTER.
8. REMOVE EXISTING SINK AND CASEWORK. REMOVE AND CAP ASSOCIATED
PLUMBING BACK TO MAIN.
9. REMOVE EXISTING COLD WAVE UNIT, ASSOCIATED DUCTWORK,
DISCONNECT SWITCH & ASSOCIATED ELEC. REMOVE ASSOCIATED
PLUMBING - CAP AT SOURCE
10. REMOVE EXISTING SPEAKER AND 'NOW SERVING' SIGN NEAR CEILING.
REMOVE ANY ASSOCIATED WIRING BACK TO SOURCE.
11. REMOVE EXISTING EYEWASH. REMOVE PIPE BACK TO MAIN & CAP
12. RETAIN CARD READER ON CASEWORK FOR REINSTALLATION ON NEAREST
WALL.
13. PROTECT EXISTING MOBILE AIR CONDITIONER FOR REINSTALLATION
UNDER NEW CASEWORK - SEE PLAN AND ELEVATIONS
14. REMOVE EXISTING EYEWASH AND TURN OVER TO MC. REMOVE
ASSOCIATED DRAIN/SUPPLY AS NECCESSARY TO REPORPOSE FOR NEW
KITCHEN SINK.
15. REMOVE EXISTING PLASTIC CORNER GUARDS THROUGHOUT SPACE &
PREP FOR INSTALLATION OF NEW SS CORNER GUARDS TO 8'-0" AFF.
16. DEMO WALL FOR INSTALLATION OF EXHAUST FAN IN EXISTING OPENING.
17. REMOVE EXISTING WATER SUPPLY FOR EYEWASH BACK TO MAIN.
18. REMOVE EXISTING PASS THRU - PREP FINISHES FOR INFILL
19. REMOVE EXISTING WINDOW INCLUDING SS TRANSACTION TOP AND
CAMERA AND ASSOCIATED WIRING- PREP FINISHES FOR INFILL
20. REMOVE EXISTING CHAIR RAIL. PREP FOR PAINT
21. REMOVE EXISTING WALL PROTECTION - PREP FOR PAINT.
22. REMOVE EXISTING FRAME/DISPLAY. PATCH/PREP SURFACES FOR PAINT.
23. REMOVE EXITING FLOOR TILE AND PREP FOR INSTALLATION OF NEW
FLOORING.
24. REMOVE EXISTING DOOR. EXISTING FRAME TO REMIAN. SEE DOOR
SCHEDULE.
25. REMOVE EXISTING WOOD TRIM AT TOP OF VAULT
26. RELOCATE FIRE EXTINGUISHER IN SAME ROOM. SEE PLAN
27. REMOVE EXISTING RUBBER BASE. PREP TO RECEIVE NEW BASE.
DEMOLITION PLAN KEYNOTES#
EXISTING PARTITION OR WALL
TO REMAIN
NEW PARTITION
NORTH ARROW
SYMBOLS
EXISTING PARTITION OR
CONSTRUCTION TO BE
REMOVED
EXISTING DOOR TO
REMAIN
NEW DOOR
ROOM NAME AND NUMBER
SECTION - BUILDING
CEILING HEIGHT
EXISTING DOOR TO BE REMOVED
PARTITION TYPE01
KEYNOTE#
AD888
AD888
SIM
SECTION - WALL
SECTION - CASEWORK
PLAN
NORTH
TRUE
NORTH
ARCHITECTURAL ANNOTATION
ARCHITECTURAL MODELING
Room Name
10'-0"
NOT ALL SYMBOLS ARE USED
NOT ALL SYMBOLS ARE USED
AD888
SECTION - DETAIL
NOT IN
CONTRACT
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-AD-100
DEMO PLANS
HT
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
DEMO PLAN
GENERAL NOTE: ALL UTILITY OUTAGES WILL BE
REVIEWED, COORDINATED WITH MC. CONTRACTOR
SHOULD PLAN FOR OUTAGES TO BE AFTER HOURS
PLAN
NORTH
FAP
FAP
UP
EQUIP.
PIT
OPEN WORK
GW04
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
BREAK
GW05A
CONFERENCE
GW07
01-AE-100 5
STORAGE
GW04B
A
04B
CORRIDOR
H0011
04A
Room
GW04A
EXISTING PARTITION OR WALL
TO REMAIN
NEW PARTITION
NORTH ARROW
SYMBOLS
EXISTING PARTITION OR
CONSTRUCTION TO BE
REMOVED
EXISTING DOOR TO
REMAIN
NEW DOOR
ROOM NAME AND NUMBER
SECTION - BUILDING
CEILING HEIGHT
EXISTING DOOR TO BE REMOVED
PARTITION TYPE01
KEYNOTE#
AD888
AD888
SIM
SECTION - WALL
SECTION - CASEWORK
PLAN
NORTH
TRUE
NORTH
ARCHITECTURAL ANNOTATION
ARCHITECTURAL MODELING
Room Name
10'-0"
NOT ALL SYMBOLS ARE USED
NOT ALL SYMBOLS ARE USED
AD888
SECTION - DETAIL
NOT IN
CONTRACT
1. INFILL OPENING. MATCH EXISTING CONDITIONS
2. MAINTAIN CLEAR AREA FOR AIR INTAKE AT EXISTING AIR
CONDITIONER
3. REINSULATE EXISTING 1 1/2"-2" STEAM PIPE AT 12" AFF. CONTACT
COR IN THE EVENT OF ANY CUTTING TO IDENTIFY ANY SPECIAL
PRECAUTIONS.
4. INFILL WALL AT REMOVED PASS THRU. MATCH EXISTING
CONDITIONS.
5. PROVIDE DOMESTIC WATER AND HOT WATER CONNECTION WITH
VALVES AT TIE-IN ABOVE CEILING IN ADJACENT SPACE AND AT
FIXTURE.
6. REWORK OPENING TO RECEIVE NEW HM DOOR & FRAME. FINISH
WITH DRYWALL. PAINT TO MATCH ADJACENT FINISHES. DOOR
HARDWARE TO INCLUDE 1 1/2 PAIR HINGES, CLOSER, LEVER
HANDLE WITH CLASSROOM LOCKSET. PAINT PT-1
7. PROVIDE & INSTALL BUTTON FOR AUTOMATIC DOOR OPENER -
HARD WIRED W/ SURFACE MOUNT CONDUIT
8. PROVIDE & INSTALL NEW OPERATOR AND AUTOMATIC DOOR
OPERATOR FOR EXISTING DOOR
9. INFILL WHERE EXHAUST FAN WAS REMOVED TO MATCH
ADJACENT CONSTRUCTION/FINISHES.
10. PROVIDE & INSTALL EXHAUST FAN
11. PROVIDE WATERLINE FOR VA PROVIDED REFRIGERATOR
12. PROVIDE COVER FOR EXISTING RADIATOR TO REMAIN.
13. PROTECT EXISTING PIPE AT THE FLOOR W/ 16 GA ALUMINUN
METAL SHROUD -PAINT
14. NOT USED
15. PATCH AND PAINT AT REMOVED CHAIR RAIL
16. PATCH AND PAINT AT REMOVED WALL PROTECTION
17. PROVIDE INSULATION AT EXISTING PIPES
18. EXISTING VERTICAL PIPE TO REMAIN - PAINT TO MATCH WALL
19. CLOSE OFF AREA BEHIND VAULT & INSTALL 6' ACCESS PANEL
20. INFILL EXISTING DOOR FRAME AT DOOR TO REMAIN WITH GYP
BOARD FLUSH WITH FACE OF FRAME. FINISH/PAINT TO MATCH
ADJACENT.
21. INFILL GAP BETWEEN EXISTING VAULT AND WALL WITH GYP. BD.
PAINT TO MATCH ADJACENT.
22. PATCH ANY HOLES IN PIPE COVERING. PAINT.
23. INSTALL 5/8" EXTERIOR GRADE GYP. BD. - PAINT TO MATCH
ADJACENT FINISHES
FLOOR PLAN KEYNOTES#
4' - 4" 3' - 0" 5' - 11"
OPEN EXISTING WALL AT
EXISTING WALL
PENETRATION - PROVIDE &
INSTALL EXHAUST FAN
PROVIDE FINAL
CONNECTIONS TO
RELOCATED MOBILE AIR
CONDITIONER
OPEN
FRIG
BY MC
LOCKABLE PLAM CABINETS
RB1
SOLID SURFACE TOP W/ 4"
INTEGRAL BACKSPLASH 4
01-AE-100
01-AE-100
ANGLED PLAM APRON
SINGLE BOWL STAINLESS
STEEL SINK W/ GOOSENECK
AND WRISTBLADE HANDLES.
GC TO PROVIDE HOT WATER
SUPPLY & WRAP EXPOSED
PIPE PER SPEC
Wall Base; REF: Schedule
FIN Floor; REF: Schedule
3-5/8" MTL Studs
@ 16" OC
Soffit Above
(1) Layer 5/8" GWB Type "X" Both Sides
STC 39
Exisitng Sub-floor / Slab
Partition Type Not to ScaleA
4 7/8"
Notes:
1. Head Similar
2. Provide (3) Anchors MIN per Jamb; (4) at Rated Partitions
3. Refer to Door Schedule for Ratings Required
4. HM Jamb Throat 1/8" Larger than Partition, Caulk and Paint , TYP
Double Stud @ Jamb
Welded HM Frame
X
P-Type;
REF: Plan
/1
1/2"
/3
1 13/16" ± Varies
REF:
Schedule
ADA COMPLIANT SINK & FAUCET; REF:
SPECS
1/2' SOLID SURFACE COUNTERTOP
- SCRIBE TO WALL
PLAM ON 3/4” MDF
1"
REMOVABLE GUARD - PLAM
ON 3/4” MDF, ATTACH TO
WOOD BLOCKJING BEYOND
WITH PANEL CLIPS
WOOD BLOCKING BEYOND,
ATTACH TO SIDE PANEL/WALL
8" MIN.
10" MIN.
M
IN
PLAM IN 1/4” MDF BACKING
RB-1
/4
3/4" EXTERIOR GRADE MDF
/2
4" BACKSPLASH
SOLID SURFACE SIDESPLASH - WHERE OCCURS
/8
2' - 1"
WASTE DISPOSER
PROTECT ANY EXPOSED PIPE PER
SPEC
CABINET PULL
(VERT. MOUNT)
1/2" SOLID SURFACE
COUNTERTOP
SEALANT
PLAM BASE CABINET;
NOTE: CABINET
INTERIOR, & ADJ.
SHELF TO BE BLACK
MELAMINE
SCHEDULED BASE
2X FTWD BLOCKING
2' - 1" U.O.N.
R E
F
E
LE
V A
T
IO
N S
2' - 0" 3"
R
'-1 /2
" T Y P
/2
TYP. SOLID SURFACE
EDGE PROFILE
/8
/2
TREATED WOOD BLOCKNIG
@ STRAP SUPPORT (TYP.)
2x4 FIRE TREATED WD CLEAT (PAINT)
2" DIA. GROMMET (WHERE OCCURS)
REF: ARCHITECTURE DRAWINGS
SS COUNTERTOP - SCRIBE TO WALL
2X FTWD BLOCKING(TYP.)
4" PLAM SS BACKSPLASH(WHERE OCCURS)
REF: FINISH SCHEDULE AND PLANS
2' - 6"
0'
/2
1' - 0" 45.00°
MTL STRAP SUPPORT BRACKET (PAINT)
R E
: E
LE
V A
T
IO
N
Ceiling
Light Gauge Metal Studs
@ 16" OC
Structure Above
(1) Layer 5/8" Gyp. Bd. Paint TO 4" above CLG
Exisitng Vault th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-AE-100
FLOOR PLANS
HT
6 164
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
FLOOR PLAN
1/4" = 1'-0"
BREAKROOM ELEVATION
PLAN
NORTH
Door Schedule
Mark Size Door TYPE Frame Type
Frame Material Jamb Detail Head Detail Door Hardware Set
04A 3-0 x 7-0 MTL EXIST.-PT4 PAINT PT-4 EXIST EXIST HW-4A REMOVE & SALVAGE EXISTING MAG LOCK & COORDINATE
INSTALL W/ NEW HARDWARE
04B 2-6 x 6-0 MTL HM -P4 PAINT PT-4 3/A-101 3/A-101 HW-11
07 3-0 x 7-0 MTL HM -P4 PAINT PT-4 3/A-101
SIM
3/A-101
SIM
HW-3
08 3-0 x 7-0 MTL EXIST.-PT4 PAINT PT-4 EXIST EXIST HW-3
011 3-8 x 7-0 MTL EXIST.-PT4 PAINT PT-4 EXIST EXIST HW-4A REMOVE & SALVAGE EXISTING MAG LOCK & COORDINATE
INSTALL W/ NEW HARDWARE
3" = 1'-0"
Detail - HM Door Jamb
1" = 1'-0"
DETAIL - ADA SINK
1" = 1'-0"
DETAIL - BASE CABINET
1" = 1'-0"
DETAIL - COUNTERTOP SUPPORT LEG
1" = 1'-0"
Detail at Vault-Ceiling Connection
(PAIR)
9' - 0"
11' - 6"
11' - 8"
6' - 6"
11' - 3"
SD SM
SD
FASFAS ME
SCSD
FAS
CONFERENCE
GW07
OPEN WORK
GW04
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
BREAK
GW05A
FAS
SD
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
SD
SD
SD
SD
SD
SD
SD
OS
OS
OS
L
IG
H T
IN
G
Z O
N E
L
IG
H
T
IN
G Z
O N
E
L
IG
H T
IN
G
Z O
N E
STORAGE
GW04B
HW
CW
CW
HW
7 7
9' - 0"
8' - 3"
8' - 7"
8' - 7"
7' - 5"
9' - 0"
7' - 7"
9' - 0"
7' - 7"
8' - 9"
7' - 3"
7' - 8"
8' - 8"
01-AE-100
CORRIDOR
H0011
NIC
N.I.C.
N.I.C.
N.I.C.
N E
W C
L G
E X
IS
T
C
L G
N
.I .C
8' - 0"
1. EXISTING MOTION SENSING LIGHTING CONTROL DEVICE TO BE
REWIRED TO ACHIEVE LIGHTING ZONES SHOWN ON PLLAN.
COORDINATE GROUPINGS AND LOCATIONS WITH COR. EACH
ZONE TO HAVE SEPARATE OCCUPANCY SENSOR.
2. EXISTING GYP. BD. CEILING TO REMAIN - PAINT
3. EXISTING LIGHTING TO REMAIN - PROTECT AND REINSTALL AT
CEILINGS TO BE REPLACED.
4. PROVIDE AND INSTLALL MOTION SENSING LIGHTING CONTROL
DEVICE.
5. REMOVE EXISTING CAMERA AND ASSOCIATED WIRING BACK
TO SOURCE. TURN OVER DEVICE TO MEDICAL CENTER.
6. REMOVE EXISTING WATER SUPPLY FOR EYEWASH BACK TO
MAIN
7. REPLACE EXISTING SURFACE MOUNTED LIGHT FIXTURES WITH
STANDARD 2X4 LED LAY IN FIXTURE
CEILING PLAN KEYNOTES#
EXIT LIGHT
24"x48" LAY-IN LED MECH. RETURN AIR
DIFFUSER
MECH SUPPLY AIR
DIFFUSER
REFLECTED CEILING PLAN LEGEND
GYP. BD. CEILING
CEILING HEIGHTX-X
12" x 48" LED
STRIP FIXTURE
24"x48" LAY-IN
LED -
EMERGENCY
24"x24" LAY-IN LED
SPRINKLER HEAD
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-AE-101
CEILING PLANS
HT
6 164
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
CEILING PLAN
GENERAL RCP NOTES:
1. PROVIDE NEW CEILING THROUGHOUT PROJECT AREA
AT PREVIOUS HEIGHTS U.N.O. CONTRACTOR TO
FIELD VERIFY EXITING CONSTRUCTION PRIOR TO
DEMOLITION FOR REINSTALLATION OF ALL CEILING
COMPONENTS / DEVICES IN PREVIOUS LOCATIONS.
2. A REDUCTION OF THE NUMBER OF CEILINGS AND
MAXIMIZING THE CEILING HEIGHT IS THE
PREFFERENCE OF THE MEDICAL CENTER.
WHENEVER POSSIBLE, IDENTIFY ANY OPPORTUNITIES
TO SIMPLIFY AND RAISE THE CEILING AND
COORDINATE SUCH CHANGES WITH COR.
3. MODIFY EXISTING MOTION SENSING LIGHTING
CONTROL DEVICES AS NECESARY TO ACHIEVE 3 THE
LIGHTING ZONES AS SHOWN ON PLAN. COORDINATE
FINAL GROUPINGS AND LOCATIONS WITH COR. EACH
ZONE TO HAVE SEPERATE OCCUPANCY SENSOR.
MODIFY SWITCHES ACCORDINGLY.
4. ALL LIGHT FIXTURES ARE NEW LED LUMINAIRES
U.N.O.
5. PROVIDE DOMESTIC WATER AND HOT WATER
CONNECTION WITH VALVES AT TIE-IN ABOVE CEILING
IN ADJACENT SPACE AND AT FIXTURE.
1. EXISTING PERIMETER RACEWAY AT 48" AFF TO REMAIN.
PLUG OPEN PORTS.
2. REMOVE EXISTING ELECTRICAL PANEL AND ASSOCIATED
WIRING.
3. REMOVE WHIP BACK TO JUNCTION BOX. TYP.
4. EXISTING AIR CONDITIONER AND SHUT OFF TO REMAIN
5. DEMO EMPTY CONDUIT TYP.
6. REMOVE EXISTING DATA JACK AND CABLING
7. REMOVE EXISTING POWER POLE AND WIRING BACK TO
SOURCE.
8. REMOVE CABINET MOUNTED CARD READER AND TURN OVER
TO MC.
ELECTRICAL DEMO KEYNOTES#
FE
FE
FAP
FAP
UP
EQUIP.
PIT
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
BREAK
GW05A
48" (2) 48" 48"
48" (2) 48" 48"48"
48"
36"
EXIST.
EP
J
J
J
3 (4) @ 30"
(2) @ 36"
(2) @ 72"
(2) 84"
72"
OPEN WORK
GW04
(2) 84"
CR
TYP
FE
J
T
48"
48"
X2
X2
J
J
X5
(6) 48"
X4
X3
X6 J
X2
X4
J
T
T
@CLG
T
T
J
48"
@CLG
48"
X5X5 30"
T
48"
48"
48"
48"
GFCI
J
CR
CONFERENCE
GW07
GENERAL NOTES: ELEC DEMO PLAN
1. REMOVE ANY REMAINING WHIPS BACK TO
JUNCTION BOXES TYP.
2. EXISTING ACCESS PANELS TO REMAIN
3. REMOVE ALL DATA OUTLETS AND CABLING BACK
TO CLOSET 1W01
4. REMOVE CAMERA & ASSOCIATED
WIRING/CONDUIT BACK TO SOURCE. TURN OVER
TO MC.
5. REMOVE JBOX AND ASSOCIATED WIRING BACK TO
SOURCE
6. ALL EXISTING PHONE LINES TO REMAIN.
7. REMOVE ANY EMPTY CONDUIT.
CR
e e e e e e e 72"
OPEN WORK
GW04
BREAK
GW05A
CONFERENCE
GW07
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
48" 48"
48" 48"
48"
J
J
J
(2) @ 72"
72"
(2) 84"
J
48"
48"
J
J
X4
J
J
J
48"
48"
48"
48"
GFCI
J e e e e e e e 72"
X2
X5
NOTE:
1. ALL ELECTRIC SHOWN IS
EXISTING U.N.O.
2. FURNITURE SHOWN IS
SUGGESTED BASED ON
PROVIDED DESIGN CRITERIA.
FINAL FURNITURE LAYOUT IS
BY CERNER. TBD.
3. ALL DATA IS TO BE INSTALLED
NEW WITH CAT6A CABLING
BACK TO DATA CLOSET IN
GC11.
4. NEW PATCH PANELS
COORDINATED W/ NEWLY
INSTALLED DATA DROPS
PROVIDE AND
INSTALL NEW
QUAD
RECEPTACLE
EXISTING MECH.
WAITING
GW10
PRINTING AREA
PROVIDE POWER
FOR NEW
AUTOMATIC DOOR
OPERATOR AND
OPENER/BUTTON
PROVIDE & INSTALL
NEW WIRELESS
AUTOMATIC DOOR
OPENER
STORAGE
GW04B
PROVIDE AND
INSTALL NEW
QUAD
RECEPTACLE
CORRIDOR
H0011
1. THE HOSPITAL INTENDS TO OCCUPY ADJACENT AREAS OF WORK WITHIN THE REMODEL AREA DURING DEMOLITION. UTILITIES AND SERVICES TO ANY EXISTING FACILITIES NOT BEING REMODELED SHALL NOT BE INTERUPTED WITHOUT THE PROJECT ENGINEER'S APPROVAL AS TO THE TIME AND DURATION.
2. FOR ALL EXISTING ELECTRICAL DEVICES TO BE REMOVED FROM WALLS WHICH REMAIN, CONTRACTOR
SHALL DISCONNECT POWER, REMOVE CONDUCTORS AND REMOVE DEVICE. WHERE FIXTURES,
EQUIPMENT OR DEVICES ARE REMOVED, PATCH THE SURFACE AS REQUIRED TO MATCH THE EXISTING.
SEE FLOOR PLANS FOR ADDITIONAL DETAILS
3. ALL EXISTING ELECTRICAL EQUIPMENT, MISCELLANEOUS CABLES, CONDUITS, WIRING DEVICES, ETC. TO BE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR, UNLESS OTHERWISE NOTED. THE
CONTRACTOR SHALL REMOVE THESE ITEMS FROM THE PREMISES.
4. ALL WIRING FOR A CIRCUIT WHICH IS TO BE REMOVED SHALL BE REMOVED BY THE CONTRACTOR BACK
TO THE PANEL WHICH SUPPLIED THE CIRCUIT U.N.O.
5. PROVIDE DEDICATED CIRCUIT FOR EACH WORKSTATION IN TELEHEALTH, A115.
6. WHERE LIGHTS ARE RELOCATED, MOVE ASSOCIATED OCCUPANCY SENSOR.
7. CONTRACTOR SHALL PROVIDE BOXES, CONDUIT, WIRE, AND RECONNECTIONS AS REQUIRED TO
RECONNECT ANY AND ALL EXISTING LIGHT FIXTURES, RECEPTACLES, OR DEVICES REMAINING IN USE.
REMOVAL OF ANY ELECTRICAL EQUIPMENT SHALL NOT AFFECT THE OPERATION OF EQUIPMENT
REMAINING IN USE.
8. A GREEN GROUND SHALL BE RUN WITH ALL FEEDERS AND WITH ALL CIRCUITS TO RECEPTACLES, MOTORS, FIXED EQUIPMENT, AND APPLIANCES.
9. PANELBOARDS AND CIRCUIT BREAKERS SHALL HAVE THE FOLLOWING MINIMUM INTERRUPTING RATINGS:
120/208 - 22,000 AMPERES SYMMETRICAL.
10. CONTINUITY OF ALL SERVICES TO AND FROM THE FACILITIES IN THE EXISTING BUILDING SHALL BE MAINTAINED WITHOUT INTERRUPTION, EXCEPT FOR SUCH PERIODS OF TIME WHICH THE V.A. MAY DESIGNATE. IF TEMPORARY CONNECTIONS, ETC. ARE NECESSARY TO ASSURE THE CONTINUITY OF SERVICE, THEY SHALL BE FURNISHED WITHOUT ADDITIONAL CHARGE TO THE V.A. AND SHALL BE
REMOVED WHEN NO LONGER NECESSARY.
11. ALL INSTALLATIONS AND EQUIPMENT SHALL FOLLOW THE GUIDELINES ESTABLISHED BY THE CURRENT
NATIONAL ELECTRIC CODE.
12. LOCATIONS OF EXISTING DUCTWORK, ELECTRICAL, MECHANICAL, PIPING, CABLE TRAYS, ETC., ARE NOT NECESSARILY SHOWN ACCURATELY ON THE DRAWINGS. FIELD VERIFY THE LOCATIONS OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. AFFECTING THE PERFORMANCE OF THE WORK. NOTIFY THE
CONTRACTING OFFICER'S REPRESENTATIVE IMMEDIATELY IF SIGNIFICANT DISCREPANCIES OR
OMISSIONS ARE DISCOVERED THAT AFFECT PERFORMANCE OF THE WORK.
13. CONTRACTOR SHALL NOT INSTALL CONDUIT, PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THAT WILL ELIMINATE OR OBSTRUCT ACCESS TO COILS, MOTORS, VALVES, SWITCHES, PANELS, ETC.
14. EXISTING CIRCUITRY (CONDUIT, BOXES, WIRE, ETC.) MAY BE REUSED AT THE CONTRACTOR'S OPTION AS LONG AS IT MEETS THE SAME SPECIFICATIONS REQUIRED FOR NEW CIRCUITRY. ALL WORK, NEW AND
EXISTING, SHALL COMPLY WITH THE LATEST NEC CODE.
15. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL ARRANGEMENT OF EACH SYSTEM. BECAUSE OF THE SMALL SCALE OF DRAWINGS IT IS NOT POSSIBLE TO SHOW OR INDICATE ALL BRANCHES, OFFSETS, FITTINGS, BOXES, AND ACCESSORIES WHICH MAY BE REQUIRED.
16. LOCATIONS OF NEW EQUIPMENT, PIPING, AND ASSOCIATED ITEMS ARE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL FIELD COORDINATE LOCATIONS AND ELEVATIONS FOR THE WORK, INCLUDING CONNECTIONS TO EXISTING WORK. REQUIRED OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC. TO HAVE A COMPLETE AND FUNCTIONAL SYSTEM ARE INCLUDED IN THE SCOPE OF THE WORK. NOTIFY THE
CONTRACTING OFFICER'S REPRESENTATIVE IMMEDIATELY IF SIGNIFICANT DISCREPANCIES OR
OMISSIONS ARE DISCOVERED THAT AFFECT PERFORMANCE OF THE WORK.
17. ALL RECEPTACLES, OUTLETS, JUNCTION BOXES FOR EQUIPMENT CONNECTIONS, ETC., SHALL BE
MOUNTED 18" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.
18. WORK THAT REQUIRES A UTILITY OR SYSTEM SHUTDOWN; OR THAT MUST BE COMPLETED IN OCCUPIED
AREAS OF THE MEDICAL CENTER MUST BE DONE DURING TIMES OTHER THAN NORMAL WORKING
HOURS. WORK MUST BE SCHEDULED WITH THE VA PROJECT ENGINEER.
19. SEVERE NOISE PRODUCING WORK WILL NOT BE ALLOWED DURING NORMAL WORKING HOURS AND
MUST BE SCHEDULED WITH THE VA PROJECT ENGINEER FOR OTHER TIMES. THIS INCLUDES
JACKHAMMERING CONCRETE, SAWCUTTING CONCRETE, FREQUENT HAMMER DRILLING OF CONCRETE, ETC.
20. CONTRACTOR SHALL PROVIDE AND INSTALL ELECTRIC DISCONNECT SWITCHES FOR ALL EQUIPMENT
REQUIRING DISCONNECT SWITCHES BY THE NATIONAL ELECTRIC CODE WHETHER OR NOT THE
DISCONNECT SWITCH IS SPECIFICALLY SHOWN ON THE DRAWINGS. SWITCHES SHALL BE SIZED FOR THE
SERVICE AND SHALL BE VISIBLE TO THE EQUIPMENT PER THE N.E.C.
21. DUPLEX POWER OUTLETS SHALL BE SPACED AT 10' (TEN FEET) MAX IN FINISHED SPACES UNLESS
OTHERWISE NOTED. MINIMUM 1 (ONE) PER WALL.
22. CONTRACTOR TO COORDINATE ALL POWER RUN ROUTINGS AND CIRCUIT LOCATIONS WITH ANTICIPATED
LOADS IN EACH SPACE.
23. ELECTRICAL LIGHTING SHALL BE COORDINATED IN THE FIELD WITH C.O.R. AT A MINIMUM, INSTALL NUMBER OF FIXTURES DEPICTED ON REFLECTED CEILING PLANS. ALL SPACES INSIDE THE BUILDING, FINISHED AND UNFINISHED SPACES SHALL HAVE CEILING AND LIGHTING.
24. ALL LIGHTING SHALL BE 2X4 L.E.D. FIXTURES, UNLESS NOTED OTHERWISE. COORDINATE TYPE WITH C.O.R. (SIMILAR TO B2 AT JOHN COCHRAN IN RECENTLY RENOVATED SPACE.) SEE REFLECTED CEILING
PLANS FOR APPROXIMATE LOCATIONS.
25. PROVIDE BATTERY-BACKUP L.E.D. LAY-IN 2X4 FIXTURES TO PROVIDE ADEQUATE EGRESS LIGHTING.
26. LIGHT SWITCHES LOCATED AT DOORWAYS TO SPACE UNLESS OTHERWISE NOTED.
27. INSTALL NEW DEVICES IN EXISTING OUTLET BOXES RETAINED IN DEMO. IF NOT FEASABLE TO USE
EXISTING CONTRACTOR SHALL INSTALL NEW SURFACE MOUNTED DEVICES.
28. ROUTE ALL NEW DATA CABLING TO EXISTING DATA ROOM.
29. ROUTE ALL TELEPHONE CABLING TO TELEPHONE CLOSET. CONTRACTOR SHALL PROVIDE NEW PUNCH
DOWN BLOCKS, SIZED TO MATCH FUTURE NEEDS OF BUILDING.
30. CONTRACTOR SHALL INSTALL 1 INCH CONDUITS FROM PANEL LOCATIONS TO EVERY ROOM IN BUILDING
6 AND 6A. (TO INCLUDE FINISHED SPACES AND UNFINISHED SPACES) JUNSTION BOXES SHALL BE
INSTALLED IN ROOM SIDE OF LINE ALONG WITH PULL STRINGS.
31. CONTRACTOR SHALL COORDINATE DATA AND TELEPHONE ROUTINGS FROM DEPICTED LOCATIONS TO
DATA AND TELEPHONE CLOSETS.
32. EACH DATA / TELEPHONE LOCATION SHALL CONSIST OF 2 DATA AND 1 TELEPHONE JACK.
33. CONTRACTOR MAY USE EXISTING CABLE TRAY AND “J”HOOKS IF USABLE. IF NO SUPPORTS ARE
PRESSENT CONTRACTOR SHALL INSTALL AS NECESSARY.
34. ALL ROOMS SHALL HAVE OCCUPANCY SENSORS. PLACEMENT TO BE COORDINATED IN THE FIELD.
35. CONTRACTOR TO PROVIDE ELECTRONIC AS-BUILT DRAWINGS SAVED IN AUTOCAD AND PDF FORMATS.
ELECTRICAL GENERAL NOTES
DUPLEX RECEPTACLE - MOUNT 18"AFF, UNO
DUPLEX RECEPTACLE - EMERGENCY POWER
QUADRUPLEX OUTLET - MOUNT 18" AFF, UNO
DATA OUTLET - FOUR JACKS PER OUTLET - MOUNT 18"AFF, UNO
(REMOVE ALL EXISTING OUTLETS AND CABLING) - NOTE ALL NEW
CABLING TO BE CAT6A CONNECTED BACK TO
EXISTING DATA OUTLET - ALL EXISTING DATA AND ASSOCIATED
CABLEING TO BE REMOVED BACK TO 1W01
PHONE
EXIT LIGHT - CEILING MOUNTED
ELECTRICAL SYMBOLS LEGEND
DATA DATA
PHONEBLANK
ALL DATA DROPS TO
MIMIC TYPICAL DETAIL
ABOVE. ALL CABLING TO
BE CAT 6A. PHONES TO
BE VOIP SYSTEM
TYPICAL DATA DROP
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-E-100
ELECTRICAL PLAN
HT
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
ELEC DEMO PLAN
1/8" = 1'-0"
POWER AND DATA PLAN
01-AE-100 5
OPEN WORK
GW04
BREAK
GW05A
CONFERENCE
GW07
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
STORAGE
GW04B
FINISH SCHEDULE ABBREVIATIONS
FLOORS:
CPT CARPET
E EXISTING
LVT LUXURY VINYL TILE
BASE: (4" UNLESS NOTED OTHERWISE)
E EXISTING
RB RUBBER BASE
WALLS:
E EXISTING
GYP GYPSUM BOARD
PT PAINT
CEILING:
ACT ACOUSTICAL CEILING TILE
E EXISTING
X EXPOSED
PT PAINT
CASEWORK:
PLAM PLASTIC LAMINATE
PAINT
PT1
MFR: SHERWIN-
WILLIAMS
TYPE: PROMAR 200
COLOR; SW7008
ALABASTER
FINISH: EGGSHELL
PT2
MFR: SHERWIN-
WILLIAMS
TYPE: PROMAR 200
COLOR; SW9145
SLEEPY HOLLOW
FINISH: EGGSHELL
PT3
MFR: SHERWIN-
WILLIAMS
TYPE: PROMAR 200
COLOR; SW7757
HIGH REFLECTIVE
WHITE
FINISH: FLAT
MATERIAL LEGEND
CEILING TILE
ACT1
ARMSTRONG
FINE FISSURED
24"X48"
BASE
WALLS CEILINGS
RUBBER BASE
RB1
MFR: ROPPE
COLOR: BLACK
TYPE: 4" COVE
DOOR PAINTS
PT4 (HM FRAMES)
MFR: SHERWIN-
WILIAMS
TYPE: PRE-
WATERBASE
EPOXY
COLOR: MATCH
ADJACENT WALL
COLOR
FINISH: SATIN
MISCELLANEOUS
LUXURY VINYL TILE
LVT1
MFR: MOHAWK
GROUP
TYPE: 36" SQ. TILE
PATTERN: BOLDER
COLOR: PEBBLE
C0010/925
E
EXISTING
MATERIAL TO
REMAIN
FLOOR
CASEWORK
PLASTIC LAMINATE
PL1 (CABINETS)
MADE OF MARINE
GRADE PLYWOOD
MFR: NEVAMAR
COLOR: CLEAR
MAPLE WM8340-T
SOLID SURFACE
SS (COUNTERTOPS)
MFR: CORIAN
COLOR:
ARROWROOT
FLOORS
F1. ALL FLOORING MATERIALS TO EXTEND TO WALL UNDER OPEN CASEWORK.
MISC.
M1. ALL HOLLOW METAL DOOR FRAMES WILL BE PAINTED PT3 UNLESS OTHERWISE
NOTED.
M2. PROVIDE TRANSITION STRIP AT ALL FLOORING MATERIAL JUNCTURES. CENTER OF
TRANSITION STRIP TO BE LOCATED UNDER CENTER OF DOOR.
INTERIOR FINISH NOTES
01-AE-100 5
OPEN WORK
GW04
BREAK
GW05A
CONFERENCE
GW07
CONFERENCE
ROOM
GW08
OFFICE
GW09A
OFFICE
GW09
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2 P2
P2
EXISTING MECH.
STORAGE
GW04B
PAINT EXISTING
DOOR & FRAME
PT-4
A. PROVIDE INTERIOR ROOM IDENTIFICATION AND WAYFINDING SIGNAGE THROUGHOUT THE RENEWED
AREAS. COORDINATE REQUIREMENTS W/ OWNER'S REPRESENTATIVE.
B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVER-CURRENT PROJECTION DEVICE.
COMPLETELY REMOVE ALL ABANDONED WIRING.
C. ALL FURNITURE SHALL BE PROVIDED AND INSTALLED BY OTHERS.
D. PAINT ALL WALLS P1 U.N.O.
GENERAL FINISH PLAN NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
EHRM CERNER ADMIN SPACE
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FACILITIES & ENGINEERING SERVICE
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
UNITED STATES OF AMERICA
/2
/2
:5 :1
P
M
01-AI-100
FURNITURE & FINISHES
HT
CM04/22/21
657-21-711JB
CONSTRUCTION DOCUMENTS
1/8" = 1'-0"
FFE PLAN
Finish Schedule
Number Name Floor Finish
Base Finis h East
Finish North Finish
South Finish
West Finish Ceiling Type
Ceiling Finish
GW04 OPEN WORK LVT1 RB1 SEE
PLAN
SEE
PLAN
SEE
PLAN
SEE
PLAN
ACT1 ACT1
GW08 CONFERENCE ROOM LVT1 RB1 PT1 PT1 PT1 PT2 EXIST GYP PT-3
GW09A OFFICE LVT1 RB1 PT1 PT1 PT1 PT1 ACT1 ACT1
GW09 OFFICE LVT1 RB1 PT1 PT1 PT1 PT1 ACT1 ACT1
GW05A BREAK LVT1 RB1 PT2 PT2 PT2 PT1 ACT1 ACT1
GW07 CONFERENCE LVT1 RB1 PT1 PT1 PT1 PT1 ACT1 ACT1
GW10 WAITING LVT1 RB1 PT1 PT1 PT1 PT1 ACT1 ACT1
GW04A STORAGE LVT1 RB1 PT1 PT1 PT1 PT1 EXIST GYP PT-3
H0011 CORRIDOR LVT1 RB1 PT1 PT1 PT1 PT1 ACT1 ACT1
Equipment Schedule
Item Responsible
1 MICROWAVE VV
2 REFRIGERATOR VC
3 EXHAUST FAN CC
4 PRINTERS VV
5 PHONES VV
6 FURN - SYSTEM VV-CERNER
7 FURN- BREAKROOM VV-CERNER
8 FURN-CONFERENCE VV-CERNER
1/8" = 1'-0"
FINISH PLAN
VV- PROVIDED AND INSTALLED BY VA
VV-CERNER - PROVIDED AND INSTALLED BY CERNER
CC -PROVIDED AND INSTALLED BY CONTRACTOR
| Sheets |
| 01-G1-000 - COVER SHEET |
| 01-GI-001 - ICRA PLAN |
| 01-HA-011 - HAZARDOUS ABATEMENT |
| 01-AD-100 - DEMO PLANS |
| 01-AE-100 - FLOOR PLANS |
| 01-AE-101 - CEILING PLANS |
| 01-E-100 - ELECTRICAL PLAN |
| 01-AI-100 - FURNITURE & FINISHES |
File details come from the government source that posted it. Updated .