S05-RFI Question 6 - Controls.pdf
PDF 784 KB Posted
- Attached to
- J028--Emergency Backup Generator Repair Federal contract opportunity
- Solicitation number
- 36C26221Q0424
About this file
This document outlines a solicitation for emergency backup generator repair services. The Department of Veterans Affairs is seeking a contractor to repair an EMD 16-645-E4 emergency backup generator at its Sepulveda Ambulatory Care Center. Key work includes replacing obsolete generator controls and control systems, overhauling the engine, repairing electrical and fuel systems, and performing a load test. Offerors must have experience overhauling similar sized generators and be trained to repair EMD models. Quotes are due by March 17, 2021. The contract will have a base year and four option years. The repair work must be completed within 60 days of award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S05-RFIs Gen Repair.docx | DOCX document | |
| 36C26221Q0424 0002_1.docx | DOCX document | |
| 36C26221Q0424 0001_1.docx | DOCX document | |
| Photos.pdf | ||
| 36C26221Q0424.docx | DOCX document | |
| CSS Gen Repair Enclosure 2.docx | DOCX document | |
| CSS Gen Repair Enclosure 1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. Replace the obsolete Allen Bradley PLC genset control system in the genset control cabinet.
B. Replace the obsolete Woodward speed control module in the genset control cabinet.
C. Replace the obsolete Allen Bradley PLC switchgear feeder breaker control system.
D. Replace the obsolete Woodward generator load control (DSLC) in the switchgear.
E. Replace the obsolete generator rotating exciter motor with a static non rotating exciter.
Item A replacement parts would be a digital controller and 10 inch color data display module.
Item B replacement part would be a new electronic speed controller.
Item C replacement part would be a digital controller and utility parallel protection monitor.
Item D replacement part would be a digital load control module.
Item E replacement part would be a static - non rotating generator exciter / voltage regulator.