VETERAN ELECTRICAL POWER SYSTEMS 1223 S. FLOWER ST. BURBANK, CA 91502 (818) 861‐7610
May 23, 2018
Subject: VA Sepulveda Building 99 Main Switchgear
| At | the | request | of | VA | Sepulveda | Ambulatory | Care | Center, | Veteran | Electrical | Power | |||
| Systems | inspected | and | tested | the | electrical | system | that | feeds | building | 99 | to | establish | the | |
| condition | of | the | current | system. | Multiple | deficiencies | were | found | throughout | the |
Switchgear.
| Excessive | signs | of | heat | from | the | Incoming | power | from | R3 | and | R4 | feed. | Cables | are | melting |
| back | the | insulation. |
VETERAN ELECTRICAL POWER SYSTEMS 1223 S. FLOWER ST. BURBANK, CA 91502 (818) 861‐7610
Signs of tracking on the insulators
VETERAN ELECTRICAL POWER SYSTEMS 1223 S. FLOWER ST. BURBANK, CA 91502 (818) 861‐7610
The complete Substation
VETERAN ELECTRICAL POWER SYSTEMS 1223 S. FLOWER ST. BURBANK, CA 91502 (818) 861‐7610
Switchgear has excessive corrosion with water marks throughout the inside of each cabinet
VETERAN ELECTRICAL POWER SYSTEMS 1223 S. FLOWER ST. BURBANK, CA 91502 (818) 861‐7610
Load Interrupter Switch blades showing signs of excessive heat.
| Recommendation: | VEPS | recommends | replacing | the | switchgear, | as | well | as | the | incoming | line | |||||
| from | R3 | and | R4 | to | the | outgoing | line | to | building | 99. | The | test | Results | were | unsatisfactory | per |
| NETA | Standards. | |||||||||||||||
| If | there | are | any | questions | please | feel | free | to | contact | me. |
Respectfully,
| Sergio | Rangel | |||
| Operations | Manager | |||
| Veteran | Electrical | Power | Systems, | Inc. |