This document provides electrical one-line diagrams and specifications for a federal contract opportunity to perform switchgear and battery testing certification services at a Department of Veterans Affairs medical center. Key requirements include testing and maintenance of paralleling switchgear, automatic throw over equipment, uninterruptible power supply units, circuit breakers, transformers, relays, transfer switches, and lead acid batteries across 26 electrical substations and unit substations. The solicitation will be available on June 11, 2020 with proposals due 25 days later by 10:00 AM Mountain Time. The NAICS code is 811219 for other commercial and industrial machinery and equipment rental and leasing with a $22 million small business size standard. This will be a set-aside for verified service-disabled veteran-owned small businesses. The solicitation number is 36C25920Q0417.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25920Q0417.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 06-29-2020 na 36C259 Department of Veterans Affairs Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village
CO
80111 36C259 Department of Veterans Affairs Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village
CO
80111 To all Offerors/Bidders
36C25920Q0417
X
X N/A The purpose of this amendment is to answer questions.
Mary Emily Good Contracting Officer
2.0.3 - Switchgear and Switchboard Assemblies.
How many sections and how many cells are in each section? Y1500 GE Zenith Paralleling Switchgear Systems, 480V and 15kV
(29) Double Ended Sub-Stations 13,800 Volt distribution to 480 Volt.
(64) Automatic Transfer Switches from 1200 Amps to 400 Amps.
2.0.4 - Medium Voltage Vacuum Circuit Breakers
How many breakers and what type? (89) Approximately
SQ D / TYPE- VR/ CAT#- V5DB133Y000/ MFG 4/14/FACTORY ORDER NO- 17-34613254-003
15kV 1200A
I don't know what test they are refereeing to. We test to NETA standard, so I assume, meg, ductor and hi-pot. Manufactures Recommended Testing
2.0.5 - Substation Transformers (Dry Type)
How many and what size? 2000 kVA Delta- Y (25) 2500 kVA Y-Y (1) All Dry Type
2.0.6 - Low Voltage Circuit Breakers (480 VAC)
How many, who is the manufacture and what size? Are they bolt in or draw out? Approximately (430) GE Model SELA36ATT0150 Bolt in and approximately (150) DRAW OUT
Can they provide 100a / 480vac circuit for the test set? Is there a place to set up the test set? YES
What trip unit is on the breakers? PQMII for “MAIN” at Sub-station and Plug-In Trip Units at distribution panels
2.0.7 - Low Voltage Insulated Case Circuit Breakers
How many panels and how many breakers are there? Approximately (430) GE Model SELA36ATT0150 Bolt in and approximately (150) DRAW OUT at Sub-Stations
2.0.8 - Protective Relay Calibration (Solid State/ Digital as applicable)
Quantity, manufacturer and type? Do they have a recent coordination study or setting from an engineer? RESA Power has Coordination Settings.
Manufacturer: GE Industrial Counts are approximate.
(90) PQM II-T20-C-A 480v Relay
(3) Multilin MIB High Impedance MODEL: MIB30HICE00000/ SERIAL NO: 91.725.803
(5) G-60 Relays MODEL: G60EOOHCHF8FH6GM8FP6KU5CWXX / SERIAL: AALC14000378
(90) Multilin 350 MODEL: 350-E-P5-G5-H-E-S-N-M-SN-D-N / SER: MLOA14000106 / MFG: JAN 20, 2014
(2) Multilin 750 MODEL: 750-P5-G5-S5-HI-A20-R-E / MFG: MAR 29 2014
2.0.9 - GE Multilin 750
How many? Two (2) Multilin 750 MODEL- 750-P5-G5-S5-HI-A20-R-E / MFG- MAR 29 2014
I will have to assume the work was not done by SECO and we will be doing all this work. Yes
2.0.10 - Metering and Instrumentation
How many and what are they? See Relay information.
GE Power Management Y1500 SCADA with 12 Remote Terminus Units at ESSENTIAL SUB-STATIONS. Communication from 2 redundant LAN Fiberoptic loops to the MASTER Human/ Machine Interface with a third fiber loop for metering and communication of alarms and status.
Counts are approximate.
(90) PQM II-T20-C-A 480v Serial: E7340818
(3) Multilin MIB High Impedance MODEL: MIB30HICE00000/ SERIAL NO: 91.725.803
(5) G-60 Relays MODEL: G60EOOHCHF8FH6GM8FP6KU5CWXX / SERIAL: AALC14000378
(90) Multilin 350 MODEL: 350-E-P5-G5-H-E-S-N-M-SN-D-N / SER: MLOA14000106 / MFG: JAN 20, 2014
(2) Multilin 750 MODEL: 750-P5-G5-S5-HI-A20-R-E / MFG: MAR 29 2014
See “One Line” for PT and CT count and location.
2.0.11 - Engineering Appraisal
Is PowerDB acceptable? Must not contain proprietary software.
I understand we will need to help develop a time line, but for a firm price up front we will need to know how many trips (outages) there will be, when the outages will take place and what equipment will be done on each outage. This will be coordinated with POC and CO and dependent on contractors means and methods.
3.5.2 - Inspection of electrical vaults
We can not enter underground vaults that are energized. IS this actually part of the scope? If some how many are there? Around (44) Underground Vaults. These will need to be IR Scanned when energized
3.5.3 – Protective Relay Calibration Study
Can they provide a full one line that have been "red lined" of all the electrical systems? Do they have CAD or SKM models for this or do we have to create them from scratch? BIM is Available.
We don't have the manuals for their equipment. Can we get copies of the manuals? Internet
Will you provide the Make/Model/Serial Number/Size/How many of each for the following items?
0. Switchgear (26) Sub-Stations/ (1) MTM or ATO/ (1) PSG
0. Breakers (430) GE Model SELA36ATT0150 Bolt in and approximately (150) DRAW OUT
0. Transfer switches Approximately (64) Automatic Transfer Switches
0. Transformers (25) 2000 kVA Delta- Y (1) 2500 kVA Y-Y (400) 480- 120/208 All Dry Type
0. Relays See answers above and ‘1 LINE’ drawings.
Is this proposal to include monthly testing of the UPS’s? UPS’s are tested at Generator Tests
Will you provide electrical one-lines?
See provided “ONE LINE” Drawings.
Drawing 02.ES.601
(1) Unit Substation "02-NDCP1" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(8) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 02.ES.602
(1) Unit Substation "02-EMDCP1" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(5) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 03.ES.601-A
(1) Unit Substation "03-NDCP3" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(11) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 03.ES.602-A
(1) Unit Substation "03-EMDCP2" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(7) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(4) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 03.ES.602-B/C
(1) Unit Substation "03-EMDCP1" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(12) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(8) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 04.ES.601
(1) Unit Substation "04-NDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(8) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 04.ES.602
(1) Unit Substation "04-EMDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(4) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 05.ES.601
(1) Unit Substation "05-NDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 02.ES.602
(1) Unit Substation "05-EMDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(7) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(4) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 06.ES.600
(1) Double Ended Substation
(15) Medium Voltage Vacuum Circuit Breakers
(16) Protective Relays
(32) Sets of CT's
(2) PT's Drawing 06.ES.601
(1) Generator Paralleling Switchgear
(19) Medium Voltage Vacuum Circuit Breakers
(26) Protective Relays
(39) Sets of CT's
(12) PT's
(1) Medium Voltage Dry Type Transformer
(3) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps) Drawing 06.ES.602
(1) Unit Substation "D6-NDCP1" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(1) Unit Substation "D6-NDCP2" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(5) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(1) Unit Substation "D6-NDCP3" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(5) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(1) Unit Substation "D6-NDCP4" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(5) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 06.ES.603
(1) Unit Substation "06-EMDCP1" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(1) Unit Substation "06-EMDCP2" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(6) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 06.ES.604
(1) Unit Substation "06-EMDCP3" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(1) Unit Substation "06-EMDCP4" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(5) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(5) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 08.ES.601
(1) Unit Substation "08-NDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 08.ES.602
(1) Unit Substation "08-EMDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(6) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(3) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 09.ES.601
(1) Unit Substation "09-NDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(8) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 09.ES.602
(1) Unit Substation "09-EMDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(5) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(3) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 10.ES.601
(1) Unit Substation "10-NDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(4) Protective Relays
(6) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 10.ES.602
(1) Unit Substation "10-EMDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(4) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 10.ES.631
(1) Unit Substation "CBS-NDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 10.ES.632
(1) Unit Substation "10-EMDCP" w/
(2) Medium Voltage Vacuum Circuit Breakers
(2) Protective Relays
(2) Sets of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(4) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 11.ES.601
(1) Unit Substation "11-NDCP" w/
(1) Medium Voltage Vacuum Circuit Breaker
(1) Protective Relay
(1) Set of CT's
(1) Medium Voltage Dry Type Transformer
(8) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 11.ES.602
(1) Unit Substation "11-EMDCP" w/
(1) Medium Voltage Vacuum Circuit Breaker
(1) Protective Relay
(1) Set of CT's
(1) Medium Voltage Dry Type Transformer
(5) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(3) Low Voltage Bypass Isolation Automatic Transfer Switches Drawing 13.ES.601
(1) Unit Substation "13-NDCP" w/
(1) Medium Voltage Vacuum Circuit Breaker
(1) Protective Relay
(1) Set of CT's
(1) Medium Voltage Dry Type Transformer
(9) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's Drawing 13.ES.602
(1) Unit Substation "13-EMDCP" w/
(1) Medium Voltage Vacuum Circuit Breaker
(1) Protective Relay
(1) Set of CT's
(1) Medium Voltage Dry Type Transformer
(7) Low Voltage Power/Insulated Case Circuit Breakers (≥225 amps)
(1) Meter
(1) Set of CT's
(5) Low Voltage Bypass Isolation Automatic Transfer Switches
(4) Strings of Lead Acid Batteries
(4) Battery Chargers
(1) 60 kVA GE Digital Energy UPS
(2) 300 kVA GE SG Series UPS's
(1) 10 kVA Emerson/Liebert UPS
(25) LIM Panels
TEST PROCEDURES
Medium Voltage Transformers Visual and Mechanical Inspection Inspect physical and mechanical condition.
Verify settings and operation of all temperature devices, if applicable
See attached document: Electrical one lines.