(CON)(660) Engineering PET Scanner Site Prep Federal contract opportunity
Solicitation number
36C25919R0182
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document includes a pre-solicitation notice and federal contract opportunity related to engineering site preparation services for a PET scanner project at the Salt Lake City Veterans Affairs Medical Center. Work includes architectural, electrical, mechanical, plumbing, site investigation, and testing/special inspection services per drawings and specifications to remodel an existing PET scanner room and control room, modify adjacent corridors and mechanical spaces, and provide all necessary site preparation for new scanner equipment. The project construction magnitude is between $100,000 and $250,000. Responses are due on or about August 27, 2019. This opportunity is a 100% set-aside for Service Disabled Veteran-Owned Small Businesses. The Department of Veterans Affairs is the contracting agency. Apparent successful offerors must be verified as SDVOSBs by the VA's Center for Verification and Evaluation prior to award.

36C25919R0182 PN 660-CSI-108 100PCT Stamped - Mechanical Cutsheets.pdf

View the file

Other files for this federal contract opportunity

Other files attached to (CON)(660) Engineering PET Scanner Site Prep, newest first.
File Type Posted
36C25919R0182-002.pdf PDF
36C25919R0182-005.docx DOCX document
36C25919R0182-001.docx DOCX document
36C25919R0182-004.pdf PDF
36C25919R0182-002.pdf PDF
36C25919R0182-003.pdf PDF
36C25919R0182-005.docx DOCX document
36C25919R0182-004.pdf PDF
36C25919R0182-001.docx DOCX document
36C25919R0182-000.docx DOCX document
36C25919R0182-000.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fan Coils Schedule Line

Tag Family Cab Size CFM ESP Motor Type HP Spec Total

FLA

C- Rws

Cool-

EDB

Cool-

EWB

Cool- Fluid

Cool- Temp

Total

BTU

Sensible

BTU

Cool-

LDB

Cool-

LWB

Cool-

LWT

Cool-

GPM

Cool- Water

PD

KW H-

Rws

Heat-

EDB

Heat- Fluid

Heat- Temp

Total BTU Heat-

LDB

Heat-

LWT

Heat-

GPM

Heat- Water

PD

1 FCU-1 HP

Horizontal

HPEF 006 559 0.25 Standard 1/6 120/1/60 2.8 6 80.00 67.00 Water 45.00 19,536 13,580 53.2 53.2 55.0 3.9 4.1 None 0 0.0 None 0.0 na na na na na

Company: The Whalen Company Project Name: 18.13 SLC PET Scanner FCU ,Salt Lake City ,Utah

Proposal: 85827 Date: 03-06-2019

Information contained herein are not express warranties nor do they constitute an agreement between the parties. The Whalen Company ® may change the design and product specifications at anytime. Contact the factory for current information. AHU OM-January 2012:

Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Fan Coils Schedule Supplemental Data Line

Tag UOM Mot Cnt

BHP Min

HP

RPM FLA MCA MOP Motor Speed

Motor Watts

Velo-city

Altitude Fins Per In

Total

MCA

Total

MOP

C-

CKT

EDP Cool- Delta T

Cool-

Glycol

Refrig-erant

SST H-

CKT

Heat- Delta T

Heat-

Glycol

Heat- Flow

Heat- Conden-sate

Elec.

Heat

BTU

Elec.

Heat

FLA

Elec.

Heat

MCA

Elec.

Heat

MOP

Shp ng Wt

Opr Wt

User Appvl

1 FCU-1 Standard 1 0.0 na 0.0 2.8 3.5 15.0 High Speed 336 459 4,700.00 12 3.5 15.0 3 61.6 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 192 153 None

Information contained herein are not express warranties nor do they constitute an agreement between the parties. The Whalen Company ® may change the design and product specifications at anytime. Contact the factory for current information. AHU OM-January 2012:

Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Performance Summary - Unit 1 , FCU-1

85827-1 Horizontal Fan Coil Cabinet Exposed (HPEF) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (HPEF006)

"The Horizontal Deluxe fan coil is designed for horizontal exposed ceiling-mounted applications where high static performance is required. The Deluxe is our basic unit housed in a fully-cased cabinet intended for ""free-blow"" exposed ceiling mounting. "

Performance Calculations are at an altitude of 4,700.00 feet

Fan Performance

Motor Voltage:

120/1/60

Motor Type:

Standard

External Static:

0.25 InWC

Airflow at High Speed: 559 cfm

Cooling Coil Performance - 6 rows, 3 circuit, 12 fins/inch

Entering Dry Bulb:

Entering Wet Bulb:

Fluid Type:

80.00 oF

67.00 oF Water

Leaving Dry Bulb:

Leaving Wet Bulb:

Flow Rate:

53.2 oF

53.2 oF

3.9 GPM

Entering Fluid Temp:

EAT Dew Point:

45.00 oF

61.6 oF

Leaving Fluid Temp:

Fluid Pressure Drop:

55.0 oF

4.1 FtWC

Total Cooling Capacity:

19,536 BTUH

Sensible Cooling Capacity:

13,580 BTUH

Information contained herein are not express warranties nor do they constitute an agreement between the parties. The Whalen Company ® may change the design and product specifications at anytime.

Contact the factory for current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430.

Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

SUPPLY

AIRSTREAM

12 X 48

12 X 42

12 X 36

611800

2200 67

1500 55

57-7/8

63-7/8

51-7/8

(2) 17 X 20 X 1

(2) 17 X 20 X 1

(2) 17 X 25 X 1

(2) 16 X 20

(2) 16 X 20

(2) 16 X 25

B

A

REAR VIEW

TOP VIEW

SIDE VIEW

ACCESS PANEL

RETURN-AIR

GRILLE & FILTER

SUPPLY-AIR

GRILLE HWR

CWR

HWS

CWS

406.40 X 635.00

406.40 X 635.00

406.40 X 508.20

304.80 X 762.00

304.80 X 609.60

304.80 X 457.20939.80 860.43

1092.20 1012.83

1165.231244.60

406.40 X 508.20758.83838.20 304.80 X 355.60

MM

MM

MM

MM

(1) 17 X 20 X 116 X 2033-7/8 008 800 37 12 X 18

(1) 17 X 25 X 1 16 X 2539-7/8 010 1000 43 12 X 24

12 X 30 012 1200 49 45-7/8 (1) 17 X 25 X 1 16 X 25

(MM)

INRIGHT HAND SHOWN

16 X 20

(1) 17 X 20 X 1

Return Air Grille Filter Size

29-7/833 006 600

Model CFM A B Supply Air

Grille

12 X 14

1549.40

1701.80

1317.63

1470.03

1622.43

304.80 X 914.40

304.80 X 1066.80

304.80 X 1219.20

406.40 X 508.20

406.40 X 508.20

406.40 X 635.00

MM

MM

MM

COIL CONNECTION

1-1/8" KNOCKOUT

(28.58) (8) PLACES ELECTRICAL CONNECTION

7/8" KNOCKOUT

(22.23) (8) PLACES

DRAIN CONNECTION

(PRIMARY AND SECONDARY)

1-1/8" KNOCKOUT

(28.58) (4) PLACES

(SECONDARY OPTIONAL)

BLOWERBLOWER

MOTORMOTOR

SPARK

TRAY

SPARK

TRAY

JUNCTION BOX

JUNCTION BOX

(IF SAME SIDE)

JUNCTION BOX

(IF SAME SIDE)

1/2" MOUNTING HOLE

(12.7) (4) PLACES

(8

.8

1- 9/

(3 9.

7)

(7

.6

1-9/16" (39.7)

-1

/2

(4

.9

Detail Report

Generated by DriCalc® software, Version 4.00.00 04-22-19 at 10:35 AM | 1

Report information

Report generated date 04-22-19

Systems/tags included in this report:

H-1

Project Information

Project name 18.13 SLC Humidifier

Project description

Project status Open

Project phase Design

Unit of measure Inch-pound

Project name: 18.13 SLC Humidifier

System/tag H-1

System images

Steam generator dimensions and clearances

Dimensions (in.) Clearances (in.)

A B C D E F H I

18.6 16.1 24.2 36 36 18 12 24

Dispersion dimensions Ultra-sorb connections

Dimensions (in.)

A B C

39.0 29.0 5.0

Generated by DriCalc® software, Version 4.00.00 04-22-19 at 10:35 AM | 2

Project ID: 57120

Project name: 18.13 SLC Humidifier

System/tag H-1

System view

Mixed air system dispersion installed in duct or AHU

Airflow plan view

Outside air

55.0 °F

10% RH

1400 cfm

Exhaust air

1400 cfm

Return air

70.0 °F

47% RH

0 cfm Mixed air

55 °F

10% RH

1400 cfm

Before dispersion

51.6 °F

11% RH

1400 cfm

After dispersion

56.0 °F

77% RH

1400 cfm

Humidified space

70.0 °F

Desired RH

50% RH

Actual RH

47% RH

Project name: 18.13 SLC Humidifier

System/tag H-1, continued

Application

System Quantity 1

System Location United States

Elevation at project site (ft) 4250.0

Ventilation system type Mixed Air System, Dispersion Installed In Duct Or AHU

Outside air dry bulb temperature (°F) 55.0

Outside air moisture content (%RH) 10.0

Outside air intake rate Constant

Outside air intake (%) 100.0

Total air volume (cfm) 1400.0

Desired air dry bulb temperature (°F) in humidified space

70.0

Desired air moisture content (% RH) in humidified space

50.0

Actual moisture content (% RH) in humidified space 47.0

Non-wetting distance (inches) 12

Calculated load User-entered

Load (lbs/hr) 40.0

Load plus loss (lbs/hr) 43.36

Dispersion installation location Duct

Airflow direction Horizontal

Airflow pressure drop (inches w.c.) 0.006

Duct dry bulb temp before dispersion (°F) 51.6

Duct RH before dispersion (%) 11

Duct dry bulb temp after dispersion (°F) 56.0

Application, continued

Duct RH after dispersion (%) 77

Heat gain from steam (°F) 1.92

Heat gain from assembly (°F) 2.48

Steam dispersion

Dispersion product Ultra-sorb

Dispersion model LV

Unit quantity 1

Header location Outside Duct

Trap location Outside Duct

Air movement Through Dispersion Assmbly

Available inside duct/AHU width (inches) 36.0

Available inside duct/AHU height (inches) 20.0

Duct/AHU wall thickness (inches) 0.0

Face width (inches) 36.0

Face height (inches) 20.0

Header diameter(inches) 3.0

Overall dimensions W x H x L (inches) 39.0 X 29.0 X 5.0

Air velocity (ft/min) 280.0

Tube diameter (inches) 1.5

Tube spacing on-center (inches) 3.0

Tube quantity 10

Enclosure material Galvanized Steel

Header and tube material 304 Stainless Steel

Generated by DriCalc® software, Version 4.00.00 04-22-19 at 10:35 AM | 3

Project name: 18.13 SLC Humidifier

System/tag H-1, continued

Steam dispersion, continued

Dispersion same side piping No

High-Efficiency Insulated Tubes Yes

Ship unassembled No

Seismic-certified No

Operating weight (lbs) 81

Shipping weight (lbs) 105

Steam generation

Generation product Vapormist

Generation model VM-16

Unit quantity 1

Unit capacity (lbs/hr) 48.0

Water type Potable

Energy source Electricity

Voltage (Vac) 208

Phase 3

Max Amps per unit(s) 44.4

Overall dimensions H x W x L (inches) 24 X 18 X 16

Operating weight (lbs) 139

Shipping weight (lbs) 93

Tank material 304 Stainless Steel

Enclosure

End-of-season drain Yes

Seismic certified humidifier No

Notes

Minimum water conductivity of 30 uS/cm

Damage caused by chloride corrosion is not covered by your DriSteem warranty.

Connections

Steam generator outlet connection type NPT

Steam generator outlet diameter (inches) 1.5

Steam supply inlet location B3

Dispersion steam inlet connection type NPT

Dispersion steam inlet diameter (inches) 1.5

Condensate outlet location on condensate header C7

Steam hose length (ft) 0

Control

Humidifier controller Vapor-logic

Multiple-tank control No

Operating mode TP Modulation

Interoperability None

Keypad/display Mounted Permanently

Control, continued

Keypad/display language English

Keypad/display unit of measure Inch-pound

Input signal type Humidity Transmitter

Remote temperature sensor No

Accessories

Generation Condensate Pump None

Dispersion Condensate pump None

Generation Drane-kooler Yes

Generation Drane-kooler mounting Floor Stand

Dispersion Drane-kooler Yes

Dispersion Drane-kooler mounting Wall Mount

NEMA-1 safety switch Yes

High-limit humidistat None

Airflow proving switch Electric Pressure

Humidity transmitter None

HPEF Rev A (Rear Return).pdf
Model

File details come from the government source that posted it. Updated .