36C25518R0049-005.pdf
PDF 3 MB Posted
- Attached to
- Structural Improvements to Building 42 Project Number 657-343 Federal contract opportunity
- Solicitation number
- 36C25518R0049
About this file
36C25518R0049 Drawings 657-343 Structural (28 pages).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25518C0148-000.docx | DOCX document | |
| 36C25518R0049-00004005.docx | DOCX document | |
| 36C25518R0049-00003000.docx | DOCX document | |
| 36C25518R0049-00002000.docx | DOCX document | |
| 36C25518R0049-00002001.pdf | ||
| 36C25518R0049-00001000.docx | DOCX document | |
| 36C25518R0049-011.pdf | ||
| 36C25518R0049-008.pdf | ||
| 36C25518R0049-003.pdf | ||
| 36C25518R0049-010.pdf | ||
| 36C25518R0049-001.docx | DOCX document | |
| 36C25518R0049-006.pdf | ||
| 36C25518R0049-007.pdf | ||
| 36C25518R0049-002.pdf | ||
| 36C25518R0049-009.pdf | ||
| 36C25518R0049-004.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STEEL BEAM LEGEND
W18X40 C=1"
CAMBERBEAM SIZE
20K20K
BEAM REACTION,
TYP
(8) (8)(4)
QUANTITY OF SHEAR STUDS,
UNIFORMLY SPACED BETWEEN
ADJACENT FRAMING, TYP
(COMPOSITE CONSTRUCTION
ONLY)
NOTES:
1) REACTION VALUE IS ASD (KIPS), UNO.
2) WHERE NO VALUE IS SHOWN, DESIGN CONNECTION FOR A MINIMUM REACTION OF 16 KIPS.
3) POSITIVE CAMBER UPWARDS, NEGATIVE CAMBER DOWNWARDS. CAMBER SHOWN
ON CANTILEVERS IS AT END OF CANTILEVER.
4) BEAMS ARE PRIMARY MEMBERS FOR FIREPROOFING UNLESS NOTED AS SECONDARY.
5) "M" IN PLACE OF BEAM SIZE INDICATES W10X12.
6) LATERAL FORCE TO BE TRANSFERED THROUGH SUPPORT BY CONNECTIONS IN ADDITION
TO VERTICAL REACTION FORCES. FORCE MAY ACT IN EITHER DIRECTION. (FORCE IS
GREATER OF 0.6W OR 0.7E, UNO.
MOMENT CONNECTION
CANT BM, SAME SIZE
AND END REACTION AS
BACKSPAN, UNO
C=1/2" CAMBER
##K
NOTE 6
MISCELLANEOUS SYMBOLS
NORTH ARROW GRIDLINES
EARTH
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION
REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
C# COLUMN NOTATION
Z# PRECAST/ BRICK SUPPORT
L# LINTEL NOTATION
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PB ## POST-TENSIONED CONCRETE
BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRAVEL
Name
Elevation
WALL PIER NOTATIONWP ##
W ## WALL NOTATION
CONCRETE SYMBOLS
POST-TENSION TENDON
ANCHOR DEAD END
LOCATION
POST-TENSION TENDON
ANCHOR JACKING
LOCATION
REBAR
CHANGE OF SLAB
ELEVATION
SLOPING SLAB
CHANGE OF SLAB
THICKNESS
MECHANICAL COUPLER
REBAR SPLICE
LIMIT OF MEMBER OR
SPAN MARK
DIRECTION OF SPAN
OPENING
SELF-EXPANDING
WATERSTOP
CONTROL JOINT LOCATION
IN CONCRETE WALLS
REBAR TERMINATOR
INTENTIONALLY
ROUGHENED
CONSTRUCTION JOINT
TO 1/4" AMPLITUDE
WELDED WIRE FABRIC
PVC WATERSTOP
COLUMN CONTINUES
COLUMN TERMINATED
FORM-SAVER
SLAB ON GRADE MARKSOG#
CONNECTORS
HEADED STUD
CONNECTOR SECTION END/ALT VIEW
CAST-IN ANCHOR
ROD
POST-INSTALLED
MECHANICAL ANCHOR
BOLT
POST INSTALLED
ADHESIVE ANCHOR
STEEL MEMBERS
W-SHAPE BEAM
SHAPE SECTION PLAN VIEWELEVATION
CHANNEL
ANGLE
DOUBLE ANGLE
HOLLOW STRUCTURAL
SECTION
-RECTANGULAR
LLV LLH
HOLLOW STRUCTURAL
SECTION
-CIRCULAR (PIPE)
OPEN WEB STEEL
JOIST
STEEL SYMBOLS
STEEL DECK
STEEL DECK MARK AND
SPAN DIRECTION
BEAM SPLICE
CONNECTION
BEAM MOMENT CONNECTION
AT COLUMN
BEAM SHEAR CONNECTION
AT COLUMN
BEAM CONTINUOUS OVER
COLUMN
SLAB ON STEEL
DECK
SLAB ON STEEL
DECK
WWF
COLUMN STARTS HERE
DIAGONAL BRACING
BRACING
HANGER OR POST
HANGER OR POST
BELOW FLOOR
SLAB-ON-DECK MARK AND
SPAN DIRECTION
OR
D#
S#
C# COLUMN MARK
MASONRY MEMBERS
CMU SECTION
CMU BOND BEAM SECTION
(FULLY GROUTED)
CMU LINTEL SECTION
(FULLY GROUTED)
SINGLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
DOUBLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
PLAN
PLAN
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABRATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSL LAMINATED STRAND LUMBER
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MF MOMENT FRAME
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
OWJ PRE-MANUFACTURED OPEN WEB JOIST
PC PRECAST CONCRETE
PEMB PRE-ENGINEERED METAL BUILDING
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
RTU ROOFTOP MECHANICAL UNIT
S SLOPE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TEMP TEMPERATURE
THRU THROUGH
TJI PREFABRICATED WOOD I-JOIST
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WH WEEP HOLE
WP WORK POINT
WT WEIGHT, STRUCTURAL T
WWF WELDED WIRE FABRIC
XS EXTRA STRONG (PIPE)
XXS DOUBLE EXTRA STRONG (PIPE)
& AND
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BD BOARD
BF BRACED FRAME
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
BU BUILT UP
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GL GLUED LAMINATED TIMBER (GLULAM)
GRND GROUND
GT GIRDER TRUSS
HAS HEADED ANCHOR STUD
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
STRUCTURAL DRAWINGS ABBREVIATIONS
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
MARION VAMC
MARION, IL, 62959
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Project Number Scale
16-198 ADD STRUCTURAL
IMPROVEMENTS TO BUILDING
657-343AS INDICATED
100% CONSTRUCTION DOCUMENTS
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
09/06/17
Baysinger Design Group, Inc.
Marion, Illinois 62959
4501 West DeYoung Street, Suite 100B
Fax: 618.998.8032
Phone: 618.998.8015 www.BaysingerDesignGroup.com
Illinois Design Firm No. 184-004212
/1
/2
:2
:2
P
M
SS-001
ABBREVIATIONS AND SYMBOLS
DGC JHC 1
GENERAL
STRUCTURES INDICATED ON THESE DRAWINGS HAVE BEEN DESIGNED FOR THE
IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES
OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE
STRUCTURES ARE DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER
CONSTRUCTION IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
DETERMINE CONSTRUCTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF
THE STRUCTURES AND RELATED COMPONENTS DURING CONSTRUCTION. THIS
INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING,
GUYS, TIEDOWNS, ETC.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT CONSTRUCTION LOADS
DO NOT EXCEED THE CAPACITY OF ANY STRUCTURAL ELEMENT AT THE TIME THE
LOADS ARE APPLIED.
THE STRUCTURAL DRAWINGS AND SPECIFICATIONS SHALL BE USED IN CONJUNCTION
WITH THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER DISCIPLINES, TRADES, AND
DELEGATED DESIGN ELEMENTS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATION OF THE STRUCTURAL WORK WITH ALL OTHER APPLICABLE TRADES.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH
THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT.
IF A DISCREPANCY IS NOTED ON THE DRAWINGS, GENERAL NOTES, OR SPECIFICATIONS,
THE CONTRACTOR SHALL SUBMIT TO THE STRUCTURAL ENGINEER A WRITTEN REQUEST
FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE AFFECTED WORK WITHOUT
DOCUMENTED RESOLUTION OF THE DISCREPANCY. ALL COSTS RESULTING FROM THE
CONTRACTOR IMPROPERLY PROCEEDING WITH THE AFFECTED WORK PRIOR TO
DOCUMENTED RESOLUTION OF THE DISCREPANCY, INCLUDING COST OF REMOVAL
AND REPLACEMENT OF NON-CONFORMING WORK, SHALL BE BORNE BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER
A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL
BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE
CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE
OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING
INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION
OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION,
AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND
LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION
OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND
MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN
ACCORDANCE WITH "STANDARD DEVIATION" DETERMINATION OUTLINED IN
ACI 318.
13. TEMPERATURE CONTROL PLAN INCLUDING MIX DESIGN CALCULATIONS FOR
TEMPERATURE GAIN, PROTECTION, AND INSULATION MEASURES AND COOLING
METHODS IF APPROPRIATE.
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC
ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE
SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
1. FIBER REINFORCEMENT FOR CONCRETE
2. CONCRETE CURING COMPOUND
3. CONCRETE JOINT SEALANT
4. WATER STOPS
5. NON-SHRINK GROUT
6. COLD-FORMED STEEL FRAMING
7. COLD-FORMED STEEL FRAMING CONNECTOR HARDWARE
8. VAPOR RETARDER
RENOVATION (EXISTING CONDITIONS)
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS
TAKEN FROM DRAWINGS THAT WERE PREPARED FOR THE US DEPARTMENT FOR VETERAN
AFFAIRS, PREPARED BY FGM, INC, ENTITLED CLINCAL AND OUTPATIENT ADDITION, DATED 25
MARCH 1994.
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS
PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS
INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES,
MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY
THE STRUCTURAL ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK
ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR
DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR TO THE FABRICATION AND
ERECTION OF ANY NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THIS PROJECT,
THAT BECOME DAMAGED, SHALL BE REPLACED WITH NEW MATERIAL OF EQUAL
QUALITY AND APPEARANCE, AT THE CONTRACTOR'S EXPENSE.
ALL WORK SHALL BE PERFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK.
ADJACENT EXISTING CONSTRUCTION SHALL BE PROTECTED FROM DUST, DIRT AND
DEBRIS ACCUMULATION AT ALL TIMES.
FOUNDATIONS
FOUNDATION EXCAVATIONS AND SOIL RELATED WORK SHALL BE PERFORMED IN
ACCORDANCE WITH THE GEOTECHNICAL REPORT NUMBER 2017-3060.10
PREPARED BY SCI ENGINEERING, INC. DATED MARCH 27, 2017.
DESIGN NET SOIL PRESSURE:
SPREAD FOOTINGS: 4,000 PSF
CONTINUOUS WALL FOOTINGS: 4,000 PSF
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED
GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS SHALL BE FORWARDED TO THE
STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM
THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE
STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER
CONSTRUCTION IS ATTEMPTED.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS
FOOTINGS AND MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO
UNIFORM SURFACE AND SHALL BE PROTECTED AND MAINTAINED UNIFORM UNTIL
CONCRETE IS PLACED.
BELOW-GRADE WALLS
DO NOT BACKFILL AGAINST BELOW-GRADE CONCRETE (OR MASONRY) WALLS UNTIL
THE CONCRETE (OR MASONRY ASSEMBLAGE) HAS REACHED ITS 28-DAY
COMPRESSIVE STRENGTH.
WHERE BACKFILL IS REQUIRED ON BOTH SIDES OF BELOW-GRADE WALLS, BACKFILL
EVENLY ON EACH SIDE OF EACH WALL TO PREVENT UNBALANCED SOIL LOADS
AGAINST THE WALL.
UNLESS NOTED OTHERWISE, DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL THE
BASEMENT AND GROUND FLOOR SLABS HAVE BEEN COMPLETELY INSTALLED AND
REACHED THEIR 28-DAY COMPRESSIVE STRENGTH AND ALL FLOOR FRAMING AND
SLAB CONNECTIONS TO THE BASEMENT WALLS HAVE BEEN COMPLETELY INSTALLED.
WHERE BASEMENT WALLS OCCUR, BACKFILL EVENLY ON ALL SIDES OF THE BUILDING
TO PREVENT UNBALANCED SOIL LOADS AGAINST THE BASEMENT STRUCTURE,
UNLESS NOTED OTHERWISE.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND COMMENTARY
(ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE
LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301).
READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94/C94M.
IN CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150/C150M, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33/C33M.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494/C494M.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260/C260M AND SHALL BE
CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN
0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
CONCRETE ELEMENTS WITH A MINIMUM DIMENSION OF 4 FEET SHALL BE CONSIDERED MASS
CONCRETE. REFERENCE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. MASS
CONCRETE SHALL BE PLACED AND CURED UNDER THE FOLLOWING CONDITIONS: INITIAL
CONCRETE TEMPERATURE SHALL NOT EXCEED 70 DEGREES F. TEMPERATURE DIFFERENTIAL
WITHIN THE CONCRETE DURING CURING SHALL NOT EXCEED 35 DEGREES F. MAXIMUM
INTERNAL TEMPERATURE OF THE CONCRETE SHALL NOT EXCEED 160 DEGREES F.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON
THE DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL HAVE THE PROPERTIES AS INDICATED IN THE
CONCRETE MIX SCHEDULE AND SPECIFICATIONS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM
A1064/A1064M. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND LAPPED A MINIMUM OF
ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON GRADE: 2 INCHES DOWN FROM TOP OF SLAB.
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
FIBER REINFORCEMENT (SYNTHETIC)
MICRO-FIBER REINFORCEMENT SHALL BE VIRGIN (NON-RECYCLED) NYLON OR
POLYPROPYLENE FIBERS COMPLYING WITH ASTM C1116/C1116M, WITH LONGEST FIBERS
NOT LESS THAN 0.75 INCHES.
MACRO-FIBER REINFORCEMENT SHALL BE VIRGIN (NON-RECYCLED) POLYPROPYLENE /
POLYETHYLENE FIBER BLEND COMPLYING WITH ASTM C1116, WITH LONGEST FIBERS
NOT LESS THAN 1.75 INCHES.
FIBERS SHALL BE INTRODUCED INTO CONCRETE MIX AT THE BATCH PLANT AND MIXED
IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
DOSAGE RATES SHALL BE AS INDICATED IN THE CONTRACT DOCUMENTS. USE ONLY
THE FIBER TYPE INDICATED FOR EACH APPLICATION. SUBSTITUTION OF FIBER TYPES
IS NOT PERMITTED.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31/C31M FOR EACH
DAY'S POUR AND FOR EACH 50 CUBIC YARDS FOR EACH TYPE OF CONCRETE PLACED.
EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, ONE SPECIMEN TESTED
AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE
DIRECTION OF THE STRUCTURAL ENGINEER. AFTER GOOD CONCRETE QUALITY
CONTROL HAS BEEN ESTABLISHED AND MAINTAINED BY THE COR, MAKE ONE SET OF
TEST CYLINDERS FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS FOR EACH
TYPE OF CONCRETE PLACED. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER
CASTING UNLESS DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET
OF TEST CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES
DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN
ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED.
THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED
UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL CURING BOXES
ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
COMPOSITE STEEL BEAMS
COMPOSITE BEAM SHEAR CONNECTORS SHALL BE NELSON STUD TYPE S3L AS
MANUFACTURED BY THE NELSON STUD WELDING COMPANY, OR AN EQUIVALENT
SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER.
STUDS SHALL BE MANUFACTURED OF COLD-DRAWN STEEL CONFORMING TO ASTM
A108. STUDS SHALL BE 3/4" DIAMETER, UNLESS NOTED OTHERWISE. STUD DESIGN
HAS BEEN BASED ON AN ULTIMATE SHEAR CAPACITY OF 17.7 KIPS PER STUD.
INSTALLED STUD LENGTH SHALL BE 1" LESS THAN TOTAL NOMINAL SLAB THICKNESS,
UNLESS NOTED OTHERWISE.
COMPOSITE STEEL BEAMS HAVE BEEN DESIGNED TO ALLOW INSTALLATION OF THE
SLAB CONCRETE IN AN UNSHORED CONDITION UNLESS NOTED OTHERWISE.
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE
STEEL DECK INSTITUTE'S SPECIFICATIONS AND CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS
EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION,
WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS.
PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION
UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS
AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE
WET WEIGHT OF CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT
THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION
WHEREVER POSSIBLE. WHERE THREE SPAN CONDITION IS NOT POSSIBLE, NOTIFY
STRUCTURAL ENGINEER PRIOR TO FABRICATION OF DECK SO THAT EVALUATION OF
THE LESSER SPAN CONDITION(S) CAN BE PERFORMED.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK SUPPORTING EXTERIOR SLABS WITH A GALVANIZED FINISH IN
ACCORDANCE WITH ASTM A924/A924M G90.
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL
DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN A CONSTANT
SLAB THICKNESS.
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO
THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES
AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE
BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR
SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING,
INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS. CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY
DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER STEEL ELEVATIONS, ETC.)
IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR
REVIEW BY THE STRUCTURAL ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED
NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT
WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS;
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL
NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE
STRUCTURAL ENGINEER.
PROVIDE SLABS ON METAL DECK WITH A SMOOTH TROWEL FINISH UNLESS NOTED
OTHERWISE.
CONTRACTOR SHALL REVIEW ALL REQUIRED FLOOR FINISH MATERIAL REQUIREMENTS
PRIOR TO PLACEMENT OF CONCRETE AND SHALL PROVIDE FLOOR SLAB FLATNESS
MEETING THE FINISH MATERIAL SUPPLIER’S WRITTEN REQUIREMENTS. FLATNESS
SHALL BE THE MORE STRINGENT OF THE FINISH MATERIAL REQUIREMENTS AND THE
FOLLOWING:
ALL SLABS, UNO:
OVERALL VALUES: FF=25
LOCAL VALUES: FF=20
CONTRACTOR SHALL PROVIDE ALL NECESSARY REPAIR, GRINDING AND/OR LEVELING OF
THE CONCRETE SLAB TO ACCOMMODATE ALL FLOOR FINISHES PRIOR TO INSTALLATION
OF THE FINISH MATERIALS WITH NO ADDITIONAL COST TO THE PROJECT.
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST
SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON
THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS ON METAL DECK AS REQUIRED TO
ACCOMMODATE FLOOR FINISHES AND FINISH MATERIALS PER THE ARCHITECTURAL
DRAWINGS AND SPECIFICATIONS. REVIEW ALL FLOOR FINISH REQUIREMENTS PRIOR
TO PLACEMENT OF CONCRETE SLABS AND COORDINATE SLAB MIX, PLACEMENT AND
CURING TO COMPLY WITH FINISH FLOORING MATERIAL MANUFACTURER’S
REQUIREMENTS.
CURING PROCEDURES SHALL COMPLY WITH ACI 302.1R AND USE OF CURING MATERIALS
SHALL BE APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.
MOISTURE RETENTION COVERS, IF USED, SHALL BE APPLIED FLAT AND SMOOTH TO
RESULT IN A UNIFORM APPEARANCE AND MINIMIZE SURFACE MARKINGS AND BLEMISHES.
UNLESS NOTED OTHERWISE, OR UNLESS MORE STRINGENT REQUIREMENTS APPLY,
CURE SLABS ON METAL DECK AS FOLLOWS:
SLABS RECEIVING FLOOR COVERING MATERIALS: MOIST CURE A MINIMUM OF
7 DAYS (OR, IF APPROVED BY FLOOR FINISH MATERIAL MANUFACTURER, USE
ASTM C309, TYPE 1, CLASS B, WATERBORNE, MEMBRANE-FORMING CURING
COMPOUND, DISSIPATING). REMOVAL OF CURING COMPOUND MATERIAL, IF
REQUIRED FOR PROPER INSTALLATION OF FLOOR FINISH MATERIALS, SHALL BE
PERFORMED BY THE CONCRETE CONTRACTOR.
EXPOSED SLABS: USE ASTM C1315, TYPE 1, CLASS A, WATERBORNE, MEMBRANE-
FORMING CURING AND SEALING COMPOUND.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND
SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE
LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 301, ACI 315, ACI 318, ACI
DETAILING MANUAL (SP66), AND CRSI MANUAL OF STANDARD PRACTICE.
THE CONTRACTOR SHALL PROVIDE BAR SUPPORTS AND SPACERS AS REQUIRED TO
MAINTAIN PROPER SUPPORT AND POSITIONING OF THE REINFORCING STEEL
THROUGHOUT CONCRETE PLACEMENT OPERATIONS. DESIGN OF THE SUPPORT
SYSTEM SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE
THE FOLLOWING MINIMUM CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST EARTH: 3 INCHES
FOUNDATION TOP REINFORCEMENT: 2 INCHES
FOUNDATION BOTTOM AND SIDE REINFORCEMENT: 3 INCHES
WALL REINFORCEMENT - #5 AND SMALLER: 1-1/2 INCHES
WALL REINFORCEMENT - #6 AND LARGER: 2 INCHES
ELEVATED SLAB TOP REINFORCEMENT: 2 INCHES
ELEVATED SLAB BOTTOM REINFORCEMENT: 1 INCH
BEAM TOP REINFORCEMENT: 2-1/2 INCHES
BEAM BOTTOM REINFORCEMENT: 2 INCHES
BEAM STIRRUPS AT TOP: 2 INCHES
COLUMN LONGITUDINAL REINFORCEMENT: 2 INCHES
COLUMN TIES: 1-1/2 INCHES
SLAB ON METAL DECK REINFORCEMENT: SEE DETAILS
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT
UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE
STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT
CORNERS OF ALL WALLS AND GRADE BEAMS. LAP SPLICE CORNERS BARS WITH
STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE)
AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE
BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
DESIGN DATA
NEW STRUCTURES ON THESE DRAWINGS HAVE BEEN DESIGNED IN ACCORDANCE WITH
THE 2015 INTERNATIONAL BUILDING CODE.
FLOOR LOADS
LIVE LOAD 100 PSF
DEAD LOAD 58 PSF
UNLESS OTHERWISE NOTED, FLOOR FRAMING HAS BEEN DESIGNED UTILIZING LIVE
LOAD REDUCTIONS TO THE EXTENT ALLOWED BY THE BUILDING CODE.
ROOF LOADS
LIVE LOAD 20 PSF
DEAD LOAD 12 PSF
SNOW LOAD DESIGN DATA
GROUND SNOW LOAD (PG) = 15 PSF
SNOW EXPOSURE FACTOR (CE) = 1.0
THERMAL FACTOR (CT) = 1.0
SNOW LOAD IMPORTANCE FACTOR (IS) = 1.2
LOW-SLOPE ROOF SNOW LOAD (PF) = 12.6 PSF
MINIMUM LOW-SLOPE ROOF SNOW LOAD (PM) = 18 PSF
WIND LOAD DESIGN DATA
BASIC WIND SPEED (3-SECOND GUST) = 120 MPH
WIND EXPOSURE = C
WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
EARTHQUAKE DESIGN DATA
SHORT PERIOD SPECTRAL RESPONSE (SS) = 0.909
1-SECOND SPECTRAL RESPONSE (S1) = 0.31
SEISMIC IMPORTANCE FACTOR (IE) = 1.50
RISK CATEGORY = IV
SEISMIC DESIGN CATEGORY = D
SITE CLASSIFICATION = C
SHORT PERIOD SPECTRAL RESPONSE (SDS) = 0.628
1-SECOND SPECTRAL RESPONSE (SD1) = 0.308
SEISMIC RESISTING SYSTEM: SPECIAL CONCENTRICALLY BRACED STEEL FRAMES
ANALYSIS PROCEDURE UTILIZED = MODAL RESPONSE SPECTRUM ANALYSIS
RESPONSE MODIFICATION COEFFICIENT (R) = 6.0
SEISMIC RESPONSE COEFFICIENT (CS) = 0.157
THE STRUCTURE ON THESE DRAWINGS HAVE BEEN DESIGNED FOR A VERTICAL EXPANSION
OF TWO LEVELS.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50
COAL TAR MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THE
STRUCTURAL ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS.
PROVIDE FULL COVERAGE OVER ITEMS INDICATED TO RECEIVE COATING.
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST
EDITION OF THE GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST
SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT
ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS ON GRADE AS REQUIRED TO ACCOMMODATE
FLOOR FINISHES AND FINISH MATERIALS PER THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS. REVIEW ALL FLOOR FINISH REQUIREMENTS PRIOR TO PLACEMENT
OF CONCRETE SLABS AND COORDINATE SLAB MIX, PLACEMENT AND CURING TO
COMPLY WITH FINISH FLOORING MATERIAL MANUFACTURER’S REQUIREMENTS.
CURING PROCEDURES SHALL COMPLY WITH ACI 302.1R AND USE OF CURING
MATERIALS SHALL BE APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER’S
REQUIREMENTS. MOISTURE RETENTION COVERS, IF USED, SHALL BE APPLIED
FLAT AND SMOOTH TO RESULT IN A UNIFORM APPEARANCE AND MINIMIZE SURFACE
MARKINGS AND BLEMISHES.
UNLESS NOTED OTHERWISE, OR UNLESS MORE STRINGENT REQUIREMENTS APPLY,
CURE SLABS ON GRADE AS FOLLOWS:
SLABS RECEIVING FLOOR COVERING MATERIALS: MOIST CURE A MINIMUM OF
7 DAYS (OR, IF APPROVED BY FLOOR FINISH MATERIAL MANUFACTURER, USE
ASTM C309, TYPE 1, CLASS B, WATERBORNE, MEMBRANE-FORMING CURING
COMPOUND, DISSIPATING). REMOVAL OF CURING COMPOUND MATERIAL, IF
REQUIRED FOR PROPER INSTALLATION OF FLOOR FINISH MATERIALS, SHALL BE
PERFORMED BY THE CONCRETE CONTRACTOR.
EXPOSED SLABS UNO: ASTM C1315, TYPE 1, CLASS A, WATERBORNE, MEMBRANE-
FORMING CURING AND SEALING COMPOUND.
EXPOSED WAREHOUSE SLABS: USE ASHFORD FORMULA CURING/ SEALING/
HARDENING COMPOUND.
PROVIDE SLABS ON GRADE WITH A SMOOTH TROWEL FINISH UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL REVIEW ALL REQUIRED FLOOR FINISH MATERIAL REQUIREMENTS
PRIOR TO PLACEMENT OF CONCRETE AND SHALL PROVIDE FLOOR SLAB FLATNESS
AND LEVELNESS MEETING THE FINISH MATERIAL SUPPLIER’S WRITTEN REQUIREMENTS.
FLATNESS AND LEVELNESS SHALL BE THE MORE STRINGENT OF THE FINISH MATERIAL
REQUIREMENTS AND THE FOLLOWING:
ALL SLABS, UNO:
OVERALL VALUES: FF=25 FL=20
LOCAL VALUES: FF=20 FL=15
WAREHOUSE SLABS:
OVERALL VALUES: FF=35 FL=25
LOCAL VALUES: FF=25 FL=15
CONTRACTOR SHALL PROVIDE ALL NECESSARY REPAIR, GRINDING AND/OR LEVELING
OF THE CONCRETE SLAB TO ACCOMMODATE ALL FLOOR FINISHES PRIOR TO
INSTALLATION OF THE FINISH MATERIALS WITH NO ADDITIONAL COST TO THE PROJECT.
THE MINIMUM LOCAL AREA SHALL BE ANY BAY DEFINED BY COLUMN LINES.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION
JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB
THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO
ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR
SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL
UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN
ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED,
NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA
SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS.
GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF 5,000 PSI IN
28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURER'S WRITTEN INSTRUCTIONS.
VAPOR RETARDER
VAPOR RETARDER SHALL BE ASTM E1745 CLASS A WITH A PERMEANCE OF 0.1 PERMS
OR LESS, UNO. INSTALL, INSPECT AND REPAIR IN ACCORDANCE WITH ASTM E1643 AND
MANUFACTURER’S WRITTEN REQUIREMENTS. INSTALL VAPOR RETARDER ONLY AT
LOCATIONS SPECIFICALLY INDICATED.
DELEGATED DESIGN
FOR ALL SUBMITTALS INDICATED AS "DELEGATED DESIGN," THE CONTRACTOR SHALL
ENGAGE A LICENSED PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE
PROJECT IS LOCATED TO DESIGN AND DETAIL THE ITEMS NOTED IN THE STRUCTURAL
SUBMITTALS AND SPECIFICATIONS AS A DELEGATED DESIGN.
THE SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED FOR REVIEW AND
CONTAIN OR INDICATE THE FOLLOWING AT A MINIMUM:
1. PROFESSIONAL ENGINEER’S SEAL AND SIGNATURE RESPONSIBLE FOR THEIR
PREPARATION.
2. COMPLIANCE WITH THE PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA
NOTED IN THE CONTRACT DOCUMENTS (DRAWINGS AND SPECIFICATIONS).
3. LOCATION, TYPE, MAGNITUDE AND DIRECTION OF ALL LOADS IMPOSED ON THE
BUILDING STRUCTURE
SUBMITTALS THAT DO NOT CONTAIN THE INFORMATION NOTED ABOVE WILL BE
REJECTED WITHOUT COMMENT.
THE STRUCTURAL ENGINEER’S REVIEW OF DELEGATED DESIGN SUBMITTALS WILL BE
FOR GENERAL CONFORMANCE WITH THE DESIGN LOADING, DESIGN INTENT AND LOADS
IMPOSED.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO
FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE
WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE
REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE
CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO
SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT
CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
PROVIDE ALL SUBMITTALS IN ELECTRONIC PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. STRUCTURAL STEEL
3. STEEL DECK
SUBMIT DELEGATED DESIGN SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. STRUCTURAL STEEL CONNECTIONS (INCLUDING DESIGN CALCULATIONS AND
SUMMARY PAGE FOR CONNECTIONS NOT SPECIFICALLY DETAILED IN THE
CONTRACT DRAWINGS)
2. COLD-FORMED STEEL FRAMING (INCLUDING DESIGN CALCULATIONS, MEMBER
PROPERTIES, FASTENER REQUIREMENTS, ASSEMBLY DETAILS AND
CONNECTION DETAILS)
STRUCTURAL STEEL - ASD
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE
ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH
AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS
AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992/A992M.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES
SHALL CONFORM TO ASTM A36/A36M, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500/A500M, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53/A53M, GRADE B.
STRUCTURAL STEEL ROD HANGERS AND BRACING SHALL CONFORM TO ASTM A36,
UNLESS NOTED OTHERWISE.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36/A36M, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL
JOINTS USING ASTM F3125/F3125M GRADE 120 OR 150 BOLTS, APPROVED BY THE RESEARCH COUNCIL
ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR
STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER F3125/F3125M BOLTS, UNLESS NOTED OTHERWISE. BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN BRACE ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A
FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN
WELDING SOCIETY'S STRUCTURAL WELDING CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992/A992M STEEL AS A BASE METAL SHALL BE MADE
WITH E70XX LOW HYDROGEN ELECTRODES. UNLESS OTHERWISE SHOWN OR NOTED ON
THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX
ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST
INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL
VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE ARCHITECT.
COORDINATE FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES
NOT RECEIVE FINISH PAINT SHALL NOT BE SHOP-PRIMED, UNLESS NOTED OTHERWISE ON
THE DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN
CONFORMANCE WITH ASTM A123/A123M.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN
ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE.
FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED
STEEL, USE A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD
SPECIFICATION ANDMANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE
ON THE DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM
SHEAR REACTION OF 16 KIPS ASD. PROVIDE NO LESS THAN 2 BOLTS IN
ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
PROVIDE L4X4X1/4 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR
LARGER ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO
MECHANICAL AND PLUMBING DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED
OPENING SIZES AND LOCATIONS WITH THE MECHANICAL AND PLUMBING CONTRACTORS.
FLOWABLE FILL
WHERE INDICATED ON THE STRUCTURAL DRAWINGS, FLOWABLE FILL SHALL BE A
CONTROLLED LOW-STRENGTH MATERIAL (CLSM) PRODUCED AND PLACED IN
ACCORDANCE WITH RECOMMENDATIONS OF ACI 229. PROVIDE MATERIAL WITH
28-DAY COMPRESSIVE STRENGTH OF 1,000 PSI UNLESS NOTED OTHERWISE.
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
MARION VAMC
MARION, IL, 62959
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Project Number Scale
16-198 ADD STRUCTURAL
IMPROVEMENTS TO BUILDING
657-343AS INDICATED
100% CONSTRUCTION DOCUMENTS
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
09/06/17
Baysinger Design Group, Inc.
Marion, Illinois 62959
4501 West DeYoung Street, Suite 100B
Fax: 618.998.8032
Phone: 618.998.8015 www.BaysingerDesignGroup.com
Illinois Design Firm No. 184-004212
/1
/2
:2
:2
P
M
SS-002
GENERAL NOTES
DGC JHC
CONCRETE UNIT MASONRY
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE LATEST
EDITION OF THE BUILDING CODE REQUIREMENTS OF CONCRETE MASONRY
STRUCTURES (ACI 530).
CONCRETE MASONRY SHALL CONSIST OF HOLLOW UNITS CONFORMING TO THE
REQUIREMENTS OF ASTM C90, WITH A MINIMUM NET AREA COMPRESSIVE STRENGTH
OF 1,900 PSI. CONCRETE MASONRY ASSEMBLAGES SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH (F'M) OF 1,500 PSI AT 28 DAYS.
MORTAR SHALL BE TYPE S PROPORTIONED IN ACCORDANCE WITH ASTM C270.
GROUT FOR REINFORCED MASONRY SHALL BE PROPORTIONED IN ACCORDANCE WITH
ASTM C476. COARSE AND FINE AGGREGATES SHALL CONFORM TO ASTM C 404. USE
COARSE GROUT FOR ALL GROUTING EXCEPT HIGH-LIFT POURS DEFINED BY ACI 530-05
TABLE 1.16.1, WHERE FINE GROUT SHALL BE USED.
PROVIDED 9-GAUGE GALVANIZED STEEL WIRE JOINT REINFORCEMENT IN ALL MASONRY
CONSTRUCTION. REINFORCEMENT SHALL BE CONTINOUS AND BE LAPPED EIGHT
INCHES AT SPLICES. CUT REINFORCEMENT AT ALL CONTROL AND EXPANSION JOINTS.
SPACE REINFORCEMENT AT 8" ON CENTER FOR PARAPETS AND BELOW GROUND
FLOOR ELEVATION. ELSEWHERE SPACE REINFORCEMENT AT 16 INCHES ON CENTER.
BEAMS AND LINTELS SHALL BEAR A MINIMUM OF 8 INCHES ONTO SUPPORTING
MASONRY, UNLESS NOTE OTHERWISE. BEARING FOR ALL BEAMS, LINTELS, JOISTS,
ETC. SHALL BE GROUTED SOLID A MINIMUM OF ONE COURSE (8 INCHES) BELOW
BEARING ELEVATION, UNLESS NOTED OTHERWISE.
PROVIDE MASONRY CONTROL JOINTS AT 25'-0" OC MAXIMUM, UNO. LOCATE JOINTS IN
ACCORDANCE WITH NCMA TEK 10-2C "CONTROL JOINTS FOR CONCRETE MASONRY
WALLS - EMPIRICAL METHOD" AT OFFSETS, SETBACKS, WALL INTERSECTIONS,
CORNERS, CHANGES IN THICKNESS, CHANGES IN HEIGHT, OR EDGE OF OPENINGS.
DEDUCTIVE BID OPTION
BID DEDUCTS ARE AS INDICATED ON SHEET GI102
SPECIAL INSPECTION SERVICES SCHEDULE - CONCRETE CONSTRUCTION
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
MATERIAL TESTING
QUALITY CONTROL
REINFORCING STEEL
CAST-IN-PLACE
BOLTS AND
ANCHOR RODS
CONCRETE MIX
DESIGN
FORMWORK
MATERIAL SAMPLING
AND TESTING
CONCRETE
PLACEMENT
CURING AND
PROTECTION
CONSTRUCTION
JOINTS
TEST
REFERENCE CAST-IN-PLACE CONCRETE SPECIFICATION FOR EXTENT OF TESTING
REQUIRED
INSPECTION VERIFY THAT QUALITY CONTROL TESTING IS PROVIDED IN ACCORDANCE WITH THE
PROJECT REQUIREMENTS.
INSPECTION
INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS (WHEN
USED) AND PLACEMENT AS FOLLOWS:
VERIFY THAT REINFORCEMENT SURFACES ARE FREE OF EXCESS RUST OR OTHER
COATINGS THAT MAY ADVERSELY AFFECT BONDING CAPACITY. IF OILING OF FORMS
IS REQUIRED, VERIFY THAT IT IS APPLIED BEFORE REINFORCING IS PLACED.
VERIFY REINFORCING BARS FOR COMPLIANCE WITH CONTRACT DOCUMENTS AND
APPROVED SHOP DRAWINGS AS FOLLOWS:
MATERIAL GRADE, SIZE, QUANTITY, SPACING, AND LAYERING; BARS ARE
ADEQUATELY TIED AND SUPPORTED ON CHAIRS OR BOLSTERS; PROPER HOOK
TYPE AND LOCATION; SPLICE LOCATIONS AND REQUIRED LENGTH OF LAP;
PROPER CLEARANCE AND COVER REQUIREMENTS FROM CONCRETE SURFACES;
SUFFICIENT SPACING BETWEEN REINFORCEMENT FOR CONCRETE PLACEMENT;
VERIFY THAT UNSCHEDULED/ADDITIONAL REINFORCING BARS SHOWN ON
PLAN, IN DETAIL, OR SPECIFIED IN NOTES ARE PROVIDED AND ARE IN
COMPLIANCE WITH CONTRACT DOCUMENTS AND APPROVED SHOP DRAWINGS.
MECHANICAL SPLICES:
(TENSION AND/OR COMPRESSION) ON THE PROJECT. VERIFY COMPLIANCE
WITH SPECIFICATIONS AND CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS FOR INSTALLATION. VERIFY THAT THE MANUFACTURER IS
PRESENT FOR THE FIRST INSTALLATION OF EACH TYPE OF SPLICE ON THE
PROJECT.
VERIFY THAT WELDED WIRE REINFORCEMENT IS COMPOSED OF FLAT SHEETS, HAS
PROPER WIRE GAUGE AND SPACING, IS PROPERLY SUPPORTED, AND IS PROPERLY
LAPPED.
INSPECT HEADED STUD SHEAR REINFORCEMENT TO ENSURE THAT IT CONFORMS
TO THE PROJECT REQUIREMENTS:
REVIEW TYPE AND SPACING; VERIFY THAT REINFORCING IS ADEQUATELY
SUPPORTED TO RESIST DISPLACEMENT OR SHIFTING DURING CONCRETE
PLACEMENT; VERIFY WELDING OF REINFORCEMENT IS PERFORMED ACCORDING
TO AWS REQUIREMENTS AND THAT IT IS INSPECTED BY THE TESTING
LABORATORY.
INSPECT BOLTS AND ANCHOR RODS TO BE CAST IN CONCRETE PRIOR TO PLACEMENT OF
CONCRETE FOR SIZE, QUANTITY, LOCATION, POSITION AND EMBEDMENT. INSPECT
DURING PLACEMENT FOR PROPER CONCRETE CONSOLIDATION AROUND BOLTS AND
ANCHORS.INSPECTION
BOLTS AND/OR ANCHOR RODS USED IN LATERAL FORCE RESISTING SYSTEM AT THE
FOLLOWING LOCATIONS: <LIST GRID LOCATIONS>
20% OF BOLTS AND/OR ANCHOR RODS USED ELSEWHERE.
INSPECTION
REVIEW AND BECOME FAMILIAR WITH THE MIX DESIGNS SPECIFIED ON THE
PROJECT. VERIFY MIX DESIGN PROVIDED BY THE CONTRACTOR IS CONSISTENT WITH
PROJECT SPECIFICATIONS AT LOCATION INDICATED. REVIEW CONCRETE BATCH
TICKETS TO PROPER MIX ID, TYPE OF CONCRETE AND STRENGTH FOR THE PLACEMENT
LOCATION. VERIFY THAT WATER ADDED AT SITE (IF PERMITTED), DOES NOT EXCEED
THAT ALLOWED BY THE MIX DESIGN.
INSPECTION OF
FORMED AREA
INSPECTION VERIFY THAT ALL DEBRIS AND FOREIGN MATTER HAVE BEEN REMOVED BEFORE
CONCRETE IS PLACED
INSPECTION
INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE
MEMBER BEING FORMED. VERIFY FORMWORK USED IN COMPLIANCE WITH THE
SPECIFICATIONS AND APPROVAL SHOP DRAWINGS (WHEN REQUIRED).
TEST
AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE
INSPECTION
INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES AS FOLLOWS:
VERIFY THE CONCRETE IS NOT OVER 90 MINUTES OLD AT TIME OF PLACEMENT;
HOT-WEATHER OR COLD-WEATHER TECHNIQUES ARE BEING APPLIED AS
REQUIRED; CONCRETE BEING DEPOSITED IN UNIFORM, THAT THE VERTICAL DROP
DOES NOT EXCEED SIX FEET, AND THAT CONCRETE IS NOT PERMITTED TO DROP
FREELY OVER REINFORCEMENT CAUSING SEGREGATION; CONCRETE IS PROPERLY
VIBRATED; EMBEDDED ITEMS AND REINFORCING STEEL ARE NOT ADVERSELY
ALTERED DURING PLACEMENT. NOTE IF ANYTHING WAS DISPLACED OR
OTHERWISE ALTERED DURING PLACEMENT; VERIFY THAT THERE ARE NO COLD
JOINTS WITHIN THE AREA OF THE POUR
INSPECTION
VERIFY THE CURING PROCESS IS AS SPECIFIED IN THE CONTRACT DOCUMENTS AND
THAT ANY CURING COMPOUND USED IS APPLIED IN ACCORDANCE WITH
MANUFACTURER'S PRINTED APPLICATION INSTRUCTIONS.
INSPECTION
VERIFY THAT LOCATION OF VERTICAL AND HORIZONTAL CONSTRUCTION JOINTS FOR
COMPLIANCE WITH THE CONSTRUCTION JOINT LOCATION PLAN SUBMITTED BY THE
CONTRACTOR TO ENGINEER OF RECORD. VERIFY THAT REINFORCEMENT, DOWELS, KEYS,
AND BULKHEADS AT CONSTRUCTION JOINTS ARE IN CONFORMANCE WITH THE
CONTRACT DOCUMENTS.
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
PERIODIC
PERIODIC
PERIODIC
CONTINUOUS
PERIODIC
PERIODIC
CONTINUOUS
PERIODIC
PERIODIC
PERIODIC
PERIODIC
CONTINUOUS
CONTINUOUS
PERIODIC
PERIODIC
N
SPECIAL INSPECTION SERVICES SCHEDULE - FOUNDATION WALLS AND PITS
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
CONCRETE
PLACEMENT
FORMWORK
DIMENSIONS
EMBEDDED ITEMS
REINFORCEMENT
BACKFILL
OPERATIONS
CONCRETE
INSPECTION
THE INSPECTOR MUST BE PRESENT FULL TIME DURING THE ENTIRE PLACEMENT
OF THE FIRST 2 SHALLOW FOUNDATION CONCRETE POURS AND THEN MUST BE
PRESENT AT THE START OF 100% OF OTHER CONCRETE POURS.
INSPECTION VERIFY THAT FORMS ARE PLUMB AND STRAIGHT, BRACED AGAINST MOVEMENT,
AND LUBRICATED FOR REMOVAL.
INSPECTION
INSPECTION
INSPECTION
WATERSTOPS INSPECTION
INSPECTION
INSPECTION
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
VERIFY WALL/PIT DIMENSIONS.
VERIFY ANCHOR RODS AND/OR DOWELS ARE INSTALLED WITH THE EMBEDMENT
AND PROJECTED LENGTHS AND IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
VERIFY PIT/WALL REINFORCEMENT PRIOR TO PLACEMENT OF CONCRETE
VERIFY WATER STOPS ARE PROPERLY INSTALLED AND ANCHORED INTO POSITION
PRIOR TO PLACEMENT OF CONCRETE.
VERIFY THAT FOUNDATION AND PIT WALLS WITH UNEVEN BACKFILL CONDITIONS
ARE NOT BACKFILLED UNTIL FLOOR CONSTRUCTION AT TOP OF WALL IS COMPLETE
OR TEMPORARY BRACING IS PROVIDED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
VERIFY CONCRETE PLACEMENT AS OUTLINED IN THIS INSPECTION PLAN.
Y
Y
Y
Y
Y
Y
Y
Y
SPECIAL INSPECTION SERVICES SCHEDULE - SHALLOW FOUNDATIONS
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
CONCRETE
PLACEMENT
FOOTING SUBGRADE
FORMWORK
EARTH-FORMED
FOUNDATION
DIMENSIONS
REINFORCEMENT
CONCRETE
INSPECTION
THE INSPECTOR MUST BE PRESENT FULL TIME DURING THE ENTIRE PLACEMENT
OF THE FIRST 2 SHALLOW FOUNDATION CONCRETE POURS AND THEN MUST BE
PRESENT AT THE START OF 100% OF OTHER CONCRETE POURS.
INSPECTION
VERIFY APPROVAL OF THE FOOTING SUBGRADE PRIOR TO PLACEMENT OF FOUNDATION
CONCRETE.
INSPECTION
INSPECTION
EMBEDDED ITEMS INSPECTION
INSPECTION
INSPECTION
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
VERIFY THAT FORMS ARE PLUMB AND STRAIGHT, BRACED AGAINST MOVEMENT, AND
LUBRICATED FOR REMOVAL.
FOR EARTH-FORMED FOUNDATIONS, VERIFY THAT EARTH FORMS ARE SUFFICIENTLY
UNIFORM TO ALLOW FOR PROPER DIMENSIONS AND REQUIRED CONCRETE COVER
OVER REINFORCEMENT.
VERIFY FOUNDATION DIMENSIONS.
VERIFY ANCHOR RODS AND/OR DOWELS ARE INSTALLED WITH THE EMBEDMENT AND
PROJECTED LENGTHS AND IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
VERIFY FOUNDATION REINFORCEMENT PRIOR TO PLACEMENT OF CONCRETE.
VERIFY CONCRETE PLACEMENT AS OUTLINED IN THIS INSPECTION PLAN.
INSPECTION
Y
Y
Y
Y
Y
Y
Y
Y
SPECIAL INSPECTION SERVICES SCHEDULE - SOILS AND EARTHWORK
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
FOOTING SUBGRADE
COMPACTION OF
SOILS
CONTROLLED
STRUCTURAL FILL
FOOTING SUBGRADE
MATERIAL
EXCAVATION
USE OF PROPER
MATERIALS
OBSERVATION OF
SUBGRADE
TEST REFERENCE EARTHWORK SPECIFICATION FOR EXTENT OF TESTING REQUIRED
TEST REFERENCE EARTHWORK SPECIFICATION FOR EXTENT OF TESTING REQUIRED
TEST
INSPECTION
CLASSIFICATION OF
CONTROLLED FILL
INSPECTION
INSPECTION
INSPECTION
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
CONTINUOUS
REFERENCE EARTHWORK SPECIFICATION FOR EXTENT OF TESTING REQUIRED
INSPECT SOILS BELOW FOUNDATIONS AND SLABS FOR ADEQUATE
COMPACTION AND BEARING CAPACITY PROPER TO PLACEMENT OF CONCRETE.
VERIFY EXCAVATIONS ARE EXTENDED TO THE PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL.
1) INSPECT PLACEMENT, LIFT THICKNESS AND COMPACTION OF CONTROLLED FILL.
2) VERIFY EXTENT AND SLOPE OF FILL PLACEMENT.
VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF CONTROLLED FILL
PRIOR TO PLACEMENT OF CONTROLLED FILL, OBSERVE SUBGRADE AND VERIFY THAT
SITE HAS BEEN PREPARED PROPERLY
INSPECTION
Y
Y
Y
Y
Y
Y
Y
Y
SPECIAL INSPECTION SERVICES SCHEDULE - MASONRY CONSTRUCTION
(LEVEL 1 INSPECTION)
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
MATERIAL TESTING
QUALITY CONTROL
TEST REFERENCE MASONRY SPECIFICATION FOR EXTENT OF TESTING REQUIRED
INSPECTION
VERIFY THAT QUALITY CONTROL TESTING IS PROVIDED IN ACCORDANCE WITH THE
PROJECT REQUIREMENTS.
Y PERIODIC
CONTINUOUS
MATERIALS
WALL LOCATIONS
CONTROL JOINTS
OPENINGS
CONNECTIONS
REINFORCING STEEL
MORTAR AND GROUT
PROTECTION
EMBEDDED ITEMS
VERIFY THE MATERIALS ARE STORED PROPERLY BEFORE PLACEMENT IN THE STRUCTURE
VERIFY THE WALL LOCATIONS AND THICKNESSES
VERIFY THE PROPER INSTALLATION OF CONTROL JOINTS, TYPE AND LOCATION
VERIFY THE PROPER INSTALLATION OF STRUCTURAL ELEMENTS AROUND OPENINGS
INCLUDING LINTELS, SILLS, AND DOOR OR WINDOW JAMBS INCLUDING MASONRY UNIT
TYPE AND REINFORCEMENT
VERIFY THE MASONRY IS PROPERLY CONNECTED TO THE SUPPORTING STRUCTURE(S)
INSPECTION OF REINFORCING STEEL AND PLACEMENT AS FOLLOWS:
VERIFY THAT REINFORCEMENT SURFACES ARE FREE OF EXCESS RUST OR OTHER
COATINGS THAT MAY ADVERSELY AFFECT BONDING CAPACITY.
VERIFY REINFORCING BARS AND HORIZONTAL JOINT REINFORCEMENT FOR COMPLIANCE
WITH CONTRACT DOCUMENTS AND APPROVED SHOP DRAWINGS AS FOLLOWS:
MATERIAL GRADE, SIZE, QUANTITY, SPACING, AND LAYERING; BARS ARE ADEQUATELY
TIED AND SUPPORTED ON CHAIRS AND CENTERED AS REQUIRED; PROPER HOOK TYPE
AND LOCATION; SPLICE LOCATIONS AND REQUIRED LENGTH OF LAP; PROPER
CLEARANCE AND COVER REQUIREMENTS FROM MASONRY SURFACES; SUFFICIENT
SPACING BETWEEN REINFORCEMENT FOR GROUT PLACEMENT; VERIFY THAT
UNSCHEDULED/ADDITIONAL REINFORCING BARS SHOWN ON PLAN, IN DETAILS, OR
SPECIFIED IN NOTES ARE PROVIDED AND ARE IN COMPLIANCE WITH CONTRACT
DOCUMENTS AND APPROVED SHOP DRAWINGS.
INSPECT EMBEDDED ITEMS TO BE CAST IN MASONRY PRIOR TO PLACEMENT OF GROUT
FOR SIZE, QUANTITY, LOCATION, POSITION AND EMBEDMENT. INSPECT DURING
PLACEMENT FOR PROPER GROUT CONSOLIDATION EMBEDDED ITEMS.
INSPECT THE MORTAR AND GROUT USED ON THE PROJECT AS FOLLOWS:
VERIFY THAT MORTAR AND GROUT MATERIALS COMPLY WITH THE CONTRACT
DOCUMENTS AND APPROVED SUBMITTALS.
SITE-MIXED MORTAR: VERIFY THE MORTAR IS MIXED IN ACCORDANCE WITH SPECIFIED
PROPORTIONS.
BAG-MIX MORTAR: VERIFY THE MORTAR IS MIXED ACCORDING TO THE
MANUFACTURER’S INSTRUCTIONS.
VERIFY PROPER MORTAR PLACEMENT.
GROUT BAG MIX: VERIFY THAT THE GROUT IS MIXED ACCORDING TO THE
MANUFACTURER’S INSTRUCTIONS.
READY-MIX GROUT: VERIFY THE MIX NUMBER AND GROUT STRENGTH.
PRIOR TO ANY GROUTING PROCEDURE, INSPECT THE GROUT SPACE TO VERIFY THAT
IT IS CLEAN AND THAT CLEANOUTS, IF REQUIRED, ARE IN PLACE AND CONFORM TO
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
VERIFY THE PROPER GROUT PLACEMENT AND CONSOLIDATION.
VERIFY THAT GROUT TESTING IS PERFORMED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
VERIFY THE PROPER CONSTRUCTION TECHNIQUES ARE FOLLOWED FOR PROTECTION
OF MASONRY DURING HOT-WEATHER AND/OR COLD-WEATHER CONSTRUCTION.
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
SPECIAL INSPECTION SERVICES SCHEDULE - STEEL CONSTRUCTION
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N) FREQUENCY
FABRICATOR QUALITY
CONTROL PROCESS
QUALITY
MILL TEST REPORTS
WELDED
CONNECTIONS
BOLTED
CONNECTIONS
STEEL FRAMING,
DETAILS AND
CONNECTORS
COMPOSITE BEAM
SHEAR CONNECTORS
GRATING
INSPECTION
VERIFY THE FABRICATOR MEETS AISC CERTIFIED…