36C25020B0033-021.pdf

PDF Posted

Attached to
Z1DA--Replace CAT Scan AHU 539-20-213 Federal contract opportunity
Solicitation number
36C25020B0033
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document provides details for a federal contract opportunity to replace a CAT scan air handling unit at the Veterans Affairs Medical Center in Cincinnati, Ohio. The project involves removing the existing AHU and installing a new unit along with associated ductwork, piping, controls and other mechanical work. The solicitation number is 36C25020B0033 and will be released on or around January 21, 2020. The work must be completed within 365 calendar days of receiving notice to proceed. The contract is set aside for service-disabled veteran-owned small businesses, which must be registered and verified in the Vendor Information Pages and System for Award Management databases. Interested contractors should monitor the Federal Business Opportunities website for the full solicitation package.

36C25020B0033 Attach 3 Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Replace CAT Scan AHU 539-20-213, newest first.
File Type Posted
36C25020B0033 0007.docx DOCX document
36C25020B0033 0006.docx DOCX document
36C25020B0033 0005.docx DOCX document
36C25020B0033 0004.pdf PDF
36C25020B0033 0003.docx DOCX document
36C25020B0033-0002000.docx DOCX document
36C25020B0033-0001000.docx DOCX document
36C25020B0033-023.docx DOCX document
36C25020B0033-019.pdf PDF
36C25020B0033-018.docx DOCX document
36C25020B0033-024.docx DOCX document
36C25020B0033-020.pdf PDF
36C25020B0033-022.pdf PDF
36C25020B0033-025.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

EXTERIOR ELEVATION

INTERIOR ELEVATION

SEE 700 SERIES SHEETS

SECTION/DETAIL NUMBER

DRAWING NUMBER

EQUIPMENT TAG

COLUMN GRID

NOTE

WINDOW OPENING

DOOR OPENING

ROOM NAME

ROOM NUMBER

WALL TYPE

SEE SHEET A001

CEILING HEIGHT

FINISH DESIGNATION

X

10'-8"

X

X

XX.X-X

XX

X

1/A101

X

A101

XX

TOILET ACCESSORY TAGX SIGNAGE TAGX

XXXX

X

SIM

Ludlow Ave.

C lif to n A v e

CINCINNAT

I STATE

TECH.

Hopple St.

M.L.K. Dr.

McMillan St.

UNIV. OF

CINCINNAT

I

W.H.T Rd.

VAMC

3200 VINE ST.

M.L.K. Dr.

V in e

S t.

ZOO

Jefferson A ve.

UNIV.

HOSPITAL

Mitchell Ave.

R ea di ng

R d.

V ic to ry

P kw

y. XAVIER

UNIV.

P: 937-224-0861 www.heapy.com

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T R

ED RA

C H

TI

E C T

VA Project No.

JPA Project No.

Department of Veterans Affairs Medical Center

JOHN POE ARCHITECTS

HEAPY ENGINEERING

MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY

1400 WEST DOROTHY LANE

DAYTON, OH 45409

937.224.0861 P

937.224.5777 F

ARCHITECTURE PLANNING INTERIOR DESIGN

3131 NEWMARK DRIVE, SUITE 200

MIAMISBURG, OHIO 45342

800.362.1523 P

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT NO. STATE COA FIRM NO.2019-05085 01528

/2

/2

:1

:4

A

M

Replace CAT Scan AHU

01/21/20

COVER SHEET

G001

DWKR

19003.00

539-20-213

Cincinnati, OH

Replace CAT Scan AHU

3200 Vine St. Cincinnati, OH 45220 PROJECT #: 539-20-213

Station 539

KEVIN HENDERSON

CONSTRUCTION

DOCUMENTS

G001 COVER SHEET

G100 CODE DATA

A101-N FLOOR PLANS AND SCHEDULES

FX102 PARTIAL SECOND FLOOR PLAN -FIRE SUPPRESSION

M001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS

MD102 PARTIAL FLOOR PLANS - REMOVALS

M102 PARTIAL SECOND FLOOR PLANS

M104 PARTIAL FOURTH FLOOR PLANS

M301 AHU SECTIONS AND DETAILS

M501 DETAILS

M502 DETAILS

M503 DETAILS

M601 SCHEDULES & DIAGRAMS

M701 CONTROLS

M702 CONTROLS

E001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS

ED102 PARTIAL FLOOR PLANS - REMOVALS

E102 PARTIAL SECOND FLOOR PLANS

E104 PARTIAL FOURTH FLOOR PLANS

E501 DETAILS

E601 SCHEDULES & DIAGRAMS

GENERAL CONSTRUCTION NOTES

7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO

BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE

SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT

THROUGH FINISHED OPENINGS.

8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,

HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS

AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT

DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL

WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.

9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS

SPECIFICALLY NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A

PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS

INDICATED AT SIMILAR CONDITIONS.

10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL

SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE

THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE

NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR

SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.

11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED

WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF

THE WALL.

12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO

AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER

RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS

RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS

IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY

FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.

* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE

CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.

1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,

INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA

PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE

ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,

TECHNICAL INFORMATION LIBRRARY WEBSITE.

2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND

DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13

WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS

TECHNICAL INFORMATION LIBRARY WEBSITE.

3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT

EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED

WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.

4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH

ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT

ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.

5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF

NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO

REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT

SURFACES TO REMAIN.

6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND

DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW

MATERIALS.

DRAWING INDEX VICINITY MAP

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

GRAPHIC SYMBOLS

Revisions Date

1 SD SUBMITTAL 07/15/19

2 DD SUBMITTAL 10/01/19

3 95% CD SUBMITTAL 11/27/19

4 100% OWNER REVIEW SUBMITTAL 12/20/19

5 BID SET 01/21/20

0-HR Smoke Partition - OBC 710

1-HR Smoke Barrier - OBC 709

1-HR Fire Barrier - OBC 706

2-HR Fire Barrier - OBC 706

Means of Egress

Existing Wall to Remain

New Wall

CODE LEGEND

92' - 11" ACTUAL, MAX = 200' - 0"

135' - 7" ACTUAL, MAX = 200' - 0"

G100

CT Scanner

C214B

Prep Rm.

C214

Control

C215

P: 937-224-0861 www.heapy.com

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T R

ED RA

C H

TI

E C T

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT NO. STATE COA FIRM NO.2019-05085 01528

/2

/2

:1

:5

A

M

Replace CAT Scan AHU

01/21/20

CODE DATA

G100

DWKR

19003.00

539-20-213

Cincinnati, OH

Station 539

KEVIN HENDERSON

CONSTRUCTION

DOCUMENTS

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

N Scale: 1" = 20'-0"

SECOND FLOOR CODE PLAN

Scale: 1/8" = 1'-0"1

ENLARGED CODE PLAN

Chapter 18 – New Health Care Occupancies

• 18.1.6.1 – Construction Type: II (222), Sprinkled (noncombustible)

Allowable number of stories: ≥4 Actual number of stories: 10 + Basement (existing)

• 18.1.7 – Occupant load – Determined per 7.3.1.2 or determined as the max. probable population, whichever is greater.

• 18.2.1 - Means of egress components shall be per Chapter 7 and 18.2.2.2 thru 18.2.11.

• 18.2.2.2.4 – Doors within means of egress shall not be equipped with latches or locks that requires the use of a tool or key from egress side. Doors will be locked at all times to provide level of control required for some patients. Exception 1 locks complying with 18.2.2.2.5 are allowed.

• 18.2.2.2.5.1 - Door locking arrangements shall be permitted where clinical need requires security, provided that staff can unlock doors at all times in accordance with 18.2.2.2.6.

• 18.2.2.2.6 - Doors located in means of egress are permitted to be locked provided both the following: (both requirements are being met)

• 1. Keying all locks to keys carried by staff at all times

• 2. Only one locking device shall be permitted on each door.

• 18.2.2.5.1.1 – Minimum of 30 s.f. per patient in hospital shall be provided within the aggregated areas of corridors, patient rms, treatment rms., lounge or dining areas, and other similar areas on each side of the horizontal exit.

• 18.2.2.5.4 – A horiz. exit involving a corridor of 8’ or more in width and serving as a means of egress from both sides: pair of opposite swinging doors, with each door having 41-1/2” min clear width.

• 18.2.2.10 - Areas of Refuge as part of accessible means of egress: per 7.2.12.

• 18.2.3.1 – Capacity of Means of Egress per 7.3 and 18.2.3.

• 18.2.3.4 – Min. corridor width for exit access (hospital) – 8’ min., exceptions:

(1) Aisles, corridors, ramps in adjunct areas not intended for patients: 44” min. clear.

(2) Noncontin. projections 6" max. from corridor walls, 39" min. above the floor are permitted.

(3) Exit access within a room or suite per 18.2.5 are permitted.

(4) Projections into the req'd width permitted for wheeled equip., provided all of the following are met:

a. Wheeled equip. doesn't reduce clear width to less than 60"

b. Fire safety plan and training program address relocation of wheeled equip. during fire emergency

c. Wheeled equip. limited to the following:

i. Equip. and carts in use.

ii. Medical emerg. equip. not in use.

iii. Patient lift and transport equip.

(5) Where corridor width is at least 8', projections into req'd width permitted for fixed furniture, provided all of the following conditions are met:

a. Securely attached to floor or wall.

b. Doesn't reduce clear corridor width to less than 6', except as permitted by 18.2.3.4(2).

c. Located only on one side of corridor.

d. Grouped such each group doesn't exceed 50 sf.

e. Groups in 18.2.3.4(5)(d) are separated by at least 10'.

f. Located such to not obstruct access to building service and F.P. equip.

g. Corridors throughout smoke compartment are protected by auto-smoke detection per 18.3.4 or fixed furniture is arranged to allow direct staff supervision from nurses' station.

(6) Cross-corridor door openings in 8' corridors = 6'-11" clear width for pairs of doors or 41-1/2" for single doors.

• 18.2.3.6 – Min clear door width @ means of egress from sleeping rms., treatment rms. in Hospitals and Nursing Homes: 41-1/2”

• 18.2.3.7 – Req’ts of 18.2.3.6 shall not apply as follows:

1. Doors not subject to use by any health care occupant: 32” min clear.

2. Doors in exit enclosures: 32” min clear.

3. NA

4. Where pair of doors is provided, the following criteria shall be met:

a. 1 door min. = 32” min. clear opening.

b. Rabbet, bevel, or astragal at meeting edge.

c. Inactive leaf shall have automatic flush bolt for positive latching.

• 18.2.4.1 – Number of means of egress shall be per 7.4.

• 18.2.4.2 - Min. 2 exits provided on every story.

• 18.2.4.3 – Min 2 separate exits shall be accessible from every part of every story.

• 18.2.4.4 – Min 2 accessible exits from ea. smoke compartment, and egress shall be permitted thru an adjacent compartment, provided that the 2 req'd egress paths are arranged so that both do not pass through the same adj. smoke compartments.

• 18.2.5.1 – Arrangement of means of egress per 7.5 and 18.2.5.

• 18.2.5.2 – Dead-end corridors: 30’ max.

• 18.2.5.3 – Common path of travel: 100’ max.

• 18.2.5.7.1.2 – Suite Separation – Suites shall be separated from remainder of the building by walls and doors per 18.3.6.2 thru 18.3.6.5 (0-hr smoke partitions).

• 18.2.5.7.4 – Non-patient-care Suites: Egress in accord w/ primary use and occupancy of space, except max travel distance to an exit from within a suite = 200’.

• 18.2.6.2.1 – Max travel distance between any point in a room and an exit = 200’.

• 18.2.6.2.3 – Max travel distance between any point in healthcare sleeping room and exit access door in that room = 50’ max.

• 18.3.2.1 – Hazardous Area Protection per 8.7 and 18.3.2.1.

5 Soiled Linen rms w/ volume >64 gal. = 1-hr.

6 Trash collection rms w/ volume >64 gal. = 1 hr.

7 Storage Rms w/ comb. mat’ls >100 s.f. = 1-hr.

• 18.3.3.1 – Interior finish per 10.2 and 18.3.3.

• 18.3.3.2 – Interior wall and ceiling – Class A permitted except per 18.3.3.2.1 or 18.3.3.2.2.

• 18.3.3.2.1 – Walls and Ceilings @ indiv. rooms w/ 4 occup max = Class A or B.

• 18.3.3.2.2 – Corridor wall finish 48” max hgt. (lower half of wall) = Class A or B.

• 18.3.3.3.2 – Interior Floor fin @ exit enclosures and exit access corridors and spaces not separated from them by walls per 18.3.6 = Class I or II.

• 18.3.4.3.3.2 – Annunciation -alarm zone shall be permitted to coincide with the permitted area for smoke compartments.

• 18.3.4.1 – Health care occupancies shall be provided with a Fire Alarm system per 9.6.

• 18.3.4.2.2 – Manual fire alarm boxes in patient sleeping areas not req’d at exits if located at all nurses’ control stations.

• 18.3.4.3.2.1 - Fire department notification shall be per 9.6.4.

• 18.3.4.3.3.2 - The alarm zone shall be permitted to coincide with the permitted area for smoke compartments.

• 18.3.4.3.3.3 - The provision of 9.6.7.4.5, which permits sprinkler systems waterflow to be annunciated as a single building zone, shall be prohibited.

• 18.3.4.5.1 - Detection systems, where required, shall be per 9.6.

• 18.3.4.5.2 - Detection in spaces open to corridors - see 18.3.6.1.

• 18.3.5.1 – Buildings containing healthcare occupancies shall be protected throughout by a supervised automatic sprinkler system per 9.7, unless otherwise permitted by 18.3.5.5.

• 18.3.5.6 – Quick-response sprinklers shall be used throughout smoke compartments containing patient sleeping rooms.

• 18.3.5.12 – Portable fire extinguishers shall be provided in all health care occupancies per 9.7.4.1.

• 18.3.6.1 – Corridors shall be separated from all other areas by partitions per 18.3.6.2 thru 18.3.6.5, unless otherwise permitted by one of the following:

(1) Spaces shall be permitted to be unlimited in area and open to corridor provided all of the following criteria are met:

a. The spaces are not used for patient sleeping, treatment or hazardous storage areas.

b. Corridors onto which spaces open in same smoke compartment are protected by an auto. smoke detection system

c. Open space is protected by auto smoke detection system.

d. Space does not obstruct access to req’d exits.

• 18.3.6.2.2 – No fire resistance rating shall be required for corridor walls.

• 18.3.6.2.3 – Corridor walls shall form a barrier to limit the transfer of smoke.

• 18.3.6.3.1 – Doors protecting corridor opg’s shall resist passage of smoke and:

(1) Comply with NFPA 80

(2) 1” max. undercut

(4) Doors to toilet rms, shower rms, and sim auxiliary spaces that do not contain combustible materials: smoke resist not req’d.

• 18.3.6.3.5 – Corridor doors shall be self-latching and provided with positive-latching hardware.

• 18.3.6.3.5 – Doors to toilet rms, shower rms, and sim auxiliary spaces that do not contain combustible materials: latching req’ts of 18.3.6.3.5 not req’d.

• 18.3.6.3.7 - Powered corridor doors per 7.2.1.9 not req’d to meet latching req’ts of 18.3.6.3.5 if:

(1) Door is equipped w/ means of keeping door closed acceptable to AHJ.

(2) Device capable of keeping door closed w/ 5lb force to latch edge of swinging door and any direction to sliding/folding door, whether or not power is applied.

• 18.3.6.3.11 – Door closing devices not req’d on corridor doors other than those serving req’d exits, smoke barriers, or enclosures of vertical openings and hazardous areas.

• 18.3.7.1 – Heath care facilities shall be subdivided by Smoke Barriers as follows:

(1) Divide every story used by inpatients for sleeping or treatment into a minimum of 2 smoke compartments.

(2) Divide every story having occup. load >50, regardless of use into a minimum of 2 smoke compartments.

(3) Size of each smoke compartment = 22,500 s.f. max. (unless the area is an atrium separated per 8.6.7).

(4) Max. travel from any point in smoke compartment to a door in smoke barrier = 200’ max.

• 18.3.7.3 – Any Smoke Barrier shall be per 8.5 and min.1-hr fire-rating, unless:

(1) NA

(2) Smoke dampers shall not be req’d in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air- conditioning systems.

• 18.3.7.5.1 – Hospital or Nursing home = 30 net s.f. per patient shall be provided within the aggregated areas of corridors, patient rms, treatment rms., lounge or dining areas, and other low hazard areas on each side of the smoke barrier.

• 18.3.7.6 - Doors in Smoke Barriers- min 1/3 hr fire-rated and as follows:

(1) Non-rated protective plates allowed.

(2) Cross-corridor openings – pair of swinging doors per 7.2.1.14

(3) Cross-corridor pairs of doors must be opposite swinging.

(4) Min clear ea. swinging doors @ Hosp., nursing homes = 41-1/2” clear.

(5) Min clear ea. horiz. sliding doors @ Hosp., nursing homes = 6’-11” clear.

(6) Max clearance under door = ¾” max.

• 18.3.7.8 –Doors in Smoke Barriers shall comply with 8.5.4 and all of the following:

(1) Shall be self-closing or auto-closing per 18.2.2.2.7.

(2) Positive latching – Not Required.

(3) Stops required at head and sides of door frames.

(4) Rabbets, bevels, or astragals at meeting edges and stops – Required

(5) Center mullions – Prohibited.

• 18.3.7.9. – Vision panels w/ fire-rated glazing shall be provided in each cross-corridor swinging door in a smoke barrier.

Chapter 6 – Classification of Occupancy and Hazard of Contents

• 6.1.5 – Healthcare, New (Chap 18)

• 6.2.2 - Hazard classif.: Ordinary (high hazard areas protected per 18.3.2.1).

NFPA 101 2018 Code Review

• Existing building is presumed to be within compliance of NFPA 101 existing building requirements.

• Square Footages

Existing Area - Floor 2: 109,779 sf Renovation Area - CT Scanner: 782 sf

Chapter 7 – Means of Egress

• 7.3.1 – Occupant Load:

2nd Floor (Modification):

HC-Ambulatory 782 s.f. @ 150 sf/occ = 6 occup.

Total occupants = 6 occup

• 7.3.3.1 – Egress capacity (Health care, sprinklered):

• Stairs - .3” per occup; Level components and ramps - .2” per occup.

• 7.4.1.1 – Min. number of means of egress from any story = 2.

• 7.5.1.3.3 – Remoteness of exits – Bldgs. protected by AFSS per 9.7, Min. separation distance between 2 exits = 1/3 max. overall diag. dimension of the area or bldg. served.

• 7.5.4.1.3 - Accessible means of egress not req'd in health care occupancies protected throughout by an AFSS per 9.7.

Revisions Date

1 SD SUBMITTAL 07/15/19

2 DD SUBMITTAL 10/01/19

3 95% CD SUBMITTAL 11/27/19

S

S

S

S

Prep Rm.

C214

Tlt.

C214A

CT Scanner

C214B

Control

C215

2.51

2.51

2.51

2.51

CT Scanner

C214B

Control

C215

Tlt.

C214A

Prep Rm.

C214

9.13

8'-8"

9.13

ACT-1

ACT-1

ACT-1

7'-5"

7'-11"

REFLECTED CEILING PLAN LEGEND

Recessed downlight fixture

Supply Air Diffuser

Return Air Grille2' x 4' light fixture

2' x 2' acoustical tile ceiling

Gypsum board / portland cement plaster ceiling / soffit - painted

Chain-hung light fixture

Access panel

Surface-mounted strip light fixture

AREA OF

WORK

P: 937-224-0861 www.heapy.com

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T R

ED RA

C H

TI

E C T

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT NO. STATE COA FIRM NO.2019-05085 01528

/2

/2

:1

:4

A

M

Replace CAT Scan AHU

01/21/20

FLOOR PLANS AND SCHEDULES

A101-N

DWKR

19003.00

539-20-213

Cincinnati, OH

Station 539

KEVIN HENDERSON

CONSTRUCTION

DOCUMENTS

NOTES

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

GENERAL NOTES

A. All wood blocking to be fire retardent treated.

2.51 Remove all suspended ceiling tile & grid in this room.

9.13 Patch opening in wall above ceiling where existing duct is being removed.

N Scale: 1/4" = 1'-0"1

SECOND FLOOR NOTE PLAN

N Scale: 1/4" = 1'-0"2

SECOND FLOOR REFLECTED CEILING PLAN SECOND FLOOR KEY PLAN

FINISH LEGEND

CODE FINISH TYPE MANUFACTURER PRODUCT / COLOR COMMENTS

ACT-1 ACOUSTIC CEILING TILE ARMSTRONG OR EQUAL ULTIMA, 1910, 24"x24", SQUARE LAY-IN

BID ITEM 3: DELETE ALL WORK THIS PAGE BID ITEM 3: DELETE ALL WORK THIS PAGE

Revisions Date

1 SD SUBMITTAL 07/15/19

2 DD SUBMITTAL 10/01/19

3 95% CD SUBMITTAL 11/27/19

A1

P1 P1OR

OH

P2

B

P2

GENERAL FLOOR PLAN NOTES

DETAIL: B = DETAIL DESIGNATION

P2 = SHEET W HERE DETAIL IS LOCATED

FIRE SUPPRESSION HAZARD CLASSIFICATION AND

HAZARD CLASSIFICATION GROUP

SECTION: 1 = SECTION DESIGNATION

P2 = SHEET W HERE DETAIL IS LOCATED

EQUIPMENT REFERENCE. LETTER DESIGNATION

VARIES. REFER TO SCHEDULES.

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.

LETTER DESIGNATIONS REFER TO SCHEDULES.

CONNECT TO EXISTING

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT

IS SHOW N UNLESS NOTED OTHERW ISE.

DETAIL NOTE. APPLIES ONLY TO THE

ASSOCIATED DETAIL.

10" 10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOE: 3' - 0"

BOE: 0' - 6"

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR

TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED

OTHERW ISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR

TO CENTERLINE OF PIPE, UNLESS NOTED

OTHERW ISE

FIRE SUPPRESSION SYMBOLS

CONCEALED PENDENT SPRINKLER

FS

PIV

S

FIRE HYDRANT

FLOW SW ITCH

GATE VALVE OS&Y

INSTITUTIONAL PENDENT SPRINKLER

PENDENT SPRINKLER

POST INDICATOR VALVE

RECESSED PENDENT SPRINKLER

SIDE W ALL SPRINKLER

SUPERVISED VALVE

UPRIGHT SPRINKLER

PIPING SYMBOLS

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE:

BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOW N

ELBOW UP

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

D

R

FIRE SUPPRESSION PIPING

DESIGNATIONS

EXISTING PIPE TO REMAIN

EXISTING PIPE TO BE REMOVED

COMPRESSED AIR PIPE

COMBINATION FIRE SUPPRESSION AND

DOMESTIC W ATER SERVICE

SPRINKLER PIPE (DRY)

FIRE SUPPRESSION (STANDPIPE /

SPRINKLER MAIN)

FIRE SERVICE

PRE-ACTION / DELUGE SPRINKLER PIPE

SPRINKLER PIPE (W ET)

SPRINKLER DRAIN PIPE

W ATER SERVICE

CA

CW S

DS

F

FS

PS

S

SD

W S

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

BALL VALVE, BUTTERFLY VALVE OR GATE VALVE.

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

UNION

CLEANOUT

STRAINER

STRAINER W ITH A BLOW DOW N VALVE AND HOSE

CONNECTION

DRAIN VALVE W ITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN

AND OUT

EXPANSION JOINT

PRESSURE REGULATING VALVE

SAFETY RELIEF VALVE. PIPE DISCHARGE AIR

GAPPED TO FLOOR DRAIN UNLESS NOTED

OTHERW ISE.

PRESSURE AND TEMPERATURE TEST PLUG

VACUUM GAUGE W ITH STOP

END CAP

PLUG

PLUG VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

V

VB

COMBINATION SHUTOFF AND BALANCING VALVE

(REFER TO SPECIFICATIONS FOR REQUIRED

TYPE BASED ON APPLICATIONS)

VALVES AND FITTINGS

SOLENOID VALVE

S

P/T PRESSURE AND TEMPERATURE SAFETY RELIEF

VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR

DRAIN UNLESS NOTED OTHERW ISE.

FIRE DEPARTMENT VALVE

W ATER METERM

ABBREVIATIONS

AC - AIR COMPRESSOR

ACC - ACCESS

AD - ACCESS DOOR

ADB - ACID DILUTION BASIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BTW N - BETW EEN

CA - COMPRESSED AIR

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CLG - CEILING

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

CW S - COMBINATION W ATER SERVICE

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DN - DOW N

DS - SPRINKLER (DRY)

DW G - DRAW ING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQ - EQUAL

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EQS - EQUIPMENT SUPPLIER

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)

FCE - FIRE CONTROL EQUIPMENT

FCO - FLOOR CLEANOUT

FD - FLOOR DRAIN

FDC - FIRE DEPARTMENT CONNECTION

FDV - FIRE DEPARTMENT VALVE

FF - FINISHED FLOOR ELEVATION

FHC - FIRE HOSE CABINET

FLR - FLOOR

FPM - FEET PER MINUTE

FR - FIRE RISER

FS - FIRE SERVICE

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES

GPM - GALLONS PER MINUTE

HC - HVAC (D IVISION 23)

HD - HUB DRAIN

HP - HORSEPOW ER OR H IGH POINT

HR - HOSE REEL

HT - HEAT TRACE

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

JS - JANITOR SINK

L - LENGTH

LBS - POUNDS

MAX - MAXIMUM

MB - MOP BASIN

MC - MECHANICAL (D IVISION 23)

MEZZ - MEZZANINE

MFR - MANUFACTURER

MIN - MINIMUM

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

N/C - NORMALLY CLOSED

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NOM - NOMINAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTDOOR AIR

OD - OUTSIDE DIAMETER

OFCI - OW NER FURNISHED CONTRACTOR

INSTALLED

OFOI - OW NER FURNISHED OW NER INSTALLED

PC - PLUMBING (DIVISION 22)

OR PUMPED CONDENSATE RETURN

PIV - POST INDICATOR VALVE

PLBG - PLUMBING

PS - PRE-ACTION/DELUGE SPRINKLER

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSV - PRESSURE SUSTAINING VALVE

PSIG - POUNDS PER SQUARE INCH GAUGE

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RPM - REVOLUTIONS PER MINUTE

S - SPRINKLER (W ET)

SCH - SCHEDULE

SD - SPRINKLER DRAIN

SHT - SHEET

SK - SINK

SPEC - SPECIFICATIONS

SQ - SQUARE

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

VEL - VELO CITY

VIB - VALVE IN BOX

VOL - VOLUME

W / - W ITH

W /O - W ITHOUT

W IV - W ALL INDICATOR VALVE

W S - W ATER SERVICE

PIPE RISER

A PROVIDE A COMPLETE FIRE SUPPRESSION SPRINKLER SYSTEM

AS INDICATED ON THE DRAW INGS.

B COORDINATE W ORK W ITH VAMC, PHASING PLAN AND OTHER TRADES.

EACH CONTRACTOR SHALL BE RESPONSIBLE FOR OFFSETTING AND/ OR

RELOCATING SERVICES TO ACCOMMODATE NEW W ORK OF

OTHER TRADES.

C VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING

REQUIRED TO COMPLETE THIS W ORK.

D ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM

OF STRUCTURE IN EXPOSED STRUCTURAL AREAS) UNLESS OTHERW ISE

INDICATED.

E THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE

SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A W ET PIPE SYSTEM

HYDRAULICALLY CALCULATED FOR A:

1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER

SPRINKLER W ITH THE DENSITY OF 0.10 GPM/ SQ. FT. OVER THE

MOST REMOTE 1500 SQ. FT. PROVIDE AN ADDITION OF 100 GPM

HOSE ALLOW ANCE.

F AUTOMATIC SPRINKLER SYSTEM SHALL BE MAINTAINED IN FULLY

OPERATIONAL CONDITION. SPRINKLER SYSTEM MAY BE TAKEN OFF-LINE FOR

UP TO 8 HOURS, AS REQUIRED TO MAKE MODIFICATIONS/ CONNECTIONS TO

EXISTING SYSTEM. COORDINATE ALL DOW NTIME AND FIRE W ATCH W ITH COR

A MINIMUM OF TW O (2) W EEKS IN ADVANCE.

G THE ENTIRE SPRINKLER SYSTEM SHALL CONFORM TO VAMC STANDARDS, RULES

AND REGULATIONS. REFER TO VA FIRE PROTECTION DESIGN MANUAL.

H CAREFULLY COORDINATE THE LOCATION OF ALL SPRINKLERS AND

PIPING W ITH ALL OTHER TRADES AND THE ARCHITECT.

I VERIFY THE LOCATION OF ALL LIGHTING FIXTURES AND AIR DEVICES

BEFORE INSTALLATION OF SPRINKLERS.

J ALL SPRINKLER PIPING LAYOUT AND SIZING SHALL BE BY THE

CONTRACTOR.

K ALL SPRINKLER LOCATIONS MUST BE COORDINATED W ITH ALL EQUIPMENT

KINDRED TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE

APPROVED BY THE ARCHITECT BEFORE W ORK COMMENCES. REFER TO

THE ARCHITECTURAL AND REFLECTIVE CEILING PLANS FOR ADDITIONAL

INFORMATION ON ALL CEILING TYPES, HEIGHTS AND OTHER ARCHITECTURAL

FEATURES.

L MAKE NECESSARY FLOW TESTS, LAYOUT SYSTEMS, OBTAIN APPROVALS

FROM THE AUTHORITIES HAVING JURISDICTION PRIOR TO BEGINNING ANY

FABRICATION OR INSTALLATION W ORK.

M SPRINKLER PIPING SHALL BE 1" MINIMUM SIZE.

N SPRINKLERS (UNLESS OTHERW ISE NOTED):

EXPOSED AREAS - UPRIGHT OR PENDENT TYPE - STANDARD BRASS

CEILING AREA - RECESSED PENDENT TYPE

ALL SPRINKLERS SHALL BE UL LISTED AND FM APPROVED.

O SPRINKLERS SHALL BE "QUICK RESPONSE" TYPE IN ALL AREAS.

P ALL PENDENT TYPE SPRINKLERS LOCATED IN SUSPENDED CEILING TILE

AREAS SHALL BE LOCATED IN THE CENTER OF THE CEILING TILE.

Q ANNULAR SPACE AT PIPE AND OTHER SIMILAR PENETRATION OF FIRE

RATED ASSEMBLIES SHALL BE FIRESTOPPED. REFER TO ARCHITECTURAL

DRAW INGS FOR CONSTRUCTION, LAYOUT AND FIRE RATING OF FLOORS, W ALLS,

PARTITIONS AND OTHER BUILDING ELEMENTS.

R BLDG 01 FIRE PUMP TEST DATE: 02/01/19

SUCTION PRESSURE: 95 PSI

DISCHARGE PRESSURE: 140 PSI

SPECIFICATION SECTION 21 13 13 FOR FLOW TEST INFORMATION.

S ALL SPRINKLER ZONES SHALL MATCH SMOKE COMPARTMENTS.

T REFER TO ARCHITECTURAL DRAW INGS FOR INFORMATION ON SMOKE

COMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.

U PHASING: REFER TO ARCHITECTURAL DRAW INGS FOR AN OUTLINE OF

PROJECT PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS

MAY BE INCLUDED THROUGHOUT THIS DRAW ING SET.

FIRE SUPPRESSION DESIGN NOTES GENERAL NOTES

A ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION W ITH ALL

TRADES IS CRITICAL, PRIOR TO INSTALLATION OF ANY W ORK.

B LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED

FROM A REVIEW OF EXISTING DRAW INGS AND/ OR SITE INSPECTION,

W HERE POSSIBLE. FIELD VERIFICATION OF EXACT LOCATIONS,

ELEVATIONS, INVERTS, SIZES, DIRECTION OF FLOW , ETC., SHALL BE

REQUIRED PRIOR TO BEGINNING NEW W ORK.

C NEW CONNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAME

SIZE AS THE EXISTING PIPING, UNLESS OTHERW ISE NOTED.

D ALL REMOVED MATERIAL AND EQUIPMENT, SO DESIGNATED BY THE

COR, SHALL BE TURNED OVER AND PLACED W HERE DIRECTED.

ALL MATERIAL AND EQUIPMENT, W HICH THE COR DOES NOT W ISH

TO RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTOR.

REFER TO SPECIFICATION SECTION 01 74 19, CONSTRUCTION W ASTE

MANAGEMENT.

E REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING

REQUIREMENTS.

F CONTRACTOR SHALL UTILIZE X-RAY METHOD TO VERIFY EXISTENCE

OF OBSTRUCTIONS, INCLUDING EXISTING ELECTRICAL, PLUMBING,

HVAC, FIRE SUPPRESSION, AND/ OR STEEL REINFORCEMENT W HEN

CUTTING OR CORE-DRILLING FLOOR SLAB. EITHER RE-ROUTE

EXISTING SYSTEM(S), BRACE FLOOR, OR ALTER LOCATION OF NEW

W ORK TO MAINTAIN EXISTING SYSTEM(S).

Corridor C*2*20

Prep Rm.

C214

CT Scanner

C214B

Tlt.

C214A

Nurse Station A279

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project T itle

Location

Issue Date Checked Drawn

Draw ing Title

Approved:

VA FO RM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT NO. STATE COA FIRM NO.2019-05085 01528

/2

/2

:3

:0

A

M

REPLACE CAT SCAN AHU

1/21/2020

PARTIAL SECOND FLOOR PLAN -

FIRE SUPPRESSION

FX102

RLCDPB

19003.00

539-20-213

Cincinnati, Ohio

Station 539

KEVIN HENDERSON

CONSTRUCTION

DOCUMENTS

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

INDEX OF DRAWINGS - FIRE SUPPRESSION

SHEET NUMBER SHEET NAME

FX102 PARTIAL SECOND FLOOR PLAN - FIRE SUPPRESSION

NOTES

1 EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED)

TO REMAIN.

2 LIMITS OF RENOVATED AREA REQUIRING EXISTING SPRINKLER

SYSTEM MODIFICATIONS. MODIFICATIONS INCLUDE, BUT ARE NOT

LIMITED TO, REPLACING ALL SPRINKLERS AND PIPE BRANCHES TO

CONFORM TO NEW ARCHITECTURAL/ MECHANICAL LAYOUTS WHERE

NECESSARY. EXISTING PIPING SHALL BE RE-USED AS MUCH AS

POSSIBLE.

3 COORDINATE SPRINKLER AND SPRINKLER PIPING WORK WITH

EQUIPMENT STRUCTURAL MEMBERS. REFER TO ARCHITECTURAL

DRAWINGS FOR ADDITIONAL INFORMATION.

N Scale: 1/4" = 1'-0"

PARTIAL SECOND FLOOR PLAN - FIRE SUPPRESSION

Revisions Date

1 100% CONSTRUCTION DOCUMENTS 12/20/2019

2 BID SET 01/21/2020

NOTE: ALL SYMBOLS AND ABBREVIATIONS

ARE SUBJECT TO MODIFICATIONS

ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS

MIGHT NOT NECESSARILY BE USED ON

THIS PROJECT.

ABBREVIATIONS

AC - AIR COMPRESSOR OR AIR CONDITIONER

ACCU - AIR COOLED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AFMS - AIR FLOW MEASURING STATION

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATC - AUTOMATIC TEMPERATURE CONTROL

BDD - BACK DRAFT DAMPER

BFP - BACKFLOW PREVENTER

BLDG - BUILD ING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

CBD - COUNTER BALANCED BACKDRAFT DAMPER

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CFM - CUBIC FEET PER MINUTE

CHS - CHILLED W ATER SUPPLY

CHR - CHILLED W ATER RETURN

CHGR - CHILLED W ATER GLYCOL SOLUTION RETURN

CHGS - CHILLED W ATER GLYCOL SOLUTION SUPPLY

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CTR - CENTER

CU - COPPER

CW - COLD W ATER

CW R - CONDENSER W ATER RETURN

CW S - CONDENSER W ATER SUPPLY

D - DRAIN LINE

DB - DRY BULB

DDC - D IRECT D IGITAL CONTROLS

DI - DEIONIZED W ATER

DIA - D IAMETER

DIM - D IMENSION

DN - DOW N

DW G - DRAW ING

EA - EACH OR EXHAUST AIR

EAT - ENTERING AIR TEMPERATURE

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQUIP - EQUIPMENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

EQS - EQUIPMENT SUPPLIER

EW T - ENTERING W ATER TEMPERATURE

EXH - EXHAUST

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

FD - FLOOR DRAIN

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL GAUGE

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT ON TOP

FPM - FEET PER MINUTE

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

G - GAS OR NATURAL GAS

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES CONTRACTOR

GPM - GALLONS PER MINUTE

HB - HOSE BIBB

HC - HVAC (DIVISION 23)

HD - HUB DRAIN

HG - REFRIGERANT HOT GAS

HP - HORSEPOW ER

HPC - H IGH PRESSURE CONDENSATE RETURN

HPS - H IGH PRESSURE STEAM SUPPLY

HR - HOUR

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

HW - HOT W ATER

HW R - HEATING HOT W ATER RETURN

HW S - HEATING HOT W ATER SUPPLY

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LAT - LEAVING AIR TEMPERATURE

LAV - LAVATORY

LBS - POUNDS

LPC - LOW PRESSURE CONDENSATE RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LW T - LEAVING W ATER TEMPERATURE

MAX - MAXIMUM

MDD - MOTORIZED DAMPER

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE

MIN - MIN IMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

MPC - MEDIUM PRESSURE CONDENSATE

RETURN

MPS - MEDIUM PRESSURE STEAM SUPPLY

MU - W ATER MAKE-UP

N/C - NORMALLY CLOSED

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NOM - NOMINAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTDOOR AIR

OBD - OPPOSED BLADE DAMPER

OD - OUTSIDE DIAMETER

OFCI - OW NER FURNISHED CONTRACTOR

INSTALLED

OFOI - OW NER FURNISHED O W NER INSTALLED

P - PROPANE GAS

PC - PLUMBING (DIVISION 22)

OR PUMPED CONDENSATE RETURN

PLBG - PLUMBING

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSIG - POUNDS PER SQUARE INCH GAUGE

RA - RETURN AIR

RAD - RADIUS

RCP - REFLECTED CEILING PLAN

RD - ROOF DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS W ATER SUPPLY

ROR - REVERSE OSMOSIS W ATER RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTIO N

S - SPRINKLER (W ET)

SA - SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD W ATER

SHT - SHEET

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SRV - SAFETY RELIEF VALVE

SS - STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

V - VENT

VAC - VACUUM

VEL - VELO CITY

VIB - VALVE IN BOX

VOL - VOLUME

VTR - VENT THROUGH ROOF

VR - VENT RISER

W / - W ITH

W /O - W ITHOUT

W B - W ET BULB

W CO - W ALL CLEANOUT

GENERAL FLOOR PLAN NOTES

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS

NOTED OTHERW ISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

A1

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS

REFER TO SCHEDULES.

H1 H1OR

EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO

SCHEDULES.

H2

B

H2

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

H2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

H2 = SHEET W HERE DETAIL IS LOCATED

A1 "UP TO" SYM BOL (ITEM ON FLOOR ABOVE)

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF

EQUIPMENT, UNLESS NOTED OTHERW ISE

10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOD: 8' - 10"

BOD: 7' - 2"

20x20

20x20

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF

DUCTW ORK, UNLESS NOTED OTHERW ISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE,

UNLESS NOTED OTHERW ISE

DL-1

UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH

UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.

DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.

CONNECT TO EXISTING

HVAC PIPING DESIGNATIONS

CHILLED W ATER SUPPLY PIPECHS

CONDENSER W ATER SUPPLY PIPECW S

CONDENSER W ATER RETURN PIPECW R

DRAIN LINE. PITCH IN DIRECTION INDICATEDD

HEATING HOT W ATER SUPPLY PIPEHW S

HEATING HOT W ATER RETURN PIPEHW R

W ATER MAKE-UP PIPEMU

VENT PIPEV

REFRIGERANT LIQUID LINERL

REFRIGERANT SUCTION LINERS

EXPANSION TANK PIPEET

REFRIGERANT HOT GAS LINEHG

LOW PRESSURE CONDENSATE RETURN PIPELPC

LOW PRESSURE STEAM SUPPLY PIPELPS

M EDIUM PRESSURE CON DENSATE RETURN PIPEMPC

MEDIUM PRESSURE STEAM SUPPLY PIPEMPS

PUMPED CONDENSATE RETURN PIPEPC

HIGH PRESSURE CONDENSATE RETURN PIPEHPC

HIGH PRESSURE STEAM SUPPLY PIPEHPS

STEAM SUPPLY PIPE - NUMBER IND ICATES P.S.I.G.10

MISC SYMBOLS

DUCTWORK SYMBOLS

ROUND BRANCH DUCTW ORKCONICAL

FITTING

ACOUSTIC

FITTING

ACOUSTIC

FITTING

ADAD

D

R R

D

REC TANGULAR BR ANCH DUCTW ORK

SQUARE TEE W ITH TURNING VANES

NOTE: ALL SQUARE ELBOW S IN

RECTANGULAR AND ROUND / OVAL

DUCTW ORK SHALL BE PROVIDED W ITH

TURNING VANES. REFER TO

SPECIFICATIONS FOR ADDITIONAL DETAILS.

EXISTING DUCTW ORK TO REMOVED

RETURN AIR , RELIEF AIR, O R TRANSFER AIR

DUCTW ORK. (UP AND DOW N) RADIUSED

OR SQUARE W ITH TURNING VANES.

SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.

(UP AND DOW N) RADIUSED OR SQUARE

W ITH TURNING VANES.

EXHAUST AIR DUCTW ORK. (UP AND DOW N)

RADIUSED OR SQUARE W ITH TURNING

VANES.

RECTANGULAR AND ROUND / OVAL

DUCTW ORK RISE / DROP W ITH 90° RADIUSED

OR SQUARE ELBOW S AND TURNING VANES.

RADIUS ELBOW

90° SQUARE ELBOW (W ITH TURNING VANES)

NOTE: ALL SQUARE ELBOW S IN

RECTANGULAR AND ROUND DUCTW ORK

SHALL BE PROVIDED W ITH TURNING VANES.

ACCESS DOOR OR PANEL

DUCTW ORK RISE IN DIRECTION OF AIR

FLOW

DUCTW ORK DROP IN DIRECTION OF AIR

FLOW

DUCTW ORK W ITH ACOUSTICAL LINER.

LISTED DUCT SIZES ARE INSIDE CLEAR

DIMENSIONS.

RECTANGULAR ROUND / OVAL

FLEXIBLE DUCTW ORK

FLEXIBLE CONNECTION

DUCTW ORK CONSTRUCTED OF SPECIAL

MATERIAL AS NOTED

DIRECTION OF PITCH

RECTANGULAR DUCTW ORK DIMENSIONS

(W x H)26x20

ROUND DUCTW ORK DIMENSIONS (DIA)26ø

OVAL DUCTW ORK DIMENSIONS (W x H)26x20 OV

DUCTWORK DEVICE SYMBOLS

W ALL OR DUCTW ORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER

TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).

300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM

OF GRILLE.

A3 10ø

MANUAL BALANCING VALVE DAMPER W ITH LOCKING DEVICE

BDD = BACK DRAFT DAMPER

CBD = COUNTER-BALANCED BACK DRAFT DAMPER

SD = SMOKE DAMPER

FS = COMBINATION FIRE - SMOKE DAMPER

MDD = MOTORIZED DAMPER

AFMS = AIR FLOW MEASURING STATION

DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.

HUMIDITY SENSOR - DUCT MOUNTED

SG1

20x12

BOG : 9'-0"

XXX

A-D

XX

H

SD

SP

AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE

SCHEDULE FOR VARIOUS DESIGNATIONS).

10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE

DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S. AIR DEVICE

SHOW N IS 2-W AY SIDE THROW . METHOD OF IDENTIFICATION ALSO APPLIES

TO OTHER CEILING MOUNTED AIR DEVICES.

FIRE DAMPER

A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)

D OR S = DYNAMIC OR STATIC

STATIC PRESSURE SENSOR - DUCT MOUNTED

C

CARBON DIOXIDE SENSOR - DUCT MOUNTED

S

TEMPERATURE SENSOR - DUCT MOUNTED

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

COMBINATION SHUTOFF AND BALANCING VALVE

(REFER TO SPECIFICATIONS FOR REQUIRED

TYPE BASED ON APPLICATIONS)

BALL VALVE

BUTTERFLY VALVE

GATE VALVE

VALVES AND FITTINGS

DOUBLE LINE SINGLE LINE

10"

TOE: 3' - 0"

BOE: 0' - 6"

CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR

CHILLED W ATER GLYCOL SOLUTION SUPPLY PIPECHGS

CHILLED W ATER RETURN PIPECHR

SQUARE THROAT / RADIUS HEEL

FITTINGS NOT ACCEPTABLE

PIPING SYMBOLS

DOUBLE LINE SINGLE LINE

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE:

BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOW N

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

DD

RR

PIPE RISER

RADIUS'D BRANCH

RADIUS'D TEE

EXISTING DUCTW ORK TO REMAIN

UNLESS NOTED OTHERW ISE ON DRAW INGS,

15° MAX FOR DIVERGING, 30° MAX FOR

CONVERGING TRANSITION

EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERW ISE.

SPACE TEMPERATURE SENSOR / THERMOSTAT. W HEN W ALL MOUNTED, MOUNTING

HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH

COORDINATE W ITH ARCHITECT.

T

DP

DIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO

MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH

ARCHITECT.

H

HUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

C

CO

CARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET

ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH

ARCHITECT.

TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH

ARCHITECT.

S

S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.

STATIC PRESSURE SENSOR.SP

STRAINER W ITH A BLOW DOW N VALVE AND HOSE

CONNECTION

DRAIN VALVE W ITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN

AND OUT

EXPANSION JOINT

MANUAL AIR VENT

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE

2 PORT AUTOMATIC CONTROL VALVE

3 PORT AUTOMATIC CONTROL VALVE

QUICK OPENING MANUAL VALVE

VACUUM BREAKER

NEEDLE VALVE

PRESSURE AND TEMPERATURE TEST PLUG

VACUUM GAUGE W ITH STOP

END CAP

GLOBE VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

A

M

M

N

V

VB

SOLENOID VALVE

S

SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS

PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN

UNLESS NOTED OTHERW ISE. FOR STEAM

SYSTEMS PIPE D ISCHARGE TO OUTDOORS.

W ATER METERM

PRESSURE G AUGE W ITH COCK AND SIPHON LOOP

BI-M ETALIC STEAM TRAP AND DRIP ASSEM BLY

THERMODYNAMIC STEAM TRAP AND DRIP

ASSEMBLY

INVERTED BUCKET STEAM TRAP AND DRIP

ASSEMBLY

FLOAT AND THERMOSTATIC STEAM TRAP AND

DRIP ASSEMBLY

TH ERM OSTATIC STEAM TRAP AND DRIP ASSEM BLY

BM

TD

IB

FT

TS

FLOW METER

F

UNION

CLEANOUT

STRAINER

AUTOMATIC PRESSURE INDEPENDENT CONTROL

VALVE

M

HVAC GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF

DOCUMENTS.

B. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.

REFER TO ARCHITECTURAL DRAW INGS AND GENERAL

REQUIREMENTS.

C. INSULATE DUCTW ORK AND PIPING W HERE EXISTING INSULATION

HAS BEEN DAMAGED AND/OR REMOVED IN THE PERFORMANCE

OF W ORK IN THIS PROJECT.

D. PROVIDE ALL ROOFING PENETRATION, REPAIR &

REINFORCEMENT IN THE EXISTING BUILDING FOR W ORK

INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM

THE ROOFING W ORK. W HERE ROOFING W ORK IS REQUIRED, THE

EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT,

REMOVED AND RESTORED AS REQUIRED TO ATTAIN A

W ATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR

SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO

MAINTAIN THE EXISTING W ARRANTY ON THE ROOF.

E. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION

SECTIONS AND THESE DRAW INGS FOR DETAILS OF BUILDING

CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY

ARRANGEMENT FOR THEIR W ORK. THE VARIOUS DRAW INGS

COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE

USED JOINTLY AT ALL TIMES. THE CONTRACTOR SHALL REFER

TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE

NOTES AND SYMBOLS INDICATED ON THE DRAW INGS ARE FOR

THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND

MUST BE FOLLOW ED TO EXECUTE THE W ORK AS INTENDED. IF

DISCREPANCIES OCCUR, CONTACT THE COR THRU THE

CONTRACTING OFFICER FOR CLARIFICATION BEFORE

PROCEEDING.

F. IN ACCORDANCE W ITH GENERALLY ACCEPTED CONSTRUCTION

PRACTICES, THE CONTRACTOR W ILL BE SOLELY AND

COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON THE JOB

SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY

DURING PERFORMANCE OF THE W ORK. THIS W ILL APPLY

CONTINUOUSLY AND NOT BE LIMITED TO NORMAL W ORKING

HOURS. SEE SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON

RESPONSIBILITIES.

G. ALL W ORK MUST BE COORDINATED W ITH THE CONTRACTING

OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING

FACILITY.

H. THE CONTRACTOR SHALL COORDINATE HIS W ORK W ITH THE

W ORK OF OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE

PROGRESS AND DETAIL DEVELOPMENT OF THE W ORK OF

OTHERS AND SHALL BE RESPONSIBLE FOR COORDINATING AND

EXPEDITING HIS W ORK W ITH OTHERS SO THAT THE PROGRESS

OF THE TOTAL W ORK SHALL BE KEPT ON SCHEDULE.

I. ALL W ORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE

W ITH ALL GOVERNING CODES AND STANDARDS.

J. EXISTING CONDITIONS SHOW N HAVE BEEN BASED UPON

AVAILABLE DRAW ING INFORMATION, AND MAY BE AT VARIANCE

W ITH ACTUAL W ORK IN PLACE. THE CONTRACTOR SHALL TAKE

ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL

CONDITIONS AFFECTING THE EXECUTION OF THE W ORK. ANY

DISCREPANCIES BETW EEN EXISTING CONDITIONS AND THE

W ORK SHOW N ON THE CONTRACT DOCUMENTS W HICH MAY

IMPACT THE PROGRESS OF THE W ORK SHALL BE BROUGHT TO

THE ATTENTION OF THE CONTRACTING OFFICER IN W RITING FOR

RESOLUTION BEFORE PROCEEDING W ITH THE W ORK.

K. THE CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS

W ORK INTO OR ON THE W ORK OF OTHERS DOES SO W ITH THE

UNDERSTANDING THAT THE INSTALLATION OF HIS W ORK

CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY OF THE

W ORK IN PLACE. IF THE W ORK OF OTHERS IS NOT ACCEPTABLE,

HE SHALL NOTIFY THE COR AND SUCH W ORK SHALL BE

CORRECTED. ANY NEW W ORK INSTALLED IN UNSUITABLE

EXISTING W ORK SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR OR TRADE INSTALLING THE NEW W ORK. NO

CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING

W ORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS W ILL BE

CONSIDERED.

L. IF, IN THE PERFORMANCE OF THIS W ORK, MATERIALS ARE

OBSERVED W HICH ARE SUSPECTED TO CONTAIN ASBESTOS,

THE CONTRACTOR SHALL IMMEDIATELY INFORM THE COR.

W ORK THAT W OULD EXPOSE W ORKERS TO THE INHALATION OF

ASBESTOS PARTICLES SHALL BE TERMINATED. W ORK MAY BE

RESUMED ONLY AFTER A DETERMINATION HAS BEEN MADE AND

UNSAFE MATERIALS HAVE BEEN REMOVED OR ENCAPSULATED

AND THE AREA DECLARED SAFE.

M . CONTRACTOR SHALL TAKE SPECIAL CARE W HILE W ORKING

ADJACENT TO ASBESTOS MATERIALS AND MUST BE PROPERLY

PROTECTED W ITH CLOTHING, BREATHING APPARATUS, ETC.

VERIFY REQUIREMENTS OF VAMC'S INFECTION CONTROL R ISK

ASSESSMENT TEAM (ICRA).

N. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE

SHOW N OR INDICATED. DUCT SIZES ARE NET INSIDE

DIMENSIONS.

O. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR

ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE

DETECTORS, AUTOMATIC CONTROL DAMPERS, AND HUMIDIFIER

DISPERSION TUBES. COORDINATE SIZES AND LOCATIONS W ITH

ACCESSORIES PROVIDED BY OTHER TRADES.

P. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS

OTHERW ISE NOTED.

Q. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT

SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE

DISTURBED UNDER THIS W ORK TO MATCH EXISTING.

R. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW

EVERY VERTICAL OR HORIZONTAL OFFSET W HICH MAY BE

NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE W ORK

IN ADVANCE W ITH ALL OTHER TRADES AND REPORT

IMMEDIATELY ANY DIFFICULTIES W HICH CAN BE ANTIC IPATED.

S. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND

EQUIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO

PERFORMING W ORK.

T. ALL ABANDONED EXTRANEOUS PIPING, DUCTW ORK, SUPPORTS,

CONTROLS, ETC. SHALL BE REMOVED.

U. W HERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES

SHALL BE REMOVED BACK TO MAIN AND CAPPED; AND CONTROL

W IR ING AND CONDUIT SHALL BE REMOVED BACK TO SOURCE.

V. ALL EXISTING DUCTW ORK, PIPING, EQUIPMENT, CONTROLS, ETC.

SHOW N DASHED SHALL BE REMOVED. THE MAJORITY OF W ORK

TO BE REMOVED IS SHOW N. REMOVE ALL INCIDENTAL AND/OR

ABANDONED DUCTW ORK, PIPING, ETC. THAT MAY NOT BE

SHOW N BUT IS ASSOCIATED W ITH THE REMOVAL W ORK.

W . ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING,

CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL

BE EASILY AND SAFELY ACCESSIBLE BY PERSONS STANDING AT

FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS,

W ITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF

THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF

VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL

DEVICES, ETC.

X. REFER TO SPECIFICATIONS SECTION 01 00 00 GENERAL

REQUIREMENTS AND THESE DRAW INGS FOR DESCRIPTIONS OF

THE BID ITEMS INCLUDING DEDUCT ALTERNATES, ADDITIONAL

INFORMATION NOTED THROUGHOUT THE DRAW INGS.

Y. SYSTEMS SERVING AREAS OUTSIDE THE CONSTRUCTION ZONE

SHALL REMAIN OPERATIONAL DURING CONSTRUCTION. ANY

OUTAGES SHALL BE PERFORMED ON W EEKENDS OR W EEK

NIGHTS. DOW NTIME SHALL BE KEPT TO A MINIMUM, AND SHALL

BE COORDINATED AND SCHEDULED 4 W EEKS (30 CALENDAR

DAYS) IN ADVANCE W ITH THE COR.

Z. REFER TO NEW W ORK FLOOR PLANS FOR W ORK THAT MAY BE

REQUIRED PRIOR TO ANY REMOVAL W ORK.

AA. READ ALL NOTES THOROUGHLY PRIOR TO STARTING

CONSTRUCTION.

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project T itle

Location

Issue Date Checked Drawn

Draw ing Title

Approved:

VA FO RM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT NO. STATE COA FIRM NO.2019-05085 01528

/2

/2

:3

:0

A

M

REPLACE CAT SCAN AHU

1/21/2020

LEGEND, ABBREVIATIONS & INDEX

OF DRAWINGS

M001

DTRMSG

19003.00

539-20-213

Cincinnati, Ohio

Station 539

KEVIN HENDERSON

CONSTRUCTION

DOCUMENTS

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

INDEX OF DRAWINGS - MECHANICAL

SHEET NUMBER SHEET NAME

M001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS

MD102 PARTIAL FLOOR PLANS - REMOVALS

M102 PARTIAL SECOND FLOOR PLANS

M104 PARTIAL FOURTH FLOOR PLANS

M301 AHU SECTIONS AND DETAILS

M501 DETAILS

M502 DETAILS

M503 DETAILS

M601 SCHEDULES

M701 CONTROLS

M702 CONTROLS

Revisions Date

T

T

T

T

H

DN

UP

14x14

10ø 10ø x1

6ø

6ø x1

24x10

24x1018x10 x1

18x10

16x10 x1

14x10 ø x1

24x18 x1

6x6

6x6

16x10 x1 x1 x1 ø

3 3

16x10 x1

16x10

24/22 OV

26x20 x1

24x12

16x10 x1

32x18

32x18

M 104

1.

5"

M

P S

3"

H W

S

3"

H W

R

6" - CHR

6" - CHS

EXISTING AHU

EXISTING AHU

EXISTING

CHILLER

EXISTING

CHILLER

ROOF

EXISTING MODULAR

CHILLER

EXISTING HOT W ATER

CONVERTERS

EXISTING CHW

PUMPS

EXISTING ELECTRICAL

PANELS

EXISTING MOTOR

CONTROL CENTER

EXISTING ELECTRICAL

PANELSEXISTING

TRANSFORMER

EXISTING

VFDS

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project T itle

Loc…

This is the start of the file's text. The full file is on GovTribe.