36C25020B0033-021.pdf
PDF Posted
- Attached to
- Z1DA--Replace CAT Scan AHU 539-20-213 Federal contract opportunity
- Solicitation number
- 36C25020B0033
About this file
This document provides details for a federal contract opportunity to replace a CAT scan air handling unit at the Veterans Affairs Medical Center in Cincinnati, Ohio. The project involves removing the existing AHU and installing a new unit along with associated ductwork, piping, controls and other mechanical work. The solicitation number is 36C25020B0033 and will be released on or around January 21, 2020. The work must be completed within 365 calendar days of receiving notice to proceed. The contract is set aside for service-disabled veteran-owned small businesses, which must be registered and verified in the Vendor Information Pages and System for Award Management databases. Interested contractors should monitor the Federal Business Opportunities website for the full solicitation package.
36C25020B0033 Attach 3 Drawings.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25020B0033 0007.docx | DOCX document | |
| 36C25020B0033 0006.docx | DOCX document | |
| 36C25020B0033 0005.docx | DOCX document | |
| 36C25020B0033 0004.pdf | ||
| 36C25020B0033 0003.docx | DOCX document | |
| 36C25020B0033-0002000.docx | DOCX document | |
| 36C25020B0033-0001000.docx | DOCX document | |
| 36C25020B0033-023.docx | DOCX document | |
| 36C25020B0033-019.pdf | ||
| 36C25020B0033-018.docx | DOCX document | |
| 36C25020B0033-024.docx | DOCX document | |
| 36C25020B0033-020.pdf | ||
| 36C25020B0033-022.pdf | ||
| 36C25020B0033-025.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
EXTERIOR ELEVATION
INTERIOR ELEVATION
SEE 700 SERIES SHEETS
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
SEE SHEET A001
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAGX
XXXX
X
SIM
Ludlow Ave.
C lif to n A v e
CINCINNAT
I STATE
TECH.
Hopple St.
M.L.K. Dr.
McMillan St.
UNIV. OF
CINCINNAT
I
W.H.T Rd.
VAMC
3200 VINE ST.
M.L.K. Dr.
V in e
S t.
ZOO
Jefferson A ve.
UNIV.
HOSPITAL
Mitchell Ave.
R ea di ng
R d.
V ic to ry
P kw
y. XAVIER
UNIV.
P: 937-224-0861 www.heapy.com
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G I S
E T R
ED RA
C H
TI
E C T
VA Project No.
JPA Project No.
Department of Veterans Affairs Medical Center
JOHN POE ARCHITECTS
HEAPY ENGINEERING
MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
ARCHITECTURE PLANNING INTERIOR DESIGN
3131 NEWMARK DRIVE, SUITE 200
MIAMISBURG, OHIO 45342
800.362.1523 P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO. STATE COA FIRM NO.2019-05085 01528
/2
/2
:1
:4
A
M
Replace CAT Scan AHU
01/21/20
COVER SHEET
G001
DWKR
19003.00
539-20-213
Cincinnati, OH
Replace CAT Scan AHU
3200 Vine St. Cincinnati, OH 45220 PROJECT #: 539-20-213
Station 539
KEVIN HENDERSON
CONSTRUCTION
DOCUMENTS
G001 COVER SHEET
G100 CODE DATA
A101-N FLOOR PLANS AND SCHEDULES
FX102 PARTIAL SECOND FLOOR PLAN -FIRE SUPPRESSION
M001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS
MD102 PARTIAL FLOOR PLANS - REMOVALS
M102 PARTIAL SECOND FLOOR PLANS
M104 PARTIAL FOURTH FLOOR PLANS
M301 AHU SECTIONS AND DETAILS
M501 DETAILS
M502 DETAILS
M503 DETAILS
M601 SCHEDULES & DIAGRAMS
M701 CONTROLS
M702 CONTROLS
E001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS
ED102 PARTIAL FLOOR PLANS - REMOVALS
E102 PARTIAL SECOND FLOOR PLANS
E104 PARTIAL FOURTH FLOOR PLANS
E501 DETAILS
E601 SCHEDULES & DIAGRAMS
GENERAL CONSTRUCTION NOTES
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO
BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE
SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT
THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,
HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS
AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT
DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL
WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS
SPECIFICALLY NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A
PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS
INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL
SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE
THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE
NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR
SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED
WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF
THE WALL.
12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO
AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER
RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS
RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS
IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY
FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,
INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA
PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE
ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,
TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND
DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13
WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS
TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT
EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED
WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH
ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT
ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF
NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO
REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW
MATERIALS.
DRAWING INDEX VICINITY MAP
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
GRAPHIC SYMBOLS
Revisions Date
1 SD SUBMITTAL 07/15/19
2 DD SUBMITTAL 10/01/19
3 95% CD SUBMITTAL 11/27/19
4 100% OWNER REVIEW SUBMITTAL 12/20/19
5 BID SET 01/21/20
0-HR Smoke Partition - OBC 710
1-HR Smoke Barrier - OBC 709
1-HR Fire Barrier - OBC 706
2-HR Fire Barrier - OBC 706
Means of Egress
Existing Wall to Remain
New Wall
CODE LEGEND
92' - 11" ACTUAL, MAX = 200' - 0"
135' - 7" ACTUAL, MAX = 200' - 0"
G100
CT Scanner
C214B
Prep Rm.
C214
Control
C215
P: 937-224-0861 www.heapy.com
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G I S
E T R
ED RA
C H
TI
E C T
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO. STATE COA FIRM NO.2019-05085 01528
/2
/2
:1
:5
A
M
Replace CAT Scan AHU
01/21/20
CODE DATA
G100
DWKR
19003.00
539-20-213
Cincinnati, OH
Station 539
KEVIN HENDERSON
CONSTRUCTION
DOCUMENTS
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
N Scale: 1" = 20'-0"
SECOND FLOOR CODE PLAN
Scale: 1/8" = 1'-0"1
ENLARGED CODE PLAN
Chapter 18 – New Health Care Occupancies
• 18.1.6.1 – Construction Type: II (222), Sprinkled (noncombustible)
Allowable number of stories: ≥4 Actual number of stories: 10 + Basement (existing)
• 18.1.7 – Occupant load – Determined per 7.3.1.2 or determined as the max. probable population, whichever is greater.
• 18.2.1 - Means of egress components shall be per Chapter 7 and 18.2.2.2 thru 18.2.11.
• 18.2.2.2.4 – Doors within means of egress shall not be equipped with latches or locks that requires the use of a tool or key from egress side. Doors will be locked at all times to provide level of control required for some patients. Exception 1 locks complying with 18.2.2.2.5 are allowed.
• 18.2.2.2.5.1 - Door locking arrangements shall be permitted where clinical need requires security, provided that staff can unlock doors at all times in accordance with 18.2.2.2.6.
• 18.2.2.2.6 - Doors located in means of egress are permitted to be locked provided both the following: (both requirements are being met)
• 1. Keying all locks to keys carried by staff at all times
• 2. Only one locking device shall be permitted on each door.
• 18.2.2.5.1.1 – Minimum of 30 s.f. per patient in hospital shall be provided within the aggregated areas of corridors, patient rms, treatment rms., lounge or dining areas, and other similar areas on each side of the horizontal exit.
• 18.2.2.5.4 – A horiz. exit involving a corridor of 8’ or more in width and serving as a means of egress from both sides: pair of opposite swinging doors, with each door having 41-1/2” min clear width.
• 18.2.2.10 - Areas of Refuge as part of accessible means of egress: per 7.2.12.
• 18.2.3.1 – Capacity of Means of Egress per 7.3 and 18.2.3.
• 18.2.3.4 – Min. corridor width for exit access (hospital) – 8’ min., exceptions:
(1) Aisles, corridors, ramps in adjunct areas not intended for patients: 44” min. clear.
(2) Noncontin. projections 6" max. from corridor walls, 39" min. above the floor are permitted.
(3) Exit access within a room or suite per 18.2.5 are permitted.
(4) Projections into the req'd width permitted for wheeled equip., provided all of the following are met:
a. Wheeled equip. doesn't reduce clear width to less than 60"
b. Fire safety plan and training program address relocation of wheeled equip. during fire emergency
c. Wheeled equip. limited to the following:
i. Equip. and carts in use.
ii. Medical emerg. equip. not in use.
iii. Patient lift and transport equip.
(5) Where corridor width is at least 8', projections into req'd width permitted for fixed furniture, provided all of the following conditions are met:
a. Securely attached to floor or wall.
b. Doesn't reduce clear corridor width to less than 6', except as permitted by 18.2.3.4(2).
c. Located only on one side of corridor.
d. Grouped such each group doesn't exceed 50 sf.
e. Groups in 18.2.3.4(5)(d) are separated by at least 10'.
f. Located such to not obstruct access to building service and F.P. equip.
g. Corridors throughout smoke compartment are protected by auto-smoke detection per 18.3.4 or fixed furniture is arranged to allow direct staff supervision from nurses' station.
(6) Cross-corridor door openings in 8' corridors = 6'-11" clear width for pairs of doors or 41-1/2" for single doors.
• 18.2.3.6 – Min clear door width @ means of egress from sleeping rms., treatment rms. in Hospitals and Nursing Homes: 41-1/2”
• 18.2.3.7 – Req’ts of 18.2.3.6 shall not apply as follows:
1. Doors not subject to use by any health care occupant: 32” min clear.
2. Doors in exit enclosures: 32” min clear.
3. NA
4. Where pair of doors is provided, the following criteria shall be met:
a. 1 door min. = 32” min. clear opening.
b. Rabbet, bevel, or astragal at meeting edge.
c. Inactive leaf shall have automatic flush bolt for positive latching.
• 18.2.4.1 – Number of means of egress shall be per 7.4.
• 18.2.4.2 - Min. 2 exits provided on every story.
• 18.2.4.3 – Min 2 separate exits shall be accessible from every part of every story.
• 18.2.4.4 – Min 2 accessible exits from ea. smoke compartment, and egress shall be permitted thru an adjacent compartment, provided that the 2 req'd egress paths are arranged so that both do not pass through the same adj. smoke compartments.
• 18.2.5.1 – Arrangement of means of egress per 7.5 and 18.2.5.
• 18.2.5.2 – Dead-end corridors: 30’ max.
• 18.2.5.3 – Common path of travel: 100’ max.
• 18.2.5.7.1.2 – Suite Separation – Suites shall be separated from remainder of the building by walls and doors per 18.3.6.2 thru 18.3.6.5 (0-hr smoke partitions).
• 18.2.5.7.4 – Non-patient-care Suites: Egress in accord w/ primary use and occupancy of space, except max travel distance to an exit from within a suite = 200’.
• 18.2.6.2.1 – Max travel distance between any point in a room and an exit = 200’.
• 18.2.6.2.3 – Max travel distance between any point in healthcare sleeping room and exit access door in that room = 50’ max.
• 18.3.2.1 – Hazardous Area Protection per 8.7 and 18.3.2.1.
5 Soiled Linen rms w/ volume >64 gal. = 1-hr.
6 Trash collection rms w/ volume >64 gal. = 1 hr.
7 Storage Rms w/ comb. mat’ls >100 s.f. = 1-hr.
• 18.3.3.1 – Interior finish per 10.2 and 18.3.3.
• 18.3.3.2 – Interior wall and ceiling – Class A permitted except per 18.3.3.2.1 or 18.3.3.2.2.
• 18.3.3.2.1 – Walls and Ceilings @ indiv. rooms w/ 4 occup max = Class A or B.
• 18.3.3.2.2 – Corridor wall finish 48” max hgt. (lower half of wall) = Class A or B.
• 18.3.3.3.2 – Interior Floor fin @ exit enclosures and exit access corridors and spaces not separated from them by walls per 18.3.6 = Class I or II.
• 18.3.4.3.3.2 – Annunciation -alarm zone shall be permitted to coincide with the permitted area for smoke compartments.
• 18.3.4.1 – Health care occupancies shall be provided with a Fire Alarm system per 9.6.
• 18.3.4.2.2 – Manual fire alarm boxes in patient sleeping areas not req’d at exits if located at all nurses’ control stations.
• 18.3.4.3.2.1 - Fire department notification shall be per 9.6.4.
• 18.3.4.3.3.2 - The alarm zone shall be permitted to coincide with the permitted area for smoke compartments.
• 18.3.4.3.3.3 - The provision of 9.6.7.4.5, which permits sprinkler systems waterflow to be annunciated as a single building zone, shall be prohibited.
• 18.3.4.5.1 - Detection systems, where required, shall be per 9.6.
• 18.3.4.5.2 - Detection in spaces open to corridors - see 18.3.6.1.
• 18.3.5.1 – Buildings containing healthcare occupancies shall be protected throughout by a supervised automatic sprinkler system per 9.7, unless otherwise permitted by 18.3.5.5.
• 18.3.5.6 – Quick-response sprinklers shall be used throughout smoke compartments containing patient sleeping rooms.
• 18.3.5.12 – Portable fire extinguishers shall be provided in all health care occupancies per 9.7.4.1.
• 18.3.6.1 – Corridors shall be separated from all other areas by partitions per 18.3.6.2 thru 18.3.6.5, unless otherwise permitted by one of the following:
(1) Spaces shall be permitted to be unlimited in area and open to corridor provided all of the following criteria are met:
a. The spaces are not used for patient sleeping, treatment or hazardous storage areas.
b. Corridors onto which spaces open in same smoke compartment are protected by an auto. smoke detection system
c. Open space is protected by auto smoke detection system.
d. Space does not obstruct access to req’d exits.
• 18.3.6.2.2 – No fire resistance rating shall be required for corridor walls.
• 18.3.6.2.3 – Corridor walls shall form a barrier to limit the transfer of smoke.
• 18.3.6.3.1 – Doors protecting corridor opg’s shall resist passage of smoke and:
(1) Comply with NFPA 80
(2) 1” max. undercut
(4) Doors to toilet rms, shower rms, and sim auxiliary spaces that do not contain combustible materials: smoke resist not req’d.
• 18.3.6.3.5 – Corridor doors shall be self-latching and provided with positive-latching hardware.
• 18.3.6.3.5 – Doors to toilet rms, shower rms, and sim auxiliary spaces that do not contain combustible materials: latching req’ts of 18.3.6.3.5 not req’d.
• 18.3.6.3.7 - Powered corridor doors per 7.2.1.9 not req’d to meet latching req’ts of 18.3.6.3.5 if:
(1) Door is equipped w/ means of keeping door closed acceptable to AHJ.
(2) Device capable of keeping door closed w/ 5lb force to latch edge of swinging door and any direction to sliding/folding door, whether or not power is applied.
• 18.3.6.3.11 – Door closing devices not req’d on corridor doors other than those serving req’d exits, smoke barriers, or enclosures of vertical openings and hazardous areas.
• 18.3.7.1 – Heath care facilities shall be subdivided by Smoke Barriers as follows:
(1) Divide every story used by inpatients for sleeping or treatment into a minimum of 2 smoke compartments.
(2) Divide every story having occup. load >50, regardless of use into a minimum of 2 smoke compartments.
(3) Size of each smoke compartment = 22,500 s.f. max. (unless the area is an atrium separated per 8.6.7).
(4) Max. travel from any point in smoke compartment to a door in smoke barrier = 200’ max.
• 18.3.7.3 – Any Smoke Barrier shall be per 8.5 and min.1-hr fire-rating, unless:
(1) NA
(2) Smoke dampers shall not be req’d in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air- conditioning systems.
• 18.3.7.5.1 – Hospital or Nursing home = 30 net s.f. per patient shall be provided within the aggregated areas of corridors, patient rms, treatment rms., lounge or dining areas, and other low hazard areas on each side of the smoke barrier.
• 18.3.7.6 - Doors in Smoke Barriers- min 1/3 hr fire-rated and as follows:
(1) Non-rated protective plates allowed.
(2) Cross-corridor openings – pair of swinging doors per 7.2.1.14
(3) Cross-corridor pairs of doors must be opposite swinging.
(4) Min clear ea. swinging doors @ Hosp., nursing homes = 41-1/2” clear.
(5) Min clear ea. horiz. sliding doors @ Hosp., nursing homes = 6’-11” clear.
(6) Max clearance under door = ¾” max.
• 18.3.7.8 –Doors in Smoke Barriers shall comply with 8.5.4 and all of the following:
(1) Shall be self-closing or auto-closing per 18.2.2.2.7.
(2) Positive latching – Not Required.
(3) Stops required at head and sides of door frames.
(4) Rabbets, bevels, or astragals at meeting edges and stops – Required
(5) Center mullions – Prohibited.
• 18.3.7.9. – Vision panels w/ fire-rated glazing shall be provided in each cross-corridor swinging door in a smoke barrier.
Chapter 6 – Classification of Occupancy and Hazard of Contents
• 6.1.5 – Healthcare, New (Chap 18)
• 6.2.2 - Hazard classif.: Ordinary (high hazard areas protected per 18.3.2.1).
NFPA 101 2018 Code Review
• Existing building is presumed to be within compliance of NFPA 101 existing building requirements.
• Square Footages
Existing Area - Floor 2: 109,779 sf Renovation Area - CT Scanner: 782 sf
Chapter 7 – Means of Egress
• 7.3.1 – Occupant Load:
2nd Floor (Modification):
HC-Ambulatory 782 s.f. @ 150 sf/occ = 6 occup.
Total occupants = 6 occup
• 7.3.3.1 – Egress capacity (Health care, sprinklered):
• Stairs - .3” per occup; Level components and ramps - .2” per occup.
• 7.4.1.1 – Min. number of means of egress from any story = 2.
• 7.5.1.3.3 – Remoteness of exits – Bldgs. protected by AFSS per 9.7, Min. separation distance between 2 exits = 1/3 max. overall diag. dimension of the area or bldg. served.
• 7.5.4.1.3 - Accessible means of egress not req'd in health care occupancies protected throughout by an AFSS per 9.7.
Revisions Date
1 SD SUBMITTAL 07/15/19
2 DD SUBMITTAL 10/01/19
3 95% CD SUBMITTAL 11/27/19
S
S
S
S
Prep Rm.
C214
Tlt.
C214A
CT Scanner
C214B
Control
C215
2.51
2.51
2.51
2.51
CT Scanner
C214B
Control
C215
Tlt.
C214A
Prep Rm.
C214
9.13
8'-8"
9.13
ACT-1
ACT-1
ACT-1
7'-5"
7'-11"
REFLECTED CEILING PLAN LEGEND
Recessed downlight fixture
Supply Air Diffuser
Return Air Grille2' x 4' light fixture
2' x 2' acoustical tile ceiling
Gypsum board / portland cement plaster ceiling / soffit - painted
Chain-hung light fixture
Access panel
Surface-mounted strip light fixture
AREA OF
WORK
P: 937-224-0861 www.heapy.com
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G I S
E T R
ED RA
C H
TI
E C T
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO. STATE COA FIRM NO.2019-05085 01528
/2
/2
:1
:4
A
M
Replace CAT Scan AHU
01/21/20
FLOOR PLANS AND SCHEDULES
A101-N
DWKR
19003.00
539-20-213
Cincinnati, OH
Station 539
KEVIN HENDERSON
CONSTRUCTION
DOCUMENTS
NOTES
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
GENERAL NOTES
A. All wood blocking to be fire retardent treated.
2.51 Remove all suspended ceiling tile & grid in this room.
9.13 Patch opening in wall above ceiling where existing duct is being removed.
N Scale: 1/4" = 1'-0"1
SECOND FLOOR NOTE PLAN
N Scale: 1/4" = 1'-0"2
SECOND FLOOR REFLECTED CEILING PLAN SECOND FLOOR KEY PLAN
FINISH LEGEND
CODE FINISH TYPE MANUFACTURER PRODUCT / COLOR COMMENTS
ACT-1 ACOUSTIC CEILING TILE ARMSTRONG OR EQUAL ULTIMA, 1910, 24"x24", SQUARE LAY-IN
BID ITEM 3: DELETE ALL WORK THIS PAGE BID ITEM 3: DELETE ALL WORK THIS PAGE
Revisions Date
1 SD SUBMITTAL 07/15/19
2 DD SUBMITTAL 10/01/19
3 95% CD SUBMITTAL 11/27/19
A1
P1 P1OR
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND
HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION
VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.
LETTER DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT
IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE
ASSOCIATED DETAIL.
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR
TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED
OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR
TO CENTERLINE OF PIPE, UNLESS NOTED
OTHERW ISE
FIRE SUPPRESSION SYMBOLS
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SW ITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE W ALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLS
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
FIRE SUPPRESSION PIPING
DESIGNATIONS
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
COMPRESSED AIR PIPE
COMBINATION FIRE SUPPRESSION AND
DOMESTIC W ATER SERVICE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE /
SPRINKLER MAIN)
FIRE SERVICE
PRE-ACTION / DELUGE SPRINKLER PIPE
SPRINKLER PIPE (W ET)
SPRINKLER DRAIN PIPE
W ATER SERVICE
CA
CW S
DS
F
FS
PS
S
SD
W S
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE, BUTTERFLY VALVE OR GATE VALVE.
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER W ITH A BLOW DOW N VALVE AND HOSE
CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN
AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERW ISE.
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE W ITH STOP
END CAP
PLUG
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
VB
COMBINATION SHUTOFF AND BALANCING VALVE
(REFER TO SPECIFICATIONS FOR REQUIRED
TYPE BASED ON APPLICATIONS)
VALVES AND FITTINGS
SOLENOID VALVE
S
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF
VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR
DRAIN UNLESS NOTED OTHERW ISE.
FIRE DEPARTMENT VALVE
W ATER METERM
ABBREVIATIONS
AC - AIR COMPRESSOR
ACC - ACCESS
AD - ACCESS DOOR
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTW N - BETW EEN
CA - COMPRESSED AIR
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CLG - CEILING
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
CW S - COMBINATION W ATER SERVICE
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DN - DOW N
DS - SPRINKLER (DRY)
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EQS - EQUIPMENT SUPPLIER
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FIRE SERVICE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES
GPM - GALLONS PER MINUTE
HC - HVAC (D IVISION 23)
HD - HUB DRAIN
HP - HORSEPOW ER OR H IGH POINT
HR - HOSE REEL
HT - HEAT TRACE
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
JS - JANITOR SINK
L - LENGTH
LBS - POUNDS
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL (D IVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MIN - MINIMUM
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
N/C - NORMALLY CLOSED
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NOM - NOMINAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER
OFCI - OW NER FURNISHED CONTRACTOR
INSTALLED
OFOI - OW NER FURNISHED OW NER INSTALLED
PC - PLUMBING (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RPM - REVOLUTIONS PER MINUTE
S - SPRINKLER (W ET)
SCH - SCHEDULE
SD - SPRINKLER DRAIN
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
VEL - VELO CITY
VIB - VALVE IN BOX
VOL - VOLUME
W / - W ITH
W /O - W ITHOUT
W IV - W ALL INDICATOR VALVE
W S - W ATER SERVICE
PIPE RISER
A PROVIDE A COMPLETE FIRE SUPPRESSION SPRINKLER SYSTEM
AS INDICATED ON THE DRAW INGS.
B COORDINATE W ORK W ITH VAMC, PHASING PLAN AND OTHER TRADES.
EACH CONTRACTOR SHALL BE RESPONSIBLE FOR OFFSETTING AND/ OR
RELOCATING SERVICES TO ACCOMMODATE NEW W ORK OF
OTHER TRADES.
C VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING
REQUIRED TO COMPLETE THIS W ORK.
D ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM
OF STRUCTURE IN EXPOSED STRUCTURAL AREAS) UNLESS OTHERW ISE
INDICATED.
E THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE
SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A W ET PIPE SYSTEM
HYDRAULICALLY CALCULATED FOR A:
1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER
SPRINKLER W ITH THE DENSITY OF 0.10 GPM/ SQ. FT. OVER THE
MOST REMOTE 1500 SQ. FT. PROVIDE AN ADDITION OF 100 GPM
HOSE ALLOW ANCE.
F AUTOMATIC SPRINKLER SYSTEM SHALL BE MAINTAINED IN FULLY
OPERATIONAL CONDITION. SPRINKLER SYSTEM MAY BE TAKEN OFF-LINE FOR
UP TO 8 HOURS, AS REQUIRED TO MAKE MODIFICATIONS/ CONNECTIONS TO
EXISTING SYSTEM. COORDINATE ALL DOW NTIME AND FIRE W ATCH W ITH COR
A MINIMUM OF TW O (2) W EEKS IN ADVANCE.
G THE ENTIRE SPRINKLER SYSTEM SHALL CONFORM TO VAMC STANDARDS, RULES
AND REGULATIONS. REFER TO VA FIRE PROTECTION DESIGN MANUAL.
H CAREFULLY COORDINATE THE LOCATION OF ALL SPRINKLERS AND
PIPING W ITH ALL OTHER TRADES AND THE ARCHITECT.
I VERIFY THE LOCATION OF ALL LIGHTING FIXTURES AND AIR DEVICES
BEFORE INSTALLATION OF SPRINKLERS.
J ALL SPRINKLER PIPING LAYOUT AND SIZING SHALL BE BY THE
CONTRACTOR.
K ALL SPRINKLER LOCATIONS MUST BE COORDINATED W ITH ALL EQUIPMENT
KINDRED TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE
APPROVED BY THE ARCHITECT BEFORE W ORK COMMENCES. REFER TO
THE ARCHITECTURAL AND REFLECTIVE CEILING PLANS FOR ADDITIONAL
INFORMATION ON ALL CEILING TYPES, HEIGHTS AND OTHER ARCHITECTURAL
FEATURES.
L MAKE NECESSARY FLOW TESTS, LAYOUT SYSTEMS, OBTAIN APPROVALS
FROM THE AUTHORITIES HAVING JURISDICTION PRIOR TO BEGINNING ANY
FABRICATION OR INSTALLATION W ORK.
M SPRINKLER PIPING SHALL BE 1" MINIMUM SIZE.
N SPRINKLERS (UNLESS OTHERW ISE NOTED):
EXPOSED AREAS - UPRIGHT OR PENDENT TYPE - STANDARD BRASS
CEILING AREA - RECESSED PENDENT TYPE
ALL SPRINKLERS SHALL BE UL LISTED AND FM APPROVED.
O SPRINKLERS SHALL BE "QUICK RESPONSE" TYPE IN ALL AREAS.
P ALL PENDENT TYPE SPRINKLERS LOCATED IN SUSPENDED CEILING TILE
AREAS SHALL BE LOCATED IN THE CENTER OF THE CEILING TILE.
Q ANNULAR SPACE AT PIPE AND OTHER SIMILAR PENETRATION OF FIRE
RATED ASSEMBLIES SHALL BE FIRESTOPPED. REFER TO ARCHITECTURAL
DRAW INGS FOR CONSTRUCTION, LAYOUT AND FIRE RATING OF FLOORS, W ALLS,
PARTITIONS AND OTHER BUILDING ELEMENTS.
R BLDG 01 FIRE PUMP TEST DATE: 02/01/19
SUCTION PRESSURE: 95 PSI
DISCHARGE PRESSURE: 140 PSI
SPECIFICATION SECTION 21 13 13 FOR FLOW TEST INFORMATION.
S ALL SPRINKLER ZONES SHALL MATCH SMOKE COMPARTMENTS.
T REFER TO ARCHITECTURAL DRAW INGS FOR INFORMATION ON SMOKE
COMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.
U PHASING: REFER TO ARCHITECTURAL DRAW INGS FOR AN OUTLINE OF
PROJECT PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS
MAY BE INCLUDED THROUGHOUT THIS DRAW ING SET.
FIRE SUPPRESSION DESIGN NOTES GENERAL NOTES
A ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION W ITH ALL
TRADES IS CRITICAL, PRIOR TO INSTALLATION OF ANY W ORK.
B LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED
FROM A REVIEW OF EXISTING DRAW INGS AND/ OR SITE INSPECTION,
W HERE POSSIBLE. FIELD VERIFICATION OF EXACT LOCATIONS,
ELEVATIONS, INVERTS, SIZES, DIRECTION OF FLOW , ETC., SHALL BE
REQUIRED PRIOR TO BEGINNING NEW W ORK.
C NEW CONNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAME
SIZE AS THE EXISTING PIPING, UNLESS OTHERW ISE NOTED.
D ALL REMOVED MATERIAL AND EQUIPMENT, SO DESIGNATED BY THE
COR, SHALL BE TURNED OVER AND PLACED W HERE DIRECTED.
ALL MATERIAL AND EQUIPMENT, W HICH THE COR DOES NOT W ISH
TO RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTOR.
REFER TO SPECIFICATION SECTION 01 74 19, CONSTRUCTION W ASTE
MANAGEMENT.
E REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING
REQUIREMENTS.
F CONTRACTOR SHALL UTILIZE X-RAY METHOD TO VERIFY EXISTENCE
OF OBSTRUCTIONS, INCLUDING EXISTING ELECTRICAL, PLUMBING,
HVAC, FIRE SUPPRESSION, AND/ OR STEEL REINFORCEMENT W HEN
CUTTING OR CORE-DRILLING FLOOR SLAB. EITHER RE-ROUTE
EXISTING SYSTEM(S), BRACE FLOOR, OR ALTER LOCATION OF NEW
W ORK TO MAINTAIN EXISTING SYSTEM(S).
Corridor C*2*20
Prep Rm.
C214
CT Scanner
C214B
Tlt.
C214A
Nurse Station A279
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project T itle
Location
Issue Date Checked Drawn
Draw ing Title
Approved:
VA FO RM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO. STATE COA FIRM NO.2019-05085 01528
/2
/2
:3
:0
A
M
REPLACE CAT SCAN AHU
1/21/2020
PARTIAL SECOND FLOOR PLAN -
FIRE SUPPRESSION
FX102
RLCDPB
19003.00
539-20-213
Cincinnati, Ohio
Station 539
KEVIN HENDERSON
CONSTRUCTION
DOCUMENTS
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
INDEX OF DRAWINGS - FIRE SUPPRESSION
SHEET NUMBER SHEET NAME
FX102 PARTIAL SECOND FLOOR PLAN - FIRE SUPPRESSION
NOTES
1 EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED)
TO REMAIN.
2 LIMITS OF RENOVATED AREA REQUIRING EXISTING SPRINKLER
SYSTEM MODIFICATIONS. MODIFICATIONS INCLUDE, BUT ARE NOT
LIMITED TO, REPLACING ALL SPRINKLERS AND PIPE BRANCHES TO
CONFORM TO NEW ARCHITECTURAL/ MECHANICAL LAYOUTS WHERE
NECESSARY. EXISTING PIPING SHALL BE RE-USED AS MUCH AS
POSSIBLE.
3 COORDINATE SPRINKLER AND SPRINKLER PIPING WORK WITH
EQUIPMENT STRUCTURAL MEMBERS. REFER TO ARCHITECTURAL
DRAWINGS FOR ADDITIONAL INFORMATION.
N Scale: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - FIRE SUPPRESSION
Revisions Date
1 100% CONSTRUCTION DOCUMENTS 12/20/2019
2 BID SET 01/21/2020
NOTE: ALL SYMBOLS AND ABBREVIATIONS
ARE SUBJECT TO MODIFICATIONS
ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS
MIGHT NOT NECESSARILY BE USED ON
THIS PROJECT.
ABBREVIATIONS
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AFMS - AIR FLOW MEASURING STATION
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATC - AUTOMATIC TEMPERATURE CONTROL
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILD ING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED W ATER SUPPLY
CHR - CHILLED W ATER RETURN
CHGR - CHILLED W ATER GLYCOL SOLUTION RETURN
CHGS - CHILLED W ATER GLYCOL SOLUTION SUPPLY
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CTR - CENTER
CU - COPPER
CW - COLD W ATER
CW R - CONDENSER W ATER RETURN
CW S - CONDENSER W ATER SUPPLY
D - DRAIN LINE
DB - DRY BULB
DDC - D IRECT D IGITAL CONTROLS
DI - DEIONIZED W ATER
DIA - D IAMETER
DIM - D IMENSION
DN - DOW N
DW G - DRAW ING
EA - EACH OR EXHAUST AIR
EAT - ENTERING AIR TEMPERATURE
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
EQS - EQUIPMENT SUPPLIER
EW T - ENTERING W ATER TEMPERATURE
EXH - EXHAUST
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
FD - FLOOR DRAIN
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GPM - GALLONS PER MINUTE
HB - HOSE BIBB
HC - HVAC (DIVISION 23)
HD - HUB DRAIN
HG - REFRIGERANT HOT GAS
HP - HORSEPOW ER
HPC - H IGH PRESSURE CONDENSATE RETURN
HPS - H IGH PRESSURE STEAM SUPPLY
HR - HOUR
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
HW - HOT W ATER
HW R - HEATING HOT W ATER RETURN
HW S - HEATING HOT W ATER SUPPLY
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LAT - LEAVING AIR TEMPERATURE
LAV - LAVATORY
LBS - POUNDS
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LW T - LEAVING W ATER TEMPERATURE
MAX - MAXIMUM
MDD - MOTORIZED DAMPER
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MIN IMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE
RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - W ATER MAKE-UP
N/C - NORMALLY CLOSED
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NOM - NOMINAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOOR AIR
OBD - OPPOSED BLADE DAMPER
OD - OUTSIDE DIAMETER
OFCI - OW NER FURNISHED CONTRACTOR
INSTALLED
OFOI - OW NER FURNISHED O W NER INSTALLED
P - PROPANE GAS
PC - PLUMBING (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PLBG - PLUMBING
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSIG - POUNDS PER SQUARE INCH GAUGE
RA - RETURN AIR
RAD - RADIUS
RCP - REFLECTED CEILING PLAN
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS W ATER SUPPLY
ROR - REVERSE OSMOSIS W ATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTIO N
S - SPRINKLER (W ET)
SA - SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD W ATER
SHT - SHEET
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SRV - SAFETY RELIEF VALVE
SS - STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
V - VENT
VAC - VACUUM
VEL - VELO CITY
VIB - VALVE IN BOX
VOL - VOLUME
VTR - VENT THROUGH ROOF
VR - VENT RISER
W / - W ITH
W /O - W ITHOUT
W B - W ET BULB
W CO - W ALL CLEANOUT
GENERAL FLOOR PLAN NOTES
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS
NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
A1
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS
REFER TO SCHEDULES.
H1 H1OR
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
H2
B
H2
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
H2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
H2 = SHEET W HERE DETAIL IS LOCATED
A1 "UP TO" SYM BOL (ITEM ON FLOOR ABOVE)
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF
EQUIPMENT, UNLESS NOTED OTHERW ISE
10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOD: 8' - 10"
BOD: 7' - 2"
20x20
20x20
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF
DUCTW ORK, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE,
UNLESS NOTED OTHERW ISE
DL-1
UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH
UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.
DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.
CONNECT TO EXISTING
HVAC PIPING DESIGNATIONS
CHILLED W ATER SUPPLY PIPECHS
CONDENSER W ATER SUPPLY PIPECW S
CONDENSER W ATER RETURN PIPECW R
DRAIN LINE. PITCH IN DIRECTION INDICATEDD
HEATING HOT W ATER SUPPLY PIPEHW S
HEATING HOT W ATER RETURN PIPEHW R
W ATER MAKE-UP PIPEMU
VENT PIPEV
REFRIGERANT LIQUID LINERL
REFRIGERANT SUCTION LINERS
EXPANSION TANK PIPEET
REFRIGERANT HOT GAS LINEHG
LOW PRESSURE CONDENSATE RETURN PIPELPC
LOW PRESSURE STEAM SUPPLY PIPELPS
M EDIUM PRESSURE CON DENSATE RETURN PIPEMPC
MEDIUM PRESSURE STEAM SUPPLY PIPEMPS
PUMPED CONDENSATE RETURN PIPEPC
HIGH PRESSURE CONDENSATE RETURN PIPEHPC
HIGH PRESSURE STEAM SUPPLY PIPEHPS
STEAM SUPPLY PIPE - NUMBER IND ICATES P.S.I.G.10
MISC SYMBOLS
DUCTWORK SYMBOLS
ROUND BRANCH DUCTW ORKCONICAL
FITTING
ACOUSTIC
FITTING
ACOUSTIC
FITTING
ADAD
D
R R
D
REC TANGULAR BR ANCH DUCTW ORK
SQUARE TEE W ITH TURNING VANES
NOTE: ALL SQUARE ELBOW S IN
RECTANGULAR AND ROUND / OVAL
DUCTW ORK SHALL BE PROVIDED W ITH
TURNING VANES. REFER TO
SPECIFICATIONS FOR ADDITIONAL DETAILS.
EXISTING DUCTW ORK TO REMOVED
RETURN AIR , RELIEF AIR, O R TRANSFER AIR
DUCTW ORK. (UP AND DOW N) RADIUSED
OR SQUARE W ITH TURNING VANES.
SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.
(UP AND DOW N) RADIUSED OR SQUARE
W ITH TURNING VANES.
EXHAUST AIR DUCTW ORK. (UP AND DOW N)
RADIUSED OR SQUARE W ITH TURNING
VANES.
RECTANGULAR AND ROUND / OVAL
DUCTW ORK RISE / DROP W ITH 90° RADIUSED
OR SQUARE ELBOW S AND TURNING VANES.
RADIUS ELBOW
90° SQUARE ELBOW (W ITH TURNING VANES)
NOTE: ALL SQUARE ELBOW S IN
RECTANGULAR AND ROUND DUCTW ORK
SHALL BE PROVIDED W ITH TURNING VANES.
ACCESS DOOR OR PANEL
DUCTW ORK RISE IN DIRECTION OF AIR
FLOW
DUCTW ORK DROP IN DIRECTION OF AIR
FLOW
DUCTW ORK W ITH ACOUSTICAL LINER.
LISTED DUCT SIZES ARE INSIDE CLEAR
DIMENSIONS.
RECTANGULAR ROUND / OVAL
FLEXIBLE DUCTW ORK
FLEXIBLE CONNECTION
DUCTW ORK CONSTRUCTED OF SPECIAL
MATERIAL AS NOTED
DIRECTION OF PITCH
RECTANGULAR DUCTW ORK DIMENSIONS
(W x H)26x20
ROUND DUCTW ORK DIMENSIONS (DIA)26ø
OVAL DUCTW ORK DIMENSIONS (W x H)26x20 OV
DUCTWORK DEVICE SYMBOLS
W ALL OR DUCTW ORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER
TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).
300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM
OF GRILLE.
A3 10ø
MANUAL BALANCING VALVE DAMPER W ITH LOCKING DEVICE
BDD = BACK DRAFT DAMPER
CBD = COUNTER-BALANCED BACK DRAFT DAMPER
SD = SMOKE DAMPER
FS = COMBINATION FIRE - SMOKE DAMPER
MDD = MOTORIZED DAMPER
AFMS = AIR FLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.
HUMIDITY SENSOR - DUCT MOUNTED
SG1
20x12
BOG : 9'-0"
XXX
A-D
XX
H
SD
SP
AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE
SCHEDULE FOR VARIOUS DESIGNATIONS).
10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE
DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S. AIR DEVICE
SHOW N IS 2-W AY SIDE THROW . METHOD OF IDENTIFICATION ALSO APPLIES
TO OTHER CEILING MOUNTED AIR DEVICES.
FIRE DAMPER
A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)
D OR S = DYNAMIC OR STATIC
STATIC PRESSURE SENSOR - DUCT MOUNTED
C
CARBON DIOXIDE SENSOR - DUCT MOUNTED
S
TEMPERATURE SENSOR - DUCT MOUNTED
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
COMBINATION SHUTOFF AND BALANCING VALVE
(REFER TO SPECIFICATIONS FOR REQUIRED
TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGS
DOUBLE LINE SINGLE LINE
10"
TOE: 3' - 0"
BOE: 0' - 6"
CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR
CHILLED W ATER GLYCOL SOLUTION SUPPLY PIPECHGS
CHILLED W ATER RETURN PIPECHR
SQUARE THROAT / RADIUS HEEL
FITTINGS NOT ACCEPTABLE
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PIPE RISER
RADIUS'D BRANCH
RADIUS'D TEE
EXISTING DUCTW ORK TO REMAIN
UNLESS NOTED OTHERW ISE ON DRAW INGS,
15° MAX FOR DIVERGING, 30° MAX FOR
CONVERGING TRANSITION
EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERW ISE.
SPACE TEMPERATURE SENSOR / THERMOSTAT. W HEN W ALL MOUNTED, MOUNTING
HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH
COORDINATE W ITH ARCHITECT.
T
DP
DIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO
MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH
ARCHITECT.
H
HUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
C
CO
CARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET
ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH
ARCHITECT.
TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH
ARCHITECT.
S
S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.
STATIC PRESSURE SENSOR.SP
STRAINER W ITH A BLOW DOW N VALVE AND HOSE
CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN
AND OUT
EXPANSION JOINT
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
2 PORT AUTOMATIC CONTROL VALVE
3 PORT AUTOMATIC CONTROL VALVE
QUICK OPENING MANUAL VALVE
VACUUM BREAKER
NEEDLE VALVE
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE W ITH STOP
END CAP
GLOBE VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
A
M
M
N
V
VB
SOLENOID VALVE
S
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS
PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN
UNLESS NOTED OTHERW ISE. FOR STEAM
SYSTEMS PIPE D ISCHARGE TO OUTDOORS.
W ATER METERM
PRESSURE G AUGE W ITH COCK AND SIPHON LOOP
BI-M ETALIC STEAM TRAP AND DRIP ASSEM BLY
THERMODYNAMIC STEAM TRAP AND DRIP
ASSEMBLY
INVERTED BUCKET STEAM TRAP AND DRIP
ASSEMBLY
FLOAT AND THERMOSTATIC STEAM TRAP AND
DRIP ASSEMBLY
TH ERM OSTATIC STEAM TRAP AND DRIP ASSEM BLY
BM
TD
IB
FT
TS
FLOW METER
F
UNION
CLEANOUT
STRAINER
AUTOMATIC PRESSURE INDEPENDENT CONTROL
VALVE
M
HVAC GENERAL NOTES
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF
DOCUMENTS.
B. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING.
REFER TO ARCHITECTURAL DRAW INGS AND GENERAL
REQUIREMENTS.
C. INSULATE DUCTW ORK AND PIPING W HERE EXISTING INSULATION
HAS BEEN DAMAGED AND/OR REMOVED IN THE PERFORMANCE
OF W ORK IN THIS PROJECT.
D. PROVIDE ALL ROOFING PENETRATION, REPAIR &
REINFORCEMENT IN THE EXISTING BUILDING FOR W ORK
INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM
THE ROOFING W ORK. W HERE ROOFING W ORK IS REQUIRED, THE
EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT,
REMOVED AND RESTORED AS REQUIRED TO ATTAIN A
W ATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR
SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO
MAINTAIN THE EXISTING W ARRANTY ON THE ROOF.
E. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION
SECTIONS AND THESE DRAW INGS FOR DETAILS OF BUILDING
CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY
ARRANGEMENT FOR THEIR W ORK. THE VARIOUS DRAW INGS
COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE
USED JOINTLY AT ALL TIMES. THE CONTRACTOR SHALL REFER
TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE
NOTES AND SYMBOLS INDICATED ON THE DRAW INGS ARE FOR
THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND
MUST BE FOLLOW ED TO EXECUTE THE W ORK AS INTENDED. IF
DISCREPANCIES OCCUR, CONTACT THE COR THRU THE
CONTRACTING OFFICER FOR CLARIFICATION BEFORE
PROCEEDING.
F. IN ACCORDANCE W ITH GENERALLY ACCEPTED CONSTRUCTION
PRACTICES, THE CONTRACTOR W ILL BE SOLELY AND
COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON THE JOB
SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY
DURING PERFORMANCE OF THE W ORK. THIS W ILL APPLY
CONTINUOUSLY AND NOT BE LIMITED TO NORMAL W ORKING
HOURS. SEE SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON
RESPONSIBILITIES.
G. ALL W ORK MUST BE COORDINATED W ITH THE CONTRACTING
OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING
FACILITY.
H. THE CONTRACTOR SHALL COORDINATE HIS W ORK W ITH THE
W ORK OF OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE
PROGRESS AND DETAIL DEVELOPMENT OF THE W ORK OF
OTHERS AND SHALL BE RESPONSIBLE FOR COORDINATING AND
EXPEDITING HIS W ORK W ITH OTHERS SO THAT THE PROGRESS
OF THE TOTAL W ORK SHALL BE KEPT ON SCHEDULE.
I. ALL W ORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE
W ITH ALL GOVERNING CODES AND STANDARDS.
J. EXISTING CONDITIONS SHOW N HAVE BEEN BASED UPON
AVAILABLE DRAW ING INFORMATION, AND MAY BE AT VARIANCE
W ITH ACTUAL W ORK IN PLACE. THE CONTRACTOR SHALL TAKE
ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL
CONDITIONS AFFECTING THE EXECUTION OF THE W ORK. ANY
DISCREPANCIES BETW EEN EXISTING CONDITIONS AND THE
W ORK SHOW N ON THE CONTRACT DOCUMENTS W HICH MAY
IMPACT THE PROGRESS OF THE W ORK SHALL BE BROUGHT TO
THE ATTENTION OF THE CONTRACTING OFFICER IN W RITING FOR
RESOLUTION BEFORE PROCEEDING W ITH THE W ORK.
K. THE CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS
W ORK INTO OR ON THE W ORK OF OTHERS DOES SO W ITH THE
UNDERSTANDING THAT THE INSTALLATION OF HIS W ORK
CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY OF THE
W ORK IN PLACE. IF THE W ORK OF OTHERS IS NOT ACCEPTABLE,
HE SHALL NOTIFY THE COR AND SUCH W ORK SHALL BE
CORRECTED. ANY NEW W ORK INSTALLED IN UNSUITABLE
EXISTING W ORK SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR OR TRADE INSTALLING THE NEW W ORK. NO
CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING
W ORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS W ILL BE
CONSIDERED.
L. IF, IN THE PERFORMANCE OF THIS W ORK, MATERIALS ARE
OBSERVED W HICH ARE SUSPECTED TO CONTAIN ASBESTOS,
THE CONTRACTOR SHALL IMMEDIATELY INFORM THE COR.
W ORK THAT W OULD EXPOSE W ORKERS TO THE INHALATION OF
ASBESTOS PARTICLES SHALL BE TERMINATED. W ORK MAY BE
RESUMED ONLY AFTER A DETERMINATION HAS BEEN MADE AND
UNSAFE MATERIALS HAVE BEEN REMOVED OR ENCAPSULATED
AND THE AREA DECLARED SAFE.
M . CONTRACTOR SHALL TAKE SPECIAL CARE W HILE W ORKING
ADJACENT TO ASBESTOS MATERIALS AND MUST BE PROPERLY
PROTECTED W ITH CLOTHING, BREATHING APPARATUS, ETC.
VERIFY REQUIREMENTS OF VAMC'S INFECTION CONTROL R ISK
ASSESSMENT TEAM (ICRA).
N. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE
SHOW N OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
O. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR
ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE
DETECTORS, AUTOMATIC CONTROL DAMPERS, AND HUMIDIFIER
DISPERSION TUBES. COORDINATE SIZES AND LOCATIONS W ITH
ACCESSORIES PROVIDED BY OTHER TRADES.
P. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS
OTHERW ISE NOTED.
Q. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT
SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE
DISTURBED UNDER THIS W ORK TO MATCH EXISTING.
R. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW
EVERY VERTICAL OR HORIZONTAL OFFSET W HICH MAY BE
NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE W ORK
IN ADVANCE W ITH ALL OTHER TRADES AND REPORT
IMMEDIATELY ANY DIFFICULTIES W HICH CAN BE ANTIC IPATED.
S. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND
EQUIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO
PERFORMING W ORK.
T. ALL ABANDONED EXTRANEOUS PIPING, DUCTW ORK, SUPPORTS,
CONTROLS, ETC. SHALL BE REMOVED.
U. W HERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES
SHALL BE REMOVED BACK TO MAIN AND CAPPED; AND CONTROL
W IR ING AND CONDUIT SHALL BE REMOVED BACK TO SOURCE.
V. ALL EXISTING DUCTW ORK, PIPING, EQUIPMENT, CONTROLS, ETC.
SHOW N DASHED SHALL BE REMOVED. THE MAJORITY OF W ORK
TO BE REMOVED IS SHOW N. REMOVE ALL INCIDENTAL AND/OR
ABANDONED DUCTW ORK, PIPING, ETC. THAT MAY NOT BE
SHOW N BUT IS ASSOCIATED W ITH THE REMOVAL W ORK.
W . ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING,
CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL
BE EASILY AND SAFELY ACCESSIBLE BY PERSONS STANDING AT
FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS,
W ITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF
THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL
DEVICES, ETC.
X. REFER TO SPECIFICATIONS SECTION 01 00 00 GENERAL
REQUIREMENTS AND THESE DRAW INGS FOR DESCRIPTIONS OF
THE BID ITEMS INCLUDING DEDUCT ALTERNATES, ADDITIONAL
INFORMATION NOTED THROUGHOUT THE DRAW INGS.
Y. SYSTEMS SERVING AREAS OUTSIDE THE CONSTRUCTION ZONE
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION. ANY
OUTAGES SHALL BE PERFORMED ON W EEKENDS OR W EEK
NIGHTS. DOW NTIME SHALL BE KEPT TO A MINIMUM, AND SHALL
BE COORDINATED AND SCHEDULED 4 W EEKS (30 CALENDAR
DAYS) IN ADVANCE W ITH THE COR.
Z. REFER TO NEW W ORK FLOOR PLANS FOR W ORK THAT MAY BE
REQUIRED PRIOR TO ANY REMOVAL W ORK.
AA. READ ALL NOTES THOROUGHLY PRIOR TO STARTING
CONSTRUCTION.
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project T itle
Location
Issue Date Checked Drawn
Draw ing Title
Approved:
VA FO RM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO. STATE COA FIRM NO.2019-05085 01528
/2
/2
:3
:0
A
M
REPLACE CAT SCAN AHU
1/21/2020
LEGEND, ABBREVIATIONS & INDEX
OF DRAWINGS
M001
DTRMSG
19003.00
539-20-213
Cincinnati, Ohio
Station 539
KEVIN HENDERSON
CONSTRUCTION
DOCUMENTS
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
INDEX OF DRAWINGS - MECHANICAL
SHEET NUMBER SHEET NAME
M001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS
MD102 PARTIAL FLOOR PLANS - REMOVALS
M102 PARTIAL SECOND FLOOR PLANS
M104 PARTIAL FOURTH FLOOR PLANS
M301 AHU SECTIONS AND DETAILS
M501 DETAILS
M502 DETAILS
M503 DETAILS
M601 SCHEDULES
M701 CONTROLS
M702 CONTROLS
Revisions Date
T
T
T
T
H
DN
UP
14x14
10ø 10ø x1
6ø
6ø x1
24x10
24x1018x10 x1
18x10
16x10 x1
14x10 ø x1
24x18 x1
6x6
6x6
16x10 x1 x1 x1 ø
3 3
16x10 x1
16x10
24/22 OV
26x20 x1
24x12
16x10 x1
32x18
32x18
M 104
1.
5"
M
P S
3"
H W
S
3"
H W
R
6" - CHR
6" - CHS
EXISTING AHU
EXISTING AHU
EXISTING
CHILLER
EXISTING
CHILLER
ROOF
EXISTING MODULAR
CHILLER
EXISTING HOT W ATER
CONVERTERS
EXISTING CHW
PUMPS
EXISTING ELECTRICAL
PANELS
EXISTING MOTOR
CONTROL CENTER
EXISTING ELECTRICAL
PANELSEXISTING
TRANSFORMER
EXISTING
VFDS
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project T itle
Loc…