36C25019B0033-0001001.pdf

PDF 8 MB Posted

Attached to
541-CSI-106, Parma Mobile MRI Site Prep Federal contract opportunity
Solicitation number
36C25019B0033
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0033 0001 Attachment 1 - 541-CSI-106, Drawings_V1.1.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 541-CSI-106, Parma Mobile MRI Site Prep, newest first.
File Type Posted
36C25019B0033-0001002.pdf PDF
36C25019B0033-0001000.docx DOCX document
36C25019B0033-003.pdf PDF
36C25019B0033-002.pdf PDF
36C25019B0033-001.docx DOCX document
36C25019B0033-004.pdf PDF
36C25019B0033-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GI-1

TITLE SHEET & DRAWING

INDEX

8787 BROOKPARK RD. PARMA, OH. 44129

DEPARTMENT OF VETERANS AFFAIRS PARMA CBOC

Cleveland Veterans

Affairs Medical Center

PARMA CBOC MRI SITE PREP

DRAWING INDEX

PROJECT NO. 541-CSI-106

GI-1 TITLE SHEET & DRAWING INDEX

CIVIL

C-01 NEW WORK - SITE PLAN - CIVIL

ARCHITECTURAL

A-SD-01 ENLARGED SITE DEMOLITION PLAN

A-SD-02 ENLARGED SITE IMPROVEMENT PLAN

A-SD-03 ENLARGED WALKWAY FLOOR & ROOF PLANS AND SCHEDULES

A-SD-04 ENLARGED WALKWAY REF. CEILING PLANS

A-2.0 CONNECTOR WALKWAY EXTERIOR ELEVATIONS

A-2.1 CONNECTOR WALKWAY WALL SECTIONS AND DETAILS

A-2.2 ENLARGED DETAILS

STRUCTURAL

S-0.0 GENERAL NOTES

S-1.0 FOUNDATION PLAN AND DETAILS

S-2.0 ROOF FRAMING PLAN AND DETAILS

BID ISSUE SUBMISSION

4.17.19

SITE KEY PLAN

NORTH

PROJECT

WORK AREA

I. PROJECT LOCATION: CLEVELAND VETERANS AFFAIRS

PARMA CLINIC-BASED OUTPATIENT CLINIC

8787 BROOKPARK RD.

PARMA, OHIO

II. DESCRIPTION & USER GROUP CLASSIFICATION OF BLDG

NATURE OF PROJECT: CONSTRUCTION OF PEDESTRIAN WALKWAY AND

SITEWORK/UTILITIES PROVISIONS TO ACCOMMODATE AN

ON-SITE MRI TRAILER LOCATED IN THE EXISTING PARKING

LOT

A. DESIGN CODES: 2018 NPFA LIFE SAFETY CODE 101

2017 OHIO BUILDING CODE

2017 OHIO MECHANICAL/PLUMBING CODES

NFPA 70 / 2017 NATIONAL ELECTRICAL CODE

2009 ICC ANSI A117.1 GUIDELINES

B. USE GROUP: B "BUSINESS" (OUTPATIENT CLINIC) - EXISTING, NO

CHANGE PROPOSED

C. CONSTRUCTION TYPE: TYPE IIB - NONCOMBUSTIBLE, UNPROTECTED -

EXISTING, NO CHANGE PROPOSED

D. PROJECT/SITE AREA: 3,300 SF

E. PROJECT AREA OCCUPANT LOAD: NOT APPLICABLE (WALKWAY)

F. FIRE PROTECTION: EXISTING BUILDING FULLY SPRINKLED. WALKWAY WILL NOT

BE SPRINKLED

CODE INFORMATION

Revisions: Date

65% CD'S SUBMISSION 2.13.19

DAKCJK4.17.19

MECHANICAL

H-01 HVAC GENERAL NOTES, SYMBOL LEGEND, SCHEDULES, & DETAILS

H-02 NEW WORK - FLOOR PLAN - HVAC

PLUMBING

P-01 PLUMBING GENERAL NOTES AND SYMBOL LEGEND

P-02 NEW WORK - FLOOR PLAN - PLUMBING

ELECTRICAL

E-01 ELECTRICAL SYMBOL LEGEND, DETAILS, & GENERAL NOTES

E-02 LIGHTING/POWER/SYSTEMS - PARTIAL FLOOR PLAN - ELECTRICAL

E-03 ENLARGED PARTIAL FLOOR PLAN - ELECTRICAL

1" = 80'-0"

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT:

Office of

Construction and Facilities

Management

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

ATE

I

T C

J.

O

O

FO

H

Stanley J. Kaczmar, License #4988

Expiration Date: 12/31/2019

PARMA CBOC MOBILE MRI SITE PREP

8787 BROOKPARK RD. PARMA, OHIO

541-CSI-106

CIVIL & MECH./ELEC. ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44685

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

FULLY SPRINKLERED

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD. RICHFIELD, OH 44286

P. 330.659.6688

S

I T

E

BROOKPARK RD.

100% CD'S SUBMISSION 3.26.19

PROJECT DURATION DURING THE CONSTRUCTION PERIOD SHALL BE AS FOLLOWS:

CONSTRUCTION: 60 DAYS

TOTAL PROJECT TIMEFRAME: 60 DAYS

CONSTRUCTION TIMEFRAME:

ALL CONSTRUCTION WORK IDENTIFIED IN THE CONTRACT DOCUMENTS MUST BE

COORDINATED WITH THE COR & BUILDING OWNER TO BE PERFORMED AROUND A

WORKING OUTPATIENT CENTER THAT IS TO REMAIN OCCUPIED AND IN USE

THROUGHOUT CONSTRUCTION. CONSTRUCTION OPERATIONS SHALL BE DELINEATED AS

FOLLOWS:

· CONSTRUCTION ACTIVITIES FOR THE PROJECT ARE PERMITTED TO BE PERFORMED

DURING NORMAL DAY SHIFT HOURS

· GC SHALL COORDINATE ANY UTILITY SHUTDOWNS REQUIRED WITH COR AND

BUILDING OWNER. SHUTDOWNS LIKELY REQUIRED DURING AFTER-HOURS WHEN

THE FACILITY IS CLOSED

· CONCRETE DEMOLITION AND OTHER SIMILAR HEAVY-IMPACT DEMOLITION MUST BE

COORDINATED AND SCHEDULED WITH THE VA AND BUILDING OWNER PRIOR TO

START

BID ISSUE SUBMISSION 4.17.19

BID ADDENDUM #1 6.7.19

AutoCAD SHX Text Ex. 8" San.

AutoCAD SHX Text Ex. 8" San.

AutoCAD SHX Text Ex. 10" San.

AutoCAD SHX Text 5/8" iron pin fd. S00°00'22"W, 0.56'

AutoCAD SHX Text 5/8" iron pin fd. S75°28'14"E, 1.08'

AutoCAD SHX Text S89°59'38"E rec.&used 4101.64'calc.

AutoCAD SHX Text S89°59'38"E 420.00'deed&used

AutoCAD SHX Text S00°00'22"W 225.00'deed&used

AutoCAD SHX Text S66°06'56"E 124.96'calc. 125.46'deed

AutoCAD SHX Text N00°00'22"E 649.09'calc. 648.54'deed

AutoCAD SHX Text S89°59'38"E 131.00'deed&used

AutoCAD SHX Text N00°00'22"E 220.00'deed&used

AutoCAD SHX Text S01°14'59"W 595.18'calc. 595.50'deed

AutoCAD SHX Text N01°14'59"E 870.83'calc. 870.86'deed

AutoCAD SHX Text O.L. 1

AutoCAD SHX Text O.L. 6

AutoCAD SHX Text

CHENY TRACT

AutoCAD SHX Text Nail Set

AutoCAD SHX Text Ex. 18" Oak

AutoCAD SHX Text Ex. 6" Plum

AutoCAD SHX Text Ex. 6" Plum

AutoCAD SHX Text Ex. 6" Cherry

AutoCAD SHX Text Ex. 6" Cherry

AutoCAD SHX Text Ex. 15" Cherry

AutoCAD SHX Text Ex. 10" Ash

AutoCAD SHX Text Ex. 24" Cottonwood

AutoCAD SHX Text Ex. 36" Cottonwood

AutoCAD SHX Text Nail Set

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text version:1.1

AutoCAD SHX Text vehicle:WB-50

AutoCAD SHX Text group:AASHTO 2004 (US)

AutoCAD SHX Text hatch:SOLID,1,8,0,1.00,0.00

AutoCAD SHX Text pathUnits:feet

AutoCAD SHX Text drawname:1,4

AutoCAD SHX Text time:2010-01-20-14-02-30

AutoCAD SHX Text display:1,1,1,1,1,0,0,0,1,0,0,0,0,0,0,1,1,1,1,1,0,1,1

AutoCAD SHX Text color:6,4,7,7,2,2,3,4,5,4,3,4,4,4,8,3,6,6,3,1,1,3,5,1

AutoCAD SHX Text style:0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0

AutoCAD SHX Text fill:0,0

AutoCAD SHX Text clearance:3.000,3.000,3.000,3.000

AutoCAD SHX Text spacing:2,1.000

AutoCAD SHX Text level:10,WB-50_Truck

AutoCAD SHX Text product:AutoTURN

AutoCAD SHX Text

WB-50

AutoCAD SHX Text

AASHTO 2004 (US)

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

WV

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

DS

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.

AutoCAD SHX Text F.E.

AutoCAD SHX Text F.E.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

WC LIFT

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLAN NOTES

CODED NOTES

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT:

65% CD'S SUBMISSION

Office of

Construction and Facilities

Management

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

PARMA CBOC MOBILE MRI SITE PREP

8787 BROOKPARK RD. PARMA, OHIO

541-CSI-106

CIVIL & MECH./ELEC. ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44685

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

FULLY SPRINKLERED

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD. RICHFIELD, OH 44286

P. 330.659.6688

4.17.19

2.13.19

100% CD'S SUBMISSION 3.26.19

BID ISSUE SUBMISSION 4.17.19

NEW WORK - SITE PLAN -

CIVIL

KMN PEK

C-01

NEW WORK - SITE PLAN

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

VA MEDICAL BUILDING

AutoCAD SHX Text

75,222 SF

AutoCAD SHX Text

2 STORIES

AutoCAD SHX Text

FF=795.00

AutoCAD SHX Text

PROP. ELECTRIC

AutoCAD SHX Text

PROP. HYD.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

DS

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

WC LIFT

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

1. ALL CONTRACTORS ARE TO NOTIFY THE UTILITIES PROTECTION SERVICE, TWO WORKING DAYS PRIOR TO THE START OF CONSTRUCTION. 2. CONTRACTORS SHALL SCHEDULE THEIR OPERATIONS AND CARRY OUT THE WORK IN A MATTER TO CAUSE THE LEAST DISTURBANCE AND/OR INTERFERENCE WITH NORMAL FLOW OF THE TRAFFIC. 4. ALL POINTS OF CONNECTION OF PROPOSED IMPROVEMENTS TO EXISTING CONDITIONS SHALL BE UNCOVERED AND ELEVATIONS VERIFIED BY FIELD CHECK BEFORE ANY CONSTRUCTION BEGINS. 5. CONTRACTOR IS TO REGRADE TO MATCH EXISTING ELEVATIONS. RESEED AND MULCH IN ALL DISTURBED AREAS.

AutoCAD SHX Text

1. INSTALL YARD BASIN 4' OFFSET FROM SIDEWALK AND WITH CASTING AT 0.75" BELOW TOP OF NEW SIDEWALK. REGRADE AREA ALONG NORTH SIDE OF NEW SIDEWALK TO CREATE A 0.5' DEEP SWALE THAT SLOPES TOWARD THE NEW YARD BASIN. THE GRADE AT THE NORTH EDGE OF THE SIDEWALK IS TO BE 1" BELOW TOP OF SIDEWALK. 2. EXTEND 8" STORM SEWER AND WYE INTO ADJACENT 8" STORM. VERIFY EXACT DEPTH OF EXISTING 8" LINE PRIOR TO THE START OF CONSTRUCTION. 3. EXTEND 4" RAIN LEADER AND TIE INTO PROPOSED DOWNSPOUTS. 4. INSTALL 5' WIDE BY 9' LONG CONCRETE PAD FOR AIR HANDLER UNITS PER DETAIL ON THIS SHEET. TOP OF PAD IS TO BE AT 795.00 (SAME ELEVATION AS FINISHED FLOOR.) 5. NEW MRI TRAILER. 6. NEW ADA PARKING STALLS. REFER TO ARCHITECTURAL SITE PLAN.

AutoCAD SHX Text

5" MIN

AutoCAD SHX Text

STORM SEWER

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text 2'-0" x 2'-0"

AutoCAD SHX Text

27 1/2" SQUARE

AutoCAD SHX Text

%%UYARD/INLET BASIN

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

CEMENT CONCRETE SURFACE

AutoCAD SHX Text

ODOT ITEM 304

AutoCAD SHX Text

3" AGGREGATE BASE COURSE

AutoCAD SHX Text

COMPACTED SUBGRADE

AutoCAD SHX Text

ODOT ITEM 203

AutoCAD SHX Text

ODOT ITEM 452

AutoCAD SHX Text

6" NON-REINFORCED PORTLAND

AutoCAD SHX Text

%%UCONCRETE PAD

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text %%uNOTES:

AutoCAD SHX Text

%%UNOTE:

AutoCAD SHX Text 1'-6"

AutoCAD SHX Text 6'-6"

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text

HANDICAPPED

AutoCAD SHX Text

VAN -

AutoCAD SHX Text

ACCESSIBLE

AutoCAD SHX Text

PARKING

AutoCAD SHX Text

BLUE

AutoCAD SHX Text

WHITE

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text %%uNOTES:

AutoCAD SHX Text %%uHANDICAPPED PARKING SIGN

AutoCAD SHX Text

$250 FINE

AutoCAD SHX Text

MAXIMUM

AutoCAD SHX Text PRECAST CONCRETE CONSTRUCTION MEETING ODOT 706.13- 4000 PSI CONCRETE WITH CURB (IF REQUIRED) AND PIPE CONNECTION HOLES CORED AT THE TIME OF PRECAST MANUFACTURE

AutoCAD SHX Text SHELF FORMED WITH ASTM C-32 BRICK MASONARY WITH 1/2" CEMENT MORTAR PLASTER SLOPED 1/2" /FT, OR CONCRETE PRECAST IN BASE

AutoCAD SHX Text

1" CHAMFER (TYPICAL)

AutoCAD SHX Text

INLET FRAME AND COVER CASTING EJIW NO. 5110 OR APPROVED EQUAL.

AutoCAD SHX Text

CRUSHED STONE AGGREGATE, ODOT NO. 67, THOROUGHLY COMPACTED

AutoCAD SHX Text

EJIW 511OM3

AutoCAD SHX Text

1. MAXIMUM JOINT SPACING IS TO BE TWO TIMES OF THE THICKNESS OF THE PAVEMENT. FOR 6" PAVEMENT, PROVIDE JOINTS AT A MAXIMUM SPACING OF 12'. 2. TRAFFIC SHALL NOT BE ALLOWED ON FINISHED PAVEMENT UNTIL CONCRETE HAS ATTAINED A MINIMUM COMPRESSIVE STRENGTH OF 4,000 PSI. 3. EXPANSION JOINTS SHALL BE SEALED WITH POLYURETHANE SEALANT SO THAT MOISTURE INFILTRATION INTO THE SUBGRADE SOILS IS REDUCED. 4. WHERE TOPSOIL IS INSTALLED ADJACENT TO EDGE TOP OF COMPACTED TOPSOIL IS TO BE LEFT AT 0.5" BELOW TOP.

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text

2" ROUND STEEL PIPE

AutoCAD SHX Text

SEE NOTE #4

AutoCAD SHX Text

CONCRETE BASE. SEE ARCHITECTURAL PLANS.

AutoCAD SHX Text

1. SIGNS ARE TO CONFORM WITH SPECIFICATIONS FROM THE UNIFORM MANUAL OF TRAFFIC CONTROL DEVICES. 2. SIGN POST SHALL BE U CHANNEL TYPE PER ODOT SECTION 730.015 DRAWING TC-41.20. 3. SIGNS SHALL COMPLY TO ALL ADA CODES. 4. PROVIDE SECOND SIGN FOR SPACE DESIGNATED "VAN ACCESSIBLE". MOUNT BELOW THE SYMBOL OF ACCESSIBILITY.

AutoCAD SHX Text LOCATE SIGN @ HEAD OF EACH HANDICAP STALL. SIGN ON EACH SIDE OF PIPE WHERE APPLICABLE.

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

NOBLE

AutoCAD SHX Text K. M.

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E-56746

AutoCAD SHX Text 4.17.19

AutoCAD SHX Text 10'

AutoCAD SHX Text

AutoCAD SHX Text 20'

SCALE

3'-10"

7'-7"

55'-0" +/- EX. SIDEWALK REMOVAL

73'-2" +/-

5'-4" +/-

A-SD-01

ENLARGED SITE

DEMOLITION PLAN

Revisions: Date

65% CD'S SUBMISSION 2.13.19

DAKCJK4.17.19

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT:

Office of

Construction and Facilities

Management

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

ATE

I

T C

J.

O

O

FO

H

Stanley J. Kaczmar, License #4988

Expiration Date: 12/31/2019

PARMA CBOC MOBILE MRI SITE PREP

8787 BROOKPARK RD. PARMA, OHIO

541-CSI-106

CIVIL & MECH./ELEC. ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44685

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

FULLY SPRINKLERED

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD. RICHFIELD, OH 44286

P. 330.659.6688

GENERAL NOTES:

EXISTING BENCH TO BE RELOCATED - SEE ENLARGED SITE IMPROVEMENT PLAN FOR

NEW LOCATION

14. ALL FLOOR, WALL, CEILING, AND MISC. FIRE RESISTIVE ASSEMBLIES AND CONSTRUCTION

SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND / OR AS REQUIRED BY

CODE. ALL EXISTING FIRE RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING

NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRE

STOPPING, FIRE RATED DOORS AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT

UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.

10. ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE

APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK

SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE

LOCATION OF BARRIERS WITH OWNER.

11. THE FACILITY'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN

THE PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.

12. FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.

13. WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN

EXISTING WALL. REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR

NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E.

DOUBLE STUDS, HEADERS) AND PATCH ADJACENT WALLS TO MATCH EXISTING.

15. DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR

DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35

26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF

DEBRIS FROM THE PROJECT AREA.

16. ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE

OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS

SHALL BE PERFORMED "OFF HOURS" UNLESS OTHERWISE APPROVED BY THE COR.

CITY OF PARMA REQUIREMENTS:

1. THIS PROJECT AND THE FACILITY IN GENERAL FALL UNDER THE JURISDICTION OF THE CITY

OF PARMA, AND AS SUCH, THE CITY OF PARMA'S PERMITTING AND INSPECTION PROCESS

MUST BE FOLLOWED. THE VA IS A TENANT IN THIS BUILDING AND THE FACILITY IS NOT

OWNED BY THE FEDERAL GOVERNMENT.

2. ALL CONTRACTORS - GENERAL AND SUBS - ARE REQUIRED TO BE REGISTERED WITH THE

CITY OF PARMA IN ORDER TO PERFORM CONSTRUCTION OPERATIONS AND PULL PERMITS.

3. IT WILL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO BOTH PULL AND COVER

THE COST OF THE GENERAL BUILDING PERMIT FOR THIS PROJECT, AND ALL FEES

ASSOCIATED WITH SAME SHALL BE INCLUDED IN THE BID PRICE. ALL SUB-CONTRACTORS

WILL ALSO BE RESPONSIBLE FOR BOTH PULLING AND COVERING THE COST OF THEIR

INDIVIDUAL TRADE PERMITS.

4. THE GC SHALL BE RESPONSIBLE FOR PREPARING AND SUBMITTING ALL FIRE ALARM AND

FIRE SUPPRESSION SYSTEM DRAWINGS - TO THE EXTENT THAT MODIFICATIONS TO SAME

ARE REQUIRED FOR THIS PROJECT - TO THE CITY OF PARMA FOR REVIEW AND APPROVAL.

5. THE GC SHALL BE RESPONSIBLE FOR SCHEDULING ALL INSPECTIONS REQUIRED FOR THE

PROJECT WITH THE CITY OF PARMA AND ENSURING THAT ALL INSPECTIONS ARE

COMPLETED AND PASSED. THIS INSPECTION PROCESS SHALL BE CONSIDERED IN ADDITION

TO THOSE REQUIRED INTERNALLY BY THE VA.

6. THE GC SHALL BE RESPONSIBLE FOR OBTAINING A CERTIFICATE OF OCCUPANCY THROUGH

THE CITY OF PARMA AND OBTAINING ALL FINAL SIGN-OFFS FROM BUILDING OFFICIALS

7. ARCHITECT WILL SUBMIT DRAWINGS FOR BUILDING PERMIT REVIEW/APPROVAL. GC SHALL

BE RESPONSIBLE FOR PERMIT PICK-UP/PAYMENT. IT IS THE INTENT THAT THE PERMIT WILL

BE READY FOR PICK-UP AHEAD OF CONSTRUCTION

DEMOLITION NOTES:

1/8" = 1'-0"

SITE DEMOLITION PLAN

ENLARGED

NORTH

EXISTING PARKING STALL TO BE ELIMINATED - SEE ENLARGED SITE PLAN FOR NEW

ACCESSIBLE PARKING STALL DESIGN IN THIS LOCATION. GC SHALL REMOVE EXISTING

STALL STRIPING ON PAVEMENT

2 2 2 2 222

EXISTING POST-MOUNTED ACCESSIBLE PARKING STALL SIGNAGE TO BE REMOVED

AND RELOCATED - SEE ENLARGED SITE IMPROVEMENT PLAN FOR NEW LOCATIONS.

EXISTING CONCRETE BASE SHALL BE DEMO'D - SIGN & POST SHALL BE SALVAGED.

REMOVE SECTION OF DETECTABLE WARNING STRIP WHERE POLE BASE PENETRATED

AND REPLACE WITH NEW STRIP

AS-2.0

A

6 5

NEW 3'-10" X 7'-4" HIGH DOORWAY OPENING TO BE CUT INTO EXTERIOR WALL.

BOTTOM OF OPENING SHALL ALIGN WITH INTERIOR FINISHED FLOOR ELEVATION.

REFER TO STRUCT. DWGS. FOR STEEL LINTEL REQUIREMENTS OVER OPENING

WORKPOINT FOR WEST JAMB SIDE OF NEW OPENING SHALL ALIGN WITH EXISTING

MASONRY CONTROL JOINT

EXISTING DOWNSPOUT TO REMAIN - PROTECT AS REQ'D. THROUGHOUT

CONSTRUCTION TO ENSURE THAT SAME DOES NOT GET BLOCKED UP WITH DEBRIS,

DUST, ETC.

EXISTING TREE TO REMAIN - PROTECT AS REQ'D. THROUGHOUT

CONSTRUCTION

FOUR (4) EXISTING ACCESSIBLE PARKING STALLS TO BE ELIMINATED AND RELOCATED

- SEE ENLARGED SITE PLAN FOR NEW ACCESSIBLE PARKING STALL DESIGN. GC

SHALL REMOVE EXISTING STALL STRIPING ON PAVEMENT

EXISTING INSET

RUBBER STRIPS TO

REMAIN U.N.O.

EXISTING CONCRETE SIDEWALK TO BE DEMOLISHED IN

HATCHED PORTION. DEMOLITION SHALL OCCUR BETWEEN

EXISTING CONTROL JOINTS AS SHOWN

WORKPOINT FOR

WALK REMOVAL @

EXISTING CONTROL

JOINT

WORKPOINT FOR

WALK REMOVAL @

EXISTING CONTROL

JOINT

HATCHED AREA IN EXISTING GRASS INDICATES APPROXIMATE

EXCAVATION SCOPE REQUIRED FOR INSTALLATION OF NEW

CONNECTOR SIDEWALK. SEE IMPROVEMENT PLAN, VERIFY

FINAL EXCAVATION EXTENTS IN FIELD

GENERAL SITE DEMOLITION NOTE: ARCHITECTURAL SITE DEMOLITION PLAN DOES NOT

DEPICT ADDITIONAL EXCAVATION OR DEMOLITION REQUIRED TO INSTALL UNDERGROUND

OR ABOVE-GROUND UTILITIES. REFER TO CIVIL AND MEP DRAWINGS FOR NEW UTILITY

INSTALLATION SCOPE

TEMPORARY CONSTRUCTION FENCE TO BE PROVIDED AND

MAINTAINED BY GC THROUGHOUT THE PROJECT - VERIFY FINAL

DIMENSIONS IN FIELD. FENCE SHALL BE 8'-0" HIGH CHAIN LINK

FENCE. MINIMUM FENCE SPECS: 11-1/2 GA., 2" MESH, 1-5/8" LINE

POSTS @ 8' O.C. MAX. 2" CORNER POSTS. GC SHALL RESTORE

EXISTING SITE CONDITIONS UPON REMOVAL OF THE FENCE

MAINTAIN EXISTING LOADING

ZONE STRIPING

THROUGHOUT

CONSTRUCTION, LOCATE

FENCE JUST EAST OF EX.

STRIPE LINE

EXISTING LIT BOLLARD TO REMAIN - PROTECT THROUGHOUT

CONSTRUCTION

EXISTING VINYL FENCE

ENCLOSURE AND

LANDSCAPING SHALL BE

PROTECTED THROUGHOUT

CONSTRUCTION

TEMPORARY PROTECTIVE BARRIER

SHALL BE IN PLACE DURING DEMOLITION

OF EXTERIOR WALL OPENING (ZIPWALL

OR SIMILAR). SHALL BE SEALED 100%

FROM THE INTERIOR. COORD. ALL

RELATED WORK WITH VA AND BUILDING

OWNER

REFER TO CIVIL DRAWINGS

FOR UTILITY

INSTALLATION/GRADING IN

THIS AREA

100% CD'S SUBMISSION 3.26.19

5. WHERE NEW UTILITIES ARE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS

SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME, AND PATCH

AND REPAIR WITH NEW TO MATCH EXISTING CONDITIONS.

1. CONSIDER ALL AREAS OWNER-OCCUPIED, UNLESS OTHERWISE NOTED.

2. ALL FLOOR PLAN DIMENSIONS ARE FROM FACE OF POURED CURB TO FACE OF POURED CURB

3. ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC FIRE ALARM, ELECTRICAL, ETC.) TO

DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE

WITH THE REQUIREMENTS OF ALL APPLICABLE CODES.

4. PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING

CONDITIONS.

6. ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE

REPAIRED BY CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING,

AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE

REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO OWNER.

7. ALL NEW PENETRATIONS IN FIRE RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF

ASSEMBLY AS REQUIRED.

8. CONTRACTOR SHALL PROVIDE DUST REMOVING WALK-OFF MATS (TACKY MAT) AT ALL

CONSTRUCTION ENTRY POINTS

9. CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN

NEGATIVE PRESSURE IN WORK AREA ENSURING NO DUST OR FUMES WILL BE TRANSFERRED

TO OCCUPIED AREAS. PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST PROOF

BARRICADE TO CONFIRM PRESSURE. DUST MONITORING SHALL BE BY OWNER. SEE

SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS" ATTACHMENT AND 01 35 26 "SAFETY

REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.

BID ISSUE SUBMISSION 4.17.19

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

8'-0" 8'-0" 8'-0" 8'-0"

3'-0"

EX. STALL

TO REMAIN

5'-0"

EXISTING

8'-0" 5'-0" 8'-0" 6'-0" EXISTING STALLS

TO REMAIN

9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0"

35'-0" 27'-0"

1'-7" +/-

A-SD-02

ENLARGED SITE

IMPROVEMENT PLAN

Revisions: Date

65% CD'S SUBMISSION 2.13.19

DAKCJK4.17.19

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT:

Office of

Construction and Facilities

Management

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

ATE

I

T C

J.

O

O

FO

H

Stanley J. Kaczmar, License #4988

Expiration Date: 12/31/2019

PARMA CBOC MOBILE MRI SITE PREP

8787 BROOKPARK RD. PARMA, OHIO

541-CSI-106

CIVIL & MECH./ELEC. ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44685

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

FULLY SPRINKLERED

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD. RICHFIELD, OH 44286

P. 330.659.6688

NEW VAN ACCESSIBLE ADA PARKING STALL TO BE PAINTED/LOCATED AT FORMER

NON-ACCESSIBLE PARKING STALL LOCATION. GC SHALL PAINT ALL STRIPING, ADA

SYMBOLS, AND THE WORD "VAN" IN STALL - MATCH EXISTING VAN STALLS ON SITE

GENERAL NOTES:

14. ALL FLOOR, WALL, CEILING, AND MISC. FIRE RESISTIVE ASSEMBLIES AND CONSTRUCTION

SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND / OR AS REQUIRED BY

CODE. ALL EXISTING FIRE RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING

NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRE

STOPPING, FIRE RATED DOORS AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT

UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.

10. ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE

APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK

SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE

LOCATION OF BARRIERS WITH OWNER.

11. THE FACILITY'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN

THE PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.

12. FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.

13. WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN

EXISTING WALL. REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR

NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E.

DOUBLE STUDS, HEADERS) AND PATCH ADJACENT WALLS TO MATCH EXISTING.

15. DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR

DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35

26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF

DEBRIS FROM THE PROJECT AREA.

16. ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE

OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS

SHALL BE PERFORMED "OFF HOURS" UNLESS OTHERWISE APPROVED BY THE COR.

CITY OF PARMA REQUIREMENTS:

1. THIS PROJECT AND THE FACILITY IN GENERAL FALL UNDER THE JURISDICTION OF THE CITY

OF PARMA, AND AS SUCH, THE CITY OF PARMA'S PERMITTING AND INSPECTION PROCESS

MUST BE FOLLOWED. THE VA IS A TENANT IN THIS BUILDING AND THE FACILITY IS NOT

OWNED BY THE FEDERAL GOVERNMENT.

2. ALL CONTRACTORS - GENERAL AND SUBS - ARE REQUIRED TO BE REGISTERED WITH THE

CITY OF PARMA IN ORDER TO PERFORM CONSTRUCTION OPERATIONS AND PULL PERMITS.

3. IT WILL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO BOTH PULL AND COVER

THE COST OF THE GENERAL BUILDING PERMIT FOR THIS PROJECT, AND ALL FEES

ASSOCIATED WITH SAME SHALL BE INCLUDED IN THE BID PRICE. ALL SUB-CONTRACTORS

WILL ALSO BE RESPONSIBLE FOR BOTH PULLING AND COVERING THE COST OF THEIR

INDIVIDUAL TRADE PERMITS.

4. THE GC SHALL BE RESPONSIBLE FOR PREPARING AND SUBMITTING ALL FIRE ALARM AND

FIRE SUPPRESSION SYSTEM DRAWINGS - TO THE EXTENT THAT MODIFICATIONS TO SAME

ARE REQUIRED FOR THIS PROJECT - TO THE CITY OF PARMA FOR REVIEW AND APPROVAL.

5. THE GC SHALL BE RESPONSIBLE FOR SCHEDULING ALL INSPECTIONS REQUIRED FOR THE

PROJECT WITH THE CITY OF PARMA AND ENSURING THAT ALL INSPECTIONS ARE

COMPLETED AND PASSED. THIS INSPECTION PROCESS SHALL BE CONSIDERED IN ADDITION

TO THOSE REQUIRED INTERNALLY BY THE VA.

6. THE GC SHALL BE RESPONSIBLE FOR OBTAINING A CERTIFICATE OF OCCUPANCY THROUGH

THE CITY OF PARMA AND OBTAINING ALL FINAL SIGN-OFFS FROM BUILDING OFFICIALS

7. ARCHITECT WILL SUBMIT DRAWINGS FOR BUILDING PERMIT REVIEW/APPROVAL. GC SHALL

BE RESPONSIBLE FOR PERMIT PICK-UP/PAYMENT. IT IS THE INTENT THAT THE PERMIT WILL

BE READY FOR PICK-UP AHEAD OF CONSTRUCTION

CONSTRUCTION NOTES:

1/8" = 1'-0"

SITE IMPROVEMENT PLAN

ENLARGED

NORTH

NEW LOCATION FOR RELOCATED POST-MOUNTED VAN ACCESSIBLE STALL SIGNAGE,

CENTERED ON PARKING STALL AND ALIGNED W/ADJACENT SIGNS. GC SHALL INSTALL

SIGN SUCH THAT THE BOTTOM OF THE SIGNAGE IS MINIMUM 5'-0" ABOVE FINISHED GRADE.

SIGNAGE SHALL BE CENTERED ON PARKING STALL AND ALIGNED W/EXISTING ADJACENT

SIGNS - VERIFY IN FIELD. PROVIDE NEW CONCRETE BASE MATCHING HEIGHT AND

DIAMETER OF EXISTING, EXTEND BOTTOM MIN. 42" BELOW GRADE

NEW ACCESSIBLE ADA PARKING STALL TO BE PAINTED/LOCATED AT FORMER

NON-ACCESSIBLE PARKING STALL LOCATION. GC SHALL PAINT ALL STRIPING AND ADA

SYMBOLS IN STALL - MATCH EXISTING ADA STALLS ON SITE

ALIGN NEW/EXISTING

STRIPING

NEW LOCATION FOR RELOCATED POST-MOUNTED ACCESSIBLE STALL SIGNAGE,

CENTERED ON PARKING STALL AND ALIGNED W/ADJACENT SIGNS. GC SHALL INSTALL

SIGN SUCH THAT THE BOTTOM OF THE SIGNAGE IS MINIMUM 5'-0" ABOVE FINISHED GRADE.

SIGNAGE SHALL BE CENTERED ON PARKING STALL AND ALIGNED W/EXISTING ADJACENT

SIGNS - VERIFY IN FIELD. PROVIDE NEW CONCRETE BASE MATCHING HEIGHT AND

DIAMETER OF EXISTING, EXTEND BOTTOM MIN. 42" BELOW GRADE

3 3

EX. STALLS TO

REMAIN

EX. STALLS TO

REMAIN

5 5

NEW 2'-0" WIDE TRUNCATED DOME DETECTABLE WARNING STRIP TO BE INSTALLED

ALONG FULL LENGTH OF NEW ADA PARKING STALLS. SPEC TO MATCH EXISTING

WARNING STRIP ON SITE

6 NEW LOCATION FOR RELOCATED BENCH

36" H X 6" DIA. REMOVABLE STEEL BOLLARDS: TRAFFICGUARD LOCKING KEY LOCK

SERIES RP3506 OR APPROVED EQUAL. GC SHALL PROVIDE CONCRETE BASE FOR

STEEL INSERT - SEE BOLLARD DETAILS

(7) LOCS.

MOBILE MRI TRAILER - RETAINED BY VA UNDER SEPARATE CONTRACT. NOTE: WHEELCHAIR LIFT AND STAIR

ARE PART OF THE MRI TRAILER. GC SHALL PROVIDE UTILITIES TO TRAILER, REFER TO MEP DRAWINGS

CONTROL JOINT LOCATION FOR NEW/EXISTING SIDEWALK TRANSITION9

INFILL FORMER GRASS STRIP WITH NEW GRAVEL BETWEEN

EXISTING GRAVEL BED AND FACE OF WALKWAY CONSTRUCTION

NEW CONNECTOR

WALKWAY - SEE

ENLARGED PLAN

SHEETS FOR

DETAILS

AREA WITHIN DASHED BOUNDARY INDICATES APPROXIMATE AREA OF

EXCAVATION, SITEWORK, AND REGRADING. GC SHALL BE RESPONSIBLE

FOR RESEEDING ENTIRE AREA WITH GRASS SEED UPON COMPLETION OF

CONSTRUCTION. ACTUAL AREA MAY VARY - VERIFY FULL EXTENT IN FIELD.

GC IS RESPONSIBLE FOR REPAIRING ALL DAMAGED SITE AREAS AND

RESTORING BACK TO ORIGINAL CONDITIONS

NEW YARD BASIN, SEE CIVIL DWGS. FOR LOCATION AND GRADING

REQUIREMENTS

NEW CONDENSING UNITS ON CONCRETE PAD, SEE CIVIL AND MEP

DRAWINGS

100% CD'S SUBMISSION 3.26.19

5. WHERE NEW UTILITIES ARE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS

SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME, AND PATCH

AND REPAIR WITH NEW TO MATCH EXISTING CONDITIONS.

1. CONSIDER ALL AREAS OWNER-OCCUPIED, UNLESS OTHERWISE NOTED.

2. ALL FLOOR PLAN DIMENSIONS ARE FROM FACE OF POURED CURB TO FACE OF POURED CURB

3. ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC FIRE ALARM, ELECTRICAL, ETC.) TO

DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE

WITH THE REQUIREMENTS OF ALL APPLICABLE CODES.

4. PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING

CONDITIONS.

6. ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE

REPAIRED BY CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING,

AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE

REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO OWNER.

7. ALL NEW PENETRATIONS IN FIRE RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF

ASSEMBLY AS REQUIRED.

8. CONTRACTOR SHALL PROVIDE DUST REMOVING WALK-OFF MATS (TACKY MAT) AT ALL

CONSTRUCTION ENTRY POINTS

9. CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN

NEGATIVE PRESSURE IN WORK AREA ENSURING NO DUST OR FUMES WILL BE TRANSFERRED

TO OCCUPIED AREAS. PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST PROOF

BARRICADE TO CONFIRM PRESSURE. DUST MONITORING SHALL BE BY OWNER. SEE

SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS" ATTACHMENT AND 01 35 26 "SAFETY

REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.

MRI TRAILER WORKPOINT:

MRI TRAILER TO BE

LOCATED BY VENDOR TO

ALIGN UNIT APPROX. 19"

AWAY FROM EX. CURB.

INTENT IS TO ALLOW

CLEARANCE FOR THREE

(3) ACCESS

COMPARTMENTS ON MRI

TRAILER TO BE LOCATED

WITHIN TRAILER

BID ISSUE SUBMISSION 4.17.19

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

WC LIFT

AutoCAD SHX Text

VAN

AutoCAD SHX Text

VAN

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

7'-1 1/2" 4'-0"

4'-0" 4'-0" 8'-0" 4'-0"

8'-9 1/2"

39'-11"

7'-7" OUT-TO-OUT

CONC. CURB/STUDS

23'-6" 8'-2 1/2" 8'-2 1/2" 7'-1"

O

U T

T

O O

U T

C O

N C

C

U R

B S

T U

D S

1'-2"

21'-8"

1'-2"

17'-10"

3'-4" 2'-4"

E

X P

J T

24'-0" OUT-TO-OUT

CONC. CURB/STUDS

3'-1" +/-

L A

N D

I N

G

R A

M P

U

17'-0" RAMP UP

@ 1:20

6'-6"

1'-0"

1'-0"

1'-0"

4'-4" +/-

26'-2" HIGH ROOF

24'-6" LOW ROOF

L O

W

R

O O

F

10 1/2" TYP. OVERHANG

10 1/2" TYP.

OVERHANG

T

Y P

O V

E R

H A

N G

A-SD-03

ENLARGED WALKWAY FLOOR &

ROOF PLANS AND SCHEDULES

Revisions: Date

65% CD'S SUBMISSION 2.13.19

DAKCJK4.17.19

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT:

Office of

Construction and Facilities

Management

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

ATE

I

T C

J.

O

O

FO

H

Stanley J. Kaczmar, License #4988

Expiration Date: 12/31/2019

PARMA CBOC MOBILE MRI SITE PREP

8787 BROOKPARK RD. PARMA, OHIO

541-CSI-106

CIVIL & MECH./ELEC. ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44685

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

FULLY SPRINKLERED

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD. RICHFIELD, OH 44286

P. 330.659.6688

GENERAL NOTES:

5. WHERE NEW UTILITIES ARE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS

SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME, AND PATCH

AND REPAIR WITH NEW TO MATCH EXISTING CONDITIONS.

1. CONSIDER ALL AREAS OWNER-OCCUPIED, UNLESS OTHERWISE NOTED.

2. ALL FLOOR PLAN DIMENSIONS ARE FROM FACE OF POURED CURB TO FACE OF POURED CURB.

3. ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC FIRE ALARM, ELECTRICAL, ETC.) TO

DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE

WITH THE REQUIREMENTS OF ALL APPLICABLE CODES.

4. PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING

CONDITIONS.

6. ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE

REPAIRED BY CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING,

AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE

REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO OWNER.

7. ALL NEW PENETRATIONS IN FIRE RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF

ASSEMBLY AS REQUIRED.

14. ALL FLOOR, WALL, CEILING, AND MISC. FIRE RESISTIVE ASSEMBLIES AND CONSTRUCTION

SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND / OR AS REQUIRED BY

CODE. ALL EXISTING FIRE RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING

NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRE

STOPPING, FIRE RATED DOORS AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT

UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.

8. CONTRACTOR SHALL PROVIDE DUST REMOVING WALK-OFF MATS (TACKY MAT) AT ALL

CONSTRUCTION ENTRY POINTS

9. CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN

NEGATIVE PRESSURE IN WORK AREA ENSURING NO DUST OR FUMES WILL BE TRANSFERRED

TO OCCUPIED AREAS. PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST PROOF

BARRICADE TO CONFIRM PRESSURE. DUST MONITORING SHALL BE BY OWNER. SEE

SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS" ATTACHMENT AND 01 35 26 "SAFETY

REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.

10. ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE

APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK

SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE

LOCATION OF BARRIERS WITH OWNER.

11. THE FACILITY'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN

THE PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.

12. FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.

13. WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN

EXISTING WALL. REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR

NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E.

DOUBLE STUDS, HEADERS) AND PATCH ADJACENT WALLS TO MATCH EXISTING.

15. DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR

DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35

26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF

DEBRIS FROM THE PROJECT AREA.

16. ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE

OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS

SHALL BE PERFORMED "OFF HOURS" UNLESS OTHERWISE APPROVED BY THE COR.

CITY OF PARMA REQUIREMENTS:

1. THIS PROJECT AND THE FACILITY IN GENERAL FALL UNDER THE JURISDICTION OF THE CITY

OF PARMA, AND AS SUCH, THE CITY OF PARMA'S PERMITTING AND INSPECTION PROCESS

MUST BE FOLLOWED. THE VA IS A TENANT IN THIS BUILDING AND THE FACILITY IS NOT

OWNED BY THE FEDERAL GOVERNMENT.

2. ALL CONTRACTORS - GENERAL AND SUBS - ARE REQUIRED TO BE REGISTERED WITH THE

CITY OF PARMA IN ORDER TO PERFORM CONSTRUCTION OPERATIONS AND PULL PERMITS.

3. IT WILL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO BOTH PULL AND COVER

THE COST OF THE GENERAL BUILDING PERMIT FOR THIS PROJECT, AND ALL FEES

ASSOCIATED WITH SAME SHALL BE INCLUDED IN THE BID PRICE. ALL SUB-CONTRACTORS

WILL ALSO BE RESPONSIBLE FOR BOTH PULLING AND COVERING THE COST OF THEIR

INDIVIDUAL TRADE PERMITS.

4. THE GC SHALL BE RESPONSIBLE FOR PREPARING AND SUBMITTING ALL FIRE ALARM AND

FIRE SUPPRESSION SYSTEM DRAWINGS - TO THE EXTENT THAT MODIFICATIONS TO SAME

ARE REQUIRED FOR THIS PROJECT - TO THE CITY OF PARMA FOR REVIEW AND APPROVAL.

5. THE GC SHALL BE RESPONSIBLE FOR SCHEDULING ALL INSPECTIONS REQUIRED FOR THE

PROJECT WITH THE CITY OF PARMA AND ENSURING THAT ALL INSPECTIONS ARE

COMPLETED AND PASSED. THIS INSPECTION PROCESS SHALL BE CONSIDERED IN ADDITION

TO THOSE REQUIRED INTERNALLY BY THE VA.

6. THE GC SHALL BE RESPONSIBLE FOR OBTAINING A CERTIFICATE OF OCCUPANCY THROUGH

THE CITY OF PARMA AND OBTAINING ALL FINAL SIGN-OFFS FROM BUILDING OFFICIALS

7. ARCHITECT WILL SUBMIT DRAWINGS FOR BUILDING PERMIT REVIEW/APPROVAL. GC SHALL

BE RESPONSIBLE FOR PERMIT PICK-UP/PAYMENT. IT IS THE INTENT THAT THE PERMIT WILL

BE READY FOR PICK-UP AHEAD OF CONSTRUCTION

FLOOR PLAN NOTES:

1/4" = 1'-0"

FLOOR PLAN

ENLARGED WALKWAY

NORTH

1/4" = 1'-0"

ROOF PLAN

ENLARGED WALKWAY

NORTH

A

B

C

D

E

1 2 3 4 5

S L O

E

D

N

S L O

D

N

SLOPE DN @ 2:12

A

B

C

D

E

1 2 3 4 5

CONTINUOUS ALUM.

GUTTER - COLOR TO

MATCH EX. BUILDING

DS DS

DS

CONTINUOUS ALUM.

GUTTER - COLOR TO

MATCH EX. BUILDING

DASHED LINES INDICATE

EXTERIOR WALL BELOW,

TYP.

EPDM ROOF MEMBRANE SYSTEM OVER CONTINUOUS R-20 RIGID INSULATION BD.,

METAL ROOF DECK, AND SLOPED LIGHT GAUGE ROOF JOISTS W/R-19 BATT

INSULATION IN BETWEEN. SEE STRUCTURAL DRAWINGS FOR FRAMING

A

ROOF PLAN NOTES:

A

A

A

CONTINUOUS ALUM. GRAVEL STOPB

B

B

B

B

B

C

C

4" ALUM. DOWNSPOUT - COLOR TO MATCH EX. BUILDING DOWNSPOUTSC

AS-2.1

A

AS-2.0

B

AS-2.0

C

AS-2.0

D

AS-2.0

AS-2.1

WALKWAY

B

A

NEW CONCRETE WALKWAY SLAB OVER 10 MIL VAPOR BARRIER, GRAVEL SUBBASE,

W/PERIMETER CURB FOR NEW STUD WALL ATTACHMENT. SPACE CONTROL JOINTS

5'-0" O.C. MAX. SEE STRUCT. DWGS. AND SECTIONS FOR DETAILS

AS-2.1

AS-2.1

FLUSH

SURFACES

A S

S

I M

EX. FIRST FLOOR

ELEV. +795.00

EX. GRADE

+793.10 +/-

EX. GRADE

+793.10 +/-

+794.28

+795.00

T/SLAB @ DOOR

+793.18 +/-

B/RAMP

+793.43 +/-

1101B

WHEELCHAIR

ESCORT/

DOOR/HARDWARE NOTES:

PROVIDE WELDED HOLLOW METAL DOOR FRAMES, 16

GA., THREE (3) RUBBER BUMPER SILENCERS. PAINT

FRAMES, COLOR PER ARCHITECT

ALL DOORS (UNLESS OTHERWISE NOTED) SHALL HAVE

LEVEL-OPERATED HARDWARE PER SECTION ICC A117.1

404.2.6

ALL EGRESS DOORS SHALL BE READILY OPENABLE

FROM THE SIDE FROM WHICH EGRESS IS TO BE MADE

WITHOUT THE USE OF KEY OR SPECIAL KNOWLEDGE

OR EFFORT PER LOCAL CODE. DOORS WITH CARD

READERS SHALL BE TIED INTO EXISTING FIRE ALARM

SYSTEM. IN AN EMERGENCY, ALL CARD READERS WILL

DEACTIVATE AND DOORS SHALL OPEN FREELY.

DOOR OPENING FORCE SHALL COMPLY WITH ICC

A117.1 404.2.8.

PROVIDE COSMETIC SEALANT AT JOINT WHERE

DOOR FRAMES MEET WALL, TYP. AT ALL

FRAMES

PROVIDE MINIMUM THREE (3) ANCHORS PER

JAMB

THRESHOLDS @ ENTRY DOORS SHALL NOT EXCEED

IN HEIGHT

GENERAL FINISH NOTES:

GENERAL NOTES:

ALL FINISHES SHALL BE IN COMPLIANCE WITH OBC SECTIONS 803, 804, AND 806.

REFER TO MEP DRAWINGS FOR MECH/ELEC/TECH ITEMS TO BE FIELD PAINTED

INTERIOR WALL AND CEILING FINISHES SHALL COMPLY WITH REQUIREMENTS OF OBC

TABLE 803.11, AND SHALL BE A MINIMUM CLASS C TYPE, WITH A FLAME SPREAD INDEX

OF 76-200 AND A SMOKE-DEVELOPED INDEX OF 0-450.

THE FOLLOWING INTERIOR FINISHES SHALL BE PROVIDED IN THE NEW CONNECTOR WALKWAY:

· ALL WALLS SHALL BE PAINTED PT-1

· GYP. BD. CEILING SHALL BE PAINTED PT-2

· 6" HIGH COVED VINYL BASE SHALL BE PROVIDED ON THE ENTIRE INTERIOR PERIMETER

· HOLLOW METAL DOORS AND FRAMES AND HANDRAILS SHALL BE PAINTED PT-4

· EXPOSED UTILITIES/PIPING ALONG CEILING OR WALLS SHALL BE PAINTED TO MATCH

ADJACENT FINISHES ON THE CEILING AND WALLS RESPECTIVELY

· CONCRETE FLOOR SLAB SHALL REMAIN EXPOSED - FINISH SHALL MATCH THAT OF

ADAJCENT, EXTERIOR SIDEWALK

THE FOLLOWING INTERIOR FINISHES SHALL BE PROVIDED IN EXISTING ESCORT/WHEELCHAIR

ROOM 1101B WHERE PATCHING, REPAIRING, OR INFILL OF FINISHES IS REQUIRED:

· GYP. BD. SHALL BE PT-3 (MATCH EX. WALLS)

· INFILL BASE SHALL BE WB-1, PROFILE AND STAIN COLOR TO MATCH EXISTING WOOD BASE

IN SPACE

SCALE: 1/4" = 1'-0"

DOOR & FRAME TYPES

GALV. HOLLOW METAL,

PAINTED

A

GALV. HOLLOW METAL,

INSULATED, PAINTED

4" HEAD MAY

OCCUR, SEE

SCHED.

AS-2.1

AS-2.1

AS-2.1

A S

S

I M

2" EXPANSION JOINT SYSTEM @ EXTERIOR WALL - SEE DETAILD

AS-2.1

D

FINISHED ELEVATION OF CONCRETE SLAB IN WIDER PORTION OF WALKWAY SHALL

ALIGN WITH EXISTING FINISHED GRADES TO PROVIDE FLUSH TRANSITION FROM

WALK TO TRAILER, AS SHOWN. VERIFY EX. GRADES IN FIELD

1-1/2" DIA. PAINTED STEEL HANDRIAL @ 34" AFF TO TOP OF RAIL, SECURED TO

EXTERIOR WALL. PROVIDE FRTW BLOCKING IN WALL AS REQUIRED FOR SECURE

ATTACHMENT

PROVIDE

CLOSED,

LOOPED END

PLAM WINDOW SILL - SEE FIN. SCHED. FOR COLOR

STUD BOX COLUMN - SEE STRUCT. DWGS.

100% CD'S SUBMISSION 3.26.19

A

AS-2.2

B

AS-2.2

B

AS-2.2

J-1

AS-2.2

ALL DRYWALL INSTALLED FOR THE ENTIRE PROJECT SHALL BE

" THICKNESS, MOLD/MILDEW

RESISTANT SPEC (BLUE BOARD OR APPROVED EQUAL)

EXTEND NEW GUTTER TO

FACE OF EX. BLDG.

DOWNSPOUT. SEAL @

JOINT

1" EXPANSION JOINT @

BLDG. SEE SECTION

DETAIL

PROVIDE NEW WALL-MTD. FIRE EXTINGUISHER

NEW WALKWAY

WORKPOINT: ALIGN

EXT. FACE OF NEW

CONC. CURB AND

STUDS W/FACE OF

EX. MASONRY WALL

DS

DS

PROVIDE ALUMINUM

GUTTER "FIN" @ CORNER

LOCATION TO DIVERT

WATER AWAY FROM

CORNER

AREA WITHIN HATCHED BOX INDICATES INFLATABLE AIRLOCK DOCK SEAL TO BE

INSTALLED ON FACE OF BUILDING TO PROVIDE TIGHT SEAL BETWEEN MRI TRAILER

AND WALKWAY. SPEC: MEDIGATE AIR LOCKE DOCK SEAL (OR APPROVED EQUAL)

BID ISSUE SUBMISSION 4.17.19

AutoCAD SHX Text

WC LIFT

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EQ. EQ. EQ. EQ.

Q

E

Q

10'-0"

E Q

E

Q

5'-5"

1'-4"

1'-4"

1'-4" 1'-4"

A-SD-04

ENLARGED REF. CEILING

PLANS

Revisions: Date

65% CD'S SUBMISSION 2.13.19

DAKCJK4.17.19

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT:

Office of

Construction and Facilities

Management

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

ATE

I

T C

J.

O

O

FO

H

Stanley J. Kaczmar, License #4988

Expiration Date: 12/31/2019

PARMA CBOC MOBILE MRI SITE PREP

8787 BROOKPARK RD. PARMA, OHIO

541-CSI-106

CIVIL & MECH./ELEC. ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44685

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

FULLY SPRINKLERED

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD. RICHFIELD, OH 44286

P. 330.659.6688

FIBER CEMENT PANEL, PTD. - TYP. @ UNDERSIDE OF OVERHANGS. JOINTS SHALL

ALIGN WITH JOINTS ON ELEVATIONS

GENERAL NOTES:

14. ALL FLOOR, WALL, CEILING, AND MISC. FIRE RESISTIVE ASSEMBLIES AND CONSTRUCTION

SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND / OR AS REQUIRED BY

CODE. ALL EXISTING FIRE RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING

NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRE

STOPPING, FIRE RATED DOORS AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT

UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.

10. ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE

APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK

SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE

LOCATION OF BARRIERS WITH OWNER.

11. THE FACILITY'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN

THE PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.

12. FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.

13. WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN

EXISTING WALL. REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR

NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E.

DOUBLE STUDS, HEADERS) AND PATCH ADJACENT WALLS TO MATCH EXISTING.

15. DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR

DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35

26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF

DEBRIS FROM THE PROJECT AREA.

16. ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE

OWNER'S OPERATIONS…