36C25019B0015-021.pdf

PDF 2 MB Posted

Attached to
Repair Outdoor Ductwork Federal contract opportunity
Solicitation number
36C25019B0015
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0015 Combined 100 CD PDF Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Repair Outdoor Ductwork, newest first.
File Type Posted
36C25019C0218-000.docx DOCX document
36C25019B0015-0001000.docx DOCX document
36C25019B0015-023.docx DOCX document
36C25019B0015-019.docx DOCX document
36C25019B0015-024.docx DOCX document
36C25019B0015-020.pdf PDF
36C25019B0015-022.pdf PDF
36C25019B0015-000.docx DOCX document
36C25019B0015-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

CONSULTANTS:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18057100% CD SUBMISSION 10/12/18

CONSULTANTS:

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED

WITHOUT THE EXPRESSED WRITTEN CONSENT

OF

PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2004.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

REPAIR OUTDOOR

DUCTWORK

INSULATION

541-18-511

DMLLDH

MECHANICAL LEGEND, GENERAL

NOTES, AND DETAILS

1-M0 10/12/18

A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM EXISTING DRAWINGS. AND FIELD SURVEYING MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT

THE WORK TO BE PERFORMED AS INDICATED ON THESE DRAWINGS.

B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH VA A MINIMUM OF

SEVEN WORKING DAYS IN ADVANCE.

C. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT.

D. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS WHILE PERFORMING WORK ON ROOF.

CONTRACTOR SHALL MAINTAIN ROOFING WARRANTY. CONTACT VA C.O.R. FOR ROOFING

WARRANTY/CONTRACTOR INFORMATION.

DUCTWORK SYMBOLS:

ABBREVIATIONS:

CALL OUTS: DEMOLITION SYMBOLS:

MANUAL BALANCING DAMPER ON DUCT

ROUND DUCT SIZE

AD ACCESS DOOR

12"Ø

RECTANGULAR DUCT SIZE24x18

ELECTRICAL CONTRACTOR

GENERAL TRADES CONTRACTOR

TEMPERATURE CONTROL CONTRACTOR

HVAC CONTRACTOR

FIRE SUPPRESSION CONTRACTOR

PLUMBING CONTRACTOR

CONNECT TO EXISTING

EC

GC

FC

PC

TC

HC

CTE

TO

SUPPLY AIR DUCT

TO BE MOUNTED OVER ACCESSIBLE CEILING

ABOVE FINISHED FLOOR

EXHAUST AIR

RETURN AIR

SUPPLY AIR

AFF

EA

RA

SA

ROOF OPENINGRO

TEMPERATURE CONTROL PANELTCP

COMBINATION FIRE/SMOKE DAMPER IN DUCT

MOTOR OPERATED DAMPERMOD

FSD

RETURN AIR DUCT

EXHAUST AIR DUCT

EXISTING TO REMAIN

EXISTING TO BE REMOVED

X

XR

EXISTING TO BE RELOCATEDXRL

FIRE DAMPER IN DUCTFDD

LIMIT OF DEMOLITIONLOD

EXISTING NEW LOCATIONXNL

NOTE: THIS LEGEND IS INTENDED TO AID IN THE UNDERSTANDING OF SHORTHAND, SYMBOLS AND ABBREVIATIONS SHOWN IN THESE CONSTRUCTION DOCUMENTS. IT IS NOT THE INTENTION TO DESCRIBE THE PROJECT SCOPE OF WORK, FOR DETAILED SCOPE OF WORK PLEASE REFER TO THE SUBSEQUENT DRAWINGS.

OPENING IN TOP OF DUCT. SHALL BE A MINIMUM 1.5 TIMES

GREATER THAN THE CROSS-SECTIONAL AREA OF DUCT.

HVAC GENERAL NOTES

REFERENCE TO CODED NOTE

SECTION / DETAIL / ELEVATION MARK

DETAIL NO.

EQUIPMENT OR FIXTURE MARK

DRAWING

EQUIPMENT

TYPE

UNIT NUMBER

H4-1

X - #

MECHANICAL LEGEND

ROOF MOUNTED DUCT SUPPORT DETAIL

NOT TO SCALE

UNISTRUT SUPPORT

(TYPICAL)

ANCHOR UNISTRUT

SUPPORT TO CURB

(TYPICAL)

12" ROOF CURB

METAL DECK

ROOF INSULATION

ROOF MEMBRANE

2" RIGID POLYISOCYANURATE

INSULATION WITH 30 MIL PVC

JACKET (TYPICAL)

TAPERED RIGID POLYISOCYANURATE

ROOF INSULATION ON TOP OF 2"

INSULATION PITCH 1" PER FOOT. LOW

POINT 2" THICK AT EDGES.

(TYPICAL)

NOTES:

1. ADJUST ROOF SUPPORTS AND ANGLES SO THAT THERE IS NO PENETRATION OF

DUCT INSULATION OR JACKETING.

2. DETAIL IS TYPICAL. WHERE OTHER SUPPORT TYPES EXIST, ADJUSTMENTS SHALL

BE MADE TO AVOID PENETRATION OF INSULATION OR JACKETING.

3. TWO (2) SIDE-BY-SIDE DUCTS MAY OCCUR ON SAME FRAMES.

2" INSULATION SIDES AND BOTTOM OF

DUCTS.

A. REFER TO DWG 1-M3 FOR NOTES REGARDING DEDUCT ALTERNATE NO. 1.

B. REFER TO DWG 1-M2A FOR NOTES REGARDING DEDUCT ALTERNATE NO. 2.

C. AS PART OF DEDUCT ALTERNATE NO. 3, DELETE ALL TOPSIDE REINFORCEMENT OF DUCT (SEE DETAIL) THAT IS INDICATED ON PLANS. IN LIEU OF TOPSIDE REINFORCEMENT, PROVIDE TAPERED INSULATION AND

JACKET ONLY (PER ROOF MOUNTED DUCT SUPPORT DETAIL).

DEDUCT ALTERNATE NOTES:

EXTERIOR DUCT TOP-SIDE REINFORCEMENT DETAIL

NOT TO SCALE

ALL MATERIAL SHALL BE 18 GA.

GALVANIZED SHEET STEEL

NEW CAP

1" LIP 1" LIP

EXISTING DUCTWORK

SUPPORT X 3

W

H

1" LIP ON EACH SIDE

L=60"

W

H

3 SUPPORTS

SHEET METAL CAP WITH 1" LIP ON EACH SIDE. TACK WELD 3 SUPPORTS.

A. "H" SHALL BE HEIGHT NECESSARY TO PROVIDE 1" PITCH PER FOOT. "W" IS EXISTING DUCT WIDTH.

B. 18 GA GALVANIZED STEEL CONSTRUCTION.

C. DUCT SYSTEMS SHALL BE DRIED PRIOR TO INSULATION.

D. TACK WELD AS REQUIRED.

NOTES:

2" POLYISOCYANURATE

INSULATION W/30 MIL PVC

JACKETING. REFER TO

OTHER DETAILS FOR

ADDITIONAL INFORMATION.

E. DETAIL ILLUSTRATES TYPICAL 60" LENGTH. PROVIDE 1" OVERLAP FOR JOINED LENGTHS. TACK

WELD AND SEAL AT JOINED LENGTHS.

C

E

H

J

K

L

N

F

D D

B

G

5a 6.33B 3C3D 3E 3G

3H

3I

3J

3O 3Q 3R3V3MM 3NN

3OO

3QQ F.1F.9

X-RTU

X - 60 x 20 RA

X - 60 x 20 SA

LAB WAREHOUSE PENTHOUSE

EXISTING TPO ROOFING

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18057100% CD SUBMISSION 10/12/18

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED

WITHOUT THE EXPRESSED WRITTEN CONSENT

OF

PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2004.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

REPAIR OUTDOOR

DUCTWORK

INSULATION

541-18-511

DMLLDH

PARTIAL ROOF / SECOND FLOOR

DUCTWORK PLAN - AREA A

1-M2A 10/12/18

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN

- AREA A

1N

REMOVE EXISTING EXTERIOR INSULATION AND JACKETING COMPLETELY. INSTALL NEW 2"

THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE, PROVIDE

TAPERED POLYISOCYANURATE ROOF INSULATION, PITCHED FROM THE MIDDLE. PROVIDE

30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT

SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION. ADJUST

SUPPORT / UNISTRUT AS NEEDED.

A. AS PART OF DEDUCT ALTERNATE NO. 2, ALL WORK ON THIS PLAN SHALL BE DELETED.

DEDUCT ALTERNATE NO. 2 NOTE:

LEGEND

14a 15b 16b 17c 18d

L1

L2

Q

R

L3

18a

N1 N1

1c

Z1

Y1

5a

R1

6.3E.0 C.03D 3O 3Q 3R3V B.3C.7D.5E.2F.1F.9

X-ACCESS DOOR

X-ACCESS DOOR

X-ACCESS DOOR

X-ACCESS DOOR

X-ACCESS DOOR

X x

S A

X x

R A

X x

S A

X x

S A

X x

S A

WEST PENTHOUSE

P

T

V

W

Y

U

M

EXISTING ROOF PAVER

SYSTEM OVER ROOFING

EXISTING ROOF PAVER

SYSTEM OVER ROOFING

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

CONSULTANTS:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18057100% CD SUBMISSION 10/12/18

CONSULTANTS:

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED

WITHOUT THE EXPRESSED WRITTEN CONSENT

OF

PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2004.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

REPAIR OUTDOOR

DUCTWORK

INSULATION

541-18-511

DMLLDH

PARTIAL ROOF / SECOND FLOOR

DUCTWORK PLAN - AREA B

1-M2B 10/12/18

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN

- AREA B

1N

REMOVE EXISTING EXTERIOR INSULATION AND JACKETING COMPLETELY. INSTALL NEW

2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE,

PROVIDE TAPERED POLYISOCYANURATE ROOF INSULATION, PITCHED FROM THE

MIDDLE. PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE

COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR

INSULATION. ADJUST SUPPORT / UNISTRUT AS NEEDED.

REMOVE EXISTING INSULATION AND JACKETING COMPLETELY. PROVIDE TOP-SIDE

REINFORCEMENT (PER DETAIL, DWG 1-M0) WITH PITCH FROM MIDDLE. INSTALL NEW 2"

THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. PROVIDE 30 MIL THICK

PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS,

UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION. ADJUST

SUPPORT/UNISTRUT AS NEEDED.

2924a

C

E

H

J

L

Z

CC

F

D

B

G

Y2

CC1

AA2

X x

S A

X x

R A

X - 48 x 18 RA

X - 30 x 16 SA X - 50 x 22 SA

X - 50 x 22 RA

X x

R A

X x

S A

X - 20 x 22 RA DN

X - 24 x 12 SA DNX - 58 x 10 SA DN

X - 38 x 14 RA DN

X - 66 x 24

SA DN

X - 66 x 24 RA DN

X - 30 x 16 SA DN

X - 30 x 16 RA DN

X - ACCESS DOOR

X - ACCESS DOOR

EAST PENTHOUSE

302725 26 32 33 34 35 36 39

AA

BB

EXISTING ROOF PAVER

SYSTEM OVER ROOFING

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

CONSULTANTS:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18057100% CD SUBMISSION 10/12/18

CONSULTANTS:

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED

WITHOUT THE EXPRESSED WRITTEN CONSENT

OF

PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2004.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

REPAIR OUTDOOR

DUCTWORK

INSULATION

541-18-511

DMLLDH

PARTIAL ROOF / SECOND FLOOR

DUCTWORK PLAN - AREA C

1-M2C 10/12/18

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN

- AREA C

1N

REMOVE EXISTING EXTERIOR INSULATION AND JACKETING COMPLETELY. INSTALL NEW

2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE,

PROVIDE TAPERED POLYISOCYANURATE ROOF INSULATION, PITCHED FROM THE

MIDDLE. PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE

COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR

INSULATION. ADJUST SUPPORT / UNISTRUT AS NEEDED.

REMOVE EXISTING INSULATION AND JACKETING COMPLETELY. PROVIDE TOP-SIDE

REINFORCEMENT (PER DETAIL, DWG 1-M0) WITH PITCH FROM MIDDLE. INSTALL NEW 2"

THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. PROVIDE 30 MIL THICK

PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS,

UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION. ADJUST

L2

Q

Z

L3

N1

R2

V1

Y2

V2

R1

36a

X - ACCESS DOOR

X - 64 x 30 RA

X - 64 x 28 SA

X x

R A

X x

S A

X x

R A

X x

R A

X - 50 x 20 RA

X - ACCESS DOOR

X - EA (LEAVE EXISTING

INSULATION)

X - 48 X 28 SA (TOP)

X - 48 X 22 RA (BOTTOM)

X x

S A

X - ACCESS DOOR (RA)

X - ACCESS DOOR (RA)

X - ACCESS DOOR (SA)

X - ACCESS DOOR (SA)

X - ACCESS DOOR (SA)

X - ACCESS DOOR (SA)

X - ACCESS DOOR

X - ACCESS DOOR

X - ACCESS DOOR

X - ACCESS DOOR

X - ACCESS DOOR

X - 54 x 24 SA

X - 54 x 24 RA

302725 26

32 33 34 35 36

P

T

V

W

Y

U

M

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

CONSULTANTS:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18057100% CD SUBMISSION 10/12/18

CONSULTANTS:

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED

WITHOUT THE EXPRESSED WRITTEN CONSENT

OF

PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2004.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

REPAIR OUTDOOR

DUCTWORK

INSULATION

541-18-511

DMLLDH

PARTIAL ROOF / SECOND FLOOR

DUCTWORK PLAN - AREA D

1-M2D 10/12/18

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN

- AREA D

X x R

A(BOTTOM)

U P x S A

IN

C H W G

(TOP) AA

x

X x1

X R A

X x R A

X x

R A x

N

EAST PENTHOUSE

EXISTING ROOF PAVER

SYSTEM OVER ROOFING

EXISTING ROOF PAVER

SYSTEM OVER ROOFING

REMOVE EXISTING EXTERIOR INSULATION AND JACKETING COMPLETELY. INSTALL NEW

2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE,

PROVIDE TAPERED POLYISOCYANURATE ROOF INSULATION, PITCHED FROM THE

MIDDLE. PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE

COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR

INSULATION. ADJUST SUPPORT / UNISTRUT AS NEEDED.

REMOVE EXISTING INSULATION AND JACKETING COMPLETELY. PROVIDE TOP-SIDE

REINFORCEMENT (PER DETAIL, DWG 1-M0) WITH PITCH FROM MIDDLE. INSTALL NEW 2"

THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. PROVIDE 30 MIL THICK

PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS,

UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION. ADJUST

L2

Q

Z

L3

N1

R2

V1

Y2

V2

R1

X x

R A

X x

S A

X x

S A

X x

R A

X - ACCESS DOOR

X - ACCESS DOOR

EAST PENTHOUSE

302725 26 32 33 34 35 36

P

T

V

W

Y

U

M

EXISTING ROOF PAVER

SYSTEM OVER ROOFING

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

CONSULTANTS:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18057100% CD SUBMISSION 10/12/18

CONSULTANTS:

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED

WITHOUT THE EXPRESSED WRITTEN CONSENT

OF

PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2004.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

REPAIR OUTDOOR

DUCTWORK

INSULATION

541-18-511

DMLLDH

PARTIAL ROOF / THIRD FLOOR

DUCTWORK PLAN - AREA E

1-M3 10/12/18

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

PARTIAL ROOF / THIRD FLOOR DUCTWORK PLAN -

AREA E

1N

AS PART OF DEDUCT ALTERNATE NO. 1, DELETE WORK INDICATED BY CODED NOTE #1.

DEDUCT ALTERNATE NO. 1 NOTE:

REMOVE EXISTING EXTERIOR INSULATION AND JACKETING COMPLETELY. INSTALL NEW

2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE,

PROVIDE TAPERED POLYISOCYANURATE ROOF INSULATION, PITCHED FROM THE

MIDDLE. PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE

COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR

INSULATION. ADJUST SUPPORT / UNISTRUT AS NEEDED.

REMOVE EXISTING INSULATION AND JACKETING COMPLETELY. PROVIDE TOP-SIDE

REINFORCEMENT (PER DETAIL, DWG 1-M0) WITH PITCH FROM MIDDLE. INSTALL NEW 2"

THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. PROVIDE 30 MIL THICK

PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS,

UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION. ADJUST

SUPPORT/UNISTRUT AS NEEDED.

1-X.1 - COVER SHT
1-M0 - MECHANICAL LEGEND, GENERAL NOTES, AND DETAILS
R2017 FFH CF - 18057_dlevanduski
1-M0 - MECHANICAL LEGEND, GENERAL NOTES, AND DETAILS
1-M2A - PARTIAL ROOF SECOND FLOOR DUCTWORK PLAN - AREA A
R2017 FFH CF - 18057_dlevanduski
1-M2A - PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN - AREA A
1-M2B - PARTIAL ROOF SECOND FLOOR DUCTWORK PLAN - AREA B
R2017 FFH CF - 18057_dlevanduski
1-M2B - PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN - AREA B
1-M2C - PARTIAL ROOF SECOND FLOOR DUCTWORK PLAN - AREA C
R2017 FFH CF - 18057_dlevanduski
1-M2C - PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN - AREA C
1-M2D - PARTIAL ROOF SECOND FLOOR DUCTWORK PLAN - AREA D
R2017 FFH CF - 18057_dlevanduski
1-M2D - PARTIAL ROOF / SECOND FLOOR DUCTWORK PLAN - AREA D
1-M3 - PARTIAL ROOF THIRD FLOOR DUCTWORK PLAN - AREA E
R2017 FFH CF - 18057_dlevanduski
1-M3 - PARTIAL ROOF / THIRD FLOOR DUCTWORK PLAN - AREA E