603-20-707 Combined Set Correct Pharmacy Physical Security Deficiencies RFI.pdf
PDF 9 MB Posted
- Attached to
- Project 603-20-707, Correct Pharmacy Physical Security Federal contract opportunity
- Solicitation number
- 36C24922R0019
About this file
This federal contract opportunity notice seeks proposals for hospital construction services to correct pharmacy physical security deficiencies at the Robley Rex VA Medical Center. The requirement includes specifications and drawings for Project 603-20-707. This is a 100% set-aside for Service Disabled Veteran Owned Business in accordance with U.S.C. 38 section 8127(d). The procurement will use Lowest Price Technically Acceptable source selection pursuant to FAR Part 15. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is the contracting agency. Response and award dates are not provided.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Q-A-Amendment_02-36C24922R0019.pdf | ||
| 36C24922R0019_0002-AddDrawing_Q A_responses.pdf | ||
| S04-SiteVisit_Sign-In_Sheet (603-20-707).pdf | ||
| 36C24922R0019_0001_FixCSinfo.pdf | ||
| S02-603-20-707 Specifications Set.pdf | ||
| S02-Price Schedule Project 603-20-707.xlsx | XLSX spreadsheet | |
| P07-Wage Determination (KY20210093 03.05.2021).pdf | ||
| RFIs Questions_Answers from Sol 36C24921B0016.zip | ZIP file | |
| S02-603-20-707-Drawings CombinedSet.pdf | ||
| S02-36C24922R0019 (Solicitation).pdf | ||
| S03-OPPORTUNITIES-DESCRIPTION (36C24922R0019).pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. SEE GENERAL PROJECT NOTES FOR NEW WORK FOR ADDITIONAL REQUIREMENTS FOR WORK WITHIN THE EXISTING FACILITY.
2. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL CAREFULLY EXAMINE EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE
ARCHITECT AND C.O.R.
3. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION.
4. MAINTAIN EXIT EGRESS PATHS TO EXISTING EXIT DOORS DURING CONSTRUCTION.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK AND THE ROUTES MUST BE RETURNED TO
THEIR ORIGINAL CONDITION AT THE END OF THE PROJECT.
6. MAINTAIN THE BUILDING IN A WEATHERTIGHT CONDITION AT ALL TIMES.
7. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED WITH THE C.O.R. TO MINIMIZE DISRUPTIONS OF NORMAL FUNCTIONS OF THE VA'S OCCUPIED AREAS.
8. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. 48 HOURS BEFORE THE SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES. NO WORK SHALL BE DONE WITHOUT THE WRITTEN APPROVAL OF THE C.O.R. THE C.O.R. RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE
PERMITTED AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED SPACES.
9. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO ADJACENT DEPARTMENTS OR AREAS THAT ARE IN OPERATION AND SERVED BY THEM. COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES WITH THE C.O.R. NO SHUT DOWN OF EXISTING SERVICES IS ALLOWED TO OCCUR UNTIL RECEIVING THE C.O.R.'S WRITTEN APPROVAL OF THE SHUT DOWN SCHEDULE. PROVIDE TEMPORARY SERVICES AND/OR UTILITIES DURING INTERRUPTIONS AS REQUIRED AND APPROVED BY
THE C.O.R.
10. THE GENERAL CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE VA'S OCCUPIED AREAS ADJACENT TO NEW CONSTRUCTION OR OCCUPIED AREAS WHERE VARIOUS SYSTEM CONNECTIONS OR EXTENSIONS ARE REQUIRED. IN THESE AREAS, THE GENERAL CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY LACK OF SUFFICIENT PROTECTION FROM THE WEATHER AND FROM THE RESULTS OF ALL CONSTRUCTION ACTIVITY INCLUDING BUT NOT LIMITED TO DUST AND
WATER.
11. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM THE C.O.R. BEFORE GRINDING, USING OPEN FLAMES, WELDING RODS AND TORCHES. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS TO PROHIBIT THE MIGRATION OF SMOKE AND OTHER PRODUCTS OF COMBUSTION INTO OCCUPIED AREAS OF THE EXISTING BUILDING AND FOR OBTAINING ALL REQUIRED PERMITS RELATED TO HOT WORK.
12. PROVIDE FIRE PROTECTION IN ACCORDANCE WITH THE REQUIREMENTS OF THE GOVERNING AUTHORITY.
13. IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO PATCH ALL SPRAY-ON FIRE PROTECTION AT REMOVALS, AT ANY EXISTING LOCATIONS WHICH ARE VOID OF PROTECTION WITHIN THE AREA OF WORK AND AT NEW CONSTRUCTION WHICH DISTURBS EXISTING FIRE PROTECTION. FIREPROOFING MUST BE CONTINUOUS AND UNOBSTRUCTED.
14. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE STRUCTURAL INTEGRITY OF ALL STRUCTURAL FRAMING MEMBERS AND SYSTEMS AT ALL TIMES.
15. ALL DEMOLISHED MATERIAL, EXCEPT MATERIAL THAT IS LISTED OR MARKED BY THE ARCHITECT OR THE C.O.R. FOR RETENTION, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND IT SHALL BE DISPOSED OF. NO DEBRIS RESULTING FROM WORK SHALL BE LEFT IN THE CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK. THE WEIGHT AND COST OF DISPOSAL FOR ALL CONTROLLED SUBSTANCES SUCH AS LEAD AND ASBESTOS SHALL BE TRACKED AND REPORTED. THE GENERAL CONTRACTOR SHALL NOT USE
THE VA TRASH COMPACTOR.
G E N E R A L N O T E S F O R E X I S T I N G F A C I L I T I E S :
16. REMOVAL OF A PARTICULAR ITEM IS TO INCLUDE ALL RELATED ITEMS, SUCH AS REMOVAL OF WALLS WOULD INCLUDE ASSOCIATED DOORS, HARDWARE, ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER TO DEMOLITION DRAWINGS FOR MORE INFORMATION. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES INCLUDING BUT NOT LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING.
17. WHERE CEILINGS ARE SHOWN TO BE REMOVED, ALL UNUSED SUSPENDED EQUIPMENT, WIRES, ANGLES, ETC. SHALL BE REMOVED. SEE DEMOLITION DRAWINGS FOR ADDITIONAL INFORMATION. EXISTING LIGHTS MAY BE MAINTAINED AS TEMPORARY CONSTRUCTION LIGHTING.
18. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS REQUIRED UNTIL PERMANENT SUPPORT IS PROVIDED
IN THE FINAL CONSTRUCTION.
19. ALL OPENINGS IN EXISTING WALLS, CEILINGS AND FLOORS, WHICH ARE THE RESULT OF REMOVALS AND OTHER NEW CONSTRUCTION ACTIVITY, SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
20. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED IN THE EXISTING STRUCTURE SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH. USE ONE FIRE STOPPING SYSTEM FOR ALL SUB-CONTRACTORS.
21. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
22. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES THAT IMPACT THE NEW WORK. DETERMINE THE SIZE AND LOCATION THE PENETRATIONS FROM THE EXISTING UTILITIES WITHIN THE NEW WORK. SEAL TIGHT TO ALL PENETRATIONS AND CAULK.
23. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE SAFE'D TO ACHIEVE THE PROPER FIRE RATING BY THE
END OF CONSTRUCTION OPERATIONS FOR EACH DAY.
24. NEW HOLES IN EXISTING ELEVATED FLOOR AND ROOF STRUCTURES FOR NEW WORK MUST BE COORDINATED WITH THE EXISTING STRUCTURE SO THAT
CRITICAL STRUCTURAL MEMBERS ARE NOT DAMAGED.
25. UNLESS OTHERWISE NOTED, THE GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING SALVAGED STOCK BEFORE ORDERING NEW MATERIAL.
1. ALL WORK SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES, RULES, ORDINANCES AND REGULATIONS INCLUDING THE AMERICAN DISABILITIES ACT (ADA), ARCHITECTURAL BARRIERS ACT(ABA), THE VA BARRIER FREE DESIGN GUIDELINES AND THE AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) GUIDELINES.
2. THE C.O.R. SHALL WORK WITH THE CONTRACTOR TO PROVIDE ACCESS TO TEMPORARY SERVICES REQUIRED TO PROVIDE THE WORK INDICATED. SEE SPECIFICATION SECTION 01 00 00
FOR ADDITIONAL REQUIREMENTS ON TEMPORARY ACCESS TO VA UTILITIES.
3. THE GENERAL CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE PROVISIONS OF THE SPECIFICATIONS, INCLUDING ALL GENERAL CONDITIONS, SUPPLEMENTARY GENERAL CONDITIONS, AND MATERIAL AND CONSTRUCTION PROVISIONS, WHICH APPLY TO MATERIALS OR CONSTRUCTION METHODS REQUIRED BY THIS PROJECT.
4. PRIOR TO BIDDING, THE GENERAL CONTRACTOR SHALL VISIT THE SITE, EXAMINE, AND ACCEPT ALL EXISTING CONDITIONS. DATES FOR SITE VISITS WILL BE POSTED IN THE CONTRACT DOCUMENTS AS POSTED ON THE FEDERAL BUSINESS OPPORTUNITIES WEBPAGE FOR THIS PROJECT. UNSCHEDULED VISITS WILL NOT BE ALLOWED.
5. DO NOT PAINT ANY CAULKING OR SEALANTS WHICH ARE SUBJECT TO MOVEMENT - CONTROL JOINTS SHALL BE CAULKED AFTER PAINT AND SPECIAL COATING APPLICATIONS. PROVIDE
CAULKING OR SEALANTS IN COLORS WHICH MATCH ADJACENT FINISHED SURFACE COLORS.
6. VERIFY ALL CONDITIONS AND DIMENSIONS IN THE FIELD BEFORE FABRICATING ANY MATERIALS.
7. IT IS THE INTENT OF THE DOCUMENTS TO INDICATE COMPLETE AND OPERATIONAL SYSTEMS (I.E. STRUCTURAL, HVAC, PLUMBING, ELECTRICAL) THE CONTRACTOR SHALL PROVIDE THE SYSTEMS AS OPERATIONAL SYSTEMS WHICH COMPLY WITH APPLICABLE CODES AND REGULATIONS. THIS NOTE SHALL BE LIMITED TO THE SYSTEMS AS INDICATED BY THE DOCUMENTS AND SHALL NOT INCLUDE CHANGES TO THE SYSTEMS WHICH ALTER INDICATED CAPACITIES, OPERATIONAL CHARACTERISTICS.
8. THE GENERAL CONTRACTOR SHALL VERIFY THE SIZES OF ALL EQUIPMENT OR FIXTURES TO BE INSTALLED IN THE BUILDING THROUGH THE SUBMITTAL PROCESS, AND SHALL MAKE SPECIAL PROVISIONS FOR INSTALLATION OF ANY EQUIPMENT WHICH IS TOO LARGE TO FIT THROUGH A FINISHED OPENING.
9. ALL CONTRACTORS SHALL BE RESPONSIBLE TO PATCH AND REPAIR ALL SURFACES WHERE EXISTING CONSTRUCTION IS REMOVED OR DISTURBED BY WORK UNDER THEIR CONTRACT.
10. ALL SUSPENDED ITEMS SUCH AS CEILINGS, DUCTS, PIPES, CONDUITS, SHALL BE SUSPENDED (ATTACHED) DIRECTLY TO STRUCTURE AND SHALL NOT BE ATTACHED OR ANCHORED TO
EXISTING PLASTER, ACOUSTIC TILE.
11. NEW PENETRATIONS SUCH AS DUCTS, CONDUITS, PIPING, ELECTRICAL OUTLETS, LIGHT SWITCHES, RECESSED DEVICES OR ITEMS, HOLES, VOIDS, CRACKS. IN MODIFIED AND NEW CORRIDOR WALLS, SMOKE PARTITIONS, AND FLOOR SLABS SHALL BE SEALED TO PREVENT PASSAGE OF ANY SMOKE, FLAME, GASES. AS INDICATED IN THE CONTRACT DOCUMENTS.
12. WHERE NEW CONSTRUCTION REQUIRES CORE DRILLING THROUGH EXISTING STRUCTURAL CONCRETE FLOOR SLABS, AND WALLS THE CONTRACTOR SHALL COORDINATE HIS DRILLING WORK TO AVOID DRILLING INTO A STRUCTURAL ELEMENT, INCLUDING JOISTS, BEAMS, COLUMN. ALSO SEE ELECTRICAL. DRAWINGS AND SPECIFICATIONS.
13. WHERE NEW CONSTRUCTION IS INDICATED TO BE INSTALLED IN EXISTING CONSTRUCTION, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS FOR PROPER FIT AND FOR ACCESS INTO THE
BUILDING PRIOR TO SHOP DRAWING SUBMITTAL, ORDERING AND DELIVERING TO THE SITE.
14. FOR INFECTION CONTROL REASONS, WORK CONDUCTED IN THE CORRIDOR THAT DOES NOT GENERATE DUST MAY ONLY REMOVE UP TO 16 SQUARE FEET OF CEILING TILE AT ONCE. AS LONG AS THIS STANDARD IS FOLLOWED NEGATIVE AIR AND BARRIERS ARE NOT REQUIRED BY THE INFECTION CONTROL NURSES. IF DUST IS GENERATED AND GREATER THAN 16 SF OF CEILING TILES ARE DISTURBED AT ONCE THEN THE WORK AREA SHALL BE SEALED OFF WITH 6 MIL FIRE RETARDANT POLYETHYLENE AND NEGATIVE AIR PROVIDED. MAINTAIN 5' MINIMUM ACCESS IN CORRIDORS AT ALL TIMES. CLEAN THOROUGHLY PRIOR TO COMPLETION OF A GIVEN WORK AREA BY HEPA VACUUM AND WET MOP. REFER TO SPECIFICATION 01 35 26 FOR
ADDITIONAL INFORMATION.
15. NO PARKING ON VA CAMPUS.
G E N E R A L N O T E S F O R N E W W O R K :
PROJECT EXTENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:1
P M
GI000
COVER SHEET
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTSROBLEY REX VA
MEDICAL
CENTER
DRAWING INDEX
SHEET NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI001 ABBREVIATIONS AND SYMBOLS
GI002 OVERALL FLOOR PLAN
GI003 ICRA CLASS III REQUIREMENTS
GI004 ICRA CLASS IV REQUIREMENTS
GI103 PHASING PLANS
ARCHITECTURAL
AD101 DEMOLITION FLOOR PLANS
AD141 DEMOLITION REFLECTED CEILING PLAN
AE101 FLOOR PLANS
AC141 REFLECTED CEILING PLAN
AE411 INTERIOR ELEVATIONS, SECTIONS AND DETAILS
AE601 DOOR SCHEDULE AND DETAILS
ELECTRICAL
EE001 LEGEND AND ABBREVIATIONS
EY100 BASEMENT ELECTRICAL PLAN
EY101 FIRST FLOOR ELECTRICAL PLAN
EE501 DETAILS
ROBLEY REX VAMC
CORRECT PHARMACY DEFICIENCIES
DEPARTMENT OF VETERANS AFFAIRS
800 ZORN AVE.
LOUISVILLE, KY 40206
603-20-707
REGIONAL VICINITY MAP VICINITY MAP
N N
SITE LOCATION MAP
N
No. Revisions: Date:
10'-0"
A101
SIM
A101
SIM
A101
SIM
A101
SIM
A B B R E V I A T I O N S
LEVEL NAME W/ ELEVATION
GRID HEAD
CALL OUT HEAD W/ SHEET NUMBER
ROOM NAME W/ ROOM NUMBER, AREA & OCCUPANCY
BUILDING SECTION NUMBER W/ SHEET NUMBER
WALL SECTION NUMBER W/ SHEET NUMBER
DOOR NUMBER
WALL TAG
KEYNOTE
REVISION TAG
CEILING TAG WITH HEIGHT
DETAIL SECTION NUMBER W/ SHEET NUMBER
NORTH ARROW
A.D.
A.C.T.
ACOUS.
A/C
A.C.P.
A.B.
AREA DRAIN
ACOUSTICAL CEILING TILE
ACOUSTIC
AIR CONDITIONING
ASPHALT CONCRETE
ANCHOR BOLT
PAVING
POUND OR NUMBER
PROPERTY LINE
FLOOR LINE
ANGLE
DIAMETER
CENTERLINE
AT
AND
BD.
APPROX.
ARCH.
ASPH.
ALT.
AL.
AGG.
BLDG.
BLK.
BLKG.
BM.
BRG.
BRK.
BOT.
BITUM.
CEM.
C.B.
CARP.
CAB.
B.U.R.
BTWN.
CLKG.
CLG.J.
CLG.
C.J.
CIR.
C.I.
CER.T.
CER.
BRZ.
COMB.
COL.
C.O.
CNTR.
CMU
CLS.
CLR.
C.W.
CTR.
CONV.O.
CONT.
CONST.
CONN.
CONC.
COMP.
DF.
D.F.
DIAG.
DIA.
DIM.
DISP.
DET.
DN.
D.O.
DR.
D.S.
D.T.
D.W.
DWR.
DIV.
CLO.
DOUGLAS FIR
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DIMENSION
DISPOSAL
DIVISION
DOWN
DOOR OPENING
DOOR
DOWN SPOUT
DRAIN TILE
DISHWASHER
DRAWER
DETAIL
COLD WATER
CENTER
CONVECTION OVEN
CONTINUOUS
CONSTRUCTION
CONNECTION
CONCRETE
COMPOSITION
BENCH MARK or BEAM
BOARD
BITUMINOUS
BUILDING
BLOCK
BLOCKING
APPROXIMATE
ARCHITECT
ASPHALT
CONCRETE MASONRY
COMBINATION
COLUMN
CLEAN OUT
COUNTER
CLOSURE
CLEAR
CLOSET
CAULKING
CEILING JOIST
UNIT
CEILING
BRICK
BEARING
CONSTRUCTION JOINT
CIRCLE
CAST IRON
CERAMIC TILE
CERAMIC
CEMENT
CATCH BASIN
CARPET
CABINET
BUILT-UP ROOFING
BETWEEN
BRONZE
BOTTOM
ALTERNATE
ALUMINUM
AGGREGATE
EA.
E.E.
E.F.
E.J.
ELEC.
ELEV.
E.N.
EXISTING
EACH
EACH END
EXHAUST FAN
EXPANSION JOINT
ELECTRICAL
ELEVATION
EDGE NAIL
(E)
ADJUSTABLEADJ.
LP
LC
LF
Ø
ABOVE FINISH FLOORAFF
CONTRACTOR FURNISH/
OWNER INSTALL
C.F.O.I.
C.F.C.I. CONTRACTOR FURNISH/
CONTRACTOR INSTALL
E.C. ELECTRICAL CONTRACTOR
C.HK. COAT HOOK
C.B.B. CEMENTITIOUS BACKER
BOARD
A.C.M. ASBESTOS CONTAINING
MATERIALS
CW. CURTAINWALL
DWG(S). DRAWING(S)
FACE OF BUILDINGF.O.B.
FIXTURE
FACE OF CONCRETE
FLOOR
FLOOR JOIST
FLOOR LINE
FLASHING
FACE NAIL
GAUGE
FOOTING
FUTURE
FACE OF STUD
FIRE RETARDANT
TREATED WOOD
FACE OF MASONRY
FACE OF FINISH
F.O.S.
F.R.T.W.
FTG.
FUT.
GA.
FIXT.
F.J.
F.L.
FLASH.
FLR.
F.N.
F.O.C.
F.O.F.
F.O.M.
BEAM
GLASS
GLUE LAMINATED
GALVANIZED IRON
GRATE ELEVATION
GRAB BAR
GARBAGE DISPOSAL
GRADE
HOSE BIB
SHEET METAL
GYPSUM BOARD
HANDICAPPED
GALVANIZED
GROUND
HC.
GYP.BD.
H.B.
G.B.
G.D.
G.S.M.
GR.
GND.
GLB.
GL.
G.I.
G.E.
HEIGHT
HOUR
HEATING
HIGH POINT
HORIZONTAL
HOLLOW METAL
HARDWARE
HARDWOOD
INTERIOR
INVERT
HOT WATER
INSULATION
INSIDE DIAMETER
& AIR CONDITIONING
HEATING, VENTILATION
H.W.
INV.
INT.
INSUL.
I.D.
HDWE.
HDWD.
H.V.A.C.
HTG.
HR.
H.P.
HORIZ.
H.M.
HGT.
HDR. HEADER
JOIST
JANITOR
KITCHEN
JOINT
LABORATORY
JOIST HANGER
LAG BOLT
LAVATORY
LAMINATE
J.H.
JAN.
L.B.
LAV.
LAM.
LAB.
KIT.
JT.
JST.
EQUIV.
E.S.
E.W.
EXP.
EXP.B.
EXPO.
EXT.
F.
ENCL.
F.B.
F.BD.
F.BELL
F.B.O.
F.D.
FDN.
F.E.
FH.M.S.
F.HORN
F.F.
F.G.
FGL.
F.H.
F.E.C.
F.A.
FH.W.S.
FIN.
F.H.S.
ENCLOSURE
EQUIVALENT
EACH SIDE
EACH WAY
EXPANSION
EXPANSION BOLT
EXPOSURE
EXTERIOR
FLAT HEAD MACHINE
SCREW
SCREW
FIRE HORN
FIRE HOSE STATION
FLAT HEAD WOOD
FINISH
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER
FINISH FLOOR
FINISH GRADE
FIBERGLASS
FIRE HYDRANT
CABINET
FIRE ALARM
FACE BRICK
FIREBOARD
FIRE BELL
FURNISHED BY OTHERS
FACE
GALV. GALVANIZED
HOLLOW STRUC. STL.H.S.S.
FLUORESCENTFLOUR.
GENERAL CONTRACTORG.C.
E.W.C. ELECTRIC WATER CLOSET
FIRE VALVE CABINETF.V.C.
FOOD SERVICE EQUIPMENT
CONTRACTOR
F.S.E.C.
H.V.A.C. CONTRACTORH.C.
FIRE SUPPRESSION
CONTRACTOR
F.S.C.
PLASTIC LAMINATEP.LAM.
O.H.W.S.
SCREW
OVAL HEAD WOOD
APPROVAL)
PAPER TOWEL DISPENSER
PAPER TOWEL
PARTITION
DOUGLAS FIR
PRESSURE TREATED
REFLECTED CEILING
RADIUS
RUBBER BASE
QUARRY TILE
POLYVINYL-CHLORIDE
RECEPTACLE
R.C.P.
Q.T.
RAD.
R.B.
P.T.D.
PTN.
P.T.R.
P.V.C.
P.T.D.F.
REDWOOD
REFERENCE
REINFORCING
ROOF HATCH
ROUND HEAD METAL
RESILIENT
REFRIGERATOR
ROOF DRAIN
SCREW
ROOM
RAIN WATER LEADER
ROUGH OPENING
ROUND HEAD WOOD
SCREW
RDWD.
R.H.W.S.
R.W.L.
R.O.
RM.
R.H.M.S.
R.H.
RESIL.
REINF.
REFR.
REF.
R.D.
LIGHT
MATERIAL
LOW POINT
LIVE LOAD
LEFT HAND
MAT.
LT.
L.P.
L.L.
L.H.
MANHOLE
MINIMUM
MEDIUM
MANUFACTURER
MEMBRANE
MECHANICAL
MEDICINE CABINET
MACHINE BOLT
METAL
MASONRY OPENING
METAL THRESHOLD
MISCELLANEOUS
MODULAR
MOISTURE RESISTANT
MIRROR
M.C.
M.B.
MIN.
MH.
MFG.
MEMB.
MED.
MECH.
MIR.
MISC.
M.O.
MOD.
M.R.
M.T.
MTL.
MAX. MAXIMUM
NORTH
NATURAL
OVER
NUMBER
NOMINAL
NOT TO SCALE
NOT IN CONTRACT
OBSCURE
OUTSIDE DIAMETER
STUD
OFFICE
OUTSIDE FACE OF
ON CENTER
OVERFLOW
OVERALL
N.T.S.
O/ O.A.
OBS.
O.C.
O.D.
O.F.
OFF.
O.F.S.
(NOT PART OF OSA
N.
NAT.
N.I.C.
NO.
NOM.
PAINT
PLATE
PERFORATED
FOOT
POUNDS PER CUBIC
PANEL EDGE NAILING
PRESSED METAL
PAIR
FRAME
FOOT
POUNDS PER LINEAR
PLYWOOD
POUNDS PER SQUARE
PROPERTY
PLASTER
P.
P.C.F.
P.E.N.
PERF.
PL.
PLAS.
P.L.F.
PLYWD.
P.M.F.
PR.
P.S.F.
PROP.
OPP. OPPOSITE
POINT
PULL STATION
POUNDS PER SQUARE
INCH
P.STA.
PT.
P.S.I.
FOOT
(N) NEW
PLAN
REQUIREDREQD.
NON-COMBUSTIBLENON/COM
PLUMBING CONTRACTORP.C.
MECHANICAL, ELECTRICAL,
PLUMBING
M.E.P.
FRAMED MIRRORMR.
ROBE HOOKR.HK.
MOP HOLDERMP.H.
MOUNTEDMTD.
PAINTEDPTD.
TONGUE AND GROOVE
DRAWINGS
SOUTH
SEE CIVIL DRAWINGS
STORM DRAIN
SOLID CORE WOOD DOOR
DRAWINGS
SHEET
SIMILAR
SLIDING
SHEATHING
SHOWER
SECTION
SEALANT
SEE ELECTRICAL
SOLID BLOCKING
SOAP DISPENSER
SEE ARCHITECTURAL
S.E.D.
SHR.
SHT.
SIM.
SL.
SHTG.
S.BLKG.
S.A.D.
S.
SECT.
SEAL.
S.DISP.
S.D.
S.C.D.
SCWD
SQUARE
DRAWINGS
SPECIFICATION
SOUNDPROOF
DRAWINGS
STATION
STEEL
STORAGE
STANDARD
SUSPENDED
STRUCTURAL
DRAWINGS
STAINLESS STEEL
SEE MECHANICAL
SANITARY SEWER
SEE STRUCTURAL
SQUARE FOOT (FEET)
THICK
TEMPERED
TELEPHONE
TERRAZZO
TACKBOARD
TOP OF CURB
TRANSOM
TOP OF PLATE
TOP OF WALL
TOILET PAPER DISPENSER
TOE NAIL
TOOL JOINT
TOP OF PAVEMENT
TOP AND BOTTOM
T.O.C.
T.O.P.
T.O.PL.
T.O.W.
T.P.D.
TRN.
S.M.D.
SPEC.
S.P.
SQ.
S.S.D.
S. STL.
STO.
STL.
STD.
STA.
S.S.
SQ. FT.
T.B.
T&B.
TEL.
TEMP.
TER.
T&G.
SUSP.
T.J.
T.N.
THK.
STRUC.
S.L.D. SEE LANDSCAPE
TYPICAL
UNLESS NOTED OTHERWISE
URINAL
UNFINISHED
TELEVISION
VENT TO ROOF
VERTICAL
VESTIBULE
VERIFY IN FIELD
VINYL TILE
VINYL COMPOSITION
TILE
VERTICAL GRAIN
WEST
WITH
WINDOW
WOOD
WATER CLOSET
VINYL WALL COVERING
WITHOUT
WEIGHT
YARD
WATER PROOF
WATER HEATER
WATER COOLER
WELDED WIRE FABRIC
WATER RESISTANT
W/O
W.W.F.
W.P.
W.R.
WT.
YD.
T.V.
TYP.
UNF.
U.N.O.
V.C.T.
VERT.
VEST.
V.G.
V.I.F.
UR.
V.W.C.
W.
W/
W.C.
V.T.R.
W.F.
W.H
WDW.
WD.
V.T.
T.S. TUBE STEEL
SELF ADHERED SHEET
MEMBRANE
S.A.S.M.
SELF ADHERED FLEXIBLE
FLASHING
S.A.F.F.
WITHINW/IN
UNDERSIDEU/S
SANITARY NAPKIN
DISPOSAL
S.N.D.
T.S.C.D. TOILET SEAT COVER
DISPENSER
SANITARY NAPKIN
DISPENSER
S.N.V.
TOP OF SEATT.O.S.
SOUND ATTENUATION
BATT
S.A.B.
Name
Elevation
Room name
150 SF
S Y M B O L S
V.A. FURNISHED / CONTRACTOR
INSTALLED
(VC)
V.A. FURNISHED AND INSTALLED(VV)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:1
P M
GI001
ABBREVIATIONS AND SYMBOLS
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTSROBLEY REX VA
MEDICAL
CENTER
BVA
ELEVATOR
3/4" MP
/4
M
P
/4
M
P /4
M
P
/4
M
P
/4
M
P
1-1/4" MP
3/4" MP
3/4" MP
NINA TURNER
CRAWFORD/LIVERS
ALEXANDER, 2 QA FOLKS
GARY SMITH
SMITH/GUDGEON
EAGLE/TACKETT
SHERRELL PAYNE
FERNANDO RIOS
ED GREGORY
CAROLYN LANHAMWALT CARPENTER TERE SCHOEMEHL
ANDERSON/MADDOX/ORR
6 STAFF
TOM WHALEN ET AL
MARYJANE CROWDER
RHONDA SMITH DON PFANNENSTIEL SVC OFFICERS
BROWN/HOLLAND
LARRY MARTIN
JOHN TALLEY
CRUZ/CROUCH
SHELLY HOUSE
TOM HAYDEN
THOMPSON/HEAD/TURPIN
JOHN KOENIG
MARCIA SMITH
SERVICE OFFICERS
RITA FLOWERS
MYRA SMITH
SANDY COOPER
UP DOWN
UP
UP
UP
UP
UP
FIRE
EQUIPMENT
CLOSET
A-021
F.A.C.
A-020
H.A.C.
H.V.A.C.
EQUIPMENT
ROOM
A-005c
A-012
CLOSET
ELECTRIC
A-001
A&MM
A-017a
REPRODUCTION
MAIL ROOM
D-002b
CLOSET
TELE.
D-002a
CLOSET
ELECT.
B-002d
BASEMENT
SUB-
M-001
M-002a
STORAGE
SPD
B-004
DUMBWAITER
MACHINE
ROOM
B-002g
B-002c
ROOM
SEWING
B-002b
STORAGE
EMS
B-002
ROOM
LINEN
A.C.
EQUIPMENT
ROOM
B-002f
B-002e
RESTROOM
B-001a
STORAGE
B-001
OFFICE
B-002a
ROOM
LOCKER
B-003
LINEN
SOILED
B-008
CLOSET
ELECTRIC
M-002
STORAGE
MECH RM/
B-005
SPD
M-003
ROOM
MECHANICAL
D-004
TREATMENT CENTER
CHIEF, PROSTHETIC
D-001
STORAGE
ORTHO
STAIRWELL
#8
D-002
MAIL ROOM
BREAK/
D-005a
OFFICE
LAB
D-010
CLASSROOM
D-005
P & O
D-010c
VESTIBULE
D-010d
RESTROOM
D-010b
#9
STAIRWELL
A-018
ROOM
DECONTAMINATION
A-031d
STORAGE
A-033b
CLOSET
NARCOTICS
H.V.A.C.
EQUIPMENT
ROOM
A-033a
INCOMING
INSPECTION
ROOM
A-027
A-033h
CLOSET
ELECTRIC
A-033e
AREA
WORK
A-034
ROOM
BREAK
S-5
S-5
P-4
A-022
LOBBY
ELEVATOR
A-022a
CLOSET
ELECTRIC
A-033f
OFFICE
A-033g
OFFICE
A-024
ROOM
EQUIPMENT
A-025
STORAGE
SAFETY
P-3
P-2
P-1
A-033
PHARMACY
IN-PATIENT
A-032
LINEN
SOILED
A-026
STORAGE
A-028
BREAK ROOM
PHARMACY
A-031e
STORAGE
A-029
#6
STAIRWELL
F.A.C.
A-029a
BASEMENT
SUB-
A-030
ROOM
EQUIP.
A-031c
A-031
VENDING STORAGE
CANTEEN
A-031b
STORAGE
A-031a
STORAGE
B-016c1
ROOM
LOCKER
B-016c
LOUNGE
B-018
ADMIN
A&MM
B-019a
CLOSET
TELEPHONE
B-006a
BASEMENT
SUB-
B-039a
OFFICE
SPD
A-018a
STORAGE
B-042a
STORAGE
B-041
SHOWER
WOMEN'S
B-009
STORAGE
ENG
B-042
SHOWER
MEN'S
B-007
CLOSET
ELECTRIC
B-006
#3
STAIRWELL
B-010
ROOM
EQUIPMENT
BREAK
ROOM
B-040
HAZARDOUS
MATERIAL
STORAGE
B-039b
INSTRUMENT
PREPARATION
ROOM
B-039
TELEPHONE
EQUIPMENT
ROOM
B-019
B-005b
SPD
B-005c
OFFICE
P-7 P-8 P-9
F.A.C.
B-011b
STORAGE
ENGINEERING
A&MM
STORAGE
B-021
B-038
HOLDING
LIFT
B-037
MORGUE
B-020
RECOVERY
SILVER
B-036
ROOM
SPECIMEN
F.A.C.
B-022
SUPERVISER
MAINT. OPERATION
EMS
EQUIPMENT
STORAGE
B-017
B-015
STORAGE
ENGINEERING
B-013
EQUIPMENT
ELECTRICAL
B-016
SHOP/STORAGE
ENGINEERING
M-004
ROOM
GENERATOR
B-034
SECRETARY
EMS
B-036b
STORAGE
B-035
OFFICE
CHIEF, EMS
B-036a
RESTROOM
EMS
SIGNAGE
ROOM
B-023
EMS
OFFICE
B-024
B-025a
BASEMENT
SUB-
INTERIOR
DESIGNER'S
OFFICE
B-034a
EMS
SUPERVISOR'S
OFFICE
B-032
B-031
RESTROOM
WOMEN'S
B-033
ROOM
MULTIPURPOSE
MEN'S
LOCKER
ROOM
B-026
B-026a
RESTROOM
B-025
#5
STAIRWELL
B-026b
SHOWERS
B-027
ENGINEERING
BIOMEDICAL
WOMEN'S
LOCKER
ROOM
B-030
B-030a
SHOWERS
B-029
ENGINEERING
BIOMEDICAL
B-027a
STORAGE
BIOMED
P.M. & R.
FITNESS
ROOM
B-028
PATIENT
SERVICES
SECTION
D-003
M-005
ROOM
GENERATOR
B-016a
CLOSET
COMMUNICATIONS
PHARMACY DRUG
VAULT
CLOSET
ENG
A-017d
B-002a1
ARMORY
D-010a
STORAGE
CAGE
STORAGE
A-005
SOILED
LINEN
A-004
MEN'S
RESTROOM
A-003
WOMEN'S
RESTROOM
A-002
VOLUNTEER
ESCORT
A-006
VOLUNTER
SIGN IN
A-007
LOUNGE
A-008k PHARMACY
STORAGE
A-011
CAGE
A-011a
STAIRWELL #1
A-014
COMM
CLOSET
A-013
TELEPJONE
CLOSET
A-015
OFFICE
A-017c
ROOM
A-017b
STORAGE
A-008f
STORAGE
A-008l
SUB-BAS
A-010a
STAIRWELL #2
A-010
CHIEF
VOLUNTARY SERVICE
OFFICE
A-008g
VOLUNTARY
OFFICE
A-008h
VOLUNTARY
OFFICE
A-008i
OFFICE
A-008j
OFFICE
A-009
D-007
RECEPTION
D-008
ROOM
CAST
D-009
FITTING
EXAM
D-006
AREA
WALK
D-006a
FABRICATION
ORTHO
D-005b
SEWING ROOM
LEATHER &
D-006b
ROOM
WORK
P.M. & R.
FITNESS
ROOM
B-028
B-016d
OFFICE
BUILDING MGR
B-016e
LOCKSMITH
A-017e
STORAGE
ROOM
A-017
A-016f
HOLDING
A-016e
ROOM
BREAK
HVAC
EQUIP
A-016g
A-016c
STORAGE
A-016d
ASSISTANT
PROGRAM
A-016a
ROOM
RADIO
POLICE
OFFICE
A-016
A-016b
OFFICE
CHIEF POLICE
STERILE
SUPPLY
STORAGE
A-019b
A-023a
OFFICE
A-023
WAREHOUSE
A-019d
OFFICE
A-019c
AREA
BREAKDOWN
A-019
STORAGE
MATERIALS MANAGEMENT
A-019a
ROOM
EQUIPMENT
CART
WASH
A-018b
B-029a
OFFICE
BIOMED SUPVR
A-008b
OFFICE
A-008a
WAITINGA-008c
OFFICE
DAV
A-008e
ROOM
MULTI PURPOSE
B-005a
SPD
STERILIZERS
B-039c
SILVER
RECOVERY
A-005a
STORAGE
A-005b
#7
STAIRWELL
ELECTRIC
CLOSET
B-028a
OFFICE
B-028b
B-016b
ROOM
EQUIPMENT
STORAGE
A-011a
A-030a
COMPACTOR
TRASH
PROGRAM
ASSISTANT
OFFICE
A-008d
P-10
ELEVATOR
VOLUNTARY
SUITE
A-008
B-011
SHOP VESTIBULE
ENGINEERING
E-002
RECEPTION
A-033d
ROOM
CLEAN
A-033c1
ROOM
CHEMO
A-033c
ROOM
ANTE
B-011c
OFFICE
ENGINEERING
A-001a
ELECTRICAL
B-001
SUPERVISOR OFFICE
SUPPORT SERVICES
B-039a
OFFICE
SPD
B-011a
SHOP
A.C.
E-003
VESTIBULE
E-001
LOBBY
WEST ENTRANCE
E-005
GROUP THERAPY
E-004
STAIR
B-016d
STORAGE
ENGINEERING
E-007
MEN E-008
WOMEN
E-006
MECH
E-005a
STORAGE
B-011d
OFFICE
ENGINEERING
B-016d1
ELECTRICAL
LOADING DOCK
ENGINEERING
Basement Floor
JOAN NORMAN
DICKERSON
BARBARA HUFFINES
KELLY MONTGOMERY LINDA BRASHEARS
GLASS CANOPY ABOVE
OPAQUE CANOPY
ELEVATOR
SNACKFROZEN PEPSI
MICRO
WAVE
CHANGE
P E
P S
I
UP
B-122
ROOM
EXAM
F.A.C.
B-130
CLOSET
ELECTRIC
A-113b
SPECIALIST OFFICE
HEALTH SYSTEM
A-113a
OFFICE
PUBLIC AFFAIRS
A-104f
OFFICE
MED SVC
A-104e
OFFICE
MED SVC
A-104m
STORAGE
A-104l
STORAGE
A-120
CLOSET
TELEPHONE
A-111
OFFICE
COMPLIANCE OFFICER
ACTIVATION
OFFICE
A-112
A-104h
EXAM ROOM
OCCUPATIONAL HEALTH
A-104g
OFFICE
OCCUPATIONAL HEALTH
A-104i
OFFICE
OCCUPATIONAL HEALTH
DECEDENT
AFFAIRS
A-109
COMPLIANCE
OFFICE
A-110
A-104k
OFFICE
OCCUPATIONAL HEALTH
A-104j
MULTIPURPOSE ROOM
OCCUPATIONAL HEALTH
A-108
STORAGE
EEO
A-109a
CLOSET
A-113c
OFFICE
PATIENT ADVOCATE
A-114
CLOSET
ELECTRIC
A-118
#2
STAIRWELL
A-117a
STORAGE
A-117
ROOM
STORAGE
F.A.C.
A-126
CLOSET
ELECTRIC
A-102b
ROOM
MULTIPURPOSE
A-102
OPERATOR
TELEPHONE
A-104c
OFFICE
INFECTION CONTROL
A-104d
OFFICE
MED SVC
A-103
OFFICE
A-104
A-107
H.A.C.
A-102a
RESTROOM
A-101a
AREA
VENDING
A-154
CLOSET
ELECTRIC
A-131
LOUNGE
STAFF
A-130
CLOSET
COMM
H.V.A.C.
EQUIPMENT
ROOM
A-125
A-127
#1
STAIRWELL
F.A.C.
A-128
H.A.C. A-129
CLOSET
TELEPHONE
B-104c
CLOSET
TELEPHONE
B-104a
OFFICE
NEUROPSYCH
B-104b
OFFICE
PSYCH-TECH
B-102a
HOLDING ROOM
B-102
VA POLICE
B-103
VENDING
B-104
OFFICE
NEUROPSYCHOLOGY
B-106
CLOSET
COMPUTER
B-105
CLOSET
ELECTRIC
B-172
WAITING
EYE CLINIC
B-107
#8
STAIRWELL
D-102
CLOSET
TELE.
D-101
CLOSET
ELECTRIC
D-105
RESTROOM
STAFF
B-108
STORAGE
B-109
STORAGE
CYLINDER
D-125
RECEPTION
D-121
H.A.C.
D-129
STORAGE
D-128
UTILITY
SOILED
D-118
EXAM ROOM
SCI
B-121
ROOM
CONSULT
D-119
RESTROOM
PATIENT
D-117
LOUNGE
STAFF
D-116
#9
STAIRWELL
CONTROLLED
SUBSTANCE
AREA
A-156g
A-175e
OFFICE
CHIEF OF STAFF
A-175f
OFFICE
DIRECTOR'S
DIRECTOR'S
CONFERENCE
ROOM
A-160
A-175a
H.A.C.
A-157a
CLOSET
ELECTRIC
A-101
LOBBY
MAIN
A-175h
ROOM
MULTIPURPOSE
ASSOCIATE
DIRECTOR'S
OFFICE
A-175g
COMPLIANCE OFFICER
OFFICE
A-177 A-176
OFFICE
COMPLIANCE
A-175i
SPECIALIST
HEATH SYSTEM
A-156
PHARMACY
P-3
A-157
LOBBY
SERVICE ELEVATOR
S-5
S-6
P-4
P-2
P-1
A-159
RESTROOM
WOMEN'S
H.V.A.C.
EQUIPMENT
ROOM
A-156k
A-175
SUITE
DIRECTOR'S
A-175c
STORAGE
A-175b
ROOM
MULTIPURPOSE
AO TO
AD OF OPERATIONS
A-173
FACILITY PLANNER
OFFICE
A-174 A-171
OFFICE
NURSING
A-172
OFFICE
NURSING
A-170
ROOM
BREAK
F.A.C.
A-162
RESTROOM
MEN'S
A-161
#6
STAIRWELL
A-165
CLOSET
ELECTRIC
A-163
CLOSET
ELECTRIC
A-164
CONFERENCE ROOM
H.V.A.C.
EQUIPMENT
ROOM
A-167
A-169
OFFICE
NURSING
A-168
OFFICE
NURSING
A-166
OFFICE
NURSING
C-134
ROOM
BREAK
C-149
#5
STAIRWELL
C-139
ROOM
EXAM
C-137
ROOM
EXAM
C-138
ROOM
EXAM
C-135
ROOM
EXAM
C-136
ROOM
EXAM
C-114
RESTROOM
WOMEN'S
C-103
UTILITY
SOILED
C-126
ROOM
EXAM
C-125
ROOM
EXAM
C-123
STATION
NURSE'S
C-124
ROOM
CONSULT
B-137
ROOM
X-RAY
B-154
AREA
RECEPTION
B-155
CASHIER
AGENT
B-157
OFFICE
TRAVEL
B-149
ROOM
X-RAY
B-151
ROOM
DRESSING
A-156i
VAULT
FLAME
A-156h
VAULT
NARCOTICS
B-152
H.A.C. B-150
ROOM
DRESSING
B-148
ROOM
DRESSING
B-153
RESTROOM
B-138a
ROOM
BREAK
B-138
ROOM
BREAK/PROCESSING
B-126
TRIAGE
B-129
#3
STAIRWELL
C-155a
CLOSET
ELECTRIC
FEC
B-125
ROOM
CONSULT
B-124
ROOM
EXAM
P-7 P-8
C-100
ROOM
TREATMENT
B-135
ROOM
DRESSING
BIOMEDICAL
ENGINEERING
OFFICE
B-134
B-136
ROOM
DRESSING
P-9
C-130
RECEPTION
POD B
C-129
ROOM
CONSULT
C-128
TRIAGE
NURSE
C-127
ROOM
EXAM
B-141
ROOM
STERIS
B-143
EXAM
ENT
B-140
ROOM
EXAM
B-142
ROOM
STORAGE
B-147
EXAM
ENT
B-146
EXAM
ENT
B-144
EXAM
ENT
C-116
OFFICE
NURSE'S
B-139
ROOM
X-RAY
C-120
ROOM
EXAM
C-121
ROOM
EXAM
C-122
ROOM
CONSULT
C-131
RECEPTION
POD C
C-117
ROOM
CONSULT
C-118
ROOM
EXAM
C-119
ROOM
EXAM
B-145
EXAM
ENT
C-150
OFFICE
SURGERY ADPAC
FEC
C-132a
CLOSET
ELECTRIC
C-132b
CLOSET
COMPUTER
C-115
OFFICE
ATTENDING
C-132c2
CLOSET
TELEPHONE
C-132
POD D
C-105
ROOM
EXAM
B-123
ROOM
EXAM
C-104
UTILITY
CLEAN
C-106
ROOM
EXAM
C-107
ROOM
EXAM
C-108
ROOM
EXAM
C-110
ROOM
EXAM
C-109
ROOM
EXAM
C-111
ROOM
EXAM
C-113
RESTROOM
MEN'S
C-112
ROOM
EXAM
C-140
#7
STAIRWELL
C-148
H.A.C.
C-146
STORAGE
CLERK
OFFICE
C-147
C-145
RESTROOM
MEN'S
C-144
RESTROOM
WOMEN'S
FEC
C-143
ROOM
EXAM
C-141
ROOM
PROCEDURE
C-142
ROOM
MULTIPURPOSE
OFFICE
A-104a
A-126a
CLOSET
COMM.
VIS
COORDINATOR
OFFICE
A-116
A-113
SUITE
PATIENT ADVOCATE
A-104b
OFFICE
INFECTION CONTROL
A-158
AREA
PHARMACY CONSULT
A-156c
OFFICE
A-156d
OFFICE
A-156b
OFFICE A-156f
OFFICE
A-156e
OFFICE
A-156j
BREAK AREA
A-156i
OPTIFILL
PHARMACY
CHIEF'S OFFICE/
CONFERENCE
A-156a
RESTROOM
A-175f1
STORAGE
A-175f2
A-166A
RECEPTION
NURSING
B-154a
WAITING
C-154
WAITING
POD A/B
C-153
WAITING
POD C
C-152
WAITING
POD C
C-151
WAITING
POD D/E
C-133
OFFICE
RN SUPERVISOR
C-132c
OFFICE
C-132c1
CLOSET
MECH
D-100
WAITING
MEN'S
RESTROOM
A-124
WOMEN'S
RESTROOM
A-121
NURSE
OFFICE
A-119
B-111
OPTICIAN
B-113e
STORAGE
B-113c
ROOM
EXAM
B-113d
ROOM
EXAM
B-113b
ROOM
LASER
B-113f
ROOM
EXAM
B-113h
FIELDS
VISUAL
B-113g
ROOM
EXAM
B-114
OFFICE
SURGERYB-112
OFFICE
TECHNICIANS
B-116
SHOP
COFFEE
B-115a
STORAGEB-113a
ROOM
WAITING
B-113s
H.A.C.
B-113i
ROOM
PROCEDURE
B-113q
RESTROOM
STAFF
B-115
ROOM
CAST
B-117
OFFICE
CLINIC
B-119
ROOM
EXAM
B-118
ROOM
EXAM
ATTENDING
OFFICE
B-113r
B-110
OFFICE
BROS
B-113k
ROOM
EXAM
B-113j
ROOM
EXAM
B-113l
ROOM
EXAM B-113p
RESTROOM
B-113m
ROOM
EXAM
B-113n
ROOM
EXAM
B-113o
OFFICE
RESIDENT
B-113t
OFFICE/RECEPTION
CLINIC
TRAINING ROOM
HR LINKS
JT USE COPIER
A-115
C-101
TRIAGE
NURSE
C-102
TRIAGE
NURSE
B-128
RESTROOM
C-115a
STORAGE
CLEAN
A-100
VESTIBULE
B-100
VESTIBULE
B-101
INFORMATION
PATIENT
B-113
SUITE
EYE CLINIC
A-131a
RESTROOM
STAFF
A-153k
BAY
ISOLATION
A-153i
OFFICE
STAFF
A-153j
RESTROOM
STAFF
A-153h
BAY
ISOLATION
A-153f
BAY
ER
A-153g
BAY
ER
A-153e
BAY
ER
A-155
H.A.C.
A-153d
BAY
ER
B-159
COORDINATORS
TRANSFER
BRINK, MONTGOMERY
B-156
CLERK
FEE
B-133
WORKER
SOCIAL
B-132
H.A.C.
MEN'S
RESTROOM
B-131
WOMEN'S
RESTROOM
C-155
A-153
NURSES' STATION
EMERGENT CARE
A-153c
RESTROOM
B-158
OFFICE
MEANS
B-171
UTILITY
SOILED
B-170
OFFICE
SUPERVISOR
B-165b
OFFICE
B-165a
ROOM
FILE
B-165
ADMISSIONS
B-166
ROOM
ADMISSIONS
B-167
ROOM
ADMISSIONS
B-168
ROOM
MEANS
B-169
ROOM
PHOTO ID
B-160
OFFICE
ELIGIBILITY
B-161
OFFICE
ELIGIBILITY
B-162
OFFICE
ELIGIBILITY
B-163
OFFICE
NURSING
A-139
WAITING
URGENT
B-164
WAITING
ER
A-140
TRIAGE
A-141
OFFICE
A-142
H.A.C. A-143
UTILITY
SOILED
A-153a
BAY
ER
A-153b
BAY
ER
A-153n
BAY
ER
A-153m
BAY
ER
A-153l
BAY
ER
A-144
UTILITY
CLEAN
A-149
EQUIPMENT
CLEAN
A-148
NURSES' STATION
URGENT CARE
A-147
RESTROOM
A-146
PHLEBOTOMY
A-145
WORKROOM
DOCTORS'
A-138
DECONTAMINATION
A-137
EQUIPMENT
DECONTAMINATION
A-135
ROOM
EXAM
A-136
ROOM
EXAM
A-134
ROOM
EXAM
A-133
ROOM
EXAM
SS1-1
SHELTER-FRONT
SMOKING
A-132
VESTIBULE
AMBULANCE
P-10
ELEVATOR
A-113d
OFFICE
PATIENT ADVOCATE
D-126
RESIDENTS
UofL
D-124
ROOM
EXAM
D-111
EXAM
POLY/MED
D-110
EXAM ROOM
POLY/MED
D-109
EXAM ROOM
POLYD-108
OFFICE
POLY
D-107
EXAM ROOM
POLY
D-106
OFFICE
POLY
D-103
OFFICE
D-104
OFFICE
POLY
D-115
ROOM
EXAM
D-114
OFFICE
SCI
D-113
EXAM ROOM
MED
D-112
EXAM ROOM
POLY/MED
D-131
ROOM
EXAM
D-130
ROOM
EXAM
D-120
ROOM
TA
D-122
ROOM
EXAM
D-127
ROOM
TREATMENT
D-132
ROOM
EXAM
EXAM
ROOM
D-123
B-120
OFFICE
CLINIC MGR
B-127
OFFICE
CLINIC COORDINATOR
ASSOC. DIRECTOR
PATIENT CARE SVCS
OFFICE
A-176a
AO TO
CHIEF OF STAFF
A-175d
E-002
RECEPTION
E-003
VESTIBULE
E-001
LOBBY
WEST ENTRANCE
E-005
GROUP THERAPY
E-004
STAIR
B-016d
STORAGE
ENGINEERING
E-007
MEN E-008
WOMEN
E-006
MECH
E-005a
STORAGE
B-016d1
ELECTRICAL
First Floor
AE101
AE101
AE101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:1
P M
GI002
OVERALL FLOOR PLAN
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTS
ROBLEY REX VA
MEDICAL
TYPICAL IDEAL
CONSTRUCTION LAYOUT
CLASS III
SCALE: 1/2"=1'-0"
A A
SUSPENDED PLASTIC ZIPPER WALL
CURTAIN BARRIER
POST ICRA, ILSM, FIRE INSPECTION SHEETS
VISIBLE TO PUBLIC
PROVIDE STICKY MATS (CHANGED END OF
SHIFT OR MORE IF NECESSARY TO MAINTAIN
CLEANLINESS)
INDICATOR MUST BE AT -0.01 OR GREATER (VERIFY DAILY).
IF NOT, VERIFY ALL OPENINGS, SUCH AS DOORS, ARE
CLOSED AND / OR CHANGE OUT NEGATIVE AIR PRE-FILTER
PROVIDE A 6'-0" x 4'-0" WALK OFF MAT
INSIDE OF WORK AREA (CHANGE
WHEN NECESSARY TO MAINTAIN
CLEANLINESS)
FIRE EXTINGUISHER ON PORTABLE
FLOOR BRACKET (ILSM MAY REQUIRE
MORE THAN ONE)
TAPE ALL SERVICES TO PROTECT
AGAINST CONTAMINATION
OPTIONAL EXHAUST DUCTS (COVER
THE GRATES AND THE DIFFUSERS)
SUPPLY DUCTS EITHER KEEP
RUNNING OR COVER WHEN
RUNNING TO KEEP DUST OUT
COVER ALL RETURNS AT THE
GRATE / DIFFUSERS
OUTSIDE OF BUILDING
E
A
O
V
MONTHLY CHANGED HEPA
FILTER
HEPA NEGATIVE AIR UNIT
WEEKLY CHANGED (OR
MORE AS NEEDED) PRE-
FILTER
FIRE RATED PLYWOOD (REFER TO
ELEVATION)
F
LE
X D
U C
T
CROSS-SECTION 'A-A'
SCALE: 1/2"=1'-0"
CLASS III
FINISHED FLOORING TO BE KEPT CLEAN. FLOORS
NOT BEING REPLACED TO BE PROTECTED OR
COVERED WITH ROSEN PAPER / FIRE RATED
PLYWOOD
EXISTING CEILING
EXISTING FIRE
SPRINKLER SYSTEM
EXISTING WALLEXISTING WALL
EXISTING CONCRETE SLAB FLOORING
HEATED DETECTOR CUT-OFF
HEPA NEGATIVE AIR UNIT
FIRE RATED PLYWOOD
(TEMP. REMOVE GLASS
PANEL)
EXISTING WINDOW FRAME
MOBILE CONTAINMENT CART
SCALE: 1/2"=1'-0"
(CONST. BARRIER TYPES)
EXISTING CONCRETE SLAB FLOORING
FLEX DUCT
HEPA NEGATIVE AIR UNIT
FLEX DUCT
PLASTIC WINDOW (ON
ALL SIDES
ZIPPER SIDE ENTRY
MOBILE CONTAINMENT CART WITH
CANVAS / 1-1/4" SQUARE STEEL
TUBULAR FRAME
SWIVEL CASTERS TWO WITH
LOCKING OUTTER BRAKES
A D
JU
S
T A
B
LE
H
E
IG
H T
A D
JU
S
T A
IG
H T
ROOM ELEVATION
POST ICRA, ILSM, FIRE
INSPECTION SHEETS VISIBLE
TO PUBLIC
SUSPENDED PLASTIC ZIPPER WALL
CURTAIN BARRIER
A P
P R
O X
A
.F .F
INDICATOR MUST BE AT -0.01 OR GREATER (VERIFY
DAILY), IF NOT VERIFY ALL OPENINGS, SUCH AS DOORS,
ARE CLOSED AND/OR CHANGE OUT NEGATIVE AIR PRE-
FILTER.
INDICATOR (REFER TO PLAN
& ELEVATION)
FRAMED PICTURE OF
C.O.R. WITH CONTACT
INFO
CONST. SUPERVISOR
NAME AND CELL
PHONE
CHILLER PLANT AFTER HOURS
CONTACT PHONE NUMBER FIRE
EMERGENCY DIAL 911
COMING SOON!!!
- DESCRIPTION OF NEWLY PROPOSED OCCUPANCY -
PERSONNEL ENTERING MUST HAVE: HARD HAT, SAFETY GLASSES
AND PROPER I.D.
THIS IS A
RESTRICTED AREA
AREA UNDER CONSTRUCTION
PAPER CADDY
ICRA, ILSM, FIRE WATCH,
MISC. FORMS
FRAMED COPY OF C.O.R.
CERTIFICATION
C L A
S S
I
II
1. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL
AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH
PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS IF INDICATED.
4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
6. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL
DEPARTMENT AND THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL SERVICES
DEPARTMENT.
1. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION.
2. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.
4. WET MOP AREA WITH DISINFECTANT.
5. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
PRIOR TO ANY CONSTRUCTION
POST CONSTRUCTION
7. PLACE A WALK-OFF MAT AND A STICKY MAT AT ENTRANCE AND EXIT WORK AREAS.
3. REMOVE AND DISCARD WALK-OFF MAT AND STICKY MAT AT ENTRY AND WORK AREAS.
8. PROVIDE INSPECTED/DATED FIRE EXTINGUISHER(S) IN THE WORK AREAS.
CLASS III WORK ITEMS NOTES:
GENERAL NOTES:
ALL PERSONNEL ENTERING THE CONSTRUCTION SITE AREA MUST WEAR A HARD HAT AND SAFETY GLASSES ALONG
WITH ANY OTHER PPE REQUIRED IN THAT AREA.
ALL APPLICABLE FORMS TO BE COMPLETED AND APPROVED PRIOR TO STARTING WORK.
PERMITS TO INCLUDE:
ICRA, ILSM, ABOVE CEILING, FIRE SPRINKLER SYSTEM, MEDICAL GASES, UTILITY SHUT-DOWN, FIRE / SMOKE
WALL, FIRE ALARM SYSTEM.
THE CONSTRUCTION AREA MUST MAINTAIN A NEGATIVE PRESSURE VENTILATION. NEGATIVE AIR UNIT TO BE MAINTAINED WITH FILTER(S) REPLACEMENT PER SPECIFICATIONS. (WEEKLY REPLACEMENT OF PRE-FILTER OR AS NECESSARY. HEPA FILTER REPLACED MONTHLY. CLEAN ALL EXTERIOR SURFACES OF CARTS AND TOOLS AT THE END OF EACH SHIFT.
MONITOR NEGATIVE PRESSURE AND POST LOG AT THE END OF EACH SHIFT.
CONSTRUCTION CLASS WILL BE DETERMINED BY THE CONSTRUCTION SAFETY COMMITTEE.
DURING CONSTRUCTION BE CERTAIN THAT:
• BARRIER ARE INTACT AND MAINTAINED.
• PARTICLE COUNT METER IS AVAILABLE.
• NEGATIVE INDICATOR IS AVAILABLE
• INSPECTED / DATED FIRE EXTINGUISHER(S) ARE AVAILABLE & MOUNTED PROPERLY.
• ICRA REQUIREMENTS ARE INTACT AND VERIFY THEY ARE BEING MAINTAINED.
• WALK-OFF MATS AND STICKY MATS ARE MAINTAINED PROPERLY.
LOW RISK
OFFICE AREAS
PATIENT RISK GROUPS
MEDIUM RISK HIGH RISK HIGHEST RISK
CARDIOLOGY CCU ANY AREA CARING FOR
ECHOCARDIOGRAPHY
ENDOSCOPY
NUCLEAR MEDICINE
PHYSICAL THERAPY
RADIOLOGY/MRI
RESPIRATORY THERAPY
EMERGENCY ROOM
LABOR & DELIVERY
LABORATORY (SPECIMEN)
NEWBORN NURSERY
OUTPATIENT SURGERY
PEDIATRICS
IMMUNOCOMPROMISED PATIENTS
BURN UNIT
CARDIAC CATH LAB
CENTRAL STERILE SUPPLY
INTENSIVE CARE UNITS
MEDICAL UNIT
PHARMACY
POST ANESTHESIA CARE UNIT
SURGICAL UNITS
NEGATIVE PRESSURE ISOLATION ROOMS
ONCOLOGY
OPERATING ROOMS INCLUDING
C-SECTION ROOMS
LOW RISK GROUP
CONSTRUCTION PROJECT TYPE
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
RISK RELATED GROUP TYPE A TYPE B TYPE C TYPE D
I II II III/IV
II
II III/IV
III/IV
III
III/IV
IV
IV
IV
I
I
II
CONSTRUCTION PROJECT BY PATIENT RISK
IC MATRIX - CLASS OF PRECAUTIONS:
INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK
NOTE:
LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.
WALL CONST. TYPES (DETAILS)
ON FLOOR PLAN.
ROOF METAL DECKING
2' x 4' SUSPENDED ACOUSTICAL CEILING AS
SCHEDULED ON FLOOR PLAN
3 5/8" INSULATED WALL WITH 16 GA. METAL
STUD AT 16" O.C. WITH 5/8" GYPSUM BOARD
EACH SIDE. WALL TO EXTEND TO ROOF
METAL DECKING
4 7/8"
4" RUBBER COVE TO MATCH EXISTING
AREA BASE @ BOTH SIDES
ATYPE BTYPE
C E
IL
IN
G H
E
IG
H T
W A
L L H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
C E
IL
IN
G H
E
IG
H T
W A
L L H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
3 5/8" INSULATED WALL WITH 16 GA. METAL
STUD AT 16" O.C. WITH 5/8" GYPSUM BOARD
EACH SIDE.
2' x 4' SUSPENDED ACOUSTICAL CEILING AS
SCHEDULED ON FLOOR PLAN
4 7/8"
4" RUBBER COVE TO MATCH EXISTING
AREA BASE @ BOTH SIDES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:1
P M
GI003
ICRA CLASS III REQUIREMENTS
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTSROBLEY REX VA
MEDICAL
CROSS-SECTION 'A-A'
SCALE: 1/2"=1'-0"
CLASS IV
FINISHED FLOORING TO BE KEPT CLEAN. FLOORS
NOT BEING REPLACED TO BE PROTECTED OR
COVERED WITH ROSEN PAPER / FIRE RATED
PLYWOOD
EXISTING CEILINGEXISTING FIRE
SPRINKLER SYSTEM
EXISTING WALLEXISTING WALL
EXISTING CONCRETE SLAB FLOORING
HEATED DETECTOR CUT-OFF
HEPA NEGATIVE AIR UNIT
FIRE RATED PLYWOOD
(TEMP. REMOVE GLASS
PANEL)
EXISTING WINDOW FRAME
TYPICAL IDEAL
CONSTRUCTION LAYOUT
CLASS IV
SCALE: 1/2"=1'-0"
A A
POST ICRA, ILSM, FIRE INSPECTION SHEETS
VISIBLE TO PUBLIC
INDICATOR MUST BE AT -0.01 OR GREATER (VERIFY DAILY).
IF NOT, VERIFY ALL OPENINGS, SUCH AS DOORS, ARE
CLOSED AND / OR CHANGE OUT NEGATIVE AIR PRE-FILTER
(TYPICAL REGULATOR INSTALLATION)
PROVIDE A 6'-0" x 4'-0" WALK OFF MAT
INSIDE THE TEMPORARY ANTE ROOM
(CHANGE WHEN NECESSARY TO
MAINTAIN CLEANLINESS)
ABC TYPE FIRE EXTINGUISHER ON
PORTABLE FLOOR BRACKET. ILSM MAY
REQUIRE MORE THAN ONE OR WALL
MOUNTED. NEED INSPECTION TAG AND
MONTHLY INSPECTION. INITIALS / DATED
TAPE ALL SERVICES TO PROTECT
AGAINST CONTAMINATION
OPTIONAL EXHAUST DUCTS (COVER
THE GRATES AND THE DIFFUSERS)
SUPPLY DUCTS EITHER KEEP
RUNNING OR COVER WHEN
RUNNING TO KEEP DUST OUT
COVER ALL RETURNS AT THE
GRATE / DIFFUSERS
OUTSIDE OF BUILDING
E
A
O
V
MONTHLY CHANGED HEPA
FILTER
HEPA NEGATIVE AIR UNIT
WEEKLY CHANGED (OR
MORE AS NEEDED) PRE-
FILTER
FIRE RATED PLYWOOD (REFER TO
ELEVATION)
F
LE
X D
U C
T
ATYPE
BTYPE
TEMPORARY ANTE ROOM
HARD BARRIER
BLUE CORE LOCKSET
(LOCKED AT ALL TIMES)
PROVIDE STICKY MATS (CHANGED END OF
SHIFT OR MORE IF NECESSARY TO MAINTAIN
CLEANLINESS)
ELEVATION
(REFER TO ELEV.
DETAIL)
ANTE ROOM
ELEVATION
POST ICRA, ILSM, FIRE INSPECTION
SHEETS VISIBLE TO PUBLIC
A P
P R
O X
A
.F .F
INDICATOR MUST BE AT -0.01 OR GREATER (VERIFY
DAILY), IF NOT VERIFY ALL OPENINGS, SUCH AS DOORS,
ARE CLOSED AND/OR CHANGE OUT NEGATIVE AIR PRE-
FILTER.
PAPER CADDY
ICRA, ILSM, FIRE WATCH,
MISC. FORMS
COMING SOON!!!
- DESCRIPTION OF NEWLY PROPOSED OCCUPANCY -
PERSONNEL ENTERING MUST HAVE: HARD HAT, SAFETY GLASSES
AND PROPER I.D.
THIS IS A
RESTRICTED AREA
AREA UNDER CONSTRUCTION
FRAMED PICTURE OF
C.O.R. WITH CONTACT
INFO
CONST. SUPERVISOR
NAME AND CELL
PHONE
CHILLER PLANT AFTER HOURS
CONTACT PHONE NUMBER FIRE
EMERGENCY DIAL 911
INDICATOR (REFER TO PLAN
& ELEVATION)
MOBILE CONTAINMENT CART
SCALE: 1/2"=1'-0"
(CONST. BARRIER TYPES)
EXISTING CONCRETE SLAB FLOORING
FLEX DUCT
HEPA NEGATIVE AIR UNIT
FLEX DUCT
PLASTIC WINDOW (ON
ALL SIDES
ZIPPER SIDE ENTRY
MOBILE CONTAINMENT CART WITH
CANVAS / 1-1/4" SQUARE STEEL
TUBULAR FRAME
SWIVEL CASTERS TWO WITH
LOCKING OUTTER BRAKES
A D
JU
S
T A
IG
H T
A D
JU
S
T A
IG
H T
C L A
S S
I V
1. ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL
AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH
PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS IF INDICATED.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM
7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL.
9. ROOM AND/OR SHALL BE THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL
SERVICES DEPARTMENT.
2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION.
5. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.
6. WET MOP AREA WITH DISINFECTANT.
SO THEY CAN BE VACUUMED USING HEPA VACUUM CLEANER BEFORE LEAVING WORK
SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH
TIME THEY LEAVE THE WORK SITE.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS.
SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA.
SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH
TIME THEY LEAVE THE WORK SITE.
3. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
7. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
4. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
PRIOR TO ANY CONSTRUCTION
POST CONSTRUCTION
1. OBTAIN APPROVAL BY MCOT TEAM TO REMOVE BARRIERS.
8. PLACE A WALK-OFF MAT AND A STICKY MAT AT ENTRANCE AND EXIT WORK AREAS.
8. REMOVE AND DISCARD WALK-OFF MAT AND STICKY MAT AT ENTRY AND WORK AREAS.
9. PROVIDE INSPECTED/DATED FIRE EXTINGUISHER(S) IN THE WORK AREAS.
CLASS IV WORK ITEMS NOTES:
GENERAL NOTES:
ALL PERSONNEL ENTERING THE CONSTRUCTION SITE AREA MUST WEAR A HARD HAT AND SAFETY GLASSES ALONG
WITH ANY OTHER PPE REQUIRED IN THAT AREA.
ALL APPLICABLE FORMS TO BE COMPLETED AND APPROVED PRIOR TO STARTING WORK.
PERMITS TO INCLUDE:
ICRA, ILSM, ABOVE CEILING, FIRE SPRINKLER SYSTEM, MEDICAL GASES, UTILITY SHUT-DOWN, FIRE / SMOKE
WALL, FIRE ALARM SYSTEM.
THE CONSTRUCTION AREA MUST MAINTAIN A NEGATIVE PRESSURE VENTILATION. NEGATIVE AIR UNIT TO BE MAINTAINED WITH FILTER(S) REPLACEMENT PER SPECIFICATIONS. (WEEKLY REPLACEMENT OF PRE-FILTER OR AS NECESSARY. HEPA FILTER REPLACED MONTHLY. CLEAN ALL EXTERIOR SURFACES OF CARTS AND TOOLS AT THE END OF EACH SHIFT.
MONITOR NEGATIVE PRESSURE AND POST LOG AT THE END OF EACH SHIFT.
CONSTRUCTION CLASS WILL BE DETERMINED BY THE CONSTRUCTION SAFETY COMMITTEE.
DURING CONSTRUCTION BE CERTAIN THAT:
• BARRIER ARE INTACT AND MAINTAINED.
• PARTICLE COUNT METER IS AVAILABLE.
• NEGATIVE INDICATOR IS AVAILABLE
• INSPECTED / DATED FIRE EXTINGUISHER(S) ARE AVAILABLE & MOUNTED PROPERLY.
• ICRA REQUIREMENTS ARE INTACT AND VERIFY THEY ARE BEING MAINTAINED.
• WALK-OFF MATS AND STICKY MATS ARE MAINTAINED PROPERLY.
LOW RISK GROUP
CONSTRUCTION PROJECT TYPE
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
RISK RELATED GROUP TYPE A TYPE B TYPE C TYPE D
I II II III/IV
II
II III/IV
III/IV
III
III/IV
IV
IV
IV
I
I
II
CONSTRUCTION PROJECT BY PATIENT RISK
IC MATRIX - CLASS OF PRECAUTIONS:
INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK
NOTE:
LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.
LOW RISK
OFFICE AREAS
PATIENT RISK GROUPS
MEDIUM RISK HIGH RISK HIGHEST RISK
CARDIOLOGY CCU ANY AREA CARING FOR
ECHOCARDIOGRAPHY
ENDOSCOPY
NUCLEAR MEDICINE
PHYSICAL THERAPY
RADIOLOGY/MRI
RESPIRATORY THERAPY
EMERGENCY ROOM
LABOR & DELIVERY
LABORATORY (SPECIMEN)
NEWBORN NURSERY
OUTPATIENT SURGERY
PEDIATRICS
IMMUNOCOMPROMISED PATIENTS
BURN UNIT
CARDIAC CATH LAB
CENTRAL STERILE SUPPLY
INTENSIVE CARE UNITS
MEDICAL UNIT
PHARMACY
POST ANESTHESIA CARE UNIT
SURGICAL UNITS
NEGATIVE PRESSURE ISOLATION ROOMS
ONCOLOGY
OPERATING ROOMS INCLUDING
C-SECTION ROOMS
WALL CONST. TYPES (DETAILS)
ON FLOOR PLAN.
ROOF METAL DECKING
2' x 4' SUSPENDED ACOUSTICAL CEILING AS
SCHEDULED ON FLOOR PLAN
3 5/8" INSULATED WALL WITH 16 GA. METAL
STUD AT 16" O.C. WITH 5/8" GYPSUM BOARD
EACH SIDE. WALL TO EXTEND TO ROOF
METAL DECKING
4 7/8"
4" RUBBER COVE TO MATCH EXISTING
AREA BASE @ BOTH SIDES
ATYPE BTYPE
C E
IL
IN
G H
E
IG
H T
W A
L L H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
C E
IL
IN
G H
E
IG
H T
W A
L L H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
3 5/8" INSULATED WALL WITH 16 GA. METAL
STUD AT 16" O.C. WITH 5/8" GYPSUM BOARD
EACH SIDE.
2' x 4' SUSPENDED ACOUSTICAL CEILING AS
SCHEDULED ON FLOOR PLAN
4 7/8"
4" RUBBER COVE TO MATCH EXISTING
AREA BASE @ BOTH SIDES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:1
P M
GI004
ICRA CLASS IV REQUIREMENTS
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTSROBLEY REX VA
MEDICAL
SOILED LINEN
A-004
MEN'S RESTROOM
A-003
SILVER RECOVERY
A-005a
STORAGE
A-005b
H.V.A.C. EQUIPMENT ROOM
A-005c
STORAGE
A-005d
PHARMACY DRUG VAULT
A-005e
PHASE I
CONTROLLED SUBSTANCE
AREA
A-156g
NARCOTICS VAULT
A-156h
OFFICE
A-156e
OFFICE
A-156f
BREAK AREA
A-156jPHARMACY
A-156
PHASE II
PHARMACY OPTIFILL
A-156d
SERVICE ELEVATOR LOBBY
A-157 PHARMACY CONSULT AREA
A-158
PHASE IB
PHASE IA
P H A S I N G N O T E S :
PHASE I: INCLUDES ALL WORK ASSOCIATED WITH ROOM A-005d, STORAGE, AND ROOM A-005e, PHARMACY DRUG VAULT. WORK IS PERMITTED TO COINCIDE WITH PHASE
IA AND/OR PHASE IB.
PHASE IA: INCLUDES SHEET METAL AND GYPSUM BOARD INSTALLATION AT SERVICE
ELEVATOR LOBBY, A-157. WORK IS PERMITTED TO COINCIDE WITH PHASE I.
PHASE IB: INCLUDES WINDOW INSTALLATION IN ROOM A-156d, PHARMACY OPTIFILL AND ALL WORK ASSOCIATED WITH ROOM A-156h. WORK IS PERMITTED TO COINCIDE WITH
PHASE I AND SHALL NOT START UNTIL THE COMPLETION OF PHASE IA.
PHASE II: INCLUDES ALL WORK ASSOCIATED WITH ROOM A-156g, CONTROLLED SUBSTANCE AREA, AND ROOM A-156h, NARCOTICS VAULT. AT THE BEGINNING OF
PHASE II, THE VA SHALL TEMPORARILY RELOCATE ALL NARCOTICS AND
SUPPLIES TO A-005e, PHARMACY DRUG VAULT. ALL REMAINING EQUIPMENT
SHALL BE TEMPORARILY RELOCATED BY THE VA UNTIL COMPLETION OF PHASE.
WORK MUST BE PRECEDED BY PHASE I, BUT MAY COINCIDE WITH PHASE IA AND
PHASE IB. ALL TEMPORARY WALLS SHALL COMPLY WITH ICRA LEVEL IV DURING
THIS PHASE - REFER TO SHEET "GI004 - ICRA CLASS IV REQUIREMENTS".
DAYGATE PANEL OF DOOR-04 SHALL BE THE LAST ITEM INSTALLED IN THIS
PHASE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:2
P M
GI103
PHASING PLANS
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTS
ROBLEY REX VA
MEDICAL
CENTER
1/4" = 1'-0"
ENLARGED BASEMENT FLOOR PLAN
1/4" = 1'-0"
ENLARGED FIRST FLOOR PLAN - CONTROLLED SUBSTANCE
1/4" = 1'-0"
ENLARGED FIRST FLOOR PLAN - PHARMACY OPTIFILL
KEYPLAN - 1ST FLOOR
KEYPLAN - BASEMENT
SOILED LINEN
A-004
MEN'S RESTROOM
A-003
SILVER RECOVERY
A-005a
STORAGE
A-005b
H.V.A.C. EQUIPMENT ROOM
A-005c
STORAGE
A-005d
PHARMACY DRUG VAULT
A-005e
HOLD
1' - 6" 4' - 0" 25
CONTROLLED SUBSTANCE
AREA
A-156g
NARCOTICS VAULT
A-156h
OFFICE
A-156e
OFFICE
A-156f
BREAK AREA
A-156j
PHARMACY
A-156
FLAME VAULT
A-156i
/2
/2
HOLD
6"
TEMPORARY
ANTE ROOM
TEMPORARY
ANTE ROOM
/8
15 26
15 26
PHARMACY OPTIFILL
A-156d
SERVICE ELEVATOR LOBBY
A-157 PHARMACY CONSULT AREA
A-158
ELEV. 5
15 16
P H A S I N G N O T E S :
PHASE I: INCLUDES ALL WORK ASSOCIATED WITH ROOM A-005d, STORAGE, AND ROOM A-005e, PHARMACY DRUG VAULT. WORK IS PERMITTED TO COINCIDE WITH PHASE
IA AND/OR PHASE IB.
PHASE IA: INCLUDES SHEET METAL AND GYPSUM BOARD INSTALLATION AT SERVICE
ELEVATOR LOBBY, A-157. WORK IS PERMITTED TO COINCIDE WITH PHASE I.
PHASE IB: INCLUDES WINDOW INSTALLATION IN ROOM A-156d, PHARMACY OPTIFILL AND ALL WORK ASSOCIATED WITH ROOM A-156h. WORK IS PERMITTED TO COINCIDE WITH
PHASE I AND SHALL NOT START UNTIL THE COMPLETION OF PHASE IA.
PHASE II: INCLUDES ALL WORK ASSOCIATED WITH ROOM A-156g, CONTROLLED SUBSTANCE AREA, AND ROOM A-156h, NARCOTICS VAULT. AT THE BEGINNING OF
PHASE II, THE VA SHALL TEMPORARILY RELOCATE ALL NARCOTICS AND
SUPPLIES TO A-005e, PHARMACY DRUG VAULT. ALL REMAINING EQUIPMENT
SHALL BE TEMPORARILY RELOCATED BY THE VA UNTIL COMPLETION OF PHASE.
WORK MUST BE PRECEDED BY PHASE I, BUT MAY COINCIDE WITH PHASE IA AND
PHASE IB. ALL TEMPORARY WALLS SHALL COMPLY WITH ICRA LEVEL IV DURING
THIS PHASE - REFER TO SHEET "GI004 - ICRA CLASS IV REQUIREMENTS".
DAYGATE PANEL OF DOOR-04 SHALL BE THE LAST ITEM INSTALLED IN THIS
PHASE.
G E N E R A L N O T E S :
A. ALL WORK SHALL BE DONE DURING NORMAL V.A. BUSINESS HOURS. CONTRACTOR SHALL
SCHEDULE ALL DISRUPTIVE WORK AFTER HOURS AT THE COR'S DISCRETION.
B. CONTRACTOR SHALL PROVIDE TEMPORARY SIGNAGE TO MAINTAIN PATH OF EGRESS.
C. ALL WORK AREAS SHALL COMPLY WITH ICRA LEVEL III UNLESS NOTED OTHERWISE. MAINTAIN
NEGATIVE AIR PRESSURE WITHIN WORK SITE. REFER TO SHEET "GI003 - ICRA CLASS III
REQUIREMENTS".
D. CONTRACTOR SHALL PROVIDE TEMPORARY LIGHTING AS REQUIRED TO PROVIDE FUNCTIONAL
LIGHTING LEVELS WITHIN AND OUTSIDE OF TEMPORARY WALL CONSTRUCTION.
E. CONTRACTOR SHALL VERIFY ALL MEASUREMENTS PRIOR TO CONSTRUCTION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021
C U s e rs
\d u n n t\ D o c u m e n ts \F
F E
L o u is v ill e C o rr e c t P h a rm a c y D e fi c ie n c ie s
C o m b in e d tj .d u n n
.r v t
/3
/2
:3
:5
P M
AD101
DEMOLITION FLOOR PLANS
Owner
08/02/2021 PQ TD
CORRECT PHARMACY
DEFICIENCIES
603-20-707
LOUISVILLE, KENTUCKY
BID DOCUMENTS
ROBLEY REX VA
MEDICAL
CENTER
1/4" = 1'-0"
ENLARGED BASEMENT DEMOLITION PLAN
1/4" = 1'-0"
ENLARGED FIRST FLOOR DEMOLITION PLAN - CONTROLLED SUBSTANCE
D R A W I N G N O T E S
1 REMOVE EXISTING CHAIN-LINK FENCE AND ALL ASSOCIATED SUPPORTS.
2 REMOVE EXISTING CHAIN-LINK GATE.
3 CONTRACTOR WILL MOVE AND STORE FULL HEIGHT CASEWORK DURING CONSTRUCTION. LOCATE
WITHIN SAME ROOM AS DIRECTED BY THE COR.
4 REMOVE PHARMACY WINDOW SHOWN AS DASHED.
5 EXISTING BULLET RESISTANT PHARMACY WINDOW TO REMAIN.
6 REMOVE EXISTING WINDOW, FRAME AND STEEL BARS - PREPARE OPENING FOR INFILL AT NEW
WORK - SEE NEW WORK DRAWINGS.
7 REMOVE EXISTING HOLLOW METAL DOOR AND FRAME SHOWN AS DASHED.
8 EXISTING CMU WALL TO REMAIN.
9 REMOVE CMU AT JAMB OF EXISTING OPENING TO ACCOMMODATE NEW VAULT DOOR SIZE - REUSE
EXISTING HEAD HEIGHT AND CONCRETE LINTEL.