D ep ar tm en t of V et er an s
A ff ai rs
NOTE:
COORDINATE WITH VA FACILITIES ADMINISTRATION
FOR SPECIFIC REQUIREMENTS FOR AREAS OF
MATERIALS STAGING INDICATED AS
FOR CONSTRUCTION WORKER PARKING AND
GENERAL PROJECT ACCESS / SECURITY, ETC.
MECHANICAL
B-68
MECHANICAL
B-120
MECHANICAL
B-129
MECHANICAL
ROOM
G-129
MECHANICAL
B-4A
D ep ar tm en t of V et er an s
A ff
NOTE: LEGEND IS UNABRIDGED. SOME SYMBOLOGY &
PIPING LINETYPES INDICATED MAY NOT BE
INCLUDED IN PROJECT.
PLUMBING LEGEND (UNABRIDGED)
FLOOR CLEANOUTFCO
CLEANOUT TO GRADECOTG
WATER METER
(PULSE ACCUMULATOR
OUTPUT TO BAS)
M
CONNECT TO EXISTING
AT INDICATED POINT
HUB DRAINHD
FLOOR SINKFS-1
FLOOR DRAINFD-1
ROOF DRAINRD
OVERFLOW DRAINOD
RD
OD
ROOF DRAIN ASSEMBLY
(SEE ARCH.)
BUTTERFLY VALVE
GATE VALVE
NON-SLAM CHECK VALVE
PLUG VALVE
CIRCUIT SETTING VALVE
GAS COCK
WATER HAMMER ARRESTOR
HOSE BIBB
HB
WALL HYDRANT
WH
ELBOW, TURNED DOWN
ELBOW, TURNED UP
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
CAP OR PLUG
PUMP
RISE OR DROP
CLEANOUTCO
A
UNION
CEILING ACCESS PANEL
PRESSURE REDUCING VALVE
BALL VALVE
UNIT MARK
SEE ABBREVIATIONS
XXX-#
THERMOMETER
PRESSURE GAUGE
BACKFLOW PREVENTER
ELECTRONIC TRAP PRIMER
ETP-2-#
FLOOR SINK, FLOOR DRAIN,
HUB DRAIN CONNECTION
IDENTIFIER
ETP MARK IDENTIFIER
# DRAIN CONNECTION
IDENTIFIER
NCC NITROGEN CONTROL CABINET
NG NATURAL GAS
NO NITROUS OXIDE
NPT NATIONAL PIPE THREAD
NPW NON-POTABLE WATER
NTS NOT TO SCALE
O OXYGEN
OD OVERFLOW DRAIN
OE ORAL EVACUATION
OEE ORAL EVACUATION EXHAUST
PA PROCESS AIR
PB PRESSURE BOOSTER
PD PRESSURE DROP
PDI PLUMBING DRAINAGE INSTITUTE
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PT PLASTER TRAP
PV PLUG VALVE
PWB PLUMBING WALL BOX
RD ROOF DRAIN
REF REFERENCE
REG REGULATING
RENO RENOVATE / RENOVATION
REQD REQUIRED
RM ROOM
RO REVERSE OSMOSIS
RP RECIRCULATION PUMP
RPBP REDUCED PRESSURE BACKFLOW PREVENTER
RPM ROTATIONS PER MINUTE
RW RAINWATER
S SINK
SAN SANITARY
SCW SOFT COLD WATER
SD STORM DRAIN
SDU SUPPLY AND DRAIN UNIT
SE SEWAGE EJECTOR
SEP SEPARATOR TANK
SFU SUPPLY FIXTURE UNITS
SH SHOWER
SHT SHEET
SP SUMP PUMP
SPEC SPECIFICATION
SQ SQUARE
SRW SECONDARY RAINWATER
SS SANITARY SEWER; STAINLESS STEEL
ST SEPARATOR TANK
STRUC STRUCTURAL
SYS SYSTEM
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
T&P TEMPERATURE AND PRESSURE
TW TEPID WATER
TYP TYPICAL
UR URINAL
V VENT
VP VACUUM PUMP
VTR VENT THRU ROOF
W WASTE
W/ WITH
WAGD WASTE ANESTHETIZING GAS DISPOSAL
WAGE WASTE ANESTHETIZING GAS EXHAUST
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT, WATER HEATER
WHA WATER HAMMER ARRESTOR
WM WATER METER
WS WASTE STACK
WST WATER SOFTENER TANK
ZVB MEDICAL GAS ZONE VALVE BOX
ELEV ELEVATION
EQMT EQUIPMENT
ESEW EMERGENCY SHOWER / EYEWASH
ES-TMV EMERGENCY SHOWER THERMOSTATIC MIXING VALVE
(PROVIDED WITH FIXTURE)
ET EXPANSION TANK
ETP ELECTRONIC TRAP PRIMER
EW EYEWASH
EWC ELECTRIC WATER COOLER
EX EXISTING
FA FROM ABOVE
FB FROM BELOW
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FFE FINISHED FLOOR ELEVATION
FIN FLR FINISHED FLOOR
FLR FLOOR
FM FORCE MAIN
FRP FUEL OIL
FS FLOOR SINK
FW FILTERED WATER
G GAS
GAL GALLON
GPM GALLONS PER MINUTE
GR GREASE WASTE
GTV GATE VALVE
GV GLOBE VALVE
GWH GAS WATER HEATER
HB HOSE BIBB
HC HANDICAP
HD HUB DRAIN
HP HORSEPOWER
HVAC HEATING / VENTILATING / AIR CONDITIONING
HWCP HOT WATER CIRCULATING PUMP
IAW IN ACCORDANCE WITH
IN INCHES
IN. WC INCHES OF WATER, GAUGE
INV INVERT
IE INVERT ELEVATION
IPC INTERNATIONAL PLUMBING CODE
JS JANITORS SINK
JSN JOINT SCHEDULE NUMBER
L LAVATORY
LA LAB AIR - DENTAL / MEDICAL
LAI LAB AIR INTAKE
LAV LAVATORY
LF LINEAR FEET
LP LIQUIFIED PETROLEUM GAS
LVL LEVEL
MA MEDICAL COMPRESSED AIR
MAI MEDICAL AIR INTAKE
MAP MEDICAL GAS MASTER ALARM PANEL
MAX MAXIMUM
MECH MECHANICAL
MED MEDICAL
MFR MANUFACTURER
MG MEDICAL GAS
MIN MINIMUM
MS MOP SINK
MTD MOUNTED
MV MEDICAL SURGICAL VACUUM
MVE MEDICAL VACUUM EXHAUST
MX MIXING VALVE
N NITROGEN
NC NORMALLY CLOSED
AAP MEDICAL GAS AREA ALARM PANEL
ABBRV ABBREVIATION
AC ABOVE CEILING, AIR COMPRESSOR
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ALT ALTERNATE
APR AIR PRESSURE REDUCING STATION
ARCH ARCHITECTURAL
AUTO AUTOMATIC
BAS BASE AUTOMATION SYSTEM
BCW BOOSTED COLD WATER
BF BELOW FLOOR
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BFP BACKFLOW PREVENTER
BHW BOOSTED HOT WATER
BLDG BUILDING
BLK BLOCK
BLV BALANCING VALVE
BSMT BASEMENT
BT BRINE TANK
BTUH BRITISH THERMAL UNITS PER HOUR
BV BALL VALVE
BWV BACKWATER VALVE
CA COMPRESSED AIR
CAI COMPRESSED AIR INTAKE
CAP CAPACITY
CD CONDENSATE WASTE
CFM CUBIC FEET PER MINUTE
CFH CUBIC FEET PER HOUR
CMU CONCRETE MASONRY UNIT
CO CLEANOUT, CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMM COMMUNICATIONS
COMP. COMPOSITE
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
COTG CLEANOUT TO GRADE
CU CUBIC; COPPER
CV CHECK VALVE
DA DENTAL COMPRESSED AIR
DAI DENTAL AIR INTAKE
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DDC DIRECT DIGITAL CONTROLS
DEMO DEMOLISH / DEMOLITION
DFU DRAIN FIXTURE UNITS
DI DEIONIZED WATER
DIA DIAMETER
DN DOWN
DS DOWNSPOUT
DSV DENTAL SURGICAL VACUUM
DSVE DENTAL SURGICAL VACUUM EXHAUST
DWG DRAWING
EA EACH
ECO EXTERIOR CLEANOUT
EE-TMV EMERGENCY EYEWASH THERMOSTATIC MIXING
VALVE (PROVIDED WITH FIXTURE)
ELEC ELECTRICAL
GENERAL NOTES AND REQUIREMENTS:
1. THE CONTRACTOR SHALL VISIT THE SITE TO OBSERVE THE EXISTING CONDITIONS PRIOR TO PLACING A BID. ALL QUESTIONS SHALL BE SUBMITTED TO THE VA FOR
RESPONSE PRIOR TO BIDDING THE WORK.
2. THIS PROJECT WILL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING WORK ITEMS: THE EXISTING WATER HEATING UNITS FOR THE FOUR LOCATIONS SHOWN WILL BE REMOVED AND REPLACED. REMOVAL OF THE NATURAL GAS SYSTEMS WILL INCLUDE THE EXISTING GAS LINES AND REGULATORS TO THE MINIMUM POINT REQUIRED FOR NEW INSTALLATION. NEW GAS REGULATORS WILL BE INSTALLED FOR EACH NEW HEATER. REMOVAL OF HOT PIPING WILL BE AS SHOWN ON THE DOCUMENTS AND WILL BE MODIFIED AS REQUIRED FOR THE NEW INSTALLATION. THE EXISTING WATER HEATERS, STORAGE TANKS, EXPANSION TANKS AND MASTER THERMOSTATIC MIXING VALVES SHALL BE REMOVED AND REPLACED, EXCEPT AS LISTED IN THE BID ALTERNATES.
BUILDING 120 AND 129 WILL REQUIRE MINIMUM DISRUPTION TO THE EXISTING HOT WATER SYSTEM. TEMPORARY WATER HEATING UNITS WILL BE INSTALLED AS DESCRIBED IN NOTE 3 BELOW. OUTAGES FOR BUILDING 120 AND 129 SHALL BE LIMITED TO NO MORE THAN 8 HOURS AND WILL BE COORDINATED AT LEAST 2 WEEKS
IN ADVANCE WITH THE OWNER.
NEW POINT OF USE THERMOSTATIC MIXING VALVES SHALL BE INSTALLED AT THE LAVATORIES IN BUILDING 120 AS SHOWN.
3. A TEMPORARY, PORTABLE WATER HEATING UNIT SHALL BE PROVIDED FOR USE DURING THE MODIFICATIONS OF THE WATER HEATING SYSTEMS IN BUILDINGS 120 AND 129. THE UNIT SHALL BE TRAILER MOUNTED FOR EASY TRANSPORT. ONE UNIT SHALL BE UTILIZED FOR BOTH FACILITIES WITH THE CONTRACTOR'S PHASING OF WORK ARRANGED SUCH THAT THE UNIT CAN BE MOVED FROM ONE BUILDING LOCATION TO THE OTHER. REFER TO THE ELECTRICAL DRAWINGS FOR POWER SOURCE FOR THE HEATERS. THE HEATERS SHALL BE PROVIDED WITH AN ONBOARD PROPANE GAS SOURCE AND ALL REQUIRED PUMPS, CONTROLS, AND CONNECTIONS AS REQUIRED FOR PROPER OPERATION OF THE SYSTEM. THE SYSTEM SHALL BE SIZED IN SINGLE OR MULTIPLE UNITS WITH A TOTAL GAS INPUT
CAPACITY OF 400,000 BTUH MINIMUM.
4. THE BASIS OF DESIGN FOR MAJOR EQUIPMENT PROVIDED IN THIS PROJECT INCLUDE THE FOLLOWING:
a. SEMI-INSTANTANEOUS WATER HEATERS: NORITZ MODEL NCC
b. MASTER THERMOSTATIC MIXING VALVES: LEONARD TYPE TM EXPOSED MIXING VALVE
c. POINT OF USE THERMOSTATIC MIXING VALVES: ZURN AQUA-GARD
d. STORAGE TANKS: PVI VERTICAL AQUAPLEX SERIES
THE BASIS OF DESIGN EQUIPMENT SERVES ONLY AS A REFERENCE FOR THE ITEMS USED DURING THE DESIGN PHASE AND IS NOT INTENDED TO BE THE SOLE SOURCE OF ACCEPTABLE EQUIPMENT. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS' RECOMMENDATIONS. WHERE THOSE RECOMMENDATIONS CONFLICT WITH THIS DESIGN, THE CONTRACTOR SHALL NOTIFY THE OWNERS' REPRESENTATIVE FOR DIRECTION PRIOR TO PROCEEDING WITH
THE WORK.
5. MOUNTING FRAMES FOR THE WATER HEATERS SHALL BE PROVIDED BY THE HEATER MANUFACTURER, DESIGNED SPECIFICALLY FOR THE HEATER MODEL SUPPLIED.
6. REFER TO THE SPECIFICATIONS FOR BID ALTERNATES.
7. ALL WORK SHALL BE THOROUGHLY COORDINATED WITH EXISTING CONDITIONS AND WITH OTHER TRADES. NEW WALL PENETRATIONS FOR TEMPORARY SERVICES WILL BE HELD TO A MINIMUM AND SHALL BE RETURNED TO “NEAR ORIGINAL” CONDITION WHEN TEMPORARY SERVICES ARE REMOVED.
8. THE EXISTING NATURAL GAS MAIN LINES WILL BE REUSED. NEW NATURAL GAS PRESSURE REGULATORS AND SHUTOFF VALVES WILL BE PROVIDED FOR EACH NEW WATER HEATER. WHERE LOCATED INDOORS, THE PRESSURE REGULATORS WILL BE DIRECT VENTED TO THE EXTERIOR.
9. ALL CONTROL WIRING WILL BE INSTALLED IN CONDUIT. THE MANUFACTURERS' RECOMMENDATIONS WILL BE FOLLOWED FOR CONTROL COMMUNICATIONS LINES
BETWEEN THE WATER HEATERS.
10. THE EXISTING HOT WATER RETURN PUMPS WILL BE REUSED. NEW PRIMARY AND BACKUP HOT WATER CIRCULATION PUMPS SHALL BE PROVIDED.
11. THE NATURAL GAS VENTS FROM THE INDOOR WATER HEATERS SHALL BE AS RECOMMENDED BY THE HEATER MANUFACTURER. THE VENTS SHALL BE INSTALLED IN ACCORDANCE WITH ALL CODES AND MANUFACTURERS' RECOMMENDATIONS. THE NEW VENTS SHALL FOLLOW THE ROUTING OF THE EXISTING VENTS THAT ARE REMOVED. NEW SLEEVES IN WALLS AND ROOFS SHALL BE INSTALLED IF NEW WALL OR ROOF OPENINGS ARE REQUIRED. WHERE PENETRATIONS THROUGH THE ROOF OR WALLS ARE NOT REUSED, THE CONTRACTOR SHALL REPAIR THE OPENINGS TO NEAR ORIGINAL CONDITION.
12. A TEMPORARY, SELF CONTAINED WATER HEATING SYSTEM SHALL BE PROVIDED FOR BUILDINGS 120 AND 129 TO PROVIDE DOMESTIC HOT WATER DURING CONSTRUCTION. 120 VOLT POWER WILL BE PROVIDED TO THE TEMPORARY LOCATIONS OF THE UNIT. DOWN TIME FOR THE CONNECTION OF THE TEMPORARY UNIT TO THE SERVICE PIPING SHALL BE COORDINATED WITH THE OWNERS REPRESENTATIVE. THE SAME UNIT SHALL BE USED FOR BOTH BUILDINGS AND DURING THEIR RESPECTIVE CONSTRUCTION PHASES. THE UNIT SHALL BE PROVIDED WITH AN ONBOARD PROPANE TANK ADEQUATELY SIZED FOR THE ANTICIPATED PROPANE USAGE DURING THE TIME OF CONSTRUCTION. THE UNIT IS ANTICIPATED TO BE TRAILER MOUNTED. THE TEMPORARY LOCATION SHALL BE SECURED DURING CONSTRUCTION WITH A LOCKED FENCE OR ENCLOSURE AS A PART OF THIS PROJECT. THE UNIT SHALL BE SIZED BASED ON THE HIGHER DEMAND OF BUILDING 120 AND 127. MAXIMUM DEMAND CAN BE ANTICIPATED FROM THE SIZE OF THE PERMANENT WATER HEATERS BEING INSTALLED BY THIS PROJECT. ALL REQUIRED TEMPORARY PIPING AND FITTINGS SHALL BE PROVIDED AND INSTALLED AS A PART OF THIS TASK.
PLUMBING ABBREVIATIONS (UNABRIDGED)
BALL VALVE
WALL HYDRANTW.H.
A WATER HAMMER ARRESTOR
COLD WATER PIPING
HOT WATER PIPING
HOT WATER RETURN PIPING
VENT PIPING
SS WASTE PIPING
EX. COLD WATER PIPING
EX. HOT WATER PIPING
EX. HOT WATER RETURN PIPING
EX. VENT PIPING
SS EX. WASTE PIPING
EX. TO BE REMOVED
END DEMOLITION AT THIS POINT
CONNECT TO EXISTING AT THIS POINT
DIELECTRIC UNION
DCA DENTAL COMPRESSED AIR
DLV DENTAL LOW VACUUM (ORAL EVACUATION)
CHECK VALVE
TEMPERATURE GAUGE
PRESSURE REDUCING VALVE
CIRCUIT SETTER
D ep ar tm en t of V et er an s
A ff
140° 140° 140°
G G
G G
G G
G G
G G
G G
G G
G
140°
140°140°
140°
0°
0°
HOT
RET
HOT
RET
HOT
RET
HOT
RET
VENT
vent
VENT
VENT
STORAGE TANKS
200 GAL EACH
TO/FROM
BLDG
DEMOLISH TO
THIS POINT
7.5 HP
0°
0°
0°
G G
0°
0°DEMOLISH TO
THIS POINT
DEMOLISH TO
THIS POINT
NEW THERMOSTATIC
MIXING VALVE TMV-3A
NEW EXPANSION
TANK ET-3A
(SEE DIAGRAM 3/PP-4003)
140° 140° 140° 140° 140°
EX. DHW
EX. DHW
EX. DCW
EX. DHWR
CONNECT TO
NEW TMV
140° 140°
G G
G G
G G
G G
G G
G G
0°
0°
0°
TO/FROM
BLDG
WH 3A-1
0°
0°
0°
G G
0°
NEW STRUCTURAL
SUPPORT FRAME
G G G 140°
0°
STORAGE TANK
(400 GAL.)
ALTERNATE No. 1:
NEW CANOPY
FRAME (ABOVE)
WH 3A-3 WH 3A-2
4" Ø
4" Ø
4" Ø
NEW GAS PIPE
TO MATCH
EXISTING GAS
SUPPLY PIPE
D ep ar tm en t of V et er an s
A ff
CENTRAL ALABAMA VETERANS HEALTHCARE SYSTEM
KEY PLAN
MECHANICAL
B-4A
4- H-
4- H-
4- H-
4- H-
0°
0°
0°
0°
140° 140° 140°
0°
G G G
VE
NT
DEMOLISH EX.
STORAGE TANK
DEMOLISH
EXISTING TMV
2 BFP'S (BELOW LANDING)
WITH BY-PASS BETWEEN
TO REMAIN
VE
NT
VE
NT
VE
NT
EXPANSION
TANK TO BE
REMOVED
HIGH
LOW
140°
MECHANICAL
B-4A
G G G G G G
G G
G G
45°
G G
REGULATOR
IN GROUND
DEMOLISH TO
THIS POINT
140°
140° 140°
G G
G G
G G
45°
0°
0°
G G G
140°
0°
NEW
4-ST-2
NEW
4-ST-1
NEW TMV-4A
NEW EXPANSION
TANK ET-4A
(SEE DIAGRAM 1/PP-4003)
140°
0°
0°
0°
0°
WH 4A-1 WH 4A-2
WH 4A-4 WH 4A-3
EXISTING PUMP
AND FITTINGS
TO REMAIN
4" Ø
4" Ø
4" Ø
4" Ø
NEW GAS PIPE
TO MATCH
EXISTING GAS
SUPPLY PIPE
D ep ar tm en t of V et er an s
A ff
B-68
BFP WITH
BY-PASS
M
ELEC WH
(119 GAL)
ELEC WH
(119 GAL)
EXPANSION
TANK
TMV
MECHANICAL
B-68
NO PLUMBING WORK IN THIS AREA.
PLANS FOR INFORMATION ONLY
D ep ar tm en t of V et er an s
A ff
B-120
120-ST-1
(225 GAL)
120-ST-2
(225 GAL) 120-WH-1
(1,600,000
BTUH)
120-WH-2
(1,600,000
BTUH)
VENT
VENT
TMV
BELOW (IN-LINE WITH PUMP)
VALVE V4
140° 140°
EXIST.
MECH
EXP TANK
0°
VALVE
EXPANSION
TANK
VENTS UP
COMBUSTION
AIR INTAKE
MECHANICAL
B-120
5"Ø STAINLESS STEEL CATEGORY III GAS VENT.
STRAP SUPPORTS, CONNECTORS, FITTINGS
AND RAIN CAP AS REQUIRED. INSTALL AS
RECOMMENDED BY THE MANUFACTURER.
PATHWAY TO MATCH EXISTING VENTS THAT
ARE REMOVED.
COMBUSTION
AIR INTAKE
NOTE: TMV'S TO BE ADDED AT EACH LAVATORY ON
THIRD AND FOURTH FLOORS.
120-HW-1-CP
120-HW-2-CP
TEMPORARY MOBILE
WATER HEATING SYSTEM.
SEE GENERAL NOTE 12,
SHEET PP-0001.
NEW EXPANSION
TANK ET-120
(SEE DIAGRAM 2/PP-4003)
140°
ST-120-1
ST-120-2
G G
G
G
G
WH 120-1
WH 120-2
WH 120-3
EXIST.
MECH
EXP TANK
4" Ø
4" Ø
NEW TMV-120
TEMPORARY CONNECTION
TEE FOR TEMPORARY
WATER HEATER (TYP)
NEW GAS PIPE
TO MATCH
EXISTING GAS
SUPPLY PIPE
D ep ar tm en t of V et er an s
A ff
POINT OF USE MIXING
VALVE LOCATIONS AS
NOTED BY
ALTERNATE No. 2:
THERMOSTATIC
MIXING VALVE AT
LAVATORY (TYP.)
D ep ar tm en t of V et er an s
A ff
0 6' 12' 24'
SCALE: 3/32"=1'-0"
ALTERNATE No. 2:
THERMOSTATIC
MIXING VALVE AT
LAVATORY (TYP.)
POINT OF USE MIXING
VALVE LOCATIONS AS
NOTED BY
D ep ar tm en t of V et er an s
A ff
0 6' 12' 24'
SCALE: 3/32"=1'-0"
B-129
MECHANICAL
B-129
0°
TWO WH STACKED
TMV
0°
TWO VENTS FOR
UPPER WH
TWO VENTS FOR
LOWER WH
140°
NATURAL GAS
REGULATOR
FOR LOWER WH (SEE ELEVATION)
FOR UPPER WH (SEE ELEVATION)
G
G
G
FOR LOWER WH
FOR UPPER WH
NATURAL GAS
REGULATORS
THRU WALL
ELEVATION
NOT TO SCALE
EXPANSION
TANK
G G
GG G
G
DEMOLISH TO
THIS POINT
DEMOLISH TO
THIS POINT
STORAGE TANK
MECHANICAL
ROOM
G-129
MECHANICAL
ROOM
G-129
140° WATER SUPPLY
FROM MECHANICAL
ROOM THRU TRENCH
0°
NEW
TMV-129
CONNECT TO EXISTING COLD
WATER SUPPLY IN TUNNEL
CONNECT TO EXISTING
HOT WATER SUPPLY TO
BLDG. IN TUNNEL
NEW STRUCTURAL
SUPPORT FRAME
MECHANICAL
B-129
MECHANICAL
B-129
G G
GG G
NEW EXPANSION
TANK ET-129
(SEE DIAGRAM 4/PP-4003)
NATURAL GAS
REGULATOR
EXTEND CW, HWR AND
140° HW PIPE THRU
TUNNEL TO NEW TMV-129
NEW STRUCTURAL
SUPPORT FRAME
140°140°
SS TYPE 3 GAS VENTS TYP FOR 3,
EXTEND 3' ABOVE ROOF
LOCATION OF TEMPORARY
PORTABLE WATER HEATER. ROUTE
TEMPORARY PIPING TO TEE'S IN HOT
WATER DISTRIBUTION SYSTEM.
SEEN GENERAL NOTE 12, SHEET
PP-0001.
WH 129-1 WH 129-2
WH 129-3
4" Ø
4" Ø
TEMPORARY CONNECTION
TEE FOR TEMPORARY
WATER HEATER (TYP)
CONNECT TO EXISTING
PIPING IN TUNNEL
NEW GAS PIPE
TO MATCH
EXISTING GAS
SUPPLY PIPE
MECHANICAL
ROOM
G-129
DEMO. EXIST.
VACUUM SYSTEM
CAP VACUUM PIPING
AS HIGH AS POSSIBLE.
CAP VACUUM PIPING
AS HIGH AS POSSIBLE.
D ep ar tm en t of V et er an s
A ff
DOMESTIC WATER HEATER & RECIRCULATING PUMP SCHEDULE
MARK
WH 3A-1,2,3 5
GPM DEMAND
@ 75°F
TEMP RISE
DESCRIPTION
199,900
MINIMUM
INPUT CAP.
BTUH
ELECTRICAL
CHARACTERISTICS
120 V / 1 PH / 60 Hz
WATER HEATER CIRCULATING PUMP
MARK PUMP TYPE
CENTRIFUGAL
IN-LINE
FLOW
GPM
HEAD
FEET OF
WATER
RPM
HP
1/3
ELECTRICAL
CHARACTERISTICS
120 V / 1 PH / 60 Hz
COMMENTSINLET/OUTLET CONN.
SIZES
2" x 2"
-GAS FIRED , SEMI-INSTANTANEOUS WATER
HEATER, EXTERIOR(EACH)
SYSTEM
7.5
MINIMUM
FLOW (GPM)
CP 3A-1 & 2
(EACH)
WH 4A-1,2,3,4 5 199,900 120 V / 1 PH / 60 Hz CENTRIFUGAL
IN-LINE
9 40 3700 1/3 120 V / 1 PH / 60 Hz2" x 2"
-GAS FIRED , SEMI-INSTANTANEOUS WATER
HEATER, EXTERIOR(EACH)
10.3 CP 4A-1 & 2
(EACH)
WH 120-1,2,3 5 199,900 120 V / 1 PH / 60 Hz CENTRIFUGAL
IN-LINE
9 40 3700 1/3 120 V / 1 PH / 60 Hz2" x 2"
-GAS FIRED , SEMI-INSTANTANEOUS WATER
HEATER, INTERIOR(EACH)
9.0 CP 120-1 & 2
(EACH)
WH 129-1,2,3 5 199,900 120 V / 1 PH / 60 Hz CENTRIFUGAL
IN-LINE
9 40 3700 1/3 120 V / 1 PH / 60 Hz2" x 2"
-GAS FIRED , SEMI-INSTANTANEOUS WATER
HEATER, INTERIOR(EACH)
7.1 CP 129-1 & 2
(EACH)
THERMOSTATIC MIXING VALVE SCHEDULE
MARK DESCRIPTION DESIGN FLOW
RATE (GPM)
LOW FLOW
RATE (GPM)
MAXIMUM PRESSURE
DROP (PSIG)
COLD WATER INLET
TEMPERATURE (°F)
OUTLET WATER
TEMPERATURE (°F)
TMV-3A HIGH/LOW FLOW TYPE THERMOSTATIC MIXING
VALVE, SURFACE MOUNTED
7.51 5 65 126 MAX
122 MIN
NOTES:
1. FURNISHED WITH HIGH AND LOW FLOW THERMOSTATIC MIXING REGULATORS, SURFACE MOUNTED. PROVIDE BALL VALVES, PRESSURE GAUGES, DIAL
THERMOMETER, AND OTHER ACCESSORIES REQUIRED FOR A COMPLETE OPERATING SYSTEM.
2. PROVIDE TEMPERATURE SENSOR LOCATED IN HWR LINE SET TO START PUMP WHEN HWR CIRCULATING TEMPERATURE DROPS BELOW 122 F. WATER HEATERS TO BE PROVIDED WITH HARDWARE INCLUDING COMMUNICATION BOARD AND TWO DEVICE ADAPTERS COMPATIBLE FOR CONNECTION TO THE BUILDING DDC SYSTEM.
3. COORDINATE OUTLET WATER TEMPERATURE WITH OWNER.
HOT WATER INLET
TEMPERATURE (°F)
TMV-4A HIGH/LOW FLOW TYPE THERMOSTATIC MIXING
VALVE, SURFACE MOUNTED
5 65 126 MAX
122 MIN
REMARKS
HOT WATER STORAGE TANK SCHEDULE
MARK ORIENTATIONVOLUME
(GAL) EACH
PIPE CONNECTIONS
MINIMUM
NUMBER
WATER
TEMPERATURE (°F)
ST 3A-1 VERTICAL400 4 140
REMARKS
SIZE
2"
ST 4A-1 & 2 VERTICAL200 4 1402"
ST 120-1 & 2 VERTICAL225 4 1402"
ST 129-1 & 2 VERTICAL200 4 1402"
EXPANSION TANK SCHEDULE
MARK DESCRIPTION MINIMUM
ACCEPTANCE
VOLUME (GAL)
MINIMUM
TANK SIZE
(GAL)
MINIMUM OPERATING
TEMPERATURE
MAXIMUM DESIGN
TEMPERATURE
MAXIMUM
OPERATING
PRESSURE (PSI)
ET-3A PRESSURIZED BLADDER, VERTICAL STAND 17.526 122 140 150
MINIMUM OPERATING
PRESSURE (PSI)
REMARKS
INTERIOR
ET-4A PRESSURIZED BLADDER, VERTICAL STAND 17.526 122 140 15025
ET-120 PRESSURIZED BLADDER, VERTICAL STAND 17.526 122 140 15025
ET-129 PRESSURIZED BLADDER, VERTICAL STAND 17.526 122 140 15025
10.31
TMV-120 HIGH/LOW FLOW TYPE THERMOSTATIC MIXING
VALVE, SURFACE MOUNTED
5 65 126 MAX
122 MIN
1409.01
TMV-129 HIGH/LOW FLOW TYPE THERMOSTATIC MIXING
VALVE, SURFACE MOUNTED
5 65 126 MAX
122 MIN
1407.11
INTERIOR
INTERIOR
INTERIOR
D ep ar tm en t of V et er an s
A ff
CONC. CAP
(ABOVE)
BRICK
WALL
CONC.
SLAB BASEPLATE
W/ 2 EXPANSION
ANCHOR BOLTS
WALL BRACKET
W/ 2 EXPANSION
ANCHOR BOLTS
(TYP.)±7
'-6
6" 6'-6"
PLATE OR DECKING
FOR WEATHER
COVER
BOTTOM OF
CONC. CAP
DIAGONAL
BRACE
(TYP.)
SECTION VIEW ELEVATION
SCALE: 3 4" = 1'-0" SCALE: 3 4" = 1'-0"
FRAME PIECE
(PERPENDICULAR
TO VIEW)
BUILDING 3A COURTYARD HEATER CANOPY & FRAMING DETAIL (ALTERNATE No. 1)1 SCALE: 3/4" = 1'-0"
BASEPLATE
(TYP.)
DECKING SUPPORT
PIECE
2'-0"
2'-6" MIN.
CONC. CAP
BRICK
WALL
3'- 6"
3'- 0"
DIAGONAL
BRACE
(SKEWED
IN VIEW)
PLAN VIEW
SCALE: 3 4" = 1'-0"
NEW HEATING
UNIT
HEATING UNIT
FRAME
HEATING
UNIT
FRAME
ALTERNATE No. 1:
A FREE STANDING CANOPY WILL BE PROVIDED AS
SHOWN TO PROTECT THE WATER HEATING UNITS
FROM THE WEATHER. CANOPY WILL BE CONSTRUCTED
TO THE DIMENSIONS SHOWN AND WILL BE
CONSTRUCTED OF UNISTRUT, BRACKETS, ANCHOR
BOLTS, AND WEATHER RESISTANT ROOF DECKING.
CANOPY SHALL BE SUPPORTED ON THE EXISTING
CONCRETE PAD AND SECURED WITH ANCHOR BOLTS.
COORDINATE ALL PIPING, CONDUIT & OTHER
APPURTENANCES.
EXTERIOR
FACE
1'- 0"
2'- 81 2"
1'- 0"
4'- 81 2"
5'- 4"
THERMOSTATIC
MIXING VALVE
HOT WATER
SUPPLY
CAP FOR
TEMPERATURE
ADJUSTMENT
COLD WATER
SUPPLY
TEMPERED WATER SUPPLY
TO LAVATORY FIXTURE
COLD WATER
SUPPLY
HOT WATER
SUPPLY
TEMPERED WATER SUPPLY
TO LAVATORY FIXTURE
ISOLATION BALL
VALVE (TYP.)
CONNECTION DIAGRAM (ALTERNATE No. 2)3 NOT TO SCALE
THERMOSTATIC MIXING VALVE
0°
G G G G
140° 140° 140° 140° 140° 140° 140° 140°
REMOTE CONTROLLER (PROVIDED BY
EQUIPMENT MANUFACTURER)
UNIT 1UNIT 2
UNIT 4 (WHERE
REQUIRED)
140° 140°
140°
COLD WATER SUPPLY
NATURAL GAS SUPPLY
NEW HOT WATER
STORAGE TANK(S)
140°
HOT WATER FIXTURES
TYPICAL HEATING UNIT CONNECTION DETAIL (MULTIPLE STORAGE TANKS SIMILAR)2 NOT TO SCALE
UNION
(TYP.)
PRESSURE RELIEF
VALVE (TYP.)
ISOLATION BALL
VALVE (TYP.)
CHECK VALVE
(TYP.)
BACK-UP HOT WATER
CIRCULATING PUMP
PRIMARY HOT WATER
CIRCULATING PUMP
NEW EXISTING
UNIT 3
RELIEF VALVE PIPED TO NEAREST FLOOR
DRAIN FOR INDOOR UNITS
EXISTING HOT WATER RETURN
PUMP AND BYPASS
HWS
NEW THERMOSTATIC
MIXING VALVE
EXPANSION
TANK
D ep ar tm en t of V et er an s
A ff
140°
0°
0°
0°
140°
0°
0°
HOT
WATER
RETURN
PUMP
200 GAL
STORAGE
TANK
200 GAL
STORAGE
TANK
OUTSIDE BLDG 4
TO
FIXTURES
FROM
FIXTURES
EXPANSION
TANK
ET-4A
HIGH-LOW CAPACITY
THERMOSTATIC
MIXING VALVE
NEW WATER HEATERS WH 4A-1,
WH 4A-2, WH 4A-3 & WH 4A-4
SEE DETAIL 2
SHEET PP4002
BLDG'S 2, 3, 4, 4A FLOW DIAGRAM1 NO SCALE
TEMPERATURE
SENSOR (TYP)
140°
0°
0°
0°
140°
0°
0°
HOT
WATER
RETURN
PUMP
225 GAL
STORAGE
TANK
225 GAL
STORAGE
TANK
TO
FIXTURES
FROM
FIXTURES
EXPANSION
TANK
ET-120
NEW WATER HEATERS WH 120-1,
WH 120-2 & WH 120-3
SEE DETAIL 2
SHEET PP4002
BLDG 120 FLOW DIAGRAM2 NO SCALE
HIGH-LOW CAPACITY
THERMOSTATIC
MIXING VALVE
TEMPERATURE
SENSOR (TYP)
140°
0°
0°
0°
HOT
WATER
RETURN
PUMP
400 GAL
STORAGE
TANK
OUTSIDE BLDG 3A
BASEMENT
140° 140°
140°
TO
FIXTURES
FROM
FIXTURES
EXPANSION
TANK
ET-3A
NEW WATER HEATERS WH 3A-1,
WH 3A-2 & WH 3A-3
SEE DETAIL 2
SHEET PP4002
BLDG'S 3A & 83 FLOW DIAGRAM3 NO SCALE
HIGH-LOW CAPACITY
THERMOSTATIC
MIXING VALVE
TEMPERATURE
SENSOR (TYP)
0°
0°
0°
140°140°
HOT
WATER
RETURN
PUMP
200 GAL
STORAGE
TANK
REMOTE
MECH BLDG
BLDG 129
140° 140°
140°
140° 140°140° 140°
EXPANSION
TANK
ET-129
TO
FIXTURES
FROM
FIXTURES
200 GAL
STORAGE
TANK
NEW WATER HEATERS WH 129-1,
WH 129-2 & WH 129-3
SEE DETAIL 2
SHEET PP4002
BLDG 129 FLOW DIAGRAM4 NO SCALE
HIGH-LOW CAPACITY
THERMOSTATIC
MIXING VALVE
TEMPERATURE
SENSOR (TYP)
D ep ar tm en t of V et er an s
A ff
| _17019 Tuskegee VA - 11 sheets 30x42.pdf |
| SSA-PLBG-Abbrv & Legend-PP-0001 |
| SSA-PLBG-Building3A-3A-PP-1001 |
| SSA-PLBG-Building4A-4A-PP-1001 |
| SSA-PLBG-Building68-68-PP-1001 |
| SSA-PLBG-Building120-1st mech rm-120-PP-1001 |
| SSA-PLBG-Building120-3rd fl-120-PP-1002 |
| SSA-PLBG-Building120-4th fl-120-PP-1003 |
| SSA-PLBG-Building129-129-PP-1001 |
| SSA-PLBG-Details-3 sheets-PP-4001 |
| SSA-PLBG-Details-3 sheets-PP-4002 |
| SSA-PLBG-Details-3 sheets-PP-4003 |
| Elec-Full-Size.pdf |
| E-0001 |
| 03A-EP-0001 |
| 04A-EP-0001 |
| 068-EP-0001 |
| 120-EP-0001 |
| 129-EP-0001 |