Text version
Doors Inventory
| Washington DC VA Medical Center - Washington, DC | ||||||||||||||||
| Door ID | Location | Floor | Building | Inspector | Inspection Date | Last Modified By | Last Modified On | Handed | Wall Rating | Door Material | Door Rating | Frame Material | Frame Rating | Status | General Observation Notes | Care & Maintenance Notes |
| 013001Z | Stairwell to Penthouse | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:00 AM | Joshua Keene | 11/11/2019 09:05 AM | RH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013002Z | Double Doors to Workroom | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:06 AM | Joshua Keene | 11/11/2019 09:13 AM | RH | 2 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013003Z | Double Doors to Workroom | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:10 AM | Joshua Keene | 11/11/2019 09:12 AM | LH | 2 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013004Z | Electrical Equipment Room | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:13 AM | Joshua Keene | 11/11/2019 09:16 AM | LH | 2 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013005Z | Elevator Equipment Room | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:16 AM | Joshua Keene | 11/11/2019 09:19 AM | LH | 2 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013006Z | Electrical Room | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:19 AM | Joshua Keene | 11/11/2019 09:23 AM | RH | 2 hour | Steel | 3 hour | Steel | Frame Label Missing | Fail | ||
| 013007Z | Elevator Equipment Room | Penthouse | VA Medical Center | Joshua Keene | 11/11/2019 09:23 AM | Joshua Keene | 11/11/2019 09:26 AM | LH | 2 hour | Steel | 45 minute | Steel | Frame Label Missing | Fail | ||
| 013008Z | Stairwell S-6 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:27 AM | Joshua Keene | 11/11/2019 09:30 AM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013009Z | Mech Shaft | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:32 AM | Joshua Keene | 11/11/2019 09:35 AM | RH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013010Z | Hematology Section | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:35 AM | Joshua Keene | 11/11/2019 09:39 AM | RH | 2 hour fire/smoke | Steel | 3 hour | Steel | 3 hour | Pass | ||
| 013011Z | Office 4D-116 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:39 AM | Joshua Keene | 11/11/2019 09:46 AM | RH | 2 hour fire/smoke | Steel | 3 hour | Steel | 3 hour | Fail | ||
| 013012Z | Cross Corridor Doors by 4D-208 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:51 AM | Joshua Keene | 11/11/2019 09:52 AM | RH | 2 hour fire/smoke | Steel | 3 hour | Steel | 3 hour | Fail | ||
| 013013Z | Cross Corridor Doors by 4D-207 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:46 AM | Joshua Keene | 11/11/2019 09:51 AM | RH | 2 hour fire/smoke | Steel | Door Label Missing | Steel | 3 hour | Fail | ||
| 013014Z | Housekeeping 4D-128B | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:53 AM | Joshua Keene | 11/11/2019 09:55 AM | RH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013015Z | Storage Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 09:55 AM | Joshua Keene | 11/11/2019 10:08 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013016Z | Stairwell 8 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:09 AM | Joshua Keene | 11/11/2019 10:14 AM | LH | 2 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013017Z | 4D-148B | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:15 AM | Joshua Keene | 11/15/2019 05:00 PM | LH | 1 hour | Wood | Could not open door to verify label | Steel | Could not open door to verify label | Fail | ||
| 013018Z | Stairwell 7 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:18 AM | Joshua Keene | 11/11/2019 10:23 AM | RH | 2 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013019Z | Cross Corridor Doors to 4C | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:23 AM | Joshua Keene | 11/11/2019 10:30 AM | RH | 2 hour fire/smoke | Wood | 90 minute | Steel | 3 hour | Fail | ||
| 013020Z | Cross Corridor Doors to 4C | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:29 AM | Joshua Keene | 11/11/2019 10:30 AM | RH | 2 hour fire/smoke | Wood | 90 minute | Steel | 3 hour | Fail | ||
| 013021Z | Cross Corridor Doors by Room 4C-212 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:30 AM | Joshua Keene | 11/11/2019 10:33 AM | LH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013022Z | Cross Corridor Doors by Room 4C-212 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:33 AM | Joshua Keene | 11/11/2019 10:34 AM | LH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013023Z | Family Lounge | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:34 AM | Joshua Keene | 11/11/2019 10:36 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013024Z | Cross Corridor Doors by Nurses Station | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:45 AM | Joshua Keene | 11/11/2019 10:50 AM | RH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013025Z | Cross Corridor Doors by Nurses Station | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:48 AM | Joshua Keene | 11/11/2019 10:49 AM | RH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013026Z | Soiled Utility | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:50 AM | Joshua Keene | 11/11/2019 10:52 AM | LH | 1 hour | Steel | 60 minute | Steel | 3 hour | Fail | ||
| 013027Z | Clean Utility | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:52 AM | Joshua Keene | 11/11/2019 10:55 AM | RH | 1 hour | Wood | 45 minute | Steel | 3 hour | Fail | ||
| 013028Z | Stairwell Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 10:55 AM | Joshua Keene | 11/11/2019 10:56 AM | LH | 2 hour | Steel | 3 hour | Steel | 3 hour | Fail | ||
| 013029Z | Mechanical Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:17 AM | Joshua Keene | 11/11/2019 11:19 AM | LH | 1 hour | Wood | 45 minute | Steel | 3 hour | Pass | ||
| 013030Z | Med Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:19 AM | Joshua Keene | 11/11/2019 11:22 AM | LH | 1 hour | Wood | 45 minute | Steel | Label present, rating illegible | Fail | ||
| 013031Z | Med Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:22 AM | Joshua Keene | 11/11/2019 11:24 AM | RH | 1 hour | Wood | 45 minute | Steel | Label present, rating illegible | Fail | ||
| 013032Z | Oxygen Storage Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:24 AM | Joshua Keene | 11/11/2019 11:26 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013033Z | Stairwell Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:35 AM | Joshua Keene | 11/11/2019 11:37 AM | RH | 2 hour | Steel | 3 hour | Steel | 3 hour | Fail | ||
| 013034Z | Equipment Storage | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:37 AM | Joshua Keene | 11/11/2019 11:40 AM | LH | 1 hour | Wood | 45 minute | Steel | Frame Label Missing | Fail | ||
| 013035Z | Cross Corridor Doors by Nurses Station | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:40 AM | Joshua Keene | 11/11/2019 11:43 AM | RH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013036Z | Cross Corridor Doors by Nurses Station | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:43 AM | Joshua Keene | 11/11/2019 11:44 AM | RH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013037Z | Family Lounge | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:44 AM | Joshua Keene | 11/11/2019 11:47 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013038Z | Cross Corridor Doors by Family Lounge | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:47 AM | Joshua Keene | 11/11/2019 11:49 AM | RH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013039Z | Cross Corridor Doors by Family Lounge | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:49 AM | Joshua Keene | 11/11/2019 11:50 AM | RH | 1 hour | Wood | 20 minute | Steel | 3 hour | Fail | ||
| 013040Z | Electrical Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:50 AM | Joshua Keene | 11/11/2019 11:52 AM | LH | 1 hour | Wood | 45 minute | Steel | 3 hour | Pass | ||
| 013041Z | Double Doors to Freedom Auditorium | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:52 AM | Joshua Keene | 11/11/2019 11:57 AM | LH | 1 hour | Wood | 20 minute | Steel | Label present, rating illegible | Fail | ||
| 013042Z | Double Doors to Freedom Auditorium | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:56 AM | Joshua Keene | 11/11/2019 11:57 AM | RH | 1 hour | Wood | 20 minute | Steel | Label present, rating illegible | Fail | ||
| 013043Z | Multi-Purpose Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:57 AM | Joshua Keene | 11/11/2019 11:59 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013044Z | Freedom Auditorium Side Exit Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 11:59 AM | Joshua Keene | 11/11/2019 12:01 PM | LH | 1 hour | Wood | 20 minute | Steel | Label present, rating illegible | Fail | ||
| 013045Z | Backstage Side Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 12:02 PM | Joshua Keene | 11/11/2019 12:04 PM | RH | 1 hour | Wood | 20 minute | Steel | Label present, no rating specified | Fail | ||
| 013046Z | Backstage Side Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 12:04 PM | Joshua Keene | 11/11/2019 12:06 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Label present, no rating specified | Fail | ||
| 013047Z | Freedom Auditorium Side Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 12:06 PM | Joshua Keene | 11/11/2019 12:08 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013048Z | Multi-Purpose Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:20 PM | Garrett Brozovich | 11/15/2019 04:16 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013049Z | Double Doors to Freedom Auditorium | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:22 PM | Joshua Keene | 11/11/2019 01:24 PM | RH | 1 hour | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013050Z | Double Doors to Freedom Auditorium | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:24 PM | Joshua Keene | 11/11/2019 01:26 PM | LH | 1 hour | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013051Z | Door by Freedom Auditorium Double Doors | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:26 PM | Joshua Keene | 11/11/2019 01:28 PM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013052Z | Double Doors to Conference Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:28 PM | Joshua Keene | 11/11/2019 01:31 PM | LH | 2 hour | Wood | 20 minute | Steel | Label present, rating illegible | Fail | ||
| 013053Z | Double Doors to Conference Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:31 PM | Joshua Keene | 11/11/2019 01:32 PM | LH | 2 hour | Wood | 20 minute | Steel | Label present, rating illegible | Fail | ||
| 013054Z | Housekeeping | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:32 PM | Joshua Keene | 11/11/2019 01:35 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013055Z | Respiratory Care Storage | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:40 PM | Joshua Keene | 11/11/2019 01:44 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013056Z | Clean Utility | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:38 PM | Joshua Keene | 11/11/2019 01:40 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013057Z | Respiratory Equipment Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:44 PM | Joshua Keene | 11/15/2019 04:57 PM | RH | 1 hour | Wood | Could not open door to verify label | Steel | Could not open door to verify label | Fail | ||
| 013058Z | Respiratory Equipment Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:46 PM | Joshua Keene | 11/11/2019 01:49 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013059Z | Housekeeping | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:49 PM | Joshua Keene | 11/11/2019 01:51 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013060Z | Cross Corridor Doors by Room 4B-200 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 01:58 PM | Joshua Keene | 11/11/2019 02:01 PM | LH | 1/2 hour smoke | Wood | 30 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013061Z | Cross Corridor Doors by Room 4B-200 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:01 PM | Joshua Keene | 11/11/2019 02:02 PM | RH | 1/2 hour smoke | Wood | 30 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013062Z | Dialysis Machine Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:02 PM | Joshua Keene | 11/11/2019 02:05 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013063Z | Soiled Utility | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:05 PM | Joshua Keene | 11/11/2019 02:06 PM | LH | 1 hour | Steel | Door Label Missing | Steel | 90 minute | Fail | ||
| 013064Z | Housekeeping | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:06 PM | Joshua Keene | 11/11/2019 02:08 PM | LH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013065Z | Stairwell 3 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:08 PM | Joshua Keene | 11/11/2019 02:10 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013066Z | Med Storage | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:10 PM | Joshua Keene | 11/11/2019 02:14 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013067Z | Dirty Utility | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:14 PM | Joshua Keene | 11/11/2019 02:16 PM | RH | 1 hour | Wood | 45 minute | Steel | 90 minute | Fail | ||
| 013068Z | Stairwell 2 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:16 PM | Joshua Keene | 11/11/2019 02:18 PM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013069Z | Clean Equipment Storage | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:18 PM | Joshua Keene | 11/11/2019 02:20 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013070Z | Storage Room | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:20 PM | Joshua Keene | 11/11/2019 02:22 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013071Z | Room 4B-117 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:22 PM | Joshua Keene | 11/11/2019 02:24 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013072Z | Housekeeping | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:24 PM | Joshua Keene | 11/11/2019 02:26 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013073Z | Soiled Utility | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:27 PM | Joshua Keene | 11/11/2019 02:28 PM | RH | 1 hour | Steel | Door Label Missing | Steel | 90 minute | Fail | ||
| 013074Z | Room 4B-110 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:28 PM | Joshua Keene | 11/11/2019 02:31 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013075Z | Cardiac Cath Storage | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:31 PM | Joshua Keene | 11/11/2019 02:34 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013076Z | Cross Corridor Doors by Room 4B-101A | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:34 PM | Joshua Keene | 11/11/2019 02:37 PM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | 90 minute | Fail | ||
| 013077Z | Cross Corridor Doors by Room 4B-101A | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:37 PM | Joshua Keene | 11/11/2019 02:38 PM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | 90 minute | Fail | ||
| 013078Z | Stairwell 1 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:38 PM | Joshua Keene | 11/11/2019 02:45 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013079Z | Cross Corridor Doors by Stairwell 1 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:45 PM | Joshua Keene | 11/11/2019 02:46 PM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Pass | ||
| 013080Z | Cross Corridor Doors by Stairwell 1 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:46 PM | Joshua Keene | 11/11/2019 02:46 PM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Fail | ||
| 013081Z | Soiled Linen | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:46 PM | Joshua Keene | 11/11/2019 02:49 PM | LH | 1 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013082Z | Supply Closet | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:49 PM | Joshua Keene | 11/11/2019 02:52 PM | RH | 1 hour | Steel | 60 minute | Steel | 90 minute | Fail | ||
| 013083Z | Stairwell 10 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:52 PM | Joshua Keene | 11/11/2019 02:54 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013084Z | Housekeeping | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:54 PM | Joshua Keene | 11/11/2019 02:56 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013085Z | Room 4E-139 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:56 PM | Joshua Keene | 11/11/2019 02:58 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013086Z | Stairwell 9 Door | 4 | VA Medical Center | Joshua Keene | 11/11/2019 02:58 PM | Joshua Keene | 11/11/2019 03:02 PM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013087Z | Clean Linen | 4 | VA Medical Center | Joshua Keene | 11/11/2019 03:02 PM | Joshua Keene | 11/11/2019 03:07 PM | RH | 1 hour | Steel | 60 minute | Steel | 90 minute | Fail | ||
| 013088Z | Mech Shaft | 4 | VA Medical Center | Joshua Keene | 11/11/2019 03:04 PM | Joshua Keene | 11/11/2019 03:06 PM | LH | 2 hour | Steel | Label present, rating illegible | Steel | Label present, rating illegible | Fail | ||
| 013089Z | Soiled Linen | 4 | VA Medical Center | Joshua Keene | 11/11/2019 03:07 PM | Joshua Keene | 11/11/2019 03:10 PM | LH | 1 hour | Steel | 60 minute | Steel | 90 minute | Fail | ||
| 013090Z | Cross Corridor Doors by Room 4E-100 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 03:10 PM | Joshua Keene | 11/11/2019 03:12 PM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013091Z | Cross Corridor Doors by Room 4E-100 | 4 | VA Medical Center | Joshua Keene | 11/11/2019 03:12 PM | Joshua Keene | 11/11/2019 03:13 PM | LH | 1/2 hour fire | Wood | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013092Z | Housekeeping | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:14 PM | Joshua Keene | 11/11/2019 03:17 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013093Z | Door to 3D West | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:18 PM | Joshua Keene | 11/11/2019 03:20 PM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013094Z | Storage Room | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:22 PM | Joshua Keene | 11/11/2019 03:24 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013096Z | Bio Hazard Room | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:24 PM | Joshua Keene | 11/11/2019 03:26 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013097Z | Room 3D-218 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:27 PM | Joshua Keene | 11/15/2019 05:01 PM | LH | 1 hour | Wood | Could not open door to verify label | Steel | Could not open door to verify label | Fail | ||
| 013098Z | Supply Room | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:28 PM | Joshua Keene | 11/11/2019 03:31 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013099Z | Room 3D-221 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:31 PM | Joshua Keene | 11/15/2019 04:58 PM | RH | 1 hour | Wood | Could not open door to verify label | Steel | Could not open door to verify label | Fail | ||
| 013100Z | Stairwell 8 Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:35 PM | Joshua Keene | 11/11/2019 03:37 PM | LH | 2 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013101Z | Supply Room | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:38 PM | Joshua Keene | 11/11/2019 03:40 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013102Z | Stairwell 7 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:40 PM | Joshua Keene | 11/11/2019 03:44 PM | RH | 2 hour | Steel | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013103Z | Soiled Utility | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:44 PM | Joshua Keene | 11/11/2019 03:46 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013104Z | Restroom | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:48 PM | Joshua Keene | 11/11/2019 03:50 PM | LH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013105Z | Door to 3D East | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:50 PM | Joshua Keene | 11/11/2019 03:52 PM | RH | 1/2 hour smoke | Wood | 90 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013106Z | Stairwell 6 Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:52 PM | Joshua Keene | 11/11/2019 03:54 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013107Z | Door to 3C South | 3 | VA Medical Center | Joshua Keene | 11/11/2019 03:55 PM | Joshua Keene | 11/11/2019 03:57 PM | LH | 2 hour fire/smoke | Wood | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013108Z | Housekeeping | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:02 PM | Joshua Keene | 11/11/2019 04:07 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013109Z | Stairwell 5 Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:07 PM | Joshua Keene | 11/11/2019 04:09 PM | LH | 2 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013110Z | Room 3A-134 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:09 PM | Joshua Keene | 11/11/2019 04:14 PM | LH | 2 hour fire/smoke | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013111Z | Storage Room | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:14 PM | Joshua Keene | 11/11/2019 04:18 PM | RH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013112Z | Stairwell 4 Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:18 PM | Joshua Keene | 11/11/2019 04:20 PM | RH | 2 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013113Z | Door to 3C-North | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:22 PM | Joshua Keene | 11/11/2019 04:24 PM | LH | 2 hour fire/smoke | Wood | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013114Z | Elevator Pit | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:25 PM | Joshua Keene | 11/11/2019 04:26 PM | LH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | 90 minute | Fail | ||
| 013115Z | Chapel Back Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:26 PM | Joshua Keene | 11/11/2019 04:31 PM | RH | 1 hour | Wood | Door Label Missing | Wood | Frame Label Missing | Fail | ||
| 013116Z | Double Doors to Chapel | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:31 PM | Joshua Keene | 11/11/2019 04:35 PM | RH | 1 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013117Z | Double Doors to Chapel | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:35 PM | Joshua Keene | 11/11/2019 04:37 PM | LH | 1 hour | Wood | 90 minute | Steel | Frame Label Missing | Pass | ||
| 013118Z | Double Doors to Chapel | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:37 PM | Joshua Keene | 11/11/2019 04:38 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013119Z | Double Doors to Chapel | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:38 PM | Joshua Keene | 11/11/2019 04:39 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013120Z | Door to 3B-East | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:39 PM | Joshua Keene | 11/11/2019 04:44 PM | RH | 2 hour fire/smoke | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013121Z | Neurology Clinic | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:45 PM | Joshua Keene | 11/11/2019 04:47 PM | LH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013122Z | Housekeeping | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:47 PM | Joshua Keene | 11/11/2019 04:49 PM | RH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013123Z | Room 3B-207 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:49 PM | Joshua Keene | 11/11/2019 04:52 PM | LH | 1 hour | Steel | Label present, rating illegible | Steel | Label present, rating illegible | Fail | ||
| 013124Z | Exam Room | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:52 PM | Joshua Keene | 11/11/2019 04:54 PM | LH | 1 hour | Steel | Label present, rating illegible | Steel | Label present, rating illegible | Fail | ||
| 013125Z | Room 3B-112 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:54 PM | Joshua Keene | 11/11/2019 04:57 PM | LH | 1 hour | Wood | 90 minute | Steel | 90 minute | Fail | ||
| 013126Z | Stairwell 3 Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:57 PM | Joshua Keene | 11/11/2019 04:59 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013127Z | Stairwell 2 Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 04:59 PM | Joshua Keene | 11/11/2019 05:02 PM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013128Z | Room 3B-118 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:02 PM | Joshua Keene | 11/11/2019 05:05 PM | RH | 1 hour | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013129Z | Housekeeping | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:05 PM | Joshua Keene | 11/11/2019 05:07 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013130Z | Room 3B-112 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:07 PM | Joshua Keene | 11/11/2019 05:09 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013131Z | Room 3B-108A | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:09 PM | Joshua Keene | 11/11/2019 05:11 PM | RH | 1 hour | Steel | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013132Z | Soiled Utility | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:11 PM | Joshua Keene | 11/11/2019 05:13 PM | LH | 1 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013133Z | Cross Corridor Doors by 3B-105 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:16 PM | Joshua Keene | 11/11/2019 05:18 PM | RH | 2 hour fire/smoke | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013134Z | Cross Corridor Doors by 3B-105 | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:13 PM | Joshua Keene | 11/11/2019 05:16 PM | LH | 2 hour fire/smoke | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013135Z | Office Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:21 PM | Joshua Keene | 11/11/2019 05:23 PM | LH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013136Z | Office Door | 3 | VA Medical Center | Joshua Keene | 11/11/2019 05:23 PM | Joshua Keene | 11/11/2019 05:24 PM | LH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013137Z | Stairwell 1 Door | 3 | VA Medical Center | Joshua Keene | 11/12/2019 08:46 AM | Joshua Keene | 11/12/2019 08:50 AM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013138Z | Cross Corridor Doors to 3E-North | 3 | VA Medical Center | Joshua Keene | 11/12/2019 08:50 AM | Joshua Keene | 11/12/2019 08:59 AM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013139Z | Cross Corridor Doors to 3E-North | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:00 AM | Joshua Keene | 11/12/2019 09:01 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013140Z | Equipment Storage Room | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:01 AM | Joshua Keene | 11/12/2019 09:03 AM | LH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013141Z | Soil Room | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:03 AM | Joshua Keene | 11/12/2019 09:06 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013142Z | Ward Equipment Room | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:06 AM | Joshua Keene | 11/12/2019 09:08 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013143Z | Room 3E-217 | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:08 AM | Joshua Keene | 11/12/2019 09:24 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013144Z | EMS Closet | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:25 AM | Joshua Keene | 11/12/2019 09:26 AM | LH | 1 hour | Steel | Door Label Missing | Steel | Label present, rating illegible | Fail | ||
| 013145Z | Stairwell 10 Door | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:27 AM | Joshua Keene | 11/12/2019 09:31 AM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013146Z | Stairwell 9 Door | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:31 AM | Joshua Keene | 11/12/2019 09:34 AM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013147Z | Storage Room | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:34 AM | Joshua Keene | 11/12/2019 09:37 AM | RH | 1 hour | Steel | Label present, rating illegible | Steel | Label present, no rating specified | Fail | ||
| 013148Z | Housekeeping | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:37 AM | Joshua Keene | 11/12/2019 09:38 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013149Z | Room 3E-116 | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:39 AM | Joshua Keene | 11/12/2019 09:41 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013150Z | Soil Room | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:41 AM | Joshua Keene | 11/12/2019 09:43 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013151Z | Cross Corridor Doors to 3E-South | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:45 AM | Joshua Keene | 11/12/2019 09:46 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013152Z | Cross Corridor Doors to 3E-South | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:43 AM | Joshua Keene | 11/12/2019 09:45 AM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013153Z | GI Check-In | 3 | VA Medical Center | Joshua Keene | 11/12/2019 09:46 AM | Joshua Keene | 11/12/2019 09:48 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013154Z | Restroom | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 09:49 AM | Joshua Keene | 11/12/2019 09:53 AM | RH | 1 hour | Wood | 20 minute | Steel | Frame Label Missing | Fail | ||
| 013155Z | Double Doors to 2D-West | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 09:53 AM | Joshua Keene | 11/12/2019 09:58 AM | LH | 2 hour fire/smoke | Aluminum | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013156Z | Double Doors to 2D-West | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 09:56 AM | Joshua Keene | 11/12/2019 09:58 AM | RH | 2 hour fire/smoke | Aluminum | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013157Z | Pipe Shaft | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 09:58 AM | Joshua Keene | 11/12/2019 10:01 AM | LH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013158Z | Ward Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:01 AM | Joshua Keene | 11/12/2019 10:03 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013159Z | Clean Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:03 AM | Joshua Keene | 11/12/2019 10:05 AM | RH | 1 hour | Wood | Door Label Missing | Steel | 90 minute | Fail | ||
| 013160Z | Soiled Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:05 AM | Joshua Keene | 11/12/2019 10:06 AM | LH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013161Z | Stairwell 8 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:06 AM | Joshua Keene | 11/12/2019 10:08 AM | LH | 2 hour | Wood | 90 minute | Steel | 90 minute | Fail | ||
| 013162Z | Stairwell 7 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:09 AM | Joshua Keene | 11/12/2019 10:12 AM | LH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013163Z | Soiled Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:12 AM | Joshua Keene | 11/12/2019 10:14 AM | RH | 1 hour | Steel | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013164Z | Clean Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:14 AM | Joshua Keene | 11/12/2019 10:16 AM | LH | 1 hour | Wood | Door Label Missing | Steel | 90 minute | Fail | ||
| 013165Z | Cross Corridor Doors to 2D-East | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:16 AM | Joshua Keene | 11/12/2019 10:18 AM | RH | 2 hour fire/smoke | Aluminum | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013166Z | Cross Corridor Doors to 2D-East | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:18 AM | Joshua Keene | 11/12/2019 10:19 AM | LH | 2 hour fire/smoke | Aluminum | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013167Z | Stairwell 6 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:19 AM | Joshua Keene | 11/12/2019 10:21 AM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013168Z | Room 2C-200A | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:21 AM | Joshua Keene | 11/12/2019 10:23 AM | LH | 1/2 hour smoke | Wood | 90 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013169Z | Door to 2C-South | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:23 AM | Joshua Keene | 11/12/2019 10:25 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013170Z | Housekeeping | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:25 AM | Joshua Keene | 11/12/2019 10:29 AM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013171Z | Stairwell 5 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:29 AM | Joshua Keene | 11/12/2019 10:30 AM | LH | 2 hour | Wood | 90 minute | Steel | Frame Label Missing | Fail | ||
| 013172Z | Housekeeping | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:30 AM | Joshua Keene | 11/12/2019 10:33 AM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013173Z | Stairwell 4 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:33 AM | Joshua Keene | 11/12/2019 10:35 AM | RH | 2 hour | Wood | 90 minute | Steel | 90 minute | Pass | ||
| 013174Z | Door to 2C-North | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:35 AM | Joshua Keene | 11/12/2019 10:38 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | 90 minute | Pass | ||
| 013175Z | Soiled Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:38 AM | Joshua Keene | 11/12/2019 10:40 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013176Z | Room 2A-130 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:40 AM | Joshua Keene | 11/12/2019 10:43 AM | RH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Pass | ||
| 013177Z | Nourishments | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:43 AM | Joshua Keene | 11/12/2019 10:45 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013178Z | Double Doors to Ante Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:45 AM | Joshua Keene | 11/12/2019 10:58 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013179Z | Double Doors to Ante Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 10:58 AM | Joshua Keene | 11/12/2019 11:00 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013180Z | Door by Waiting Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:00 AM | Joshua Keene | 11/12/2019 11:02 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013181Z | Double Doors by Ante Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:02 AM | Joshua Keene | 11/12/2019 11:06 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013182Z | Double Doors by Ante Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:06 AM | Joshua Keene | 11/12/2019 11:07 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013183Z | Double Doors to Same day Surgery | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:07 AM | Joshua Keene | 11/12/2019 11:10 AM | RH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013184Z | Double Doors to Same Day Surgery | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:10 AM | Joshua Keene | 11/12/2019 11:11 AM | LH | 1 hour fire/smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013185Z | Double Doors by Room 2B-105 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:11 AM | Joshua Keene | 11/12/2019 11:18 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Fail | ||
| 013186Z | Double Doors by Room 2B-105 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:18 AM | Joshua Keene | 11/12/2019 11:20 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Fail | ||
| 013187Z | Cross Corridor Doors by Room 2A-112 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:20 AM | Joshua Keene | 11/12/2019 11:22 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Pass | ||
| 013188Z | Cross Corridor Doors by Room 2A-112 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:22 AM | Joshua Keene | 11/12/2019 11:24 AM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Fail | ||
| 013189Z | Urology Exam Room 6 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:24 AM | Joshua Keene | 11/12/2019 11:27 AM | RH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013190Z | Room 2A-111 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:27 AM | Joshua Keene | 11/12/2019 11:29 AM | LH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013191Z | Copy Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:29 AM | Joshua Keene | 11/12/2019 11:31 AM | LH | 1/2 hour smoke | Wood | 90 minute | Steel | 90 minute | Fail | ||
| 013192Z | Stairwell 3 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:31 AM | Joshua Keene | 11/12/2019 11:33 AM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013193Z | Stairwell 2 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:33 AM | Joshua Keene | 11/12/2019 11:36 AM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013194Z | Cross Corridor Doors to Waiting Area | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:40 AM | Joshua Keene | 11/12/2019 11:41 AM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Pass | ||
| 013195Z | Cross Corridor Doors to Waiting Area | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:36 AM | Joshua Keene | 11/12/2019 11:40 AM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | Label present, no rating specified | Pass | ||
| 013196Z | Stairwell 1 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:41 AM | Joshua Keene | 11/12/2019 11:44 AM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013197Z | Cross Corridor Doors by Room 2E-203 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:49 AM | Joshua Keene | 11/12/2019 11:51 AM | LH | 2 hour fire/smoke | Aluminum | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013198Z | Double Doors by Room 2E-203 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 11:44 AM | Joshua Keene | 11/12/2019 11:49 AM | RH | 2 hour fire/smoke | Aluminum | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013199Z | Equipment Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:25 PM | Joshua Keene | 11/12/2019 12:27 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013200Z | Soiled Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:27 PM | Joshua Keene | 11/12/2019 12:29 PM | LH | 1 hour | Wood | 90 minute | Steel | 90 minute | Fail | ||
| 013201Z | Clean Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:29 PM | Joshua Keene | 11/12/2019 12:31 PM | LH | 1 hour | Steel | 90 minute | Steel | 90 minute | Pass | ||
| 013202Z | Room in Clean Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:31 PM | Joshua Keene | 11/12/2019 12:33 PM | RH | 1 hour | Steel | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013203Z | Med Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:33 PM | Joshua Keene | 11/12/2019 12:36 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Label present, no rating specified | Fail | ||
| 013204Z | Stairwell 10 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:36 PM | Joshua Keene | 11/12/2019 12:39 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013205Z | SICU Supply Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:39 PM | Joshua Keene | 11/12/2019 12:43 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Label present, no rating specified | Fail | ||
| 013206Z | Door in SICU Supply Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:44 PM | Joshua Keene | 11/12/2019 12:46 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013207Z | Critical Care Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:46 PM | Joshua Keene | 11/12/2019 12:48 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013208Z | Storage Room Side Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:48 PM | Joshua Keene | 11/12/2019 12:50 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013209Z | Storage Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:50 PM | Joshua Keene | 11/12/2019 12:52 PM | LH | 1 hour | Wood | Door Label Missing | Steel | 90 minute | Fail | ||
| 013210Z | Housekeeping | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:52 PM | Joshua Keene | 11/12/2019 12:54 PM | LH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013211Z | Double Doors by Room 2E-124 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:54 PM | Joshua Keene | 11/12/2019 12:56 PM | RH | 1/2 hour smoke | Steel | 90 minute | Steel | 90 minute | Pass | ||
| 013212Z | Double Doors by Room 2E-124 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:56 PM | Joshua Keene | 11/12/2019 12:57 PM | LH | 1/2 hour smoke | Steel | 90 minute | Steel | 90 minute | Pass | ||
| 013213Z | Housekeeping | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:57 PM | Joshua Keene | 11/12/2019 12:59 PM | RH | 1 hour | Wood | 45 minute | Steel | Frame Label Missing | Fail | ||
| 013214Z | Gas Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 12:59 PM | Joshua Keene | 11/12/2019 01:01 PM | LH | 1 hour | Steel | 90 minute | Steel | 90 minute | Fail | ||
| 013215Z | Stairwell 9 Door | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:01 PM | Joshua Keene | 11/12/2019 01:03 PM | LH | 2 hour | Wood | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013216Z | Clean Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:03 PM | Joshua Keene | 11/12/2019 01:06 PM | RH | 1 hour | Wood | 45 minute | Steel | 90 minute | Pass | ||
| 013217Z | Soiled Utility | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:06 PM | Joshua Keene | 11/12/2019 01:07 PM | LH | 1 hour | Wood | 45 minute | Steel | 90 minute | Pass | ||
| 013218Z | OR Storage | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:07 PM | Joshua Keene | 11/12/2019 01:09 PM | RH | 1 hour | Wood | 45 minute | Steel | Label present, no rating specified | Pass | ||
| 013219Z | Room 2E-106 | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:09 PM | Joshua Keene | 11/12/2019 01:12 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Label present, rating illegible | Fail | ||
| 013220Z | Storage Room | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:12 PM | Joshua Keene | 11/15/2019 05:03 PM | RH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | 90 minute | Pass | ||
| 013221Z | Pipe Shaft | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:14 PM | Joshua Keene | 11/12/2019 01:16 PM | LH | 2 hour | Steel | 90 minute | Steel | Label present, rating illegible | Fail | ||
| 013222Z | Chief Resident Office | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:16 PM | Joshua Keene | 11/12/2019 01:18 PM | LH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013223Z | Double Doors to Cardiac Surgery | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:18 PM | Joshua Keene | 11/12/2019 01:24 PM | RH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | 90 minute | Fail | ||
| 013224Z | Double Doors to Cardiac Surgery | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:24 PM | Joshua Keene | 11/12/2019 01:25 PM | LH | 2 hour fire/smoke | Wood | Door Label Missing | Steel | 90 minute | Fail | ||
| 013225Z | Housekeeping | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:25 PM | Joshua Keene | 11/12/2019 01:38 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013226Z | Double Doors to OR | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:38 PM | Joshua Keene | 11/12/2019 01:41 PM | RH | 2 hour fire/smoke | Wood | 90 minute | Steel | 90 minute | Pass | ||
| 013227Z | Double Doors to OR | Floor 2 Building 1 | VA Medical Center | Joshua Keene | 11/12/2019 01:42 PM | Joshua Keene | 11/12/2019 01:43 PM | RH | 2 hour fire/smoke | Wood | 90 minute | Steel | 90 minute | Pass | ||
| 013228Z | Stairwell 19 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:02 PM | Joshua Keene | 11/12/2019 02:12 PM | LH | 2 hour | Wood | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013229Z | Double Doors to Freedom Way West | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:12 PM | Joshua Keene | 11/12/2019 02:15 PM | RH | 1/2 hour smoke | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013230Z | Double Doors to Freedom Way West | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:15 PM | Joshua Keene | 11/12/2019 02:16 PM | RH | 1/2 hour smoke | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013231Z | Housekeeping | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:16 PM | Joshua Keene | 11/12/2019 02:18 PM | LH | 1 hour | Steel | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013233Z | Room 2K-101 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:19 PM | Joshua Keene | 11/12/2019 02:22 PM | LH | 1 hour | Wood | 45 minute | Steel | Label present, rating illegible | Fail | ||
| 013234Z | Dirty Utility | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:22 PM | Joshua Keene | 11/12/2019 02:24 PM | LH | 1 hour | Wood | 45 minute | Steel | Label present, no rating specified | Fail | ||
| 013235Z | Dirty Utility | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:24 PM | Joshua Keene | 11/12/2019 02:25 PM | RH | 1 hour | Wood | 45 minute | Steel | Label present, no rating specified | Fail | ||
| 013236Z | Clean Utility | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:25 PM | Joshua Keene | 11/12/2019 02:27 PM | RH | 1 hour | Wood | 45 minute | Steel | Label present, no rating specified | Fail | ||
| 013237Z | Clean Utility | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:27 PM | Joshua Keene | 11/12/2019 02:28 PM | LH | 1 hour | Wood | 45 minute | Steel | Label present, no rating specified | Fail | ||
| 013238Z | Room 2K-208 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:28 PM | Joshua Keene | 11/15/2019 05:29 PM | LH | 2 hour | Wood | 45 minute | Steel | Frame Label Missing | Fail | ||
| 013239Z | Room 2K-206 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:31 PM | Joshua Keene | 11/12/2019 02:34 PM | LH | 1 hour | Wood | 45 minute | Steel | Frame Label Missing | Fail | ||
| 013240Z | Room 2K-206 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:34 PM | Joshua Keene | 11/12/2019 02:36 PM | RH | 1 hour | Wood | 45 minute | Steel | Frame Label Missing | Fail | ||
| 013241Z | Cross Corridor Doors by Room 2K-212 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:36 PM | Joshua Keene | 11/12/2019 02:42 PM | RH | 1/2 hour smoke | Steel | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013242Z | Cross Corridor Doors by Room 2K-212 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:38 PM | Joshua Keene | 11/12/2019 02:42 PM | RH | 1/2 hour smoke | Steel | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013243Z | Stairwell 15 Door | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:39 PM | Joshua Keene | 11/12/2019 02:41 PM | LH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013244Z | Oxygen Tank Storage | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:42 PM | Joshua Keene | 11/12/2019 02:44 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013245Z | Cross Corridor Doors by Nurses Station | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:44 PM | Joshua Keene | 11/12/2019 02:46 PM | RH | 1/2 hour smoke | Steel | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013246Z | Cross Corridor Doors by Nurses Station | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:46 PM | Joshua Keene | 11/12/2019 02:46 PM | RH | 1/2 hour smoke | Steel | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013247Z | Door by Stairwell 13 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:47 PM | Joshua Keene | 11/12/2019 02:57 PM | LH | 1/2 hour smoke | Steel | 60 minute | Steel | Label present, no rating specified | Pass | ||
| 013248Z | Stairwell 13 Door | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:57 PM | Joshua Keene | 11/12/2019 02:58 PM | RH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013249Z | Soiled Utility | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 02:59 PM | Joshua Keene | 11/12/2019 03:01 PM | RH | 1 hour | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013250Z | Clean Utility | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 03:02 PM | Joshua Keene | 11/12/2019 03:05 PM | RH | 1 hour | Steel | Label present, rating illegible | Steel | Label present, no rating specified | Fail | ||
| 013251Z | Cross Corridor Doors by Room 2H-206 | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 03:05 PM | Joshua Keene | 11/12/2019 03:06 PM | RH | 1/2 hour smoke | Steel | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013252Z | Room | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 03:06 PM | Joshua Keene | 11/12/2019 03:06 PM | RH | 1/2 hour smoke | Steel | 20 minute | Steel | No label present, not required per wall rating | Fail | ||
| 013253Z | Medication Room | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 03:06 PM | Joshua Keene | 11/12/2019 03:08 PM | RH | 1 hour | Wood | Door Label Missing | Steel | Frame Label Missing | Fail | ||
| 013254Z | Stairwell 12 Door | Floor 2 Building 6 | VA Medical Center | Joshua Keene | 11/12/2019 03:09 PM | Joshua Keene | 11/12/2019 03:11 PM | RH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013255Z | Stairwell 19 Door | 1 South | VA Medical Center | Joshua Keene | 11/12/2019 03:13 PM | Joshua Keene | 11/12/2019 03:19 PM | RH | 2 hour | Wood | 90 minute | Steel | Label present, no rating specified | Fail | ||
| 013256Z | Double Doors to Audiology | 1 South | VA Medical Center | Joshua Keene | 11/12/2019 03:19 PM | Joshua Keene | 11/12/2019 03:24 PM | LH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013257Z | Double Doors to Audiology | 1 South | VA Medical Center | Joshua Keene | 11/12/2019 03:24 PM | Joshua Keene | 11/12/2019 03:25 PM | RH | 1/2 hour smoke | Wood | 20 minute | Steel | No label present, not required per wall rating | Pass | ||
| 013258Z | Stairwell 13 Door | 1 South | VA Medical Center | Joshua Keene | 11/12/2019 03:25 PM | Joshua Keene | 11/12/2019 03:27 PM | LH | 2 hour | Steel | 90 minute | Steel | Label present, no rating specified | Pass | ||
| 013259Z | Double Doors to Audiology | 1 South | VA Medical Center | Joshua Keene | 11/12/2019 03:27 PM | Joshua Keene | 11/12/2019 03:32 PM | RH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Fail | ||
| 013260Z | Double Doors to Audiology | 1 South | VA Medical Center | Joshua Keene | 11/12/2019 03:32 PM | Joshua Keene | 11/12/2019 03:33 PM | LH | 1/2 hour smoke | Wood | No label present, not required per wall rating | Steel | No label present, not required per wall rating | Pass |