36C24419B0039-0002001.pdf
PDF 10 MB Posted
- Attached to
- Replace Keying System for Outbuildings Project Altoona VAMC Federal contract opportunity
- Solicitation number
- 36C24419B0039
About this file
36C24419B0039 0002 _17044_Stamped Drawing Set_2019_08_07.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24419B0039-0002000.docx | DOCX document | |
| 36C24419B0039-0002002.pdf | ||
| 36C24419B0039-0002004.pdf | ||
| 36C24419B0039-0002003.pdf | ||
| 36C24419B0039-0001000.docx | DOCX document | |
| 36C24419B0039-0001001.pdf | ||
| 36C24419B0039-004.pdf | ||
| 36C24419B0039-003.pdf | ||
| 36C24419B0039-002.zip | ZIP file | |
| 36C24419B0039-001.docx | DOCX document | |
| 36C24419B0039-000.docx | DOCX document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.
SYSTEMS SYMBOLS LEGEND
DRAWING KEYNOTE
EQUIPMENT TAG
REVISION TRIANGLE WITH REVISION CLOUD
EXISTING TO REMAIN
DOOR SECURITY SYMBOLS
ANNOTATION SYMBOLS
DOOR NUMBER
WP - WEATHERPROOF AS INDICATED ON PLANS
WIRELESS GATEWAY FOR ACCESS CONTROL
VALIDATION POINT
WG
VP
NEW WORK
EXISTING UNDERGROUND
TELECOM PATHWAY
WP
WIRELESS NODE FOR ACCESS CONTROLWN
UPDATERU
NEW FIRE RATED SLEEVE. ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE
STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS FOR 2-HOUR FIRE
RATING. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION.
INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER
QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED
IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
EXISTING ABOVE GROUND
TELECOM PATHWAY
ES ELECTRIC STRIKE
LATEST VERSIONS OF:
1. LIFE SAFETY CODE - NFPA 101
2. INTERNATIONAL BUILDING CODE - IBC
3. NATIONAL ELECTRICAL CODE - NFPA 70
4. HEALTHCARE FACILITIES CODE - NFPA 99
5. VA DESIGN REQUIREMENTS
A. ELECTRICAL DESIGN MANUAL FOR NEW HOSPITALS, REPLACEMENT HOSPITALS,
AMBULATORY CARE CLINICAL ADDITIONS, ENERGY CENTERS, OUTPATIENT CLINICS,
ANIMAL RESEARCH FACILITIES, LABORATORY BUILDINGS
B. FIRE PROTECTION DESIGN MANUAL
C. TELECOMMUNICATIONS AND SPECIAL TELECOMMUNICATIONS SYSTEMS DESIGN
MANUAL
APPLICABLE CODES AND STANDARDS
FIRE SEAL WITH APPROVED
CAULK OR PUTTY BY CABLE
INSTALLER
12" MINMUM
EACH SIDE
1. THROUGH PENETRANTS — ONE METALLIC CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A NOM ANNULAR SPACE
OF 3/4 IN. (19 MM) IS REQUIRED WITHIN THE FIRESTOP SYSTEM. CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR
WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF CONDUITS MAY BE USED:
A. CONDUIT - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
2. PACKING MATERIAL - MIN. 3 IN. (78 MM) THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY PACKED
INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. PACKING MATERIAL TO BE CENTERED IN WALLS AND MID DEPTH
AND RECESSED TO ALLOW FOR INSTALLATION OF FILL MATERIAL.
3. FILL, VOID OR CAVITY MATERIAL*- SEALANT - MIN. 1/2 IN. (13 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS.
FLUSH WITH TOP SURFACE OF FLOOR, IN WALLS, FILL MATERIAL TO BE APPLIED ON EACH SIDE OF PACKING MATERIAL. 3M COMPANY
TYPES FB-1000 NS, FB-10003SL (FLOORS ONLY), FB-2000 OR FB-2000+ (FLOORS ONLY).
*INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTION EMPLOYING THE UL OR CUL
CERTIFICATION (SUCH AS CANADA), RESPECTIVELY,
1A3
UL 1479
F RATING - 2 HOUR
T RATING - 0 HOUR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
1A2B
2A
UL 1479
F RATING - 2 HOUR
T RATING - 0 HOUR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
FIRE SEAL WITH APPROVED
CAULK OR PUTTY BY CABLE
INSTALLER
12" MINMUM
EACH SIDE
1. THROUGH PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM.
CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF CONDUITS
MAY BE USED:
A. CONDUIT - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT. A NOM ANNULAR
SPACE OF 3/4 IN. (19 MM) IS REQUIRED WITH THE FIRESTOP SYSTEM.
2. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MIN. 3 IN. (78 MM) THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY PACKED
INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO
ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
B. FILL, VOID OR CAVITY MATERIAL*- SEALANT - MIN. 1 IN. (25 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS.
ON BOTH SURFACES OF WALL. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT MIN 1/4 IN. (6 MM) CROWN IS FORMED
AROUND THE PENETRATING ITEM. 3M COMPANY - TYPES FB-1000 NS, FB-2000 OR FB-2000+
*INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTION EMPLOYING THE UL OR CUL
CERTIFICATION (SUCH AS CANADA), RESPECTIVELY,
SECURED CONCEALED VERTICAL RODS UNSECURED CONCEALED VERTICAL RODS
RIGHT HAND REVERSE(RHRB) DOOR
PANIC EXITING DEVICE
WITH CONCEALED
VERTICAL ROD AND
MONITOR SWITCH
SEE PLAN FOR
CONDUIT SIZE
J-BOX(RECESSED)
4"x4"x2 1/8"
MOUNTED ABOVE CEILING
(VERIFY IN FIELD W/ EC)
1/2" FLEX CO 1/2" FLEX CO
DOOR CONTACT
3/4" CO3/4" CO
CONCELAED
ELECTRIC POWER
TRANSFER
3/8" CHANNEL
3/4" CO
UPDATER
SINGLE GANG BB
(VERTICAL)
CONCEALED
ELECTRIC POWER
TRANSFER
3' -6
3' -4
6" 6"
UNSECURED SURFACE STRIKESECURED SURFACE STRIKE
RIGHT HAND REVERSE(RHRB) DOOR
PANIC
EXITING DEVICE
DOOR STRIKE
SURFACE MTD.
DOOR STRIKE
(BEYOND)
1/2" FLEX CO
DOOR CONTACT
3/4" CO
CARD READER
SINGLE GANG BB
(VERTICAL)
1/2" FLEX CO
REQUEST TO EXIT(REX)
SINGLE GANG BB
(HORIZONTAL)
4" TO 8"
6"
3' -6
3' -4
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412.287.7333
www.ae-works.com
AE WORKS PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
8/ 7/
:4
5:
A M
REPLACE KEYING SYSTEM FOR
OUTBUILDINGS
503-17-106
AEW REC
2907 Pleasant Valley Blvd, Altoona, PA 16602
ET001
SYSTEMS SYMBOLS, NOTES, AND DETAILS
02/08/2019 17044
100% DESIGN DOCUMENTS
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL TOP
T TOP
TA THROWAWAY
TAN TANGENT
TC TELECOMMUNICATIONS
CONTRACTOR
TCV TEMPERATURE CONTROL VALVE
TEMP TEMPERATURE
TER TERRAZZO
TH THERMOMETER
THRES THRESHOLD
TR TEMPERATURE RISE
TRANS TRANSITION
TRANSR TRANSFORMER
TSTAT THERMOSTAT
TYP TYPICAL
UC UNDER CABINET OR UNDER CUT
UFD UNDER FLOOR DUCT
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORIES
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VENT VENTILATION
VERT VERTICAL
VIF VERIFY IN FIELD
W WATT
W/ WITH
W/O WITHOUT
WC WALL COVERING
WCL WATER CLOSET
WF WIDE FLANGE
WHCH WHEEL CHAIR
WIN WINDOW
WP WEATHERPROOF
X DEMO
XN TO BE RELOCATED / NEW LOCATION
XR EXISTING TO REMAIN
ZVC ZONE VALVE CABINET
HPF HIGH POWER FACTOR
HT HEIGHT
HVAC HEATING, VENTILATING, AIR
CONDITIONING
HZ HERTZ
ID INSIDE DIAMETER
IG ISOLATED GROUND
IME INSULATED METAL ENCLOSURE
IN INCH
INCAND INCANDESCENT
INCL INCLUDED
INSUL INSULATION
INT INTERIOR
INTERL INTERLOCK
INV INVERT
ISO ISOLATION
IVS ISOLATED VALVE STATION
J-BOX JUNCTION BOX
JST JOIST
JT JOINT
KO KNOCK OUT
kVA KILOVOLT AMPERE kVAR KILOVAR (REACTANCE) kW KILOWATT kWH KILOWATT HOUR METER
LB POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LIN LINEAR
LOC LOCATION OR LOCATE
LPT LOW POINT
LT LIGHT
LTG LIGHTING
LV LOW VOLTAGE
LVR LOUVER
LWC LINEAR WOOD CEILING
MAN MANUAL
MATL MATERIAL
MAV MANUAL AIR VENT
MAX MAXIMUM
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MO MASONRY OPENING
MONO MONOLITHIC
MTD MOUNTED
MTG HT MOUNTING HEIGHT
MTL METAL
MTLH METAL HALIDE
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
N/A NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER OR NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OPER OPERATED
OPNG OPENING
OPP OPPOSITE
PB PULL BOX
PNL PANEL
PR PAIR
PRELIM PRELIMINARY
PRT PRESSURE TAP
PRV PRESSURE REDUCING VALVE
PT PAINT OR POTENTIAL
TRANSFORMER
RO ROUGH OPENING
QT QUARRY TILE
R RADIUS
RC REMOVE COMPLETELY
RE RELOCATE EXISTING
REC RECESSED
RECPT RECEPTACLE
REF REFERENCE
REFL REFLECTOR
REG REGISTER
REINF REINFORCING
REM REMOVE
REQD REQUIRED
RET RETURN
REV REVISE
REX REMOVE EXISTING
RF RESILIENT FLOOR
RFI REQUEST FOR INFORMATION
RGS RIGID GALVANIZED STEEL CONDUIT
RH ROOF HATCH
RM ROOM
RN REMOVE AND REPLACE WITH NEW
RR REMOVE AND REPLACE
RS RAPID START
SCHED SCHEDULE
SF SQUARE FOOT
SHT SHEET
SHT MTL SHEET METAL
SHTG SHEATHING
SIM SIMILAR
SM SURFACE MOUNTED
SNC SANITARY NAPKIN CABINET
SND SANITARY NAPKIN DISPOSER
SPC SPECIMEN PASS-THRU CABINET
SPEC SPECIFICATIONS
ST STL STAINLESS STEEL
STD STANDARD
STER STERILIZER
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SW SWITCH
& AND
AAP ALARM ANNUNCIATOR PANEL
AAV AUTOMATIC AIR VENT
ABV ABOVE
ACC DR ACCESS DOOR
ACFL ACCESS
ACT ACOUSTICAL CEILING TILE
ADA AMERICAN DISABILITIES ACT
ADD ADDENDUM
ADDL ADDITIONAL
ADJ ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AL ALIGN
ALT ALTERNATE
ALUM ALUMINUM
AMP AMPERE
APPROX APPROXIMATE
ARCH ARCHITECTURAL
BFC BELOW FINISH CEILING
BFE BOTTOM FOOTING ELEVATION
BFG BELOW FINISHED GRADE
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRKR BREAKER
BSMT BASEMENT
BTWN BETWEEN
C CONDUIT
CAB CABINET
CAP CAPACITY
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CFH CUBIC FEET / HOUR
CFM CUBIC FEET / MINUTE
CH CHANNEL
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CL CENTERLINE
CLG CEILING
CLG MTD CEILING MOUNTED
COMM COMMUNICATION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUE / CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CTR CENTER
CU COPPER
D DEPTH OR DEEP
dB DECIBEL
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAILS
DIA DIAMETER
DIAG DIAGONAL OR DIAGRAM
DIM DIMENSION
DISC DISCONNECT
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DP DISTRIBUTION PANEL
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EL ELEVATION
ELEC ELECTRICAL
ELEC CAB ELECTRICAL CABINET
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENTR ENTRANCE
EO ELECTRICAL OUTLET
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
XP EXPLOSION PROOF
F/S FIRE / SMOKE DAMPER
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FB FIRE BLANKET
FC FLEXIBLE CONNECTION OR
FOOTCANDLE
FDN FOUNDATION
FHP FULL HEIGHT PARTITION
FHV FIRE HOSE VALVE
FIN FINISH
FIXT FIXTURE
FLA FULL LOAD AMPERES
FLEX FLEXIBLE
FLG FLANGE
FLG C FLANGE CONNECTION
FLR FLOOR
FLUOR FLUORESCENT
FP FIRE PROOFING
FRMG FRAMING
FSTOP FIRESTOPPING
FT FOOT / FEET
FT HD FEET OF HEAD
FTC FOOTCANDLES
FTG FOOTING
FUR FURRING
G ELECTRICAL GROUND
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GENL GENERAL
GFCI GROUND FAULT CIRCUIT
INTERRUPTOR
GL GLASS
GND GROUND
GR GRADE
GWB GYPSUM BOARD
H HIGH
HDCP HANDICAP
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSE POWER
SYSTEMS GENERAL NOTES
1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL SYSTEM REQUIREMENTS AS
INDICATED ON ALL CONTRACT DRAWINGS.
2 DUE TO SCALE OF THE DRAWINGS, ALL SECURITY SYSTEM EQUIPMENT SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CABLING.
REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL REQUIREMENTS.
3 COORDINATE WITH ALL SYSTEM PROVIDERS ALL CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE SATISFACTION OF
ALL CONCERNED TRADES.
4 COORDINATE EXACT LOCATION(S) OF ALL CEILING MOUNTED CABLE, CONDUITS, EQUIPMENT AND/OR
DEVICES WITH ALL AFFECTED TRADES PRIOR TO INSTALLATION.
5 ALL SYSTEM WIRING, CONDUITS AND EQUIPMENT INSTALLATION SHALL BE IN ACCORDANCE WITH GOOD ENGINEERING PRACTICES AND BY ALL IEEE, EIA, NEC AND MANUFACTURER'S REQUIREMENTS.
ALL WIRING SHALL COMPLY WITH ALL STATE AND LOCAL ELECTRICAL CODES AND SHALL TEST FREE
FROM ALL GROUNDS, SHORTS STRAY VOLTAGES AND EMI.
6 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE
EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL
EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.
7 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE
ASTM AND NFPA REQUIREMENTS FOR A 2-HOUR MINUIMUM FIRE-RATING.. REFER TO RELATED
SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE
PERFORMED BY AN APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER.
INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED
INSTALLATION\ PROCEDURES.
8 REFER TO ALL RELATED CONTRACT DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND/OR REQUIREMENTS RELATED TO THE INSTALLATION, PROGRAMMING, TESTING, COMMISSIONING
AND CERTIFICATION OF ALL ELECTRONIC SECURITY SYSTEMS.
9 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X ENCLOSURES AND SHALL BE RATED FOR
THAT APPLICATION.
10 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT
THE USE OF SPECIALIZED TOOLS.
11 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON
WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND
EQUIPMENT WITH ALL AFFECTED CONTRACTORS.
12 ALL CONTROL EQUIPMENT AND EXTERIOR DEVICES MUST HAVE TRANSIENT PROTECTION TO COMPLY WITH UL AND NFPA 70 REQUIREMENTS. WHERE ANY CIRCUITS LEAVE THE BUILDING, ADDITIONAL
TRANSIENT PROTECTION MUST BE PROVIDED FOR EACH CIRCUIT. ALL TRANSIENT PROTECTION
DEVICES MUST BE UL LISTED UNDER STANDARD #497B (ISOLATED LOOP PROTECTORS).
13 REFER TO ALL RELATED CONTRACT DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND/OR REQUIREMENTS RELATED TO THE INSTALLATION, PROGRAMMING, TESTING, COMMISSIONING
AND CERTIFICATION OF ALL ELECTRONIC SECURITY SYSTEMS.
14 PROVIDE A KEY OVERRIDE FOR ALL DOORS. KEYING BY VENDOR.
15 A 7-PIN CORE SHALL BE PROVIDED WITH ALL LOCKSETS. VENDOR TO COORDINATE WITH COR ON PIN
SETTING PRIOR TO ORDERING. KEY WAY IS TYPE "D".
16 A CONTACT SWITCH SHALL BE SPECIFIED FOR EVERY DOOR.
17 THERE ARE NO CLOSERS ON THE DOORS. THE DOORS WILL BE CLOSED MANUALLY.
18 GUEST CARDS COULD BE SUPPLIED TO OUTSIDE USERS AND SPECIFICALLY 'TIMED' SO THEY COULD ONLY USED AS DIRECTED BY THE VA. THE CONTRACTOR AND MANUFACTURER WILL BE RESPONSIBLE
FOR INSTRUCTION VA STAFF IN THE PROGRAMMING OF CARDS AS PART OF THEIR TRAINING.
19 PROVIDE AN ADDITIONAL 10 (TEN) OUTDOOR PADLOCKS BESIDES WHAT IS SHOWN FOR SPECIFIC
DOORS FOR USE BY THE VA.
20 PROVIDE AN ADDITIONAL 25 (TWENTY FIVE) PERCENT SPARE CAPACITY ON WIRELESS GATEWAYS AND
NODES.
NTS
CONDUIT THROUGH EXISTING CONCRETE BLOCK / CONCRETE WALL
- FLOOR ASSEMBLY
NTS
CONDUIT THROUGH EXISTING FIRE RATED DRYWALL PARTITION
NOT TO SCALE
EGRESS DOOR ASSEMBLY - CONCEALED VERTICAL RODS
ELECTRICAL GENERAL NOTES
1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL DRAWING REQUIREMENTS AS INDICATED ON ALL ET SERIES CONTRACT DRAWINGS.
2 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL
WORK.
3 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION SECTIONS FOR
ADDITIONAL REQUIREMENTS.
4 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE SATISFACTION OF ALL CONCERNED TRADES.
5 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM OF 3/4" UNLESS
OTHERWISE NOTED.
6 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND
SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.
7 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.
8 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
9 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X STAINLESS
STEEL AND RATED FOR THAT APPLICATION.
10 ALL DEVICES, COMPONENTS OR EQUIPMENT INSTALLED ON THE EXTERIOR OF THE FACILITY SHALL BE PROVIDED IN ACCORDANCE WITH ALL MANUFACTURERS' REQUIREMENTS TO ENSURE THE PROPER OPERATION WHEN EXPOSED TO THE ENVIRONMENTAL CONDITIONS AND/OR AVERAGE ANNUAL LOWEST TEMPERATURE THAT CAN
BE ANTICIPATED FOR THE GEOGRAPHIC REGION OF THE FACILITY.
11 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF SPECIALIZED TOOLS.
12 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS).
COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.
13 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED) AND ALL OTHER APPLICABLE CODES AND
STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
14 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED
ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.
15 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
16 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY-RECOGNIZED TESTING LABORATORY.
17 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT PRIOR TO INSTALLATION.
18 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNER'S REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS
IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.
19 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.
20 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO PERFORMING ANY
WORK.
21 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED CEILING
AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS.
22 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING AND/OR
BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.
23 THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE OWNER.
24 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH THE
OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.
25 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE CONTRACTOR SHALL
COORDINATE THESE REQUIREMENTS WITH THE OWNER.
26 THE CONTRACTOR SHALL PROVIDE ALL NEW OPENINGS IN EXISTING PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY NEW ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS NEW WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES INSTALLED
THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.
27 THE CONTRACTOR SHALL CONTACT THE NATIONAL "811-CALL BEFORE YOU DIG" SYSTEM PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATION WORK. THE
CONTRACTOR SHALL HAVE ALL UTILITIES VERIFIED IN AND AROUND THE EXCAVATION AREA.
28 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS. NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING THE
REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS.
29 THESE DRAWINGS DO NOT INDICATE ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES AND EXISTING CONDITIONS.
30 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED, ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL.
31 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRATOR UPSIZES THE CONDUIT AS REQUIRED, AND THE AMPACITY ADJUSTMENTS FROM TABLE 310.15(B)(3)(a) HAVE BEEN APPLIED.
32 COLOR CODING OF WIRES SHALL BE AS PER NEC.
BID ITEM #1: BASE BID:
GENERAL CONSTRUCTION: WORK INCLUDES GENERAL CONSTRUCTION, ALTERATIONS/ NECESSARY REMOVAL OF EXISTING STRUCTURES AND CONSTRUCTION AND CERTAIN OTHER ITEMS. ELECTRICAL WORK: WORK INCLUDES ALL LABOR, MATERIAL, EQUIPMENT AND SUPERVISION TO PERFORM THE REQUIRED ELECTRICAL CONSTRUCTION WORK ON THIS PROJECT INCLUDING BUT NOT LIMITED TO THE WORK ASSOCIATED WITH PROVIDING KEYING SYSTEM VARIOUS BUILDINGS AT THE
JAMES E. VAN ZANDT MEDICAL CENTER.
BID ITEM #2: DEDUCT ALTERNATE NO.1: DELETE ALL WORK IN AND TO BUILDING 22 INCLUDING ALL SALTO LOCK WORK AND INSTALLATION AND ANY NEW FIBER RUNS
TO IT.
BID ITEM #3: DEDUCT ALTERNATE NO.2: 10 EXTRA EXTERIOR PADLOCKS (ATTIC STOCK).
BID ITEM #4: DEDUCT ALTERNATE NO.3: DELETE ALL WORK IN AND TO BUILDING #19 INCLUDING ALL SALTO LOCK WORK AND INSTALLATION AND ANY NEW FIBER
RUNS TO IT.
BID ITEM #5: DEDUCT ALTERNATE NO.4: THE REST OF THE EXTERIOR PADLOCKS THAT WERE INCLUDED IN THE BASE BID WORK.
BID ITEM #6: DEDUCT ALTERNATE NO.5: BUILDING #6 REMOVE SALTO LOCK WORK ONLY, FIBER WORK REMAINS.
BID ITEM #7: DEDUCT ALTERNATE NO.6: THE 299 QTY CORES TO BE INSTALLED IN SALTO LOCKS WHILE ACTIVATING NETWORK CHANGE OVER, THESE ARE NOT EXTRA AND ARE IN THE BASE BID CURRENTLY. CONTRACTOR “FURNISH ONLY” TO BE REMOVED AS OF THIS DEDUCT ALTERNATE.
BID ITEM #8: DEDUCT ALTERNATE NO.7: DELETE ELECTRIC STRIKES & CIRCUIT TO PANELS ON EXTERIOR ENTRY DOORS TO NINE OUTBUILDINGS. KEEP CARD READER
W/CAT 5 TO NETWORK SWITCHES.
BID ITEM #9: DEDUCT ALTERNATE NO.8: BUILDING #4 REMOVE SALTO LOCKS ONLY, FIBER REMAINS.
NOT TO SCALE
EGRESS DOOR ASSEMBLY
08/07/19
W
W
W
W
W
W
W
W
W W
W
W
RAMP
N O F I R E A R M S O R O R W E A P O N S
A L L O W E D O N T H I S P R O P E R T Y
S
O B
S C
U R
E D
A R
E A
FA
N
TRANSFORMER PAD
CONC. PAD
#30
#16
#8
#3
#19
#2
#14
#15
#11
#20
#18
#17
#1
#12
#32
#22
#33
#7
#4
#6
#5#10
EXISTING
TELECOM
HANDHOLE
EXISTING
PEDESTAL
EXISTING
TELECOM
HANDHOLE
EXISTING
TELECOM
HANDHOLE
TYPICAL
EXISTING
TELECOM
HANDHOLE
CONTRACTOR
PARKING AREA
IT/ELECTRICAL
ROOM
ROOM 180
IT ROOM 199
CANTEEN
ROOM 11
EXISTING
TELECOM
HANDHOLE
TYPICAL
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412.287.7333
www.ae-works.com
AE WORKS PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
8/ 7/
:4
5:
A M
REPLACE KEYING SYSTEM FOR
OUTBUILDINGS
503-17-106
AEW TA
2907 Pleasant Valley Blvd, Altoona, PA 16602
ET100
SYSTEMS SITE PLAN
02/08/2019 17044
100% DESIGN DOCUMENTS
NORTH
TRUE NORTH
PROJECT
1" = 60'-0"
SYSTEMS SITE PLAN
BUILDING KEY
LEGEND
APPROXIMATE LOCATION OF EXISTING
UNDERGROUND TELECOM PATHWAY.
CONTRACTOR TO VERIFY PATHWAYS.
CONTRACTOR TO UTILIZE EXISTING PATHWAYS AS INDICATED TO INSTALL
NEW 50 µ MULTIMODE LASER OPTIC FIBER - 12 STRAND TO ESTABLISH UPDATE
CONNECTIVITY TO BUILDINGS AS SHOWN. CONTRACTOR TO TERMINATE ALL
STRANDS ON NEW FIBER PATCH PANEL AT BOTH ENDS. CONTRACTOR TO UTILIZE
EXISTING RACKS AND CABINETS. REFER TO SPECIFICATIONS FOR TYPE OF FIBER AND
PATCH PANELS. COORDINATE WITH VA OIT AND SALTO REP TO LIGHT FIBER AND
ESTABLISH NEW SALTO NETWORK. TESTING TO BE PERFORMED PER
SPECIFICATIONS.
LABEL ALL FIBER AND PATHWAYS FOR IDENTIFICATION TO VA.
KEYNOTES
SEE BUILDING FLOOR PLAN FOR
CONTINUATION OF WORK. EFFORT IS TO
PROVIDE NEW SALTO NETWORK WITH USE
OF NEW FIBER NETWORK EMANATING FROM
BUILDING 11, WHERE NEW SALTO SERVER TO
BE LOCATED.
BUILDING TO RECEIVE NEW 12 STRAND, 50µ
MULTIMODE LASER OPTIMIZED FIBER
TERMINATED ON NEW FIBER PATCH PANEL.
PROVIDE NEW FIBER PATCH CABLE TO
EXISTNG SWITCH / NEW SWITCH
INSTALLATION TO ESTABLISH CONNECTIVETY
TO NEW NETWORK.
BUILDING 1 TO RECEIVE NEW 84 STRAND,50µ
MULTIMODE LASER OPTIMIZED FIBER FOR
NEW SALTO NETWORK. SEE ET500 FOR
CONTINUATION OF WORK.
PATHS AND LENGTHS OF FIBER TO BE
VERIFIED BY CONTRACTOR.
PATHWAYS INSIDE BUILDINGS SHALL BE RUN
ABOVE GROUND (CONCEALED ABOVE
CEILING).
PROVIDE NEW UNDERGROUND PATHWAY TO
PARKING GARAGE.
BLDG #1 - MEDICAL CENTER
BLDG #2 - FACILITIES
BLDG #3 - BOILER PLANT AND GARAGE
BLDG #4 - UNION
BLDG #5 - SWING SPACE
BLDG #6 - DAYCARE
BLDG #7 - HUMAN RESOURCES
BLDG #11 - COMPUTER BUILDING
BLDG #15 - TELEPHONE BUILDING
BLDG #16 - BUTLER BUILDING
BLDG #19 - VISITOR'S CENTER
BLDG #20 - IRM
BLDG #22 - MEDICAL ADMINISTRATION
BLDG #30 - WASHBAY
BLDG #32 - BEHAVIORAL HEALTH
BLDG #33 - PARKING GARAGE
CONTRACTOR SHALL CLEAN OUT EXISTING PATHWAYS AND PROVIDE INNERDUCTS
FOR ALL FIBER INSTALLATION. WHERE EXISTING PATHWAYS ARE DAMAGED OR
INACCESSIBLE, CONTRACTOR SHALL REPAIR OR PROVIDE A BYPASS OR NEW
PATHWAY. WHERE PATHWAYS DO NOT EXIST, CONTRACTOR SHALL MAKE AN
ALLOWANCE TO INSALL NEW. ALL NEW EXTERIOR PATHWAYS SHALL BE INSTALLED
UNDERGROUND AND ENCASED IN CONCRETE.
IT ROOM
199A
EXISTING FIBER TERMINATION CABINET. TERMINATE NEW FIBER - ALL STRANDS.
PROVIDE NEW 12-STRAND OPTICAL FIBER, 50µ LASER OPTIMIZED PATCH CABLE.
EXISTING EQUIPMENT RACK. TIE NEW FIBER VIA PATCH CABLE TO EXISTING SWITCHES.
COORDINATE WITH VA OIT TO ESTABLISH SALTO NETWORK.
EXISTING PULL BOX FOR INCOMING SERVICES. USE AS PULL POINT FOR NEW 84 STRAND FIBER BUNDLE
FROM BLDG. 11
EXISTING PATHWAY TO PULL NEW 108 STRAND FIBER UP THROUGH BLDG. 1.
EXISTING PATHWAY TO PULL NEW 72 STRAND FIBER UP THROUGH BLDG. 1.
EXISTING PATHWAY TO PULL NEW 60 STRAND FIBER UP THROUGH BLDG. 1.
EXISTING PATHWAY TO PULL NEW 48 STRAND FIBER UP THROUGH BLDG. 1.
EXISTING PATHWAY TO PULL NEW 24 STRAND FIBER UP THROUGH BLDG. 1.
SEE DETAIL 2 / ET500 FOR CONTINUATION TO PROVIDE SALTO TO RADIOLOGY.
J-HOOK FOR ROUTING CABLING. USE EXISTING AND PROVIDE NEW AS SCOPE OF WORK REQUIRES.
NEW 12 STRAND OPTICAL FIBER, 50µ LASER OPTIMIZED TO ESTABLISH NEW SALTO NETWORK.
NEW FIBER CONNECTION, BLDG. 1 TO BLDG. 11
FURNISH AND INSTALL NEW CAT. 6 CABLING FROM EXISTING SWITCH TO SALTO WIRELESS GATEWAY AND NODES TO ESTABLISH SALTO NETWORK. USE EXISTING J-HOOKS OR INSTALL NEW AS NEEDED. WIRELESS
GATEWAYS AND NODES AS SHOWN ON FLOOR PLANS.
EXISTING PATHWAY TO PULL NEW 96 STRAND FIBER UP THROUGH BLDG. 1.
EXISTING PATHWAY TO PULL NEW 36 STRAND FIBER UP THROUGH BLDG. 1.
EXISTING PATHWAY TO PULL NEW 12 STRAND FIBER UP THROUGH BLDG. 1 TO PARKING GARAGE. REFER
TO DETAIL 3 / ET500.
TERMINATE 12 STRAND AND PROVIDE OPEN RACK SIZED TO ACCOMODATE ALL NEW ITEMS INSTALLED IN
PROJECT.
FURNISH AND INSTALL NEW CAT6 CABLING FROM EXISTING SWITCH TO SALTO WIRELESS GATEWAY AND NODES TO ESTABLISH A SALTO NETWORK. PROVIDE 1-1/4" CONDUIT TO INSTALL CABLING. REFER TO
BUILDING FLOOR PLAN FOR DEVICE LOCATIONS.
RISER DIAGRAM KEYED NOTES:
1ST FLOOR
CEILING
2ND FLR
3RD FLR
4TH FLR
5TH FLR
BASEMENT
CEILING
HVAC
ROOM 11
ROOM
042A
ROOM
042B
ROOM
000C
12 12
4 4
1 ROOM
199B12
TYP. DOOR LOCATION
IT ROOM
CEILING
IT ROOM
1 CEILING
IT ROOM
CEILING
6TH FLR
IT ROOM
552A
CEILING
7TH FLR
IT ROOM
CEILING
8TH FLR
IT ROOM
CEILING
9TH FLR
ROOF
CEILING
TO RADIOLOGY
TO 9TH FLOOR
SEE FLOOR PLANS FOR SALTO
LOCATIONS.
TO 8TH FLOOR
SEE FLOOR PLANS FOR SALTO
LOCATIONS.
FROM BUILDING 11
TO PARKING
GARAGE
CEILING
SALTO WIRELESS LOCKSET
CAT6 CABLE
WN
WIRELESS NODE
(TYP)
CAT6 CABLE
WG
WIRELESS GATEWAY (TYP)
FLOOR
RADIOLOGY SUITE
CAT6 BACK TO
ELEC ROOM 198A
HVAC
ROOM 11
42B
42A
PARTIAL BASEMENT FLOOR PLAN - BUILDING 1 PARTIAL FLOOR PLAN - BUILDING 11 PARTIAL FLOOR PLAN - BUILDING 15
INTERCONNECTION DIAGRAM KEY NOTE
SEE RISER DIAGRAM
FOR CONTINUATION OF WORK.
EXISTING
CONDUITS FOR
TELECOM
COMPUTER ROOM
COMPUTER ROOM
EXISTING CABINETS WITH
ACTIVE SWITCHING AND SERVERS
INSTALL NEW SALTO SERVER
IN RACK 3. COORDINATE WITH
VA OIT
EXISTING CABINETS FOR
FIBER TERMINATIONS
TO BLDG'S
4, 5, 6, 7, &
MH
TO BLDG 1
TO BLDG 15
WORK RM.
STOR
TO BLDG 11 VIA MANHOLE
15-101
NEW OFFLINE
SALTO
HARDWARE
MH
TO BLDG 2
TO BLDG 3
SALTO WIRELESS LOCKSET
CAT6 CABLE
WN
WIRELESS NODE
(TYP)
CAT6 CABLE
WG
WIRELESS GATEWAY (TYP)
FLOOR
PARKING GARAGE
PATCH PANEL
LAYER II
DATA SWITCH
(EXISTING) 2
IT/ELEC ROOM
WALL MOUNTED
LOCKING ENCLOSURE
(TYP) OR EXISTING EQUIPMENT
EXISTING
120V/20A
EMER. CKT.
IF NEW PATCH PANEL IS
REQUIRED, EC SHALL RUN
2 #12, 1 #12G IN 3/4"C TO
NEAREST 120V EMERGENCY
SOURCE AND 20A BREAKER.
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412.287.7333
www.ae-works.com
AE WORKS PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
8/ 7/
:4
5:
A M
REPLACE KEYING SYSTEM FOR
OUTBUILDINGS
503-17-106
AEW TA
2907 Pleasant Valley Blvd, Altoona, PA 16602
ET500
SYSTEMS RISER DIGRAM AND
INTERCONNECTION DIAGRAM
02/08/2019 17044
100% DESIGN DOCUMENTS
NTS
BUILDING 1 - NEW FIBER RISER AND BUILDING INTERCONNECTION
NTS
RISER DIAGRAM FOR ESTABLISHING SALTO IN RADIOLOGY
NTS
SALTO NETWORK INTERCONNECTION DIAGRAM
CONTRACTOR TO UTILIZE EXISTING PATHWAYS AS INDICATED TO INSTALL
NEW 50 µ MULTIMODE LASER OPTIC FIBER - 12 STRAND TO ESTABLISH UPDATE
CONNECTIVITY TO BUILDINGS AS SHOWN. CONTRACTOR TO TERMINATE ALL
STRANDS ON NEW FIBER PATCH PANEL AT BOTH ENDS. CONTRACTOR TO UTILIZE
EXISTING RACKS AND CABINETS. REFER TO SPECIFICATIONS FOR TYPE OF FIBER AND
PATCH PANELS. COORDINATE WITH VA OIT AND SALTO REP TO LIGHT FIBER AND
ESTABLISH NEW SALTO NETWORK. TESTING TO BE PERFORMED PER
SPECIFICATIONS.
LABEL ALL FIBER AND PATHWAYS FOR IDENTIFICATION TO VA.
BACKBONE CABLING:
VERIFY USABILITY WITH VA OIT PRIOR TO WORK.
CONTRACTOR TO FURNISH AND INSTALL NEW FIBER TO
ESTABLISH SALTO NETWORK. COORDINATE WITH SITE
PLAN FOR TOTAL CONNECTIVITY. CONTRACTOR TO USE
EXISTING PATHWAYS, INCLUDING CONDUITS, FOR NEW
FIBER. PROVIDE NEW PULLBOX, OR OTHER MATERIALS
TO COMPLETE THE FIBER INSTALL.
EXISTING
TELECOM
PULLBOX
EXISTING UNDERGROUND
PATHWAYS FROM
BUILDING 11 VIA MANHOLE
SALTO TOPOLOGY
NTS - FOR REFERENCE ONLY
NTS
RISER DIAGRAM FOR ESTABLISHING SALTO IN PARKING GARAGE
131C
131D
131F
131E
131J
131A
131I
131H
128A 128B
WN
WG
LAUNDRY
141D
PATIENT CLOTHING
CORRIDOR
141G
LAUNDRY
141A
STOR
141E
OXYGEN
STORAGE
141N
SMOKING
ROOM
141M
AUTOPSY
140A
MORGUE
LITTER AREA
140B
FREEZER
STAIRS
S100
OFFICE
TLT
134A
TLT
140C
TLT
XRAY
CAT
SCAN
SOILED
UTIL
MALE
DRESSING
ROOM
128A
FEMALE
DRESSING
ROOM
128B
XRAY
CORRIDOR
CORRIDOR
TLT
CLOS
130B
CLOS
130A
STORAGE
131KCOMPUTER
CONTROL
ROOM
131C
VEST
131B
OFFICE
131D
131E
MRI ROOM
131F
131J 131I
131H
131G
ULTRASOUND
129B
RADIOLOGY
129A
INPATIENT
WAITING
129 XRAY
ROOM
TLT
126A
WOMEN
MEN
OFFICE
121 OFFICE
OFFICE
OP. MANAGER
OFFICE
120A
TEL. CL.
199A
ELEC. RM.
198A
U EXISTING
W
NEXISTING
W N
WN
WN
U
EXISTING
EXISTING
EXISTING
3 4 5 6
7 8 9 10
WN
EXISTING
EXISTING
WN
EXISTING
SALTO
SWITCH
WN
FIBER TO
PARKING
GARAGE
CAT6 TO
ELEC ROOM
198A
APPROX. LOCATION OF AREA TO RECEIVE SALTO PADLOCK DEVICES. PROVIDE (4) SALTO
OUTDOOR RATED PADLOCKS.
APPROX. LOCATION OF CONTAINMENT AREAS TO RECEIVE SALTO PADLOCK DEVICES. PROVIDE (4)
SALTO OUTDOOR RATED PADLOCKS.
FURNISH AND INSTALL NEW CAT. 6 CABLING FROM EXISTING SWITCH TO SALTO WIRELESS
GATEWAY AND NODES TO ESTABLISH SALTO NETWORK. USE EXISTING J-HOOKS OR INSTALL NEW
AS NEEDED. WIRELESS GATEWAYS AND NODES AS SHOWN ON FLOOR PLANS.
THE PLAN IS DIAGRAMMATIC ONLY AND HAVE BEEN PROVIDED TO DEPICT THE
GENERAL ARRANGEMENT AND INSTALLATION REQUIREMENTS OF EXISTING EQUIPMENT
CABINETS. THE CONTRACTOR SHALL PROVIDE EQUIPMENT IN ACCORDANCE WITH THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SHALL BE CONFIGURED TO SUPPORT ALL
EQUIPMENT, COMPONENTS AND CABLING NECESSARY TO MEET THE PERFORMANCE
REQUIREMENTS OF ALL SYSTEMS SPECIFIED. THE CONTRACTOR SHALL PROVIDE ALL ELECTRICAL
POWER, SYSTEM COMPONENTS, AND ALL APPURTENANCES AS REQUIRED TO PROVIDE FULLY
OPERATING SYSTEMS IN ACCORDANCE WITH ALL PROJECT REQUIREMENTS.
COORDINATE ALL EQUIPMENT CONFIGURATIONS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS
AND THE INSTALLATION OF ALL SYSTEMS AND SYSTEM COMPONENTS. ALL SHOP DRAWINGS
SHALL DETAIL SPACE CONDITIONS IN ORDER TO ACCOMMODATE EXISTING CONDITIONS, ALL
EQUIPMENT LOCATIONS ARE SUBJECT TO FINAL REVIEW BY THE DESIGN PROFESSIONAL.
PROVIDE IDENTIFICATION OF ALL EQUIPMENT CABINETS / RACKS, CONTROL PANELS,
SUB-CONTROL PANELS, REMOTE RELAY CABINETS AND SECURITY EQUIPMENT PANELS, SYSTEM
INTERFACE CABINETS, AND SIMILAR EQUIPMENT WITH 1-1/2 INCH WHITE LETTERING. ENGRAVED
LAMINATED PLASTIC SIGNS SHALL BE USED FOR IDENTIFICATION AND SECURELY FASTENED IN
ACCORDANCE WITH THE PROJECT REQUIREMENTS.
WORK SHALL BE NEAT IN APPEARANCE, FREE OF ROUGH EDGES, SCRATCHES, BLEMISHES,
CRACKS AND EXPOSED GAPS. ALL EQUIPMENT SHALL BE SECURED TO THE MOUNTING SURFACE,
AND FASTENED WITH HARDWARE APPROVED BY THE MANUFACTURER AND CAPABLE OF
SUPPORTING THE RATED LOAD. ALL CABLES WITHIN ENCLOSURES SHALL BE NEATLY ROUTED AND
TIE WRAPPED AT 6 INCHES ON CENTER, ALL WIRE SPLICES SHALL BE TERMINATED ON TERMINAL
STRIPS, SPLICES UTILIZING WIRE NUTS SHALL NOT BE ACCEPTABLE.
ALL WIRING SHALL TERMINATE ON FIXED TERMINAL STRIPS, PUNCH BLOCKS OR PATCH PANELS
IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. NO SPLICES SHALL BE PERMITTED IN
UNDERGROUND PULL BOXES AND NON-ACCESSIBLE JUNCTION BOXES. ALL JUNCTION BOXES
CONTAINING ANY SYSTEM SPLICES SHALL BE UNIQUELY IDENTIFIED.
ALL PENETRATIONS OF WALLS AND FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH
THE ASTM AND NFPA. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL
INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY AN
APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL
BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION
PROCEDURES.
ALL CONDUITS / RACEWAYS SHALL BE INSTALLED IN A MANNER THAT PREVENTS TAMPERING
OR REMOVAL WHEN INSTALLED IN AREAS EXPOSED TO THE GENERAL POPULATION. PROVIDE
TAMPER-RESISTANT INSTALLATION UTILIZING "TORX WITH PEG" SECURITY-FASTENING DEVICES
FOR ALL CONDUITS/RACEWAYS, EQUIPMENT, DEVICES AND APPURTENANCES IN ALL AREAS
ACCESSIBLE TO THE GENERAL POPULATION AND/OR AREAS SUBJECTED TO TAMPERING OR
VANDALISM.
FOR CONTRACTOR AND STAFF SAFETY, PRIOR TO ANY WORK IN THIS AREA , IT SHALL BE
COORDINATED WITH COR.
KEYED NOTES:
S802
WG
800A
MECHANICAL ROOM
STAIRS
S802
800B
WN
WN
WP
WP
WP
SCREENED ROOF
PASSAGE
STAIRS
S902
ELEV. ROOM
SCREENED ROOF
WN
S902A
WP
WP
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412.287.7333
www.ae-works.com
AE WORKS PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
8/ 7/
:2
6:
P M
REPLACE KEYING SYSTEM FOR
OUTBUILDINGS
503-17-106
AEW REC
2907 Pleasant Valley Blvd, Altoona, PA 16602
01-ET101
BUILDING 1 - PARTIAL FIRST FLOOR, EIGHTH
FLOOR, AND NINTH FLOOR PLANS
02/08/2019
17044
100% DESIGN DOCUMENTS
NORTH
TRUE NORTH
PROJECT
1/8" = 1'-0"
BUILDING 01-1ST FLOOR
1/8" = 1'-0"
BUILDING 01 - 8TH FLOOR PLAN
1/8" = 1'-0"
BUILDING 01 - 9TH FLOOR PLAN
REFER TO SPECIFICATIONS
SECTION 08 71 00 FOR DOOR AND
HARDWARE SET SCHEDULES.
7th
S
TR
E ET
P
A
RKING
P
A RKING
P A RKING
P A RKING
15 1 1
1 0
26 ' 2 -2
3 03' 2-2 3 30' 2-2
70'
F8
F2
3 92 ' 2 -1 3 21 ' 2 -1
6-54-3
P A RKING
T-2
2-2
F4
F5
F5
F1
90'6-2
F1
D UPLE X DA TA O U TLET
P RINTER O UTLET
S ING LE VO I CE O UTLET
C O NCENTRATO R
PO W ER PO LE
HUB
P
S ERVER
W O RK STATIO N
C O RE SLEEVE DO W N
C O RE SL EEVE UP
W ALL CO RE
S YM B O L LEG END
4 8 STRA ND FIB ER (FL O O DED)
2 4 STRA ND FIB ER (FL O O DED)
1 2 STR AND F IBER (FLO O DED)
D ISTRIB UTIO N FRAM E
E Q UIPM E NT RACK
CO M M . CABINET
PBX
CPU
L I NE T YP ES
S6.DW G
F AIR W AY DR IVE
T3
1 08'
1 08 ' 2-1 F4 F5
F 10 F9
' 4 -3 x x x x
( 61 4) -8 95- 13 13C O LUM BUS O HIO 43229
1 900 E AST DU BLIN-G RANVIL LE RD
NaCom
8 /3/94
NO D ATE
DW K
BY
R EVIS IO NS
A LTO O NA, PENN SYLV ANIA
S ITE PLAN S CA LE:
D ATE:
A PP'D FO R CO NST.
C HK 'D
D RAW N BY: DCV
8 /3/94
NO NE
1 -E1 THRU 1-E6
V ETER ANS A DM IN ISTRA TIO N
M EDIC AL CE NTER
( 513 )-4 29-2 091B eave rcre ek, O hio , 4 5431 2 29 0 L ake vie w D rive, Su ite E
X-Y X = TO TAL C O NDUIT AVAI LABLE
Y = CO NDUIT USED
x x
X
XX X X X
A s -B u ilt
110111112113114115
133 135 137 139
138136 140 142 144
143141 148
BASEMENT ENTRANCE
EXISTING RACK
LOCATION BELOW
WN
WG
WN
OFFICE
A121
OFFICE
A120
OFFICE
A119 OFFICE
A118
CORRIDOR
A126
OFFICE
A122
OFFICE
A123 OFFICE
A124
A125
CLOSET
A124A
OFFICE
A115
OFFICE
A114
OFFICE
A113
OFFICE
A112
OFFICE
A111
OFFICE
A110
CORRIDOR
A116
FIRE/SPRINKER/
JAN CLOSET
A109
VEST
A108
CONFERENCE
A107
OFFICE
A106
CORRIDOR
A105
VESTIBULE
A150
MEN'S
TOILET
A104
WOMEN'S
TOILET
A103
KITCHEN
A102
OFFICE
A101
OFFICE
A100
OFFICE
A134
OFFICE
A136
OFFICE
A138
OFFICE
A140
OFFICE
A142
OFFICE
A144
OFFICE
A146
OFFICE
A148
CLOSET
A147OFFICE
A145OFFICE
A143
OFFICE
A141
OFFICE
A139
OFFICE
A137
OFFICE
A135
OFFICE
A133
EXISTING
SALTO
PAD LOCK
1 2 3 4
5 6 7 8
U
WN
ES
WN
WN
WN
WNWG
EXISTING PANEL
RP
TO PANEL
RP
ES
TO PANEL
RP
B01
LOCATION OF EXISTING RACK AT BASEMENT
LEVEL. CONTAINS SHELF MOUNT 802.3 HUB
MOUNT 12 PORT FIBER CONNECTOR PANEL IN
EXISTING RACK IF POSSIBLE, OTHERWISE IT SHALL
BE WALL MOUNTED. EC SHALL PROVIDE WALL
MOUNTED BRACKETS AND HARDWARE AS REQUIRED.
ACCESS AREA
B00
CRAWL SPACE
B01
1 2 3 4
5 6 7 8
WN
WP
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412.287.7333
www.ae-works.com
AE WORKS PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
8/ 7/
:4
4:
A M
REPLACE KEYING SYSTEM FOR
OUTBUILDINGS
503-17-106
AEW TA
2907 Pleasant Valley Blvd, Altoona, PA 16602
02-ET101
BUILDING 2 - FLOOR PLANS
02/08/2019 17044
100% DESIGN DOCUMENTS
NORTH
TRUE NORTH
PROJECT
1/8" = 1'-0"
BUILDING 2 - FIRST FLOOR PLAN
1/8" = 1'-0"
BUILDING 2 - BASEMENT FLOOR PLAN
FURNISH AND INSTALL NEW CAT. 6 CABLING FROM EXISTING SWITCH TO SALTO
WIRELESS GATEWAY AND NODES TO ESTABLISH SALTO NETWORK. USE EXISTING J-
HOOKS OR INSTALL NEW AS NEEDED. WIRELESS GATEWAYS AND NODES AS SHOWN
ON FLOOR PLANS.
THE PLAN IS DIAGRAMMATIC ONLY AND HAVE BEEN PROVIDED TO DEPICT THE
GENERAL ARRANGEMENT AND INSTALLATION REQUIREMENTS OF EXISTING
EQUIPMENT CABINETS. THE CONTRACTOR SHALL PROVIDE EQUIPMENT IN
ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SHALL
BE CONFIGURED TO SUPPORT ALL EQUIPMENT, COMPONENTS AND CABLING
NECESSARY TO MEET THE PERFORMANCE REQUIREMENTS OF ALL SYSTEMS
SPECIFIED. THE CONTRACTOR SHALL PROVIDE ALL ELECTRICAL POWER, SYSTEM
COMPONENTS, AND ALL APPURTENANCES AS REQUIRED TO PROVIDE FULLY
OPERATING SYSTEMS IN ACCORDANCE WITH ALL PROJECT REQUIREMENTS.
COORDINATE ALL EQUIPMENT CONFIGURATIONS PRIOR TO THE SUBMITTAL OF SHOP
DRAWINGS AND THE INSTALLATION OF ALL SYSTEMS AND SYSTEM COMPONENTS. ALL
SHOP DRAWINGS SHALL DETAIL SPACE CONDITIONS IN ORDER TO ACCOMMODATE
EXISTING CONDITIONS, ALL EQUIPMENT LOCATIONS ARE SUBJECT TO FINAL REVIEW
BY THE DESIGN PROFESSIONAL.
PROVIDE IDENTIFICATION OF ALL EQUIPMENT CABINETS / RACKS, CONTROL PANELS,
SUB-CONTROL PANELS, REMOTE RELAY CABINETS AND SECURITY EQUIPMENT
PANELS, SYSTEM INTERFACE CABINETS, AND SIMILAR EQUIPMENT WITH 1-1/2 INCH
WHITE LETTERING. ENGRAVED LAMINATED PLASTIC SIGNS SHALL BE USED FOR
IDENTIFICATION AND SECURELY FASTENED IN ACCORDANCE WITH THE PROJECT
REQUIREMENTS.
WORK SHALL BE NEAT IN APPEARANCE, FREE OF ROUGH EDGES, SCRATCHES,
BLEMISHES, CRACKS AND EXPOSED GAPS. ALL EQUIPMENT SHALL BE SECURED TO
THE MOUNTING SURFACE, AND FASTENED WITH HARDWARE APPROVED BY THE
MANUFACTURER AND CAPABLE OF SUPPORTING THE RATED LOAD. ALL CABLES
WITHIN ENCLOSURES SHALL BE NEATLY ROUTED AND TIE WRAPPED AT 6 INCHES ON
CENTER, ALL WIRE SPLICES SHALL BE TERMINATED ON TERMINAL
STRIPS, SPLICES UTILIZING WIRE NUTS SHALL NOT BE ACCEPTABLE.
ALL WIRING SHALL TERMINATE ON FIXED TERMINAL STRIPS, PUNCH BLOCKS OR
PATCH PANELS IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. NO SPLICES
SHALL BE PERMITTED IN UNDERGROUND PULL BOXES AND NON-ACCESSIBLE
JUNCTION BOXES. ALL JUNCTION BOXES CONTAINING ANY SYSTEM SPLICES SHALL
BE UNIQUELY IDENTIFIED.
ALL PENETRATIONS OF WALLS AND FLOORS SHALL BE FIRE STOPPED IN
ACCORDANCE WITH THE ASTM AND NFPA. REFER TO RELATED SPECIFICATION
SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE
PERFORMED BY AN APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE
MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE
WITH MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
ALL CONDUITS / RACEWAYS SHALL BE INSTALLED IN A MANNER THAT PREVENTS
TAMPERING OR REMOVAL WHEN INSTALLED IN AREAS EXPOSED TO THE GENERAL
POPULATION. PROVIDE TAMPER-RESISTANT INSTALLATION UTILIZING "TORX WITH
PEG" SECURITY-FASTENING DEVICES FOR ALL CONDUITS/RACEWAYS, EQUIPMENT,
DEVICES AND APPURTENANCES IN ALL AREAS ACCESSIBLE TO THE GENERAL
POPULATION AND/OR AREAS SUBJECTED TO TAMPERING OR VANDALISM.
BUILDING TO RECEIVE NEW 12 STRAND, 50µ
MULTIMODE LASER OPTIMIZED FIBER TERMINATED ON NEW FIBER PATCH PANEL.
PROVIDE NEW FIBER PATCH CABLE TO EXISTNG / NEW SWITCH TO ESTABLISH
CONNECTIVETY TO NEW NETWORK.
BUILDING SHALL INCLUDE (1) ONE KEY CARD NETWORK ENCODER. THE ENCODER
SHALL BE NETWORKED SO LOCATION CAN BE ANYWHERE THERE'S A DATA OUTLET.
COORDINATE LOCATION WITH COR.
UTILIZE EXISTING 20A, 1P CIRCUIT BREAKER IN PANEL RP AND EXTEND 2#12, 1#12G IN
3/4" C AND CONNECT TO ELECTRIC STRIKE INDICATED ON PLAN.
KEYNOTES
FOR CONTINUATION
SEE DRAWING ET100
REFER TO SPECIFICATIONS
SECTION 08 71 00 FOR DOOR AND
102A
109A 111A
111B
APPROX. LOCATION OF CONTAINMENT AREAS TO
RECEIVE SALTO PADLOCK DEVICES. CONFIRM
QUANTITIES AND LOCATIONS WITH OWNER.
100A
WN
GENERATOR BLDG
ELEC. DISTR. ROOM
OFFICE
WORK
104A
WORK AREA
BATH
WORK AREA
HAC
109A
WORKSHOP
WN
TRACTOR BAYS
MECH
111A
WASH BAY
SERVICE BAY
110A
OFFICE
OFFICE
CORR
LOCKER/SHOWER
WN
TLT
GARAGE BAYS
AMBULANCE GARAGE
OPEN AREA
STORAGE
102A
GATE
WP
WP
U
U
ES
E S
WN
WN
WG
EXISTING PANEL
PPC
TO
PANEL
PPC
TO
PANEL
PPC
110B
WP
102B
101A
WP
WIRELESS GATEWAY (TYP)
EXISTING IT RACK LOCATION
WG FIRE PUMP ROOM
STORAGE
SOLVENT
STORAGE
MECHANICAL SPACE
SUMP PIT
WATER
SUPPLY
TANK
WATER RESERVOIR
FOR CONTINUATION
SEE DRAWING ET100 ~
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412.287.7333
www.ae-works.com
AE WORKS PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
8/ 6/
:5
3:
P M
REPLACE KEYING SYSTEM FOR
OUTBUILDINGS
503-17-106
AEW RC
2907 Pleasant Valley Blvd, Altoona, PA 16602
03-ET101
BUILDING 3 - FLOOR PLANS
02/08/2019
17044
100% DESIGN DOCUMENTS1/8" = 1'-0"
BUILDING 3 - FIRST FLOOR
1/8" = 1'-0"
BUILDING 3 - BASEMENT PLAN
NORTH
TRUE NORTH
PROJECT
FURNISH AND INSTALL NEW CAT. 6 CABLING FROM EXISTING SWITCH TO SALTO
WIRELESS GATEWAY AND NODES TO ESTABLISH SALTO NETWORK. USE EXISTING J-
HOOKS OR INSTALL NEW AS NEEDED. WIRELESS GATEWAYS AND NODES AS SHOWN
ON FLOOR PLANS.
THE PLAN IS DIAGRAMMATIC ONLY AND HAVE BEEN PROVIDED TO DEPICT THE
GENERAL ARRANGEMENT AND INSTALLATION REQUIREMENTS OF EXISTING
EQUIPMENT CABINETS. THE CONTRACTOR SHALL PROVIDE EQUIPMENT IN
ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SHALL
BE CONFIGURED TO SUPPORT ALL EQUIPMENT, COMPONENTS AND CABLING
NECESSARY TO MEET THE PERFORMANCE REQUIREMENTS OF ALL SYSTEMS
SPECIFIED. THE CONTRACTOR SHALL PROVIDE ALL ELECTRICAL POWER, SYSTEM
COMPONENTS, AND ALL APPURTENANCES AS REQUIRED TO PROVIDE FULLY
OPERATING SYSTEMS IN ACCORDANCE WITH ALL PROJECT REQUIREMENTS.
COORDINATE ALL EQUIPMENT CONFIGURATIONS PRIOR TO THE SUBMITTAL OF SHOP
DRAWINGS AND THE INSTALLATION OF ALL SYSTEMS AND SYSTEM COMPONENTS. ALL
SHOP DRAWINGS SHALL DETAIL SPACE CONDITIONS IN ORDER TO ACCOMMODATE
EXISTING CONDITIONS, ALL EQUIPMENT LOCATIONS ARE SUBJECT TO FINAL REVIEW
BY THE DESIGN PROFESSIONAL.
PROVIDE IDENTIFICATION OF ALL EQUIPMENT CABINETS / RACKS, CONTROL PANELS,
SUB-CONTROL PANELS, REMOTE RELAY CABINETS AND SECURITY EQUIPMENT
PANELS, SYSTEM INTERFACE CABINETS, AND SIMILAR EQUIPMENT WITH 1-1/2 INCH
WHITE LETTERING. ENGRAVED LAMINATED PLASTIC SIGNS SHALL BE USED FOR
IDENTIFICATION AND SECURELY FASTENED IN ACCORDANCE WITH THE PROJECT
REQUIREMENTS.
WORK SHALL BE NEAT IN APPEARANCE, FREE OF ROUGH EDGES, SCRATCHES,
BLEMISHES, CRACKS AND EXPOSED GAPS. ALL EQUIPMENT SHALL BE SECURED TO
THE MOUNTING SURFACE, AND FASTENED WITH HARDWARE APPROVED BY THE
MANUFACTURER AND CAPABLE OF SUPPORTING THE RATED LOAD. ALL CABLES
WITHIN ENCLOSURES SHALL BE NEATLY ROUTED AND TIE WRAPPED AT 6 INCHES ON
CENTER, ALL WIRE SPLICES SHALL BE TERMINATED ON TERMINAL
STRIPS, SPLICES UTILIZING WIRE NUTS SHALL NOT BE ACCEPTABLE.
ALL WIRING SHALL TERMINATE ON FIXED TERMINAL STRIPS, PUNCH BLOCKS OR
PATCH PANELS IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. NO SPLICES
SHALL BE PERMITTED IN UNDERGROUND PULL BOXES AND NON-ACCESSIBLE
JUNCTION BOXES. ALL JUNCTION BOXES CONTAINING ANY SYSTEM SPLICES SHALL
BE UNIQUELY IDENTIFIED.
ALL PENETRATIONS OF WALLS AND FLOORS SHALL BE FIRE STOPPED IN
ACCORDANCE WITH THE ASTM AND NFPA. REFER TO RELATED SPECIFICATION
SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE
PERFORMED BY AN APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE
MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE
WITH MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
ALL CONDUITS / RACEWAYS SHALL BE INSTALLED IN A MANNER THAT PREVENTS
TAMPERING OR REMOVAL WHEN INSTALLED IN AREAS EXPOSED TO THE GENERAL
POPULATION. PROVIDE TAMPER-RESISTANT INSTALLATION UTILIZING "TORX WITH
PEG" SECURITY-FASTENING DEVICES FOR ALL CONDUITS/RACEWAYS, EQUIPMENT,
DEVICES AND APPURTENANCES IN ALL AREAS ACCESSIBLE TO THE GENERAL
POPULATION AND/OR AREAS SUBJECTED TO TAMPERING OR VANDALISM.
BUILDING TO RECEIVE NEW 12 STRAND, 50µ
MULTIMODE LASER OPTIMIZED FIBER TERMINATED ON NEW FIBER PATCH PANEL.
PROVIDE NEW FIBER PATCH CABLE TO EXISTNG / NEW SWITCH TO ESTABLISH
CONNECTIVETY TO NEW NETWORK.
UTILIZE EXISTING 20A, 1P CIRCUIT BREAKER IN PANEL PPC AND EXTEND 2#12, 1#12G
IN 3/4" C AND CONNECT TO ELECTRIC STRIKE(S) INDICATED ON PLAN.
KEYNOTES
1 2 3 4
5 6 7 8
REFER TO SPECIFICATIONS
SECTION 08 71 00 FOR DOOR AND
UP
UP
B03
WIRELESS
NODE
B00
B01 B02
EXISTING IT
RACK LOCATION
WN
SERVICE ROOM
B00
CRAWL SPACE
BOILER ROOM
B02
STORAGE
B03
CORRIDOR
B01
STAIRS
SB00
1 2 3 4
5 6 7 8
~FOR CONTINUATION,
SEE DRAWING ET100
9WP
108B
S100102
104A
WG
PORCH
LIVING ROOM
DINING ROOM
HALL
KITCHEN
DEN
GARAGE
ELEC RM
VEST
TOILET
STAIRS
S100
VEST
WP
WP
WP
WN
U
ES
EXISTING
PANEL LP4B
204 205
WN
This is the start of the file's text. The full file is on GovTribe.