36C24419B0012-003.pdf

PDF 4 MB Posted

Attached to
Replace Legacy UPS/Power System Federal contract opportunity
Solicitation number
36C24419B0012
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

36C24419B0012 S02 Combined Drawings-Replace Legacy UPS.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Replace Legacy UPS/Power System, newest first.
File Type Posted
36C24419B0012-0004000.docx DOCX document
36C24419B0012-0003001.pdf PDF
36C24419B0012-0003000.docx DOCX document
36C24419B0012-0002001.pdf PDF
36C24419B0012-0002002.pdf PDF
36C24419B0012-0002000.docx DOCX document
36C24419B0012-0001000.docx DOCX document
36C24419B0012-014.pdf PDF
36C24419B0012-006.pdf PDF
36C24419B0012-004.pdf PDF
36C24419B0012-010.pdf PDF
36C24419B0012-011.pdf PDF
36C24419B0012-012.pdf PDF
36C24419B0012-002.pdf PDF
36C24419B0012-013.pdf PDF
36C24419B0012-008.docx DOCX document
36C24419B0012-001.docx DOCX document
36C24419B0012-007.pdf PDF
36C24419B0012-009.pdf PDF
36C24419B0012-005.pdf PDF
36C24419B0012-000.docx DOCX document
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAIN ELEC RM

EE-200

REMOVE INTERIOR PARTIAL-HEIGHT PARTITIONS AND

DOOR ASSEMBLY. REMOVE PARTIAL CEILING

ASSEMBLY INCLUDING GRID AND TILE. REMOVE

CARPET AND VCT FLOORING AND ADHESIVES.

CONTRACTOR TO PATCH CONCRETE FLOORS AS

NECESSARY. REPAINT WALLS WHERE PARTITIONS

HAVE BEEN REMOVED.

CONSULTANTS:

Drawing Title

Approved: Site Manager

Project Title

Location

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

ARCHITECTS/ENGINEERS:

6"

6"

6"

6" o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

Approved: Project ManagerApproved: Manager, Projects Section

Approved: Vice President, Facilities Management

Approved: Chief Operating Officer

Approved: Director

65432

SEAL

6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com

AE Works Project Number:

Revision# Date

VA244-16-J-5508

ICT JZ

G001 04/12/2017

FULLY SPRINKLERED

BID DOCUMENTS

ERIE VAMC - EXPAND

EMERGENCY POWER

GENERATION - PHASE II

135 E 38TH ST, ERIE PA 16504

16030

COVER SHEET

PROJECT DIRECTORY

OWNER:

ERIE VA MEDICAL CENTER

135 E 38TH STREET

ERIE, PA 16504

(814) 860-2744

CONTACT: SHAWN PURPURA

ARCHITECT/ENGINEER:

AE WORKS, LTD

6587 HAMILTON AVENUE

PITTSBURGH, PA 15206

(412) 287-7333

CONTACT: TIFFANY HAILE

DRAWING INDEX

SHEET # SHEET NAME

GENERAL

G001 COVER SHEET

PLUMBING

P/FP/H001 PLUMBING, FP AND HVAC PLAN

ELECTRICAL

E001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND NOTES

E100 PARTIAL BASEMENT FLOOR POWER PLAN

E101 PARTIAL SECOND FLOOR AND PENTHOUSE POWER PLANS

E200 ELECTRICAL RISER DIAGRAM

E300 DETAILS

NORTH

TRUE NORTH=

PROJECT

83.00°

VICINITY MAP

SITE

LOCATION MAP

SITE

ERIE VAMC - EXPAND EMERGENCY

POWER GENERATION - PHASE II

ERIE VA MEDICAL CENTER

135 E 38TH ST

ERIE, PA 16504

814-868-8661

PROJECT NO. VA244-16-J-5508

1/8" = 1'-0"

ARCHITECTURAL WORK - ROOM EE-200

prakszawski Stamp

UP

UP

MAIN TELEPHONE RM

WB-39

GENERAL SUPPLIES

WB-39A

NEW ELECTRICAL

UPS

S A

N

4"-FD-XR

2"

CO

CONNECT 2" SANITARY

TO DRAIN PAN. PROVIDE

2" TYPE "L" COPPER PIPE.

PROVIDE PIPE SLEEVE AND

MAINTAIN FIRE RATING.

2" SAN DISCHARGE

OVER EXISTING

FLOOR DRAIN. PROVIDE

ELBOW AND PIPE EXTENSION

TO FLOOR DRAIN LOCATION.

2"

ALTERNATE UPS

ADDITIONAL FOOTPRINT

PROVIDE PIPE SLEEVE AND

MAINTAIN FIRE RATING.

EXISTING DOMESTIC

WATER PIPING TO

REMAIN.

PROVIDE DRIP PAN CEILING

SYSTEM RUNNING UNDER LENGTH

OF EXISTING PIPES ABOVE NEW

UPS FOOTPRINT. COORDINATE

CEILING SYSTEM WITH APPROVED

UPS SUBMITTAL PRIOR TO

INSTALLATION. REFER TO

SECTION 09 57 56 "LEAK BARRIER

CEILINGS" FOR ADDITIONAL

INFORMATION. COORDINATE AND

TIE CEILING SYSTEM INTO 2" DRAIN

LINE AS SHOWN.

GENERAL PLUMBING NOTES

1. ALL WORK SHOWN IS NEW UNLESS INDICATED OTHERWISE.

2. ALL EXISTING SERVICES ARE SHOWN IN THEIR APPROXIMATE LOCATIONS.

3. CONTRACTOR SHALL DETERMINE THE EXACT LOCATIONS OF ALL UTILITIES BEFORE COMMENCING WORK AND SHALL BE FULLY RESPONSIBLE FOR ANY DAMAGE WHICH MIGHT OCCUR DUE TO THEIR FAILURE TO EXACTLY LOCATE AND PRESERVE ANY SERVICES, INCLUDING WORK IN EXISTING PIPE CHASES.

4. ALL EXISTING PLUMBING LINES, RISERS, ETC. ENCOUNTERED DURING ALTERATIONS, WHETHER INDICATED OR NOT, SHALL BE DETERMINED TO BE ACTIVE OR INACTIVE BY THIS CONTRACTOR, PRIOR TO COMMENCING ANY WORK. IF LINES ARE ACTIVE THEY SHALL BE OFFSET AS REQUIRED AND RECONNECTED AT THEIR ORIGINAL LOCATIONS. OFFSETS SHALL BE OF THE SAME SIZE AND MATERIAL AS EXISTING, INCLUDING ANY INSULATION. REMOVE ALL USELESS AND INACTIVE PIPING BACK TO THE MAIN, STACK OR RISER. AND CAP. ALL USELESS HOLES IN WALLS AND CEILINGS SHALL BE PATCHED TO MAINTAIN FIRE RATING. ALL SUCH

WORK SHALL BE RECORDED ON THE "RECORD" DRAWINGS.

5. THE DRAWINGS ARE DIAGRAMMATIC. THE CONTRACTOR MUST FIELD VERIFY ACTUAL CONDITIONS AT THE SITE PRIOR TO PROCEEDING WITH THE WORK.

COORDINATE INSTALLATION OF ALL NEW PIPING, EQUIPMENT, ETC. WITH ALL OTHER TRADES.

6. PATCH ALL OPENINGS IN EXISTING CONSTRUCTION WHERE PLUMBING PIPING HAS BEEN REMOVED, OR WHERE PLUMBING PIPING TO REMAIN IS NOT SEALED.

MAINTAIN EXISTING RATING.

7. COORDINATE LOCATIONS OF FLOOR DRAINS IN MECHANICAL ROOM WITH ACTUAL EQUIPMENT BEING INSTALLED.

ALL HORIZONTAL SANITARY DRAINAGE PIPING IS PITCHED AT 1/4"/FT UP TO 3" DIA. , 1/8"/FT FOR 4" DIA. TO 8" DIA., LARGER SIZES AS NOTED. ALL HORIZONTAL STORM

DRAINAGE PIPING IS PITCHED AT 1/8"/FT.

8. THE PLUMBING DRAWINGS DO NOT INDICATE ALL STRUCTURAL BEAMS, COLUMNS OR EXACT SIZES. SOME DEVIATIONS TO THE PIPING LAYOUT MAY BE REQUIRED.

COORDINATE ACTUAL LOCATIONS OF THE PLUMBING LINES DURING CONSTRUCTION.

PLUMBING SYMBOLS LEGEND

F-1, F-2, ETC. PLUMBING FIXTURE TYPE- SEE SPECIFICATION

CAP

DROP

RISE

CO

INDICATES POINT OF CONNECTION TO EXISTING

CLEANOUT AT CEILING (CO) OR WALL (WCO)

SANITARY PIPE

INDICATES POINT OF DEMOLITION

DRAWING KEYNOTE - PLAN / ELEVATION DEMO

DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK

SAN

DOMESTIC WATER PIPING (HOT WATER SUPPLY)

MAIN TELEPHONE RM

WB-39

ELEC SWITCHGEAR

WB-37

COMPUTER RM

B-20

GENERAL SUPPLIES

WB-39A

POLICE

WB-38

WB-40D

WB-40E

MECH ROOM

B-02

D

D

D

D D

D

D

D

D

DRY ALARM VALVE

WALL MOUNTED

AIR COMPRESSOR

CONNECT TO

EXISTING WET PIPE

SYSTEM IN

MECHANICAL ROOM.

EXTEND 2" BRANCH

TO NEW DRY ALARM

VALVE.

SPR

XR

EXISTING TAMPER

SWITCH AND ZONE

CONTROL VALVE.

F-DM

FIRE PROTECTION SYMBOLS

F

D

FIRE LINE

SEMI-RECESSED SPRINKLER

UPRIGHT SPRINKLER W/ GUARD

ZONE CONTROL VALVE

RISE

DROP

CAP

TS

TAMPER SWITCH

FIRE DEPARTMENT HOSE VALVEFDHV

FIRE LINE TO BE DEMOLISHED

CONNECT TO EXISTING PIPING THIS POINT

REMOVE EXISTING PIPING TO THIS POINT

DRY SPRINKLER LINE

EXISTING TO REMAINXR

DRAWING KEYNOTE - PLAN / ELEVATION DEMO

DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK

MAIN TELEPHONE RM

WB-39

GENERAL SUPPLIES

WB-39A

MAIN TELEPHONE RM

WB-39

GENERAL SUPPLIES

WB-39A

DEMOLITION KEYNOTES

EXISTING LIEBERT CHALLENGER UNIT RELOCATED AS NEEDED IF

ALTERNATE 1 IS ACCEPTED IN ORDER TO ALLOW FOR INSTALLATION OF

NEW UPS. IF ALTERNATE 1 IS NOT ACCEPTED EXISTING LIEBERT

CHALLENGER UNIT REMAINS IN SAME LOCATION.

IF ALTERNATE 1 IS ACCEPTED EXISTING SHUT-OFF VALVES THAT EXIST IN

GLYCOL SUPPLY/RETURN PIPES ABOVE FLOOR CAN BE USED TO ISOLATE

THE LIEBERT CHALLENGER UNIT.

NEW WORK KEYNOTES

IF ALTERNATE 1 IS ACCEPTED THEN EXISTING LIEBERT CHALLENGER UNIT

SHALL BE RELOCATED AS SHOWN. EXTEND UNDERFLOOR PIPING TO NEW

LOCATION AS SHOWN. IF ALTERNATE 1 IS NOT ACCEPTED EXISTING PIPING

TO LIEBERT CHALLENGER UNIT REMAINS UNCHANGED.

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com

AE Works Project Number:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

4/

/2

:4 4:

A

M ERIE VAMC - EXPAND EMERGENCY

POWER GENERATION - PHASE II

VA244-16-J-5508

CJC MEW/CJC

135 E 38TH ST, ERIE PA 16504

P/FP/H001

PLUMBING, FP AND HVAC PLAN

04/12/17 100

16030

BID DOCUMENTS

1/8" = 1'-0"

PARTIAL BASEMENT FLOOR PLUMBING PLAN

1/8" = 1'-0"

PARTIAL BASEMENT FLOOR FIRE PROTECTION PLAN

1/8" = 1'-0"

PARTIAL BASEMENT FLOOR PLAN - HVAC

1/8" = 1'-0"

PARTIAL BASEMENT FLOOR PLAN - EXISTING HVAC

PLUMBING FIRE PROTECTION HVAC

NORTH

PROJECT

THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.

RECEPTACLES, FURNITURE FEEDS

THE ABOVE MOUNTING ELEVATIONS ARE TO CENTER OF DEVICE AND SHALL BE ADHERED TO

UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS AND/OR

SPECIFICATIONS.

IN FLOOR JUNCTION BOXES FLUSH TO

FINISHED FLOOR (FF)

IN MASONRY CONSTRUCTION THE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO THE

NEAREST BLOCK OR BRICK COURSING.

COORDINATE THE INSTALLATION AND MOUNTING ELEVATIONS OF ALL EQUIPMENT, DEVICES,

CONTROLS AND APPURTENANCES WITH ARCHITECT AND ALL AFFECTED TRADES PRIOR TO

INSTALLATION. DOCUMENT ALL MOUNTING ELEVATIONS FOR ALL EQUIPMENT, DEVICES,

CONTROLS AND APPURTENANCES AT THE TIME OF SHOP DRAWING SUBMITTAL.

3.

2.

1.

0'-0"

1'-5" A.F.F.

STANDARD MOUNTING HEIGHTS

RECESSED LIGHTING FIXTURES, CEILING

MOUNTED RECEPTACLES, INDICATING LIGHTS,

ETC.

CEILING

ELECTRICAL SYMBOLS LEGEND

ABOVE COUNTER DEVICES, GFI RECEPTACLES IN

RESTROOMS.

3'-6" A.F.F.

WALL SWITCHES, THERMOSTATS, CONTROL DEVICES,

TO CENTER OF BOX

4'-0" A.F.F.

TOP OF PANELBOARDS (<6'-0" TALL)6'-0" A.F.F.

TOP MOST PORTION OF OPERATING HANDLE OF

DISCONNECT SWITCHES / CIRCUIT BREAKERS

6'-6" A.F.F.

WALL MOUNTED LIGHTS IN STAIRS, MECH ROOMS,

ETC.

7'-0" A.F.F.

DRAWING KEYNOTE - DEMOLITION

EQUIPMENT TAG

REVISION TRIANGLE WITH REVISION CLOUD

INDICATED MOUNTED ABOVE COUNTERTOP (REFER TO STANDARD

MOUNTING HEIGHTS DETAIL ON THIS SHEET)

ELECTRICAL DEMOLITION

EXISTING TO REMAIN - DEVICE SHALL REMAIN IN WORKING ORDER.

REMOVE AND REPLACE WITH NEW - EXISTING BACKBOX AND WIRING SHALL REMAIN,

RECONNECT NEW DEVICE TO EXISTING CIRCUIT.

REMOVE AND RELOCATE - DISCONNECT DEVICE, MODIFY AND EXTEND FEED TO NEW LOCATION.

REMOVE COMPLETLY - REMOVE DEVICE, CONDUIT, AND WIRING BACK TO SOURCE.

ETR

RN

RR

RC

EXISTING TO REMAIN

NEW WORK

DEMOLITION

DISCONNECT SWITCH. NEMA 1, 20A/1PH/120V UNLESS OTHERWISE

NOTED.

X - Y

RECEPTACLE TAG:

X= PANEL NAME

Y= CIRCUIT NUMBER

RISER DIAGRAM/SINGLE LINE SYMBOLS

XXXA

FUSED

SWITCH

NON-FUSED

SWITCH

MOLDED CASE

CIRCUIT

BREAKER

XXXA/3P XXXA/3P

ST

XXXA/3P

ST

XXXA/3P XXXA/3P

ST

XXXA/3P XXXA/3P

ST

MOLDED CASE

CIRCUIT

BREAKER W/

SHUNT TRIP

XXXA/3P

MOLDED CASE

CIRCUIT

BREAKER W/

SHUNT TRIP &

AUXILIARY

CONTACT

XXXA/3P

ST

XXXA

FUSED SWITCH

W/ AUXILIARY

CONTACTS

NON-FUSED

SWITCH W/

AUXILIARY

CONTACTS

FUSED DOUBLE THROW

SWITCH

XXXA

XXXA

M

UTILITY

METER

CT

CABINET

PANEL

VOLTAGE

AMPACITY

MCB OR MLO

TAG

AMPACITY

FSS

NEMA

M

AUTOMATIC TRANSFER SWITCH

REFER TO DRAWINGS FOR AMPACITY, POLES, BYPASS, ETC.

TAG

AMPACITY

NFSS

NEMA

TAG

AMPACITY

CB

NEMA

ELECTRICAL PANELBOARD

REFER TO DRAWINGS FOR VOLTAGE, AMPACITY, CIRCUIT

QUANTITY, RATINGS, AND SPECIAL FEATURES

STEP-DOWN TRANSFORMER

REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND

SPECIAL REQUIREMENTS

FUSED SAFETY

SWITCH

NON-FUSED SAFETY

SWITCH

ENCLOSED CIRCUIT

BREAKER

SINGLE PHASE MOTOR

REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND

SPECIAL REQUIREMENTS

UTILITY METER

REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND

SPECIAL REQUIREMENTS

XXXA

XXXA/3P

XXXAF

LSIG

S

IZ

E

F V

N R

X

DRAW-OUT

MEDIUM VOLTAGE

CIRCUIT BREAKER

DRAW-OUT

LOW VOLTAGE

CIRCUIT BREAKER

COMBINATION

MOTOR STARTER

SURFACE MOUNTED ELECTRICAL PANELBOARD

RECESSED MOUNTED ELECTRICAL PANELBOARD

N E

W

E X

IS

T

IN

G

N E

W

E X

IS

T

IN

G

ADA INSTALLATION GUIDELINES

34"

46"

MAX.

(NOTE #2)

44"

MAX.

(FOR 20-25")

(NOTE #2)

10-24" 25" MAX.

48"

MAX.

(FOR 20")

(NOTE #2)

OBSTRUCTED HIGH

SIDE REACH

OBSTRUCTED HIGH

FORWARD REACH

48"

MAX.

(NOTE #2)

10"

MAX.

15"

MIN.

48"

MAX.

(NOTE #2)

15"

MIN.

OBSTRUCTED

SIDE REACH

OBSTRUCTED

FORWARD REACH

NOTES:

1. THESE GUIDLINES SHALL BE USED FOR THE INSTALLATION OF THE FOLLOWING DEVICES:

- WALL SWITCHES

-CONTROL SWITCHES

-RECEPTACLES

-VISUAL DISPLAY TOUCH PANELS

2. NOTE THAT THIS HEIGHT IS TO THE TOP-MOST PART OF THE DEVICE THAT AN OCCUPANT

REQUIRES ACCESS TO.

ANNOTATION SYMBOLS

DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK

M

THREE PHASE MOTOR

REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND

SPECIAL REQUIREMENTS

WIRING CONVENTION

1. THE COMPLETE BRANCH WIRING SYSTEM IS NOT SHOWN ON THE DRAWINGS. AN

ABBREVIATED FORMAT IS USED TO INDICATE WHICH FIXTURES/DEVICES ARE CONNECTED

TO A COMMON CIRCUIT OR SWITCH. THIS IS PROVIDED AS A GUIDE TO THE CONTRACTOR TO

ILLUSTRATE CIRCUITS AND CONTROL INTENT. ACTUAL WIRING MAY BE DIFFER DUE TO FIELD

CONDITIONS.

2. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL NEUTRAL WIRE. SHARING OF NEUTRALS IS

PROHIBITED. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL GROUND WIRE. USE OF THE

CONDUIT SYSTEM FOR THE GROUND PATH IS PROHIBITED.

3. ALL CIRCUITS IN PATIENT AREAS SHALL HAVE A REDUNDANT GREEN GROUND CONDUCTOR.

CONDUCTOR SHALL BE BONDED TO THE GROUND BUS IN THE PANELBOARD AND THE METAL

BOX AT THE DEVICE PER NEC 517.

4. IF THE CONTRACTOR CHOOSES TO RUN MULTIPLE CURRENT CARRYING CONDUCTORS IN A

COMMON CONDUIT, THE NEC DERATING RULES SHALL BE FOLLOWED, AND

CONDUCTORS/CONDUIT SHALL BE UPSIZED ACCORDINGLY, INCLUDING THE GROUND WIRE.

5. CONDUCTORS INSTALLED ON ROOFTOPS SHALL HAVE THEIR SIZES INCREASED PER NEC

SECTION 310.15 DERATING FACTORS. UPSIZE CONDUCTORS AND CONDUIT ACCORDINGLY,

INCLUDING THE GROUND WIRE.

6. CONDUCTOR SIZES ARE BASED ON NEC SECTION 310.15, 60° C TEMPERATURE RATING FOR

UP TO #1 AWG, AND 75° C FOR #1/0 AND LARGER.

7. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS (AS APPLICABLE):

120/208 VOLT SYSTEM 277/480 VOLT

SYSTEM

PHASE A = BLACK PHASE A = BROWN

PHASE B = RED PHASE B = ORANGE

PHASE C = BLUE PHASE C = YELLOW

NEUTRAL = WHITE NEUTRAL = GREY

GROUND = GREEN GROUND = GREEN

SINGLE PHASE HOMERUN TO PANELBOARD

WIRING SYMBOLOGY

THIS PROJECT WILL REQUIRE SHUT-DOWNS TO THE NORMAL POWER SYSTEM OF THE HOSPITAL, WHICH WILL REQUIRE SECOND OR THIRD SHIFT WORK, AS WELL AS WEEKEND WORK. THE CONTRACTOR SHALL COORDINATE THIS WORK

WITH THE COR, AND PLAN HIS WORK ACCORDINGLY.

DURING ALL UTILITY SHUT-DOWNS OF THE NORMAL POWER SYSTEM, THE CONTRACTOR SHALL HAVE A 4160V EMERGENCY GENERATOR ON SITE WITH 24 HOURS OF FUEL. THE CONTRACTOR SHALL HAVE SUITABLE TEMPORARY CABLES NEEDED TO PROVIDE EMERGENCY CONNECTIONS TO THE SWITCHGEAR IN THE EVENT THERE IS A PROBLEM.

THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF.THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE COR SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE COR AND ENGINEER FOR SIGN OFF.

1.

UTILITY SHUTDOWNS

2.

3.

NE

N E

XX

WALL MOUNTED VOICE/DATA OUTLET

XX = CABLING CONFIGURATIONS (REFER TO COMMUNICATIONS DETAIL SHEET)

R FIRE ALARM INTERFACE MODULE.

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com

AE Works Project Number:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

3/

/2

:5 1:

A

M ERIE VAMC - EXPAND EMERGENCY

POWER GENERATION - PHASE II

VA244-16-J-5508

IT JZ

135 E 38TH ST, ERIE PA 16504

E001

ELECTRICAL SYMBOLS, ABBREVIATIONS AND

NOTES

04/12/17 100

16030

FULLY SPRINKLERED

BID DOCUMENTS

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL TOP

T TOP

TA THROWAWAY

TAN TANGENT

TC TELECOMMUNICATIONS

CONTRACTOR

TCV TEMPERATURE CONTROL VALVE

TDV TRIPLE DUTY VALVE

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TG TONGUE & GROOVE

TH THERMOMETER

THRES THRESHOLD

TR TEMPERATURE RISE

TRANS TRANSITION

TRANSR TRANSFORMER

TSTAT THERMOSTAT

TV TURNING VANES OR TELEVISION

TYP TYPICAL

UC UNDER CABINET OR UNDER CUT

UFD UNDER FLOOR DUCT

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORIES

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VAL VALVE

VD VOLUME DAMPER

VENT VENTILATION

VERT VERTICAL

VFS VENTURI FLOW STATION

VIF VERIFY IN FIELD

VL VENT LINE

VR VAPOR RETARDER

VS VENT STACK

VTR VENT THROUGH ROOF

W WATT

W/ WITH

W/O WITHOUT

WB WET BULB

WC WALL COVERING

WCL WATER CLOSET

WD WOOD

WF WIDE FLANGE

WFMD WATER FLOW MEASURING DEVICE

WG WALL GUARD OR WATER GAUGE

WHCH WHEEL CHAIR

WIN WINDOW

WMS WIRE MESH SCREEN

WP WEATHERPROOF

WPS WALL PROTECTION SYSTEM

WSCT WAINSCOT

WT WINDOW TREATMENT

WTD WATER TEMPERATURE DROP

WWF WELDED WIRE FABRIC

X DEMO

XN TO BE RELOCATED / NEW LOCATION

XR EXISTING TO REMAIN

ZVB ZONE VALVE BOX

ZVC ZONE VALVE CABINET

LTG LIGHTING

LV LOW VOLTAGE

LVR LOUVER

LWB LEAVING WET BULB

LWC LINEAR WOOD CEILING

LWT LEAVING WATER TEMPERATURE

MAN MANUAL

MAT MIXED AIR TEMPERATURE

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH ONE THOUSAND BTU / HOUR

MC MECHANICAL CONTRACTOR

MC METAL CLAD CABLE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MO MASONRY OPENING

MOD MOTOR OPERATED DAMPER

MONO MONOLITHIC

MTD MOUNTED

MTG HT MOUNTING HEIGHT

MTL METAL

MTLH METAL HALIDE

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

N/A NOT APPLICABLE

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NUMBER OR NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O OXYGEN

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

OPER OPERATED

OPNG OPENING

OPP OPPOSITE

ORD OVERFLOW ROOF DRAIN

PB PULL BOX

PC PLUMBING CONTRACTOR

PD PUMP DISCHARGE

PG PRESSURE GAUGE WITH COCK

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRD PRESSURE DIFFERENTIAL VALVE

PRELIM PRELIMINARY

PRT PRESSURE TAP

PRV PRESSURE REDUCING VALVE

PT PAINT OR POTENTIAL

TRANSFORMER

RO ROUGH OPENING

QT QUARRY TILE

R RADIUS

RA RETURN AIR / RELIEF AIR

RB RUBBER BASE

RC REMOVE COMPLETELY

RD ROOF DRAIN

RE RELOCATE EXISTING

REC RECESSED

RECPT RECEPTACLE

REF REFERENCE

REFL REFLECTOR

REG REGISTER

REINF REINFORCING

REM REMOVE

REQD REQUIRED

RET RETURN

REV REVISE

REX REMOVE EXISTING

RF RESILIENT FLOOR

RFI REQUEST FOR INFORMATION

RGS RIGID GALVANIZED STEEL CONDUIT

RH ROOF HATCH

RM ROOM

RN REMOVE AND REPLACE WITH NEW

RR REMOVE AND REPLACE

RS RAPID START

RV RELIEF VALVE

RWC RAIN WATER CONDUCTOR

SA SUPPLY AIR

SAN SANITARY SEWER ABOVE GROUND

SAN-BXR SANITARY SEWER - BURIED

EXISTING TO REMAIN

SAN-XR SANITARY SEWER ABOVE GROUND -

EXISTING TO REMAIN

SCHED SCHEDULE

SD SMOKE DAMPER OR SMOKE

DETECTOR

SDISP SOAP DISPENSER

SF SQUARE FOOT

SHT SHEET

SHT MTL SHEET METAL

SHTG SHEATHING

SIM SIMILAR

SM SURFACE MOUNTED

SNC SANITARY NAPKIN CABINET

SND SANITARY NAPKIN DISPOSER

SP STANDPIPE OR STATIC PRESSURE

SPC SPECIMEN PASS-THRU CABINET

SPEC SPECIFICATIONS

SPS STATIC PRESSURE SENSOR

SR SERVICE RECEPTOR

SS SOIL STACK

ST PR STATIC PRESSURE

ST STL STAINLESS STEEL

STD STANDARD

STER STERILIZER

STL STEEL

STOR STORAGE

STR STRAINER

STRUCT STRUCTURAL

SUSP SUSPENDED

SW SWITCH

ELEC CAB ELECTRICAL CABINET

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

ENTR ENTRANCE

EO ELECTRICAL OUTLET

EQ EQUAL

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWB ENTERING WET BULB

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX EXAUST AIR

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

XP EXPLOSION PROOF

F/S FIRE / SMOKE DAMPER

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAT FINAL AIR TEMPERATURE

FB FIRE BLANKET

FC FLEXIBLE CONNECTION OR

FOOTCANDLE

FD FLOOR DRAIN OR FIRE DAMPER

FDN FOUNDATION

FDV FIRE DEPARTMENT VALVE

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FH FIRE HOSE

FHC FIRE HOSE CABINET

FHP FULL HEIGHT PARTITION

FHV FIRE HOSE VALVE

FIN FINISH

FIXT FIXTURE

FL FLOW LINE

FLA FULL LOAD AMPERES

FLASH FLASHING

FLEX FLEXIBLE

FLG FLANGE

FLG C FLANGE CONNECTION

FLR FLOOR

FLUOR FLUORESCENT

FP FIRE PROOFING

FRMG FRAMING

FS FLOOR SINK

FSTOP FIRESTOPPING

FT FOOT / FEET

FT HD FEET OF HEAD

FTC FOOTCANDLES

FTG FOOTING

FUR FURRING

G GAS OR ELECTRICAL GROUND

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GEN GENERATOR

GENL GENERAL

GFCI GROUND FAULT CIRCUIT

INTERRUPTOR

GL GLASS

GLV GLOBE VALVE

GND GROUND

GPM GALLONS PER MINUTE

GR GRADE

GRAV GRAVITY

GRD BM GRADE BEAM

GV GATE VALVE

GWB GYPSUM BOARD

H HIGH

HB HOSE BIB

HC HEATING CONTRACTOR

HDCP HANDICAP

HDR HEADER

HDW HARDWARE

HID HIGH INTENSITY DISCHARGE

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HORSE POWER

HPD HIGH PRESSURE DRIP

HPF HIGH POWER FACTOR

HR HANDRAIL

HSKP HOUSEKEEPING

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VELOCITY

HVAC HEATING, VENTILATING, AIR

CONDITIONING

HW HOT WATER

HWD HARD WOOD

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HWS&R HOT WATER SUPPLY AND RETURN

HZ HERTZ

ID INSIDE DIAMETER

IER INVERTED ECCENTRIC REDUCER

IG ISOLATED GROUND

IME INSULATED METAL ENCLOSURE

IN INCH

INCAND INCANDESCENT

INCL INCLUDED

INSUL INSULATION

INT INTERIOR

INTERL INTERLOCK

INV INVERT

ISO ISOLATION

IVS ISOLATED VALVE STATION

J-BOX JUNCTION BOX

JST JOIST

JT JOINT

KO KNOCK OUT

kVA KILOVOLT AMPERE kVAR KILOVAR (REACTANCE) kW KILOWATT kWH KILOWATT HOUR METER

LAT LEAVING AIR TEMPERATURE

LAV LAVATORY

LB POUND

LDB LEAVING DRY BULB

LED LIGHT EMITTING DIODE

LF LINEAR FEET

LIN LINEAR

LOC LOCATION OR LOCATE

LPT LOW POINT

LSDC LINEAR SUPPLY DIFFUSER CEILING

LT LIGHT

& AND

A AIR (CLINICAL)

AAP ALARM ANNUNCIATOR PANEL

AAV AUTOMATIC AIR VENT

AB ANCHOR BOLT

ABV ABOVE

ACC DR ACCESS DOOR

ACFL ACCESS

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICAN DISABILITIES ACT

ADD ADDENDUM

ADDL ADDITIONAL

ADJ ADJUSTABLE

ADMIN ADMINISTRATION

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISHED GRADE

AFMD AIR FLOW MEASURING DEVICE

AHU AIR HANDLING UNIT

AL ALIGN

ALT ALTERNATE

ALUM ALUMINUM

AMP AMPERE

AP ACCESS PANEL

APC ARCHITECTURAL PRECAST

CONCRETE

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASY ASYMMETRIC

ATC AUTOMATIC TEMPERATURE

CONTROL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AWT AVERAGE WATER TEMPERATURE

BAT BATTERY

BC BALANCING COCK OR BARE COPPER

BDD BACKDRAFT DAMPER

BFC BELOW FINISH CEILING

BFE BOTTOM FOOTING ELEVATION

BFG BELOW FINISHED GRADE

BG BUMPER GUARD

BLDG BUILDING

BLKG BLOCKING

BLT BORROWED LIGHT

BLW BELOW

BM BEAM

BO BY OWNER

BOF BY OWNER FUTURE

BOT BOTTOM

BR BRICK

BRG BEARING

BRKR BREAKER

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT UP ROOFING

C CONDUIT

CAB CABINET

CANTL CANTILEVER

CAP CAPACITY

CATV CABLE TELEVISION

CCT CUBICLE CURTAIN TRACK

CCTV CLOSED CIRCUIT TELEVISION

CFH CUBIC FEET / HOUR

CFM CUBIC FEET / MINUTE

CH CHANNEL

CHK V CHECK VALVE

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CHWS&R CHILLED WATER SUPPLY AND

RETURN

CJ CONTROL JOINT

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CL CENTERLINE

CLG CEILING

CLG MTD CEILING MOUNTED

CLR CLR

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUE / CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

COORD COORDINATE

CORR CORRIDOR

CPT CARPET OR CONTROL POWER

TRANSFORMER

CT CERAMIC TILE

CTR CENTER

CU COPPER

CV CONTROL VALVE

CW COLD WATER

D DEPTH OR DEEP

DB DRY BULB

dB DECIBEL

DCW DOMESTIC COLD WATER

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAILS

DF DRINKING FOUNTAIN

DHW DOMESTIC HOT WATER

DIA DIAMETER

DIAG DIAGONAL OR DIAGRAM

DIFF DIFFUSER

DIM DIMENSION

DISC DISCONNECT

DISCH DISCHARGE

DISP DISPENSER

DIST DISTRIBUTION

DIV DIVISION

DL DOWN LIGHT

DN DOWN

DP DISTRIBUTION PANEL

DPR DAMPER

DR DRAIN

DS DOWNSPOUT

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

EDB ENTERING DRY BULB

EF EXHAUST FAN

EIFS EXTERIOR INSULATION AND

FINISHING SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ABBREVIATION LEGEND ELECTRICAL GENERAL NOTES

1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL E SERIES CONTRACT DRAWINGS.

2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET I.E. IF WORK SHOWN I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE

CONTRACTOR IS RESPONSIBLE FOR THAT WORK.

3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED SPECIFICATION SECTIONS FOR THE PROPER

INSTALLATION OF ALL WORK.

4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION SECTIONS

FOR ADDITIONAL REQUIREMENTS.

5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE SATISFACTION OF ALL

CONCERNED TRADES.

6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS AND ALL

AFFECTED TRADES PRIOR TO INSTALLATION.

7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM OF 3/4" UNLESS

OTHERWISE NOTED.

8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE

AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.

9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.

10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.

11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X STAINLESS

STEEL AND RATED FOR THAT APPLICATION.

12 ALL DEVICES, COMPONENTS OR EQUIPMENT INSTALLED ON THE EXTERIOR OF THE FACILITY SHALL BE PROVIDED IN ACCORDANCE WITH ALL MANUFACTURERS' REQUIREMENTS TO ENSURE THE PROPER OPERATION WHEN EXPOSED TO THE ENVIRONMENTAL CONDITIONS AND/OR AVERAGE ANNUAL LOWEST TEMPERATURE THAT

CAN BE ANTICIPATED FOR THE GEOGRAPHIC REGION OF THE FACILITY.

13 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF SPECIALIZED

TOOLS.

14 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.

15 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE CODES

AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

16 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED

ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.

17 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

18 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.

19 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.

20 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS

IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.

21 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.

22 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO PERFORMING

ANY WORK.

23 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED

CEILING AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS.

24 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING AND/OR

BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.

25 THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE OWNER.

26 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORKPERFORMED SHALL BE IN

ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.

27 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH

THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.

28 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE CONTRACTOR

SHALL COORDINATE THESE REQUIREMENTS WITH THE OWNER.

29 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING QUANTITIES OF MATERIALS REQUIRED TO

COMPLETE THE PROJECT.

30 THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.

31 THE CONTRACTOR SHALL PROVIDE ALL NEW OPENINGS IN EXISTING PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY NEW ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS NEW WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES

INSTALLED THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.

32 THE CONTRACTOR SHALL PROTECT ALL EXISTING MATERIALS THAT ARE TO REMAIN IN PLACE FROM DAMAGE. ANY DAMAGE TO EXISTING FINISHES, MATERIALS, ETC., SHALL BE REPLACED BY THE CONTRACTOR TO MATCH THE ADJACENT FINISH.

33 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK. DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.

34 THE CONTRACTOR SHALL PROVIDE ALL TRAFFIC CONTROL, FLAGMEN, SIGNAGE, ETC. WHEN DOING WORK THAT INTERFERES WITH PUBLIC RIGHT-OF-WAY.

35 THE CONTRACTOR SHALL CONTACT THE NATIONAL "811-CALL BEFORE YOU DIG" SYSTEM PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATION WORK. THE

CONTRACTOR SHALL HAVE ALL UTILITIES VERIFIED IN AND AROUND THE EXCAVATION AREA.

36 THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF. THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE OWNER SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP

SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF.

37 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS. NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING

THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS.

38 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE EXISTING AND NEW DISTRIBUTION SYSTEM REQUIRED TO ACCURATLY SIZE

AND RATE THE NEW EQUIPMENT ADDED AS PART OF THIS PROJECT.

39 ARC FLASH LABELS SHALL BE PROVIDED TO ALL NEW EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTORS ARC FLASH STUDY (SEE NOTE 39 ABOVE FOR ADDITIONAL STUDY REQUIREMENTS). ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY, AND RE LABELLED AS

REQUIRED.

40 THESE DRAWINGS DO NOT INDICATED ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES AND EXISTING CONDITIONS.

41 PROVIDE ALL JUNCTION BOXES AND OTHER PULL POINTSAS REQUIRED FOR EASE OF PULLING AND A CODE COMPLIANT INSTALLATION. ALL JUNCTION BOXES AND OTHER

PULL POINTS SHALL BE ACCESSABLE

42 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED, ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL.

43 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRATOR UPSIZES THE CONDUIT AS REQUIRED, AND THE AMPACITY ADJUSTMENTS FROM TABLE 310.15(B)(3)(a) HAVE BEEN APPLIED.

F.E.C

T 7AOANB RQPO S U

N

V

L MK5

5BQA RA 5APA

DF

UP

UP

DN.

MAIN TELEPHONE RM

WB-39

ELEC SWITCHGEAR

WB-37

COMPUTER RM

B-20

ELEC RM

B-13A

STORAGE

WB-36A-1

MAIL ROOM

WB-36-2

WB-36A-5

MED RECORDS

WB-36A-6

WB-36A-7

GENERAL SUPPLIES

WB-39A

POLICE

WB-38

WB-40D

WB-40E

SECURE STORAGE

B-25

WORK ROOM

B-24

GEN STORAGE

B-23

TELE CLOSET

B-22

CHIEF ADP

B-21

CENTRAL OFFICE

B-18

TRAINING

B-19

MECH ROOM

B-02

AIR COND RM

WB-35

WB-34

WB-36A-4

STORAGE

WB-36A-3

NEW 100kVA

UPS

EXISTING

PANEL

C-A

EXISTING

PANEL

C-B

EXISTING

PANEL B-13A

EXISTING

PANEL C-2

EXISTING

UPS

NEW PANEL

MDP-UPS

EXISTING PANELS

TO REMAIN

TO MAIN ELEC

ROOM EE-200

NEW UPS

PANEL B13A2

TO UPS

PP-2

PP-1

PP-1

AIR

COMPRESSOR

R R

DEMOLITION KEYNOTES

DEMOLISH EXISTING UPS SYSTEM ENTIRELY ONCE NEW UPS SYSTEM IS

UP AND RUNNING AND ALL LOADS HAVE BEEN MOVED OVER TO THE NEW

UPS. REMOVE ALL REMOTE CONTROL PANELS AND ALL

INTERCONNECTING WIRING. REMOVE ASSOCIATED FEEDERS AND

CONDUIT.

EXISTING WIREWAY, DISCONNECT, AND ALL ASSOCIATED CONDUIT AND

WIRING SHALL BE REMOVED BACK TO SOURCE.

EXISTING JOHNSON CONTROL CABINET IS SUPPORTED BY UNISTRUT

THAT WILL INTERFERE WITH UPS REMOVAL (DEMO NOTE 1). RELOCATE

CABINET SUCH THAT IT WILL NOT INTERFERE WITH UPS REMOVAL.

EXTEND OR REPLACE WIRING AS NEEDED. ENGAGE JOHNSON

CONTROLS FOR ANY REQUIRED SHUT DOWN OR MODIFICATION TO

CONTROLS SYSTEM TO CARRY OUT THIS WORK.

RELOCATED EXISTING LIGHTING TO MAKE WAY FOR DRIP PAN ABOVE

NEW UPS. EXTEND EXISTING BRANCH CIRCUITS FROM OLD TO NEW

LOCATIONS VIA WIRING METHODS COMPATIBLE WITH EXISTING

INSTALLATION.

EXISTING UPS CONTROL PANEL TO BE REMOVED. REMOVE ALL

INTERCONNECTING CONDUIT AND WIRE. PATCH ALL FINISHES AS

NEEDED.

DEMOLISH FLOORING UNDER FOOTPRINT OF NEW UPS FOR

REPLACEMENT WITH INCREASED WEIGHT RATING FLOORING.

PROTECT ALL UNDERFLOOR CABLING DURING DEMOLITION.

COORDINATE EXTENT OF FLOORING TO BE REMOVED WITH APPROVED

UPS SUBMITTAL PRIOR TO CARRYING OUT ANY WORK.

DEMOLISH PANEL B13A AND ASSOCIATED FEEDER AND CONDUIT. CAP

AND TAG ALL BRANCH CIRCUITS FOR EXTENSION TO NEW PANEL

LOCATION. COORDINATE PHASING OF WORK WITH VA IT PRIOR TO

CARRYING OUT ANY WORK. LOADS ON THIS PANEL SERVE IT

EQUIPMENT AND MAY NEED TEMP POWER OR THE WORK TO BE

CARRIED OUT OFF HOURS.

NEW WORK KEYNOTES

NEW UPS UNIT WITH 60 MINUTES OF FULL LOAD BACKUP TIME.

ALTERNATE SHALL BE TO ADD 123 MINUTE BATTERY CAPACITY EXTENDING

THE FOOTPRINT OF THE OVERALL UNIT. EXISTING RAISED FLOOR SHALL BE

REPLACED TO ALLOW FOR ADDED WEIGHT ON UPS UNIT.

IF ALTERNATE 1 (123 MINUTE RUN TIME UPS) IS ACCEPTED THEN EXISTING

LIEBERT UNIT SHALL BE RELOCATED. EXTEND FEED TO NEW LOCATION AS

REQUIRED. EXISTING DISCONNECT SWITCH TO REMAIN.

USE EXISTING CONDUITS FROM JUNCTION BOX TO EXISTING MAIN ELECTRIC

ROOM ON SECOND FLOOR.

NEW DATA DROP FOR UPS. PROVIDE CAT 6 CABLING FROM DROP TO PATCH

PANEL IN CLOSET B13A. FIELD VERIFY PATCH PANEL CABLING TYPE PRIOR

TO ROUGH-IN.

TIE NEW CONDUITS FOR UPS FEED INTO EXISTING PULLBOX LOCATED IN

CRAWLSPACE UNDER AMBULATORY. LOCATION OF PULLBOX SHOWN HERE

IS NOT EXACT AND IS SHOWN HERE FOR SCOPE. RUN NEW CONDUIT FROM

PULLBOX TO NEW UPS ABOVE CEILING.

UPS TO BE TIED INTO EXISTING METASYS BMS SYSTEM. CONFIRM QTY OF

ALARM POINTS WITH THE VA PRIOR TO BMS SYSTEM PROGRAMMING. AS A

MINIMUM, PICK UP ALL STANDARD UPS ANNUNCIATOR SIGNALS OUTLINED IN

THE UPS SPECIFICATION.

PROVIDE NEW FLOORING SYSTEM RATED TO CARRY UPS SYSTEM WEIGHT.

COORDINATE FOOTPRINT OF NEW FLOORING SYSTEM WITH UPS SUBMITTAL

PRIOR TO INSTALLATION. FLOORING DIRECTLY UNDER UPS TO BE REPLACED

TO THE NEAREST TILE. DO NOT CUT OFF SERVICE TO UNDERFLOOR

CABLING. REROUTE CABLING AS REQUIRED TO FACILITATE FLOORING

SYSTEM INSTALLATION. REFER TO SPECIFICATION SECTION 09 69 00

"ACCESS FLOORING" FOR ADDITIONAL REQUIREMENTS.

PROVIDE NEW 20A/1P CIRCUIT BREAKER IN EXISTING PANELBOARD AS

INDICATED. BREAKER TO BE COMPATIBLE WITH EXISTING INSTALLATION.

PROVIDE TWO NEW FIRE ALARM INTERFACE MODULES AND CONNECT TO

DRY SPRINKLER SYSTEM CONTROL PANEL. FIRE ALARM TO MONITOR

SUPERVISORY AND ALARM CONNECTIONS OF NEW DRY ALARM SYSTEM.

PROVIDE MODULES COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM AND

TIE INTO EXISITING SYSTEM AT SUITABLE LOCATION. PROVIDE ALL PARTS

AND PROGRAMMING REQUIRED TO CONNECT MODULES INTO THE EXISTING

FIRE ALARM SYSTEM.

EXTEND 20x20A BRANCH CIRCUITS FROM OLD PANEL B13A TO NEW 100A

PANEL LOCATION AS SHOWN.

NEW 42CCT, 100A, 208/120V PANELBOARD. PROVIDE QTY OF BREAKERS

REQUIRED FOR EXISTING CIRCUITS RECONNECTED TO THIS PLANEL, PLUS

AN ADDITIONAL 20x20A/1P SPARE BREAKERS.

PROVIDE NEW 42CCT/400A/208V/3P4W/10k AIC PANELBOARD. PROVIDE 3

POLE BREAKERS FOR ALL EXISTING AND NEW LOAD CENTERS AS

IDENTIFIED ON THIS PLAN AND SHOWN ON THE SINGLE LINE DIAGRAM.

PROVIDE 4xSPARE 20A/1P BREAKERS AND THE REMAINDER OF THE PANEL

AS BLANK SPACES.

RR RR

4 4

CP

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com

AE Works Project Number:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

3/

/2

:5 1:

A

M ERIE VAMC - EXPAND EMERGENCY

POWER GENERATION - PHASE II

VA244-16-J-5508

IT JZ

135 E 38TH ST, ERIE PA 16504

E100

PARTIAL BASEMENT FLOOR POWER PLAN

04/12/17 100

16030

FULLY SPRINKLERED

BID DOCUMENTS

NORTH

PROJECT

1/8" = 1'-0"

PARTIAL BASEMENT FLOOR POWER PLAN

1/8" = 1'-0"

PARTIAL BASEMENT FLOOR DEMOLITION PLAN

ATS-IT

ATS-EL

MDP-2MDP-1

100kVA IT

VOLTAGE

REGULATOR

MAIN ELEC RM

EE-200

150kVA ELEV

VOLTAGE

REGULATOR

UNOCCUPIED

VENT ROOM

STAIR

UNOCCUPIED

ELEV PENTHOUSE

EXISTING

ELEV MOTOR

EXISTING

ELEV MOTOR

EXISTING

ELEV MOTOR

EXISTING

HVAC UNIT

EXISTING

PANEL A

EXISTING

PANEL A-1

EXISTING

ELEV DISC

SWITCHES

EXISTING ELEV

TRANSFORMER

EXISTING ELEV

CONTROLLERS

EXISTING

PANEL A

EXISTING

JUNCTION

BOX

EXISTING

PANEL A-1

EXISTING

ELEV DISC

SWITCHES

UNOCCUPIED

UNOCCUPIED

ELEV PENTHOUSE

STAIR

VENT ROOM

EXISTING ELEV

TRANSFORMER

EXISTING ELEV

CONTROLLERS

EXISTING

ELEV MOTOR

EXISTING

ELEV MOTOR

EXISTING

ELEV MOTOR

EXISTING

HVAC UNIT

NEW WORK KEYNOTES

MODIFY EXISTING ATS-IT WITH DOUBLE LUGS, REFER TO RISER DIAGRAM.

REMOVE EXISTING JUNCTION BOX AND ASSOCIATED CONDUIT/WIRE.

INTERCEPT CONDUIT ON FLOOR BELOW AND EXTEND NEW FEED TO NEW

VOLTAGE REGULATOR. REFER TO RISER DIAGRAM.

DEMOLITION KEYNOTES

WALL AS INDICATED TO BE DEMOLISHED, REFER TO ARCHITECTURAL

DRAWINGS FOR MORE INFORMATION. REMOVE ALL CONDUIT, WIRING

AND ELECTRICAL DEVICES PRIOR TO DEMOLITION. CEILING SYSTEM

ALSO TO BE REMOVED, DEMOLISH ALL LIGHT FIXTURES AND

ASSOCIATED WIRING FROM WITHIN THE AREA OF DEMOLITION. PATCH

AND MAINTAIN ALL CIRCUITS TO EXISTING TO REMAIN DEVICES

AFFECTED BY THE DEMOLITION WORK VIA WIRING METHODS

COMPATIBLE WITH THE EXISTING INSTALLATION.

REMOVE ALL ABANDONED CONDUIT AND WIRE AND FIRE STOP ALL

PENITRATIONS.

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com

AE Works Project Number:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

/2

/2

:5

:3

A

M ERIE VAMC - EXPAND EMERGENCY

POWER GENERATION - PHASE II

VA244-16-J-5508

IT JZ

135 E 38TH ST, ERIE PA 16504

E101

PARTIAL SECOND FLOOR AND PENTHOUSE

POWER PLANS

04/12/17 100

16030

FULLY SPRINKLERED

BID DOCUMENTS

NORTH

PROJECT

1/8" = 1'-0"

PARTIAL SECOND FLOOR POWER PLAN

1/8" = 1'-0"

PENTHOUSE POWER PLAN

1/8" = 1'-0"

PENTHOUSE DEMOLITION PLAN

EXISTING MDP-1

EXISTING

ATS-IT

EXISTING

ATS-EL

EXISTING

400A

PANEL

EXISTING

LAB AHU

SECOND FLOOR ELEC RM

FIRST FLOOR

BASEMENT FLOOR

ELEV PENTHOUSE

EXISTING EMDP-1

EXISTING

PANEL

WB-H

10 TON

LIEBERT

UNIT

100kVA

ELEC VOLTAGE

REGULATOR

1ST FLOOR

HR DEPT

PBX RM WB-39

NEW

400A

PANEL

MDP-UPS

NEW

100kVA UPSEXISTING

PANEL

C-A

SERVER RM

B20

EXISTING

PANEL

C-B

SERVER RM

B20

EXISTING

PANEL

C-2

MAIL RM

EXISTING

PANEL

B13A

B13A

EXISTING

65kVA UPS

EXISTING

PULL BOX

NEW PULL BOX TO

INTERCEPT EXISTING

CONDUITS

EXISTING (2) 3"

CONDUITS

EIGHTH FLOOR MECH ROOM

B13A2

NEW

100A

OUTPUT

TRANSFORMER

MAINTENANCE

BYPASS SWITCH

BYPASS INPUT BREAKER

FUSE

RECTIFIER

INVERTER

BATTERY BREAKER

BATTERY CABINET UPS SIDECAR OUTPUT SECTION

TO MDP-UPS

FROM IT SYSTEM EVR

BATTERY

CONVERTER

60 MINUTES UPS INTERNAL WIRING DIAGRAM

B13A

EXISTING

600A

ELEV

PANEL

150KVA

ELEC VOLTAGE

REGULATOR

EXISTING

JBOX

INTERCEPT EXISTING FEED TO

ELEV PANEL IN 8TH FLOOR MECH

ROOM. PROVIDE PULLBOX AND

EXTEND NEW FEED TO NEW

VOLTAGE REGULATOR AS SHOWN.

UTILIZE AND RESEAL EXISTING

CONDUIT PENITRATION.

AMPS 1PH, 2W, & GROUND 1PH, 3W, & GROUND 3PH, 3W, & GROUND 3PH, 4W, & GROUND 3PH, 4W, & SERVICE GROUND AMPS 3PH, 5W, & GROUND (200% NEUTRAL)AMPSAMPSAMPSAMPS

(2) #12 & 1#12 G IN 3/4" C15

(2) #12 & 1#12 G IN 3/4" C

(2) #10 & 1#10 G IN 3/4" C

(2) #10 & 1#10 G IN 3/4" C

(2) #8 & 1#10 G IN 3/4" C

(2) #8 & 1#10 G IN 3/4" C

(2) #6 & 1#10 G IN 3/4" C

(2) #6 & 1#10 G IN 3/4" C

(2) #4 & 1#10 G IN 1" C

(2) #4 & 1#8 G IN 1" C

(2) #3 & 1#8 G IN 1" C

(2) #2 & 1#8 G IN 1" C

(2) #1 & 1#8 G IN 1 1/4" C

ELECTRICAL FEEDER SCHEDULE

2 3 4 4S 5

(3) #12 & 1#12 G IN 3/4" C15

(3) #12 & 1#12 G IN 3/4" C

(3) #10 & 1#10 G IN 3/4" C

(3) #10 & 1#10 G IN 3/4" C

(3) #8 & 1#10 G IN 3/4" C

(3) #8 & 1#10 G IN 3/4" C

(3) #6 & 1#10 G IN 3/4" C

(3) #6 & 1#10 G IN 3/4" C

(3) #4 & 1#10 G IN 1" C

(3) #4 & 1#8 G IN 1 1/4" C

(3) #3 & 1#8 G IN 1 1/4" C

(3) #2 & 1#8 G IN 1 1/4" C

(3) #1 & 1#8 G IN 1 1/2" C

(4) #12 & 1#12 G IN 3/4" C15

(4) #12 & 1#12 G IN 3/4" C

(4) #10 & 1#10 G IN 3/4" C

(4) #10 & 1#10 G IN 3/4" C

(4) #8 & 1#10 G IN 3/4" C

(4) #8 & 1#10 G IN 3/4" C

(4) #6 & 1#10 G IN 1" C

(4) #6 & 1#10 G IN 1" C

(4) #4 & 1#10 G IN 1 1/4" C

(4) #4 & 1#8 G IN 1 1/4" C

(4) #3 & 1#8 G IN 1 1/4" C

(4) #2 & 1#8 G IN 1 1/4" C

(4) #1 & 1#8 G IN 1 1/2" C

(3) #1 & 1#6 G IN 1 1/2" C

(3) #1/0 & 1#6 G IN 1 1/2" C

(3) #2/0 & 1#6 G IN 2" C

(3) #3/0 & 1#6 G IN 2" C

(3) #4/0 & 1#4 G IN 2" C

(3) #250 KCMIL & 1#4 G IN 2 1/2" C

(3) #350 KCMIL & 1#4 G IN 2 1/2" C

(3) #500 KCMIL & 1#3 G IN 3" C

(3) #500 KCMIL & 1#3 G IN 3" C

2 SETS OF (3) #4/0 & 1#2 G IN 2" C

2 SETS OF (3) #250 KCMIL 1#2 G IN 2 1/2" C

2 SETS OF (3) #350 KCMIL & 1#1 G IN 3" C

2 SETS OF (3) #500 KCMIL & 1#1/0 G IN 3" C

(3) #1 & 1#6 G IN 1 1/2" C

(3) #1/0 & 1#6 G IN 1 1/2" C

(3) #2/0 & 1#6 G IN 2" C

(3) #3/0 & 1#6 G IN 2" C

(3) #4/0 & 1#4 G IN 2" C

(3) #250 KCMIL & 1#4 G IN 2 1/2" C

(3) #350 KCMIL & 1#4 G IN 2 1/2" C

(3) #500 KCMIL & 1#3 G IN 3" C

(3) #500 KCMIL & 1#3 G IN 3" C

2 SETS OF (3) #4/0 & 1#2 G IN 2" C

2 SETS OF (3) #250 KCMIL 1#2 G IN 2 1/2" C

2 SETS OF (3) #350 KCMIL & 1#1 G IN 3" C

2 SETS OF (3) #500 KCMIL & 1#1/0 G IN 3" C

(4) #1 & 1#6 G IN 1 1/2" C

(4) #1/0 & 1#6 G IN 1 1/2" C

(4) #2/0 & 1#6 G IN 2" C

(4) #3/0 & 1#6 G IN 2" C

(4) #4/0 & 1#4 G IN 2" C

(4) #250 KCMIL & 1#4 G IN 2 1/2" C

(4) #350 KCMIL & 1#4 G IN 2 1/2" C

(4) #500 KCMIL & 1#3 G IN 3" C

(4) #500 KCMIL & 1#3 G IN 3" C

(3) #12 & 1#12 G IN 3/4" C

(3) #12 & 1#12 G IN 3/4" C

(3) #10 & 1#10 G IN 3/4" C

(3) #10 & 1#10 G IN 3/4" C

(3) #8 & 1#10 G IN 3/4" C

(3) #8 & 1#10 G IN 3/4" C

(3) #6 & 1#10 G IN 3/4" C

(3) #6 & 1#10 G IN 3/4" C

(3) #4 & 1#10 G IN 1" C

(3) #4 & 1#8 G IN 1 1/4" C

(3) #3 & 1#8 G IN 1 1/4" C

(3) #2 & 1#8 G IN 1 1/4" C

(3) #1 & 1#8 G IN 1 1/2" C

3 SETS OF (3) #350 KCMIL & 1#2/0 G IN 3" C

3 SETS OF (3) #500 KCMIL & 1#2/0 G IN 3" C

4 SETS OF (3) #350 KCMIL & 1#3/0 G IN 3" C

5 SETS OF (3) #500 KCMIL & 1#4/0 G IN 3" C

6 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

7 SETS OF (3) #500 KCMIL & 1#350 KCMIL G IN 3 1/2" C

8 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

11 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

10 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

2 SETS OF (4) #4/0 & 1#2 G IN 2 1/2" C

2 SETS OF (4) #250 KCMIL 1#2 G IN 3" C

2 SETS OF (4) #350 KCMIL & 1#1 G IN 3" C

2 SETS OF (4) #500 KCMIL & 1#1/0 G IN 3 1/2" C

3 SETS OF (4) #350 KCMIL & 1#2/0 G IN 3" C

3 SETS OF (4) #500 KCMIL & 1#2/0 G IN 3 1/2" C

4 SETS OF (4) #350 KCMIL & 1#3/0 G IN 3" C

5 SETS OF (4) #500 KCMIL & 1#4/0 G IN 3 1/2" C

6 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

7 SETS OF (4) #500 KCMIL & 1#350 KCMIL G IN 3 1/2" C

8 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

11 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

10 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

(4) #12 & 1#8 G IN 3/4" C

(4) #12 & 1#8 G IN 3/4" C

(4) #10 & 1#8 G IN 3/4" C

(4) #10 & 1#8 G IN 3/4" C

(4) #8 & 1#8 G IN 1" C

(4) #8 & 1#8 G IN 1" C

(4) #6 & 1#8 G IN 1" C

(4) #6 & 1#8 G IN 1" C

(4) #4 & 1#8 G IN 1 1/4" C

(4) #4 & 1#8 G IN 1 1/4" C

(4) #3 & 1#8 G IN 1 1/4" C

(4) #2 & 1#8 G IN 1 1/4" C

(4) #1 & 1#6 G IN 1 1/2" C

(4) #1 & 1#6 G IN 1 1/2" C

(4) #1/0 & 1#6 G IN 1 1/2" C

(4) #2/0 & 1#4 G IN 2" C

(4) #3/0 & 1#4 G IN 2" C

(4) #4/0 & 1#2 G IN 2" C

(4) #250 KCMIL & 1#2 G IN 2 1/2" C

(4) #350 KCMIL & 1#2 G IN 2 1/2" C

(4) #500 KCMIL & 1#1/0 G IN 3" C

(4) #500 KCMIL & 1#1/0 G IN 3" C

2 SETS OF (4) #4/0 & 1#1/0 G IN 2 1/2" C

2 SETS OF (4) #250 KCMIL 1#2/0 G IN 3" C

2 SETS OF (4) #350 KCMIL & 1#2/0 G IN 3" C

2 SETS OF (4) #500 KCMIL & 1#2/0 G IN 3 1/2" C

3 SETS OF (4) #350 KCMIL & 1#2/0 G IN 3" C

3 SETS OF (4) #500 KCMIL & 1#2/0 G IN 3 1/2" C

4 SETS OF (4) #350 KCMIL & 1#3/0 G IN 3" C

5 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C

6 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C

7 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C

8 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C

11 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C

10 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C

(5) #12 & 1#12 G IN 3/4" C

(5) #12 & 1#12 G IN 3/4" C

(5) #10 & 1#10 G IN 3/4" C

(5) #10 & 1#10 G IN 3/4" C

(5) #8 & 1#10 G IN 1" C

(5) #8 & 1#10 G IN 1" C

(5) #6 & 1#10 G IN 1" C

(5) #6 & 1#10 G IN 1" C

(5) #4 & 1#10 G IN 1 1/4" C

(5) #4 & 1#8 G IN 1 1/4" C

(5) #3 & 1#10 G IN 1 1/4" C

(5) #2 & 1#8 G IN 1 1/4" C

(5) #1 & 1#8 G IN 1 1/2" C

(5) #1 & 1#6 G IN 1 1/2" C

(5) #1/0 & 1#6 G IN 1 1/2" C

(5) #2/0 & 1#6 G IN 2" C

(5) #3/0 & 1#6 G IN 2" C

(5) #4/0 & 1#4 G IN 2" C

(5) #250 KCMIL & 1#4 G IN 2 1/2" C

(5) #350 KCMIL & 1#4 G IN 2 1/2" C

(5) #500 KCMIL & 1#3 G IN 3" C

(5) #500 KCMIL & 1#3 G IN 3" C

2 SETS OF (5) #4/0 & 1#2 G IN 2 1/2" C

2 SETS OF (5) #250 KCMIL 1#2 G IN 3" C

2 SETS OF (5) #350 KCMIL & 1#1 G IN 3" C

2 SETS OF (5) #500 KCMIL & 1#1/0 G IN 3 1/2" C

3 SETS OF (5) #350 KCMIL & 1#2/0 G IN 3" C

3 SETS OF (5) #500 KCMIL & 1#2/0 G IN 3 1/2" C

4 SETS OF (5) #350 KCMIL & 1#3/0 G IN 3" C

5 SETS OF (5) #500 KCMIL & 1#4/0 G IN 3 1/2" C

6 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

7 SETS OF (5) #500 KCMIL & 1#350 KCMIL G IN 3 1/2" C

8 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C

11 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 4" C

10 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 4" C

NOTES:

1. CONDUIT SIZES FOR THHN/THWN COPPER CONDUCTORS ONLY. OTHER CONDUCTOR TYPES MAY REQUIRE INCREASED CONDUIT SIZE.

2. GROUND CONDUCTORS SPECIFIED IS FOR EQUIPMENT GROUND PER N.E.C. UNLESS NOTED OTHERWISE.

TOP NUMBER REFERS TO COLUMNS

BOTTOM NUMBER REFERS TO ROWS (AMPS)

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com

AE Works Project Number:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

3/

/2

:5 1:

A

M ERIE VAMC - EXPAND EMERGENCY

POWER GENERATION - PHASE II

VA244-16-J-5508

IT JZ

135 E 38TH ST, ERIE PA 16504

E200

ELECTRICAL RISER DIAGRAM

04/12/17 100

16030

FULLY SPRINKLERED

BID DOCUMENTS

NORTH

PROJECT

NTS

ELECTRICAL RISER DIAGRAM

1. REFER TO DRAWING E001 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND NOTES.

2. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE MEP & ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.

3. PROVIDE 100% RATED CIRCUIT BREAKERS NEW UPS OUTPUT PANELBOARD.

4. AS A MINIMUM, DISCONNECT SWITCHES SHALL BE RATED AS THE UPSTREAM PROTECTIVE DEVICE RATING.

5. TRANSFORMER SECONDARIES SHALL BE GROUNDED TO THE MAIN GROUND BAR VIA A COPPER GROUNDING CONDUCTOR…

This is the start of the file's text. The full file is on GovTribe.