36C24419B0012-003.pdf
PDF 4 MB Posted
- Attached to
- Replace Legacy UPS/Power System Federal contract opportunity
- Solicitation number
- 36C24419B0012
About this file
36C24419B0012 S02 Combined Drawings-Replace Legacy UPS.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24419B0012-0004000.docx | DOCX document | |
| 36C24419B0012-0003001.pdf | ||
| 36C24419B0012-0003000.docx | DOCX document | |
| 36C24419B0012-0002001.pdf | ||
| 36C24419B0012-0002002.pdf | ||
| 36C24419B0012-0002000.docx | DOCX document | |
| 36C24419B0012-0001000.docx | DOCX document | |
| 36C24419B0012-014.pdf | ||
| 36C24419B0012-006.pdf | ||
| 36C24419B0012-004.pdf | ||
| 36C24419B0012-010.pdf | ||
| 36C24419B0012-011.pdf | ||
| 36C24419B0012-012.pdf | ||
| 36C24419B0012-002.pdf | ||
| 36C24419B0012-013.pdf | ||
| 36C24419B0012-008.docx | DOCX document | |
| 36C24419B0012-001.docx | DOCX document | |
| 36C24419B0012-007.pdf | ||
| 36C24419B0012-009.pdf | ||
| 36C24419B0012-005.pdf | ||
| 36C24419B0012-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAIN ELEC RM
EE-200
REMOVE INTERIOR PARTIAL-HEIGHT PARTITIONS AND
DOOR ASSEMBLY. REMOVE PARTIAL CEILING
ASSEMBLY INCLUDING GRID AND TILE. REMOVE
CARPET AND VCT FLOORING AND ADHESIVES.
CONTRACTOR TO PATCH CONCRETE FLOORS AS
NECESSARY. REPAINT WALLS WHERE PARTITIONS
HAVE BEEN REMOVED.
CONSULTANTS:
Drawing Title
Approved: Site Manager
Project Title
Location
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
6"
6"
6"
6" o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Approved: Project ManagerApproved: Manager, Projects Section
Approved: Vice President, Facilities Management
Approved: Chief Operating Officer
Approved: Director
65432
SEAL
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
Revision# Date
VA244-16-J-5508
ICT JZ
G001 04/12/2017
FULLY SPRINKLERED
BID DOCUMENTS
ERIE VAMC - EXPAND
EMERGENCY POWER
GENERATION - PHASE II
135 E 38TH ST, ERIE PA 16504
16030
COVER SHEET
PROJECT DIRECTORY
OWNER:
ERIE VA MEDICAL CENTER
135 E 38TH STREET
ERIE, PA 16504
(814) 860-2744
CONTACT: SHAWN PURPURA
ARCHITECT/ENGINEER:
AE WORKS, LTD
6587 HAMILTON AVENUE
PITTSBURGH, PA 15206
(412) 287-7333
CONTACT: TIFFANY HAILE
DRAWING INDEX
SHEET # SHEET NAME
GENERAL
G001 COVER SHEET
PLUMBING
P/FP/H001 PLUMBING, FP AND HVAC PLAN
ELECTRICAL
E001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND NOTES
E100 PARTIAL BASEMENT FLOOR POWER PLAN
E101 PARTIAL SECOND FLOOR AND PENTHOUSE POWER PLANS
E200 ELECTRICAL RISER DIAGRAM
E300 DETAILS
NORTH
TRUE NORTH=
PROJECT
83.00°
VICINITY MAP
SITE
LOCATION MAP
SITE
ERIE VAMC - EXPAND EMERGENCY
POWER GENERATION - PHASE II
ERIE VA MEDICAL CENTER
135 E 38TH ST
ERIE, PA 16504
814-868-8661
PROJECT NO. VA244-16-J-5508
1/8" = 1'-0"
ARCHITECTURAL WORK - ROOM EE-200
prakszawski Stamp
UP
UP
MAIN TELEPHONE RM
WB-39
GENERAL SUPPLIES
WB-39A
NEW ELECTRICAL
UPS
S A
N
4"-FD-XR
2"
CO
CONNECT 2" SANITARY
TO DRAIN PAN. PROVIDE
2" TYPE "L" COPPER PIPE.
PROVIDE PIPE SLEEVE AND
MAINTAIN FIRE RATING.
2" SAN DISCHARGE
OVER EXISTING
FLOOR DRAIN. PROVIDE
ELBOW AND PIPE EXTENSION
TO FLOOR DRAIN LOCATION.
2"
ALTERNATE UPS
ADDITIONAL FOOTPRINT
PROVIDE PIPE SLEEVE AND
MAINTAIN FIRE RATING.
EXISTING DOMESTIC
WATER PIPING TO
REMAIN.
PROVIDE DRIP PAN CEILING
SYSTEM RUNNING UNDER LENGTH
OF EXISTING PIPES ABOVE NEW
UPS FOOTPRINT. COORDINATE
CEILING SYSTEM WITH APPROVED
UPS SUBMITTAL PRIOR TO
INSTALLATION. REFER TO
SECTION 09 57 56 "LEAK BARRIER
CEILINGS" FOR ADDITIONAL
INFORMATION. COORDINATE AND
TIE CEILING SYSTEM INTO 2" DRAIN
LINE AS SHOWN.
GENERAL PLUMBING NOTES
1. ALL WORK SHOWN IS NEW UNLESS INDICATED OTHERWISE.
2. ALL EXISTING SERVICES ARE SHOWN IN THEIR APPROXIMATE LOCATIONS.
3. CONTRACTOR SHALL DETERMINE THE EXACT LOCATIONS OF ALL UTILITIES BEFORE COMMENCING WORK AND SHALL BE FULLY RESPONSIBLE FOR ANY DAMAGE WHICH MIGHT OCCUR DUE TO THEIR FAILURE TO EXACTLY LOCATE AND PRESERVE ANY SERVICES, INCLUDING WORK IN EXISTING PIPE CHASES.
4. ALL EXISTING PLUMBING LINES, RISERS, ETC. ENCOUNTERED DURING ALTERATIONS, WHETHER INDICATED OR NOT, SHALL BE DETERMINED TO BE ACTIVE OR INACTIVE BY THIS CONTRACTOR, PRIOR TO COMMENCING ANY WORK. IF LINES ARE ACTIVE THEY SHALL BE OFFSET AS REQUIRED AND RECONNECTED AT THEIR ORIGINAL LOCATIONS. OFFSETS SHALL BE OF THE SAME SIZE AND MATERIAL AS EXISTING, INCLUDING ANY INSULATION. REMOVE ALL USELESS AND INACTIVE PIPING BACK TO THE MAIN, STACK OR RISER. AND CAP. ALL USELESS HOLES IN WALLS AND CEILINGS SHALL BE PATCHED TO MAINTAIN FIRE RATING. ALL SUCH
WORK SHALL BE RECORDED ON THE "RECORD" DRAWINGS.
5. THE DRAWINGS ARE DIAGRAMMATIC. THE CONTRACTOR MUST FIELD VERIFY ACTUAL CONDITIONS AT THE SITE PRIOR TO PROCEEDING WITH THE WORK.
COORDINATE INSTALLATION OF ALL NEW PIPING, EQUIPMENT, ETC. WITH ALL OTHER TRADES.
6. PATCH ALL OPENINGS IN EXISTING CONSTRUCTION WHERE PLUMBING PIPING HAS BEEN REMOVED, OR WHERE PLUMBING PIPING TO REMAIN IS NOT SEALED.
MAINTAIN EXISTING RATING.
7. COORDINATE LOCATIONS OF FLOOR DRAINS IN MECHANICAL ROOM WITH ACTUAL EQUIPMENT BEING INSTALLED.
ALL HORIZONTAL SANITARY DRAINAGE PIPING IS PITCHED AT 1/4"/FT UP TO 3" DIA. , 1/8"/FT FOR 4" DIA. TO 8" DIA., LARGER SIZES AS NOTED. ALL HORIZONTAL STORM
DRAINAGE PIPING IS PITCHED AT 1/8"/FT.
8. THE PLUMBING DRAWINGS DO NOT INDICATE ALL STRUCTURAL BEAMS, COLUMNS OR EXACT SIZES. SOME DEVIATIONS TO THE PIPING LAYOUT MAY BE REQUIRED.
COORDINATE ACTUAL LOCATIONS OF THE PLUMBING LINES DURING CONSTRUCTION.
PLUMBING SYMBOLS LEGEND
F-1, F-2, ETC. PLUMBING FIXTURE TYPE- SEE SPECIFICATION
CAP
DROP
RISE
CO
INDICATES POINT OF CONNECTION TO EXISTING
CLEANOUT AT CEILING (CO) OR WALL (WCO)
SANITARY PIPE
INDICATES POINT OF DEMOLITION
DRAWING KEYNOTE - PLAN / ELEVATION DEMO
DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK
SAN
DOMESTIC WATER PIPING (HOT WATER SUPPLY)
MAIN TELEPHONE RM
WB-39
ELEC SWITCHGEAR
WB-37
COMPUTER RM
B-20
GENERAL SUPPLIES
WB-39A
POLICE
WB-38
WB-40D
WB-40E
MECH ROOM
B-02
D
D
D
D D
D
D
D
D
DRY ALARM VALVE
WALL MOUNTED
AIR COMPRESSOR
CONNECT TO
EXISTING WET PIPE
SYSTEM IN
MECHANICAL ROOM.
EXTEND 2" BRANCH
TO NEW DRY ALARM
VALVE.
SPR
XR
EXISTING TAMPER
SWITCH AND ZONE
CONTROL VALVE.
F-DM
FIRE PROTECTION SYMBOLS
F
D
FIRE LINE
SEMI-RECESSED SPRINKLER
UPRIGHT SPRINKLER W/ GUARD
ZONE CONTROL VALVE
RISE
DROP
CAP
TS
TAMPER SWITCH
FIRE DEPARTMENT HOSE VALVEFDHV
FIRE LINE TO BE DEMOLISHED
CONNECT TO EXISTING PIPING THIS POINT
REMOVE EXISTING PIPING TO THIS POINT
DRY SPRINKLER LINE
EXISTING TO REMAINXR
DRAWING KEYNOTE - PLAN / ELEVATION DEMO
DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK
MAIN TELEPHONE RM
WB-39
GENERAL SUPPLIES
WB-39A
MAIN TELEPHONE RM
WB-39
GENERAL SUPPLIES
WB-39A
DEMOLITION KEYNOTES
EXISTING LIEBERT CHALLENGER UNIT RELOCATED AS NEEDED IF
ALTERNATE 1 IS ACCEPTED IN ORDER TO ALLOW FOR INSTALLATION OF
NEW UPS. IF ALTERNATE 1 IS NOT ACCEPTED EXISTING LIEBERT
CHALLENGER UNIT REMAINS IN SAME LOCATION.
IF ALTERNATE 1 IS ACCEPTED EXISTING SHUT-OFF VALVES THAT EXIST IN
GLYCOL SUPPLY/RETURN PIPES ABOVE FLOOR CAN BE USED TO ISOLATE
THE LIEBERT CHALLENGER UNIT.
NEW WORK KEYNOTES
IF ALTERNATE 1 IS ACCEPTED THEN EXISTING LIEBERT CHALLENGER UNIT
SHALL BE RELOCATED AS SHOWN. EXTEND UNDERFLOOR PIPING TO NEW
LOCATION AS SHOWN. IF ALTERNATE 1 IS NOT ACCEPTED EXISTING PIPING
TO LIEBERT CHALLENGER UNIT REMAINS UNCHANGED.
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
FULLY SPRINKLERED
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
4/
/2
:4 4:
A
M ERIE VAMC - EXPAND EMERGENCY
POWER GENERATION - PHASE II
VA244-16-J-5508
CJC MEW/CJC
135 E 38TH ST, ERIE PA 16504
P/FP/H001
PLUMBING, FP AND HVAC PLAN
04/12/17 100
16030
BID DOCUMENTS
1/8" = 1'-0"
PARTIAL BASEMENT FLOOR PLUMBING PLAN
1/8" = 1'-0"
PARTIAL BASEMENT FLOOR FIRE PROTECTION PLAN
1/8" = 1'-0"
PARTIAL BASEMENT FLOOR PLAN - HVAC
1/8" = 1'-0"
PARTIAL BASEMENT FLOOR PLAN - EXISTING HVAC
PLUMBING FIRE PROTECTION HVAC
NORTH
PROJECT
THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.
RECEPTACLES, FURNITURE FEEDS
THE ABOVE MOUNTING ELEVATIONS ARE TO CENTER OF DEVICE AND SHALL BE ADHERED TO
UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS AND/OR
SPECIFICATIONS.
IN FLOOR JUNCTION BOXES FLUSH TO
FINISHED FLOOR (FF)
IN MASONRY CONSTRUCTION THE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO THE
NEAREST BLOCK OR BRICK COURSING.
COORDINATE THE INSTALLATION AND MOUNTING ELEVATIONS OF ALL EQUIPMENT, DEVICES,
CONTROLS AND APPURTENANCES WITH ARCHITECT AND ALL AFFECTED TRADES PRIOR TO
INSTALLATION. DOCUMENT ALL MOUNTING ELEVATIONS FOR ALL EQUIPMENT, DEVICES,
CONTROLS AND APPURTENANCES AT THE TIME OF SHOP DRAWING SUBMITTAL.
3.
2.
1.
0'-0"
1'-5" A.F.F.
STANDARD MOUNTING HEIGHTS
RECESSED LIGHTING FIXTURES, CEILING
MOUNTED RECEPTACLES, INDICATING LIGHTS,
ETC.
CEILING
ELECTRICAL SYMBOLS LEGEND
ABOVE COUNTER DEVICES, GFI RECEPTACLES IN
RESTROOMS.
3'-6" A.F.F.
WALL SWITCHES, THERMOSTATS, CONTROL DEVICES,
TO CENTER OF BOX
4'-0" A.F.F.
TOP OF PANELBOARDS (<6'-0" TALL)6'-0" A.F.F.
TOP MOST PORTION OF OPERATING HANDLE OF
DISCONNECT SWITCHES / CIRCUIT BREAKERS
6'-6" A.F.F.
WALL MOUNTED LIGHTS IN STAIRS, MECH ROOMS,
ETC.
7'-0" A.F.F.
DRAWING KEYNOTE - DEMOLITION
EQUIPMENT TAG
REVISION TRIANGLE WITH REVISION CLOUD
INDICATED MOUNTED ABOVE COUNTERTOP (REFER TO STANDARD
MOUNTING HEIGHTS DETAIL ON THIS SHEET)
ELECTRICAL DEMOLITION
EXISTING TO REMAIN - DEVICE SHALL REMAIN IN WORKING ORDER.
REMOVE AND REPLACE WITH NEW - EXISTING BACKBOX AND WIRING SHALL REMAIN,
RECONNECT NEW DEVICE TO EXISTING CIRCUIT.
REMOVE AND RELOCATE - DISCONNECT DEVICE, MODIFY AND EXTEND FEED TO NEW LOCATION.
REMOVE COMPLETLY - REMOVE DEVICE, CONDUIT, AND WIRING BACK TO SOURCE.
ETR
RN
RR
RC
EXISTING TO REMAIN
NEW WORK
DEMOLITION
DISCONNECT SWITCH. NEMA 1, 20A/1PH/120V UNLESS OTHERWISE
NOTED.
X - Y
RECEPTACLE TAG:
X= PANEL NAME
Y= CIRCUIT NUMBER
RISER DIAGRAM/SINGLE LINE SYMBOLS
XXXA
FUSED
SWITCH
NON-FUSED
SWITCH
MOLDED CASE
CIRCUIT
BREAKER
XXXA/3P XXXA/3P
ST
XXXA/3P
ST
XXXA/3P XXXA/3P
ST
XXXA/3P XXXA/3P
ST
MOLDED CASE
CIRCUIT
BREAKER W/
SHUNT TRIP
XXXA/3P
MOLDED CASE
CIRCUIT
BREAKER W/
SHUNT TRIP &
AUXILIARY
CONTACT
XXXA/3P
ST
XXXA
FUSED SWITCH
W/ AUXILIARY
CONTACTS
NON-FUSED
SWITCH W/
AUXILIARY
CONTACTS
FUSED DOUBLE THROW
SWITCH
XXXA
XXXA
M
UTILITY
METER
CT
CABINET
PANEL
VOLTAGE
AMPACITY
MCB OR MLO
TAG
AMPACITY
FSS
NEMA
M
AUTOMATIC TRANSFER SWITCH
REFER TO DRAWINGS FOR AMPACITY, POLES, BYPASS, ETC.
TAG
AMPACITY
NFSS
NEMA
TAG
AMPACITY
CB
NEMA
ELECTRICAL PANELBOARD
REFER TO DRAWINGS FOR VOLTAGE, AMPACITY, CIRCUIT
QUANTITY, RATINGS, AND SPECIAL FEATURES
STEP-DOWN TRANSFORMER
REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND
SPECIAL REQUIREMENTS
FUSED SAFETY
SWITCH
NON-FUSED SAFETY
SWITCH
ENCLOSED CIRCUIT
BREAKER
SINGLE PHASE MOTOR
REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND
SPECIAL REQUIREMENTS
UTILITY METER
REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND
SPECIAL REQUIREMENTS
XXXA
XXXA/3P
XXXAF
LSIG
S
IZ
E
F V
N R
X
DRAW-OUT
MEDIUM VOLTAGE
CIRCUIT BREAKER
DRAW-OUT
LOW VOLTAGE
CIRCUIT BREAKER
COMBINATION
MOTOR STARTER
SURFACE MOUNTED ELECTRICAL PANELBOARD
RECESSED MOUNTED ELECTRICAL PANELBOARD
N E
W
E X
IS
T
IN
G
N E
W
E X
IS
T
IN
G
ADA INSTALLATION GUIDELINES
34"
46"
MAX.
(NOTE #2)
44"
MAX.
(FOR 20-25")
(NOTE #2)
10-24" 25" MAX.
48"
MAX.
(FOR 20")
(NOTE #2)
OBSTRUCTED HIGH
SIDE REACH
OBSTRUCTED HIGH
FORWARD REACH
48"
MAX.
(NOTE #2)
10"
MAX.
15"
MIN.
48"
MAX.
(NOTE #2)
15"
MIN.
OBSTRUCTED
SIDE REACH
OBSTRUCTED
FORWARD REACH
NOTES:
1. THESE GUIDLINES SHALL BE USED FOR THE INSTALLATION OF THE FOLLOWING DEVICES:
- WALL SWITCHES
-CONTROL SWITCHES
-RECEPTACLES
-VISUAL DISPLAY TOUCH PANELS
2. NOTE THAT THIS HEIGHT IS TO THE TOP-MOST PART OF THE DEVICE THAT AN OCCUPANT
REQUIRES ACCESS TO.
ANNOTATION SYMBOLS
DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK
M
THREE PHASE MOTOR
REFER TO DRAWINGS FOR VOLTAGE, SIZE, TYPE AND
SPECIAL REQUIREMENTS
WIRING CONVENTION
1. THE COMPLETE BRANCH WIRING SYSTEM IS NOT SHOWN ON THE DRAWINGS. AN
ABBREVIATED FORMAT IS USED TO INDICATE WHICH FIXTURES/DEVICES ARE CONNECTED
TO A COMMON CIRCUIT OR SWITCH. THIS IS PROVIDED AS A GUIDE TO THE CONTRACTOR TO
ILLUSTRATE CIRCUITS AND CONTROL INTENT. ACTUAL WIRING MAY BE DIFFER DUE TO FIELD
CONDITIONS.
2. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL NEUTRAL WIRE. SHARING OF NEUTRALS IS
PROHIBITED. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL GROUND WIRE. USE OF THE
CONDUIT SYSTEM FOR THE GROUND PATH IS PROHIBITED.
3. ALL CIRCUITS IN PATIENT AREAS SHALL HAVE A REDUNDANT GREEN GROUND CONDUCTOR.
CONDUCTOR SHALL BE BONDED TO THE GROUND BUS IN THE PANELBOARD AND THE METAL
BOX AT THE DEVICE PER NEC 517.
4. IF THE CONTRACTOR CHOOSES TO RUN MULTIPLE CURRENT CARRYING CONDUCTORS IN A
COMMON CONDUIT, THE NEC DERATING RULES SHALL BE FOLLOWED, AND
CONDUCTORS/CONDUIT SHALL BE UPSIZED ACCORDINGLY, INCLUDING THE GROUND WIRE.
5. CONDUCTORS INSTALLED ON ROOFTOPS SHALL HAVE THEIR SIZES INCREASED PER NEC
SECTION 310.15 DERATING FACTORS. UPSIZE CONDUCTORS AND CONDUIT ACCORDINGLY,
INCLUDING THE GROUND WIRE.
6. CONDUCTOR SIZES ARE BASED ON NEC SECTION 310.15, 60° C TEMPERATURE RATING FOR
UP TO #1 AWG, AND 75° C FOR #1/0 AND LARGER.
7. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS (AS APPLICABLE):
120/208 VOLT SYSTEM 277/480 VOLT
SYSTEM
PHASE A = BLACK PHASE A = BROWN
PHASE B = RED PHASE B = ORANGE
PHASE C = BLUE PHASE C = YELLOW
NEUTRAL = WHITE NEUTRAL = GREY
GROUND = GREEN GROUND = GREEN
SINGLE PHASE HOMERUN TO PANELBOARD
WIRING SYMBOLOGY
THIS PROJECT WILL REQUIRE SHUT-DOWNS TO THE NORMAL POWER SYSTEM OF THE HOSPITAL, WHICH WILL REQUIRE SECOND OR THIRD SHIFT WORK, AS WELL AS WEEKEND WORK. THE CONTRACTOR SHALL COORDINATE THIS WORK
WITH THE COR, AND PLAN HIS WORK ACCORDINGLY.
DURING ALL UTILITY SHUT-DOWNS OF THE NORMAL POWER SYSTEM, THE CONTRACTOR SHALL HAVE A 4160V EMERGENCY GENERATOR ON SITE WITH 24 HOURS OF FUEL. THE CONTRACTOR SHALL HAVE SUITABLE TEMPORARY CABLES NEEDED TO PROVIDE EMERGENCY CONNECTIONS TO THE SWITCHGEAR IN THE EVENT THERE IS A PROBLEM.
THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF.THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE COR SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE COR AND ENGINEER FOR SIGN OFF.
1.
UTILITY SHUTDOWNS
2.
3.
NE
N E
XX
WALL MOUNTED VOICE/DATA OUTLET
XX = CABLING CONFIGURATIONS (REFER TO COMMUNICATIONS DETAIL SHEET)
R FIRE ALARM INTERFACE MODULE.
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
3/
/2
:5 1:
A
M ERIE VAMC - EXPAND EMERGENCY
POWER GENERATION - PHASE II
VA244-16-J-5508
IT JZ
135 E 38TH ST, ERIE PA 16504
E001
ELECTRICAL SYMBOLS, ABBREVIATIONS AND
NOTES
04/12/17 100
16030
FULLY SPRINKLERED
BID DOCUMENTS
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL TOP
T TOP
TA THROWAWAY
TAN TANGENT
TC TELECOMMUNICATIONS
CONTRACTOR
TCV TEMPERATURE CONTROL VALVE
TDV TRIPLE DUTY VALVE
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TG TONGUE & GROOVE
TH THERMOMETER
THRES THRESHOLD
TR TEMPERATURE RISE
TRANS TRANSITION
TRANSR TRANSFORMER
TSTAT THERMOSTAT
TV TURNING VANES OR TELEVISION
TYP TYPICAL
UC UNDER CABINET OR UNDER CUT
UFD UNDER FLOOR DUCT
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORIES
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VAL VALVE
VD VOLUME DAMPER
VENT VENTILATION
VERT VERTICAL
VFS VENTURI FLOW STATION
VIF VERIFY IN FIELD
VL VENT LINE
VR VAPOR RETARDER
VS VENT STACK
VTR VENT THROUGH ROOF
W WATT
W/ WITH
W/O WITHOUT
WB WET BULB
WC WALL COVERING
WCL WATER CLOSET
WD WOOD
WF WIDE FLANGE
WFMD WATER FLOW MEASURING DEVICE
WG WALL GUARD OR WATER GAUGE
WHCH WHEEL CHAIR
WIN WINDOW
WMS WIRE MESH SCREEN
WP WEATHERPROOF
WPS WALL PROTECTION SYSTEM
WSCT WAINSCOT
WT WINDOW TREATMENT
WTD WATER TEMPERATURE DROP
WWF WELDED WIRE FABRIC
X DEMO
XN TO BE RELOCATED / NEW LOCATION
XR EXISTING TO REMAIN
ZVB ZONE VALVE BOX
ZVC ZONE VALVE CABINET
LTG LIGHTING
LV LOW VOLTAGE
LVR LOUVER
LWB LEAVING WET BULB
LWC LINEAR WOOD CEILING
LWT LEAVING WATER TEMPERATURE
MAN MANUAL
MAT MIXED AIR TEMPERATURE
MATL MATERIAL
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH ONE THOUSAND BTU / HOUR
MC MECHANICAL CONTRACTOR
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MO MASONRY OPENING
MOD MOTOR OPERATED DAMPER
MONO MONOLITHIC
MTD MOUNTED
MTG HT MOUNTING HEIGHT
MTL METAL
MTLH METAL HALIDE
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
N/A NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NUMBER OR NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
O OXYGEN
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OPER OPERATED
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
PB PULL BOX
PC PLUMBING CONTRACTOR
PD PUMP DISCHARGE
PG PRESSURE GAUGE WITH COCK
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PNL PANEL
PR PAIR
PRD PRESSURE DIFFERENTIAL VALVE
PRELIM PRELIMINARY
PRT PRESSURE TAP
PRV PRESSURE REDUCING VALVE
PT PAINT OR POTENTIAL
TRANSFORMER
RO ROUGH OPENING
QT QUARRY TILE
R RADIUS
RA RETURN AIR / RELIEF AIR
RB RUBBER BASE
RC REMOVE COMPLETELY
RD ROOF DRAIN
RE RELOCATE EXISTING
REC RECESSED
RECPT RECEPTACLE
REF REFERENCE
REFL REFLECTOR
REG REGISTER
REINF REINFORCING
REM REMOVE
REQD REQUIRED
RET RETURN
REV REVISE
REX REMOVE EXISTING
RF RESILIENT FLOOR
RFI REQUEST FOR INFORMATION
RGS RIGID GALVANIZED STEEL CONDUIT
RH ROOF HATCH
RM ROOM
RN REMOVE AND REPLACE WITH NEW
RR REMOVE AND REPLACE
RS RAPID START
RV RELIEF VALVE
RWC RAIN WATER CONDUCTOR
SA SUPPLY AIR
SAN SANITARY SEWER ABOVE GROUND
SAN-BXR SANITARY SEWER - BURIED
EXISTING TO REMAIN
SAN-XR SANITARY SEWER ABOVE GROUND -
EXISTING TO REMAIN
SCHED SCHEDULE
SD SMOKE DAMPER OR SMOKE
DETECTOR
SDISP SOAP DISPENSER
SF SQUARE FOOT
SHT SHEET
SHT MTL SHEET METAL
SHTG SHEATHING
SIM SIMILAR
SM SURFACE MOUNTED
SNC SANITARY NAPKIN CABINET
SND SANITARY NAPKIN DISPOSER
SP STANDPIPE OR STATIC PRESSURE
SPC SPECIMEN PASS-THRU CABINET
SPEC SPECIFICATIONS
SPS STATIC PRESSURE SENSOR
SR SERVICE RECEPTOR
SS SOIL STACK
ST PR STATIC PRESSURE
ST STL STAINLESS STEEL
STD STANDARD
STER STERILIZER
STL STEEL
STOR STORAGE
STR STRAINER
STRUCT STRUCTURAL
SUSP SUSPENDED
SW SWITCH
ELEC CAB ELECTRICAL CABINET
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENTR ENTRANCE
EO ELECTRICAL OUTLET
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWB ENTERING WET BULB
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX EXAUST AIR
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
XP EXPLOSION PROOF
F/S FIRE / SMOKE DAMPER
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAT FINAL AIR TEMPERATURE
FB FIRE BLANKET
FC FLEXIBLE CONNECTION OR
FOOTCANDLE
FD FLOOR DRAIN OR FIRE DAMPER
FDN FOUNDATION
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HOSE
FHC FIRE HOSE CABINET
FHP FULL HEIGHT PARTITION
FHV FIRE HOSE VALVE
FIN FINISH
FIXT FIXTURE
FL FLOW LINE
FLA FULL LOAD AMPERES
FLASH FLASHING
FLEX FLEXIBLE
FLG FLANGE
FLG C FLANGE CONNECTION
FLR FLOOR
FLUOR FLUORESCENT
FP FIRE PROOFING
FRMG FRAMING
FS FLOOR SINK
FSTOP FIRESTOPPING
FT FOOT / FEET
FT HD FEET OF HEAD
FTC FOOTCANDLES
FTG FOOTING
FUR FURRING
G GAS OR ELECTRICAL GROUND
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERATOR
GENL GENERAL
GFCI GROUND FAULT CIRCUIT
INTERRUPTOR
GL GLASS
GLV GLOBE VALVE
GND GROUND
GPM GALLONS PER MINUTE
GR GRADE
GRAV GRAVITY
GRD BM GRADE BEAM
GV GATE VALVE
GWB GYPSUM BOARD
H HIGH
HB HOSE BIB
HC HEATING CONTRACTOR
HDCP HANDICAP
HDR HEADER
HDW HARDWARE
HID HIGH INTENSITY DISCHARGE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSE POWER
HPD HIGH PRESSURE DRIP
HPF HIGH POWER FACTOR
HR HANDRAIL
HSKP HOUSEKEEPING
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VELOCITY
HVAC HEATING, VENTILATING, AIR
CONDITIONING
HW HOT WATER
HWD HARD WOOD
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HWS&R HOT WATER SUPPLY AND RETURN
HZ HERTZ
ID INSIDE DIAMETER
IER INVERTED ECCENTRIC REDUCER
IG ISOLATED GROUND
IME INSULATED METAL ENCLOSURE
IN INCH
INCAND INCANDESCENT
INCL INCLUDED
INSUL INSULATION
INT INTERIOR
INTERL INTERLOCK
INV INVERT
ISO ISOLATION
IVS ISOLATED VALVE STATION
J-BOX JUNCTION BOX
JST JOIST
JT JOINT
KO KNOCK OUT
kVA KILOVOLT AMPERE kVAR KILOVAR (REACTANCE) kW KILOWATT kWH KILOWATT HOUR METER
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LB POUND
LDB LEAVING DRY BULB
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LIN LINEAR
LOC LOCATION OR LOCATE
LPT LOW POINT
LSDC LINEAR SUPPLY DIFFUSER CEILING
LT LIGHT
& AND
A AIR (CLINICAL)
AAP ALARM ANNUNCIATOR PANEL
AAV AUTOMATIC AIR VENT
AB ANCHOR BOLT
ABV ABOVE
ACC DR ACCESS DOOR
ACFL ACCESS
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICAN DISABILITIES ACT
ADD ADDENDUM
ADDL ADDITIONAL
ADJ ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AFMD AIR FLOW MEASURING DEVICE
AHU AIR HANDLING UNIT
AL ALIGN
ALT ALTERNATE
ALUM ALUMINUM
AMP AMPERE
AP ACCESS PANEL
APC ARCHITECTURAL PRECAST
CONCRETE
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASY ASYMMETRIC
ATC AUTOMATIC TEMPERATURE
CONTROL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AWT AVERAGE WATER TEMPERATURE
BAT BATTERY
BC BALANCING COCK OR BARE COPPER
BDD BACKDRAFT DAMPER
BFC BELOW FINISH CEILING
BFE BOTTOM FOOTING ELEVATION
BFG BELOW FINISHED GRADE
BG BUMPER GUARD
BLDG BUILDING
BLKG BLOCKING
BLT BORROWED LIGHT
BLW BELOW
BM BEAM
BO BY OWNER
BOF BY OWNER FUTURE
BOT BOTTOM
BR BRICK
BRG BEARING
BRKR BREAKER
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
C CONDUIT
CAB CABINET
CANTL CANTILEVER
CAP CAPACITY
CATV CABLE TELEVISION
CCT CUBICLE CURTAIN TRACK
CCTV CLOSED CIRCUIT TELEVISION
CFH CUBIC FEET / HOUR
CFM CUBIC FEET / MINUTE
CH CHANNEL
CHK V CHECK VALVE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CHWS&R CHILLED WATER SUPPLY AND
RETURN
CJ CONTROL JOINT
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CL CENTERLINE
CLG CEILING
CLG MTD CEILING MOUNTED
CLR CLR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUE / CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
COORD COORDINATE
CORR CORRIDOR
CPT CARPET OR CONTROL POWER
TRANSFORMER
CT CERAMIC TILE
CTR CENTER
CU COPPER
CV CONTROL VALVE
CW COLD WATER
D DEPTH OR DEEP
DB DRY BULB
dB DECIBEL
DCW DOMESTIC COLD WATER
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAILS
DF DRINKING FOUNTAIN
DHW DOMESTIC HOT WATER
DIA DIAMETER
DIAG DIAGONAL OR DIAGRAM
DIFF DIFFUSER
DIM DIMENSION
DISC DISCONNECT
DISCH DISCHARGE
DISP DISPENSER
DIST DISTRIBUTION
DIV DIVISION
DL DOWN LIGHT
DN DOWN
DP DISTRIBUTION PANEL
DPR DAMPER
DR DRAIN
DS DOWNSPOUT
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB
EF EXHAUST FAN
EIFS EXTERIOR INSULATION AND
FINISHING SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ABBREVIATION LEGEND ELECTRICAL GENERAL NOTES
1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL E SERIES CONTRACT DRAWINGS.
2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET I.E. IF WORK SHOWN I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE
CONTRACTOR IS RESPONSIBLE FOR THAT WORK.
3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED SPECIFICATION SECTIONS FOR THE PROPER
INSTALLATION OF ALL WORK.
4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION SECTIONS
FOR ADDITIONAL REQUIREMENTS.
5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE SATISFACTION OF ALL
CONCERNED TRADES.
6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS AND ALL
AFFECTED TRADES PRIOR TO INSTALLATION.
7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM OF 3/4" UNLESS
OTHERWISE NOTED.
8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE
AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.
9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.
10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X STAINLESS
STEEL AND RATED FOR THAT APPLICATION.
12 ALL DEVICES, COMPONENTS OR EQUIPMENT INSTALLED ON THE EXTERIOR OF THE FACILITY SHALL BE PROVIDED IN ACCORDANCE WITH ALL MANUFACTURERS' REQUIREMENTS TO ENSURE THE PROPER OPERATION WHEN EXPOSED TO THE ENVIRONMENTAL CONDITIONS AND/OR AVERAGE ANNUAL LOWEST TEMPERATURE THAT
CAN BE ANTICIPATED FOR THE GEOGRAPHIC REGION OF THE FACILITY.
13 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF SPECIALIZED
TOOLS.
14 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.
15 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE CODES
AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
16 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED
ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.
17 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
18 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
19 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.
20 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS
IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.
21 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.
22 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO PERFORMING
ANY WORK.
23 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED
CEILING AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS.
24 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING AND/OR
BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.
25 THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE OWNER.
26 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORKPERFORMED SHALL BE IN
ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.
27 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH
THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.
28 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE CONTRACTOR
SHALL COORDINATE THESE REQUIREMENTS WITH THE OWNER.
29 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING QUANTITIES OF MATERIALS REQUIRED TO
COMPLETE THE PROJECT.
30 THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.
31 THE CONTRACTOR SHALL PROVIDE ALL NEW OPENINGS IN EXISTING PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY NEW ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS NEW WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES
INSTALLED THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.
32 THE CONTRACTOR SHALL PROTECT ALL EXISTING MATERIALS THAT ARE TO REMAIN IN PLACE FROM DAMAGE. ANY DAMAGE TO EXISTING FINISHES, MATERIALS, ETC., SHALL BE REPLACED BY THE CONTRACTOR TO MATCH THE ADJACENT FINISH.
33 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK. DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.
34 THE CONTRACTOR SHALL PROVIDE ALL TRAFFIC CONTROL, FLAGMEN, SIGNAGE, ETC. WHEN DOING WORK THAT INTERFERES WITH PUBLIC RIGHT-OF-WAY.
35 THE CONTRACTOR SHALL CONTACT THE NATIONAL "811-CALL BEFORE YOU DIG" SYSTEM PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATION WORK. THE
CONTRACTOR SHALL HAVE ALL UTILITIES VERIFIED IN AND AROUND THE EXCAVATION AREA.
36 THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF. THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE OWNER SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP
SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF.
37 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS. NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING
THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS.
38 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE EXISTING AND NEW DISTRIBUTION SYSTEM REQUIRED TO ACCURATLY SIZE
AND RATE THE NEW EQUIPMENT ADDED AS PART OF THIS PROJECT.
39 ARC FLASH LABELS SHALL BE PROVIDED TO ALL NEW EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTORS ARC FLASH STUDY (SEE NOTE 39 ABOVE FOR ADDITIONAL STUDY REQUIREMENTS). ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY, AND RE LABELLED AS
REQUIRED.
40 THESE DRAWINGS DO NOT INDICATED ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES AND EXISTING CONDITIONS.
41 PROVIDE ALL JUNCTION BOXES AND OTHER PULL POINTSAS REQUIRED FOR EASE OF PULLING AND A CODE COMPLIANT INSTALLATION. ALL JUNCTION BOXES AND OTHER
PULL POINTS SHALL BE ACCESSABLE
42 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED, ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL.
43 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRATOR UPSIZES THE CONDUIT AS REQUIRED, AND THE AMPACITY ADJUSTMENTS FROM TABLE 310.15(B)(3)(a) HAVE BEEN APPLIED.
F.E.C
T 7AOANB RQPO S U
N
V
L MK5
5BQA RA 5APA
DF
UP
UP
DN.
MAIN TELEPHONE RM
WB-39
ELEC SWITCHGEAR
WB-37
COMPUTER RM
B-20
ELEC RM
B-13A
STORAGE
WB-36A-1
MAIL ROOM
WB-36-2
WB-36A-5
MED RECORDS
WB-36A-6
WB-36A-7
GENERAL SUPPLIES
WB-39A
POLICE
WB-38
WB-40D
WB-40E
SECURE STORAGE
B-25
WORK ROOM
B-24
GEN STORAGE
B-23
TELE CLOSET
B-22
CHIEF ADP
B-21
CENTRAL OFFICE
B-18
TRAINING
B-19
MECH ROOM
B-02
AIR COND RM
WB-35
WB-34
WB-36A-4
STORAGE
WB-36A-3
NEW 100kVA
UPS
EXISTING
PANEL
C-A
EXISTING
PANEL
C-B
EXISTING
PANEL B-13A
EXISTING
PANEL C-2
EXISTING
UPS
NEW PANEL
MDP-UPS
EXISTING PANELS
TO REMAIN
TO MAIN ELEC
ROOM EE-200
NEW UPS
PANEL B13A2
TO UPS
PP-2
PP-1
PP-1
AIR
COMPRESSOR
R R
DEMOLITION KEYNOTES
DEMOLISH EXISTING UPS SYSTEM ENTIRELY ONCE NEW UPS SYSTEM IS
UP AND RUNNING AND ALL LOADS HAVE BEEN MOVED OVER TO THE NEW
UPS. REMOVE ALL REMOTE CONTROL PANELS AND ALL
INTERCONNECTING WIRING. REMOVE ASSOCIATED FEEDERS AND
CONDUIT.
EXISTING WIREWAY, DISCONNECT, AND ALL ASSOCIATED CONDUIT AND
WIRING SHALL BE REMOVED BACK TO SOURCE.
EXISTING JOHNSON CONTROL CABINET IS SUPPORTED BY UNISTRUT
THAT WILL INTERFERE WITH UPS REMOVAL (DEMO NOTE 1). RELOCATE
CABINET SUCH THAT IT WILL NOT INTERFERE WITH UPS REMOVAL.
EXTEND OR REPLACE WIRING AS NEEDED. ENGAGE JOHNSON
CONTROLS FOR ANY REQUIRED SHUT DOWN OR MODIFICATION TO
CONTROLS SYSTEM TO CARRY OUT THIS WORK.
RELOCATED EXISTING LIGHTING TO MAKE WAY FOR DRIP PAN ABOVE
NEW UPS. EXTEND EXISTING BRANCH CIRCUITS FROM OLD TO NEW
LOCATIONS VIA WIRING METHODS COMPATIBLE WITH EXISTING
INSTALLATION.
EXISTING UPS CONTROL PANEL TO BE REMOVED. REMOVE ALL
INTERCONNECTING CONDUIT AND WIRE. PATCH ALL FINISHES AS
NEEDED.
DEMOLISH FLOORING UNDER FOOTPRINT OF NEW UPS FOR
REPLACEMENT WITH INCREASED WEIGHT RATING FLOORING.
PROTECT ALL UNDERFLOOR CABLING DURING DEMOLITION.
COORDINATE EXTENT OF FLOORING TO BE REMOVED WITH APPROVED
UPS SUBMITTAL PRIOR TO CARRYING OUT ANY WORK.
DEMOLISH PANEL B13A AND ASSOCIATED FEEDER AND CONDUIT. CAP
AND TAG ALL BRANCH CIRCUITS FOR EXTENSION TO NEW PANEL
LOCATION. COORDINATE PHASING OF WORK WITH VA IT PRIOR TO
CARRYING OUT ANY WORK. LOADS ON THIS PANEL SERVE IT
EQUIPMENT AND MAY NEED TEMP POWER OR THE WORK TO BE
CARRIED OUT OFF HOURS.
NEW WORK KEYNOTES
NEW UPS UNIT WITH 60 MINUTES OF FULL LOAD BACKUP TIME.
ALTERNATE SHALL BE TO ADD 123 MINUTE BATTERY CAPACITY EXTENDING
THE FOOTPRINT OF THE OVERALL UNIT. EXISTING RAISED FLOOR SHALL BE
REPLACED TO ALLOW FOR ADDED WEIGHT ON UPS UNIT.
IF ALTERNATE 1 (123 MINUTE RUN TIME UPS) IS ACCEPTED THEN EXISTING
LIEBERT UNIT SHALL BE RELOCATED. EXTEND FEED TO NEW LOCATION AS
REQUIRED. EXISTING DISCONNECT SWITCH TO REMAIN.
USE EXISTING CONDUITS FROM JUNCTION BOX TO EXISTING MAIN ELECTRIC
ROOM ON SECOND FLOOR.
NEW DATA DROP FOR UPS. PROVIDE CAT 6 CABLING FROM DROP TO PATCH
PANEL IN CLOSET B13A. FIELD VERIFY PATCH PANEL CABLING TYPE PRIOR
TO ROUGH-IN.
TIE NEW CONDUITS FOR UPS FEED INTO EXISTING PULLBOX LOCATED IN
CRAWLSPACE UNDER AMBULATORY. LOCATION OF PULLBOX SHOWN HERE
IS NOT EXACT AND IS SHOWN HERE FOR SCOPE. RUN NEW CONDUIT FROM
PULLBOX TO NEW UPS ABOVE CEILING.
UPS TO BE TIED INTO EXISTING METASYS BMS SYSTEM. CONFIRM QTY OF
ALARM POINTS WITH THE VA PRIOR TO BMS SYSTEM PROGRAMMING. AS A
MINIMUM, PICK UP ALL STANDARD UPS ANNUNCIATOR SIGNALS OUTLINED IN
THE UPS SPECIFICATION.
PROVIDE NEW FLOORING SYSTEM RATED TO CARRY UPS SYSTEM WEIGHT.
COORDINATE FOOTPRINT OF NEW FLOORING SYSTEM WITH UPS SUBMITTAL
PRIOR TO INSTALLATION. FLOORING DIRECTLY UNDER UPS TO BE REPLACED
TO THE NEAREST TILE. DO NOT CUT OFF SERVICE TO UNDERFLOOR
CABLING. REROUTE CABLING AS REQUIRED TO FACILITATE FLOORING
SYSTEM INSTALLATION. REFER TO SPECIFICATION SECTION 09 69 00
"ACCESS FLOORING" FOR ADDITIONAL REQUIREMENTS.
PROVIDE NEW 20A/1P CIRCUIT BREAKER IN EXISTING PANELBOARD AS
INDICATED. BREAKER TO BE COMPATIBLE WITH EXISTING INSTALLATION.
PROVIDE TWO NEW FIRE ALARM INTERFACE MODULES AND CONNECT TO
DRY SPRINKLER SYSTEM CONTROL PANEL. FIRE ALARM TO MONITOR
SUPERVISORY AND ALARM CONNECTIONS OF NEW DRY ALARM SYSTEM.
PROVIDE MODULES COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM AND
TIE INTO EXISITING SYSTEM AT SUITABLE LOCATION. PROVIDE ALL PARTS
AND PROGRAMMING REQUIRED TO CONNECT MODULES INTO THE EXISTING
FIRE ALARM SYSTEM.
EXTEND 20x20A BRANCH CIRCUITS FROM OLD PANEL B13A TO NEW 100A
PANEL LOCATION AS SHOWN.
NEW 42CCT, 100A, 208/120V PANELBOARD. PROVIDE QTY OF BREAKERS
REQUIRED FOR EXISTING CIRCUITS RECONNECTED TO THIS PLANEL, PLUS
AN ADDITIONAL 20x20A/1P SPARE BREAKERS.
PROVIDE NEW 42CCT/400A/208V/3P4W/10k AIC PANELBOARD. PROVIDE 3
POLE BREAKERS FOR ALL EXISTING AND NEW LOAD CENTERS AS
IDENTIFIED ON THIS PLAN AND SHOWN ON THE SINGLE LINE DIAGRAM.
PROVIDE 4xSPARE 20A/1P BREAKERS AND THE REMAINDER OF THE PANEL
AS BLANK SPACES.
RR RR
4 4
CP
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
3/
/2
:5 1:
A
M ERIE VAMC - EXPAND EMERGENCY
POWER GENERATION - PHASE II
VA244-16-J-5508
IT JZ
135 E 38TH ST, ERIE PA 16504
E100
PARTIAL BASEMENT FLOOR POWER PLAN
04/12/17 100
16030
FULLY SPRINKLERED
BID DOCUMENTS
NORTH
PROJECT
1/8" = 1'-0"
PARTIAL BASEMENT FLOOR POWER PLAN
1/8" = 1'-0"
PARTIAL BASEMENT FLOOR DEMOLITION PLAN
ATS-IT
ATS-EL
MDP-2MDP-1
100kVA IT
VOLTAGE
REGULATOR
MAIN ELEC RM
EE-200
150kVA ELEV
VOLTAGE
REGULATOR
UNOCCUPIED
VENT ROOM
STAIR
UNOCCUPIED
ELEV PENTHOUSE
EXISTING
ELEV MOTOR
EXISTING
ELEV MOTOR
EXISTING
ELEV MOTOR
EXISTING
HVAC UNIT
EXISTING
PANEL A
EXISTING
PANEL A-1
EXISTING
ELEV DISC
SWITCHES
EXISTING ELEV
TRANSFORMER
EXISTING ELEV
CONTROLLERS
EXISTING
PANEL A
EXISTING
JUNCTION
BOX
EXISTING
PANEL A-1
EXISTING
ELEV DISC
SWITCHES
UNOCCUPIED
UNOCCUPIED
ELEV PENTHOUSE
STAIR
VENT ROOM
EXISTING ELEV
TRANSFORMER
EXISTING ELEV
CONTROLLERS
EXISTING
ELEV MOTOR
EXISTING
ELEV MOTOR
EXISTING
ELEV MOTOR
EXISTING
HVAC UNIT
NEW WORK KEYNOTES
MODIFY EXISTING ATS-IT WITH DOUBLE LUGS, REFER TO RISER DIAGRAM.
REMOVE EXISTING JUNCTION BOX AND ASSOCIATED CONDUIT/WIRE.
INTERCEPT CONDUIT ON FLOOR BELOW AND EXTEND NEW FEED TO NEW
VOLTAGE REGULATOR. REFER TO RISER DIAGRAM.
DEMOLITION KEYNOTES
WALL AS INDICATED TO BE DEMOLISHED, REFER TO ARCHITECTURAL
DRAWINGS FOR MORE INFORMATION. REMOVE ALL CONDUIT, WIRING
AND ELECTRICAL DEVICES PRIOR TO DEMOLITION. CEILING SYSTEM
ALSO TO BE REMOVED, DEMOLISH ALL LIGHT FIXTURES AND
ASSOCIATED WIRING FROM WITHIN THE AREA OF DEMOLITION. PATCH
AND MAINTAIN ALL CIRCUITS TO EXISTING TO REMAIN DEVICES
AFFECTED BY THE DEMOLITION WORK VIA WIRING METHODS
COMPATIBLE WITH THE EXISTING INSTALLATION.
REMOVE ALL ABANDONED CONDUIT AND WIRE AND FIRE STOP ALL
PENITRATIONS.
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
/2
/2
:5
:3
A
M ERIE VAMC - EXPAND EMERGENCY
POWER GENERATION - PHASE II
VA244-16-J-5508
IT JZ
135 E 38TH ST, ERIE PA 16504
E101
PARTIAL SECOND FLOOR AND PENTHOUSE
POWER PLANS
04/12/17 100
16030
FULLY SPRINKLERED
BID DOCUMENTS
NORTH
PROJECT
1/8" = 1'-0"
PARTIAL SECOND FLOOR POWER PLAN
1/8" = 1'-0"
PENTHOUSE POWER PLAN
1/8" = 1'-0"
PENTHOUSE DEMOLITION PLAN
EXISTING MDP-1
EXISTING
ATS-IT
EXISTING
ATS-EL
EXISTING
400A
PANEL
EXISTING
LAB AHU
SECOND FLOOR ELEC RM
FIRST FLOOR
BASEMENT FLOOR
ELEV PENTHOUSE
EXISTING EMDP-1
EXISTING
PANEL
WB-H
10 TON
LIEBERT
UNIT
100kVA
ELEC VOLTAGE
REGULATOR
1ST FLOOR
HR DEPT
PBX RM WB-39
NEW
400A
PANEL
MDP-UPS
NEW
100kVA UPSEXISTING
PANEL
C-A
SERVER RM
B20
EXISTING
PANEL
C-B
SERVER RM
B20
EXISTING
PANEL
C-2
MAIL RM
EXISTING
PANEL
B13A
B13A
EXISTING
65kVA UPS
EXISTING
PULL BOX
NEW PULL BOX TO
INTERCEPT EXISTING
CONDUITS
EXISTING (2) 3"
CONDUITS
EIGHTH FLOOR MECH ROOM
B13A2
NEW
100A
OUTPUT
TRANSFORMER
MAINTENANCE
BYPASS SWITCH
BYPASS INPUT BREAKER
FUSE
RECTIFIER
INVERTER
BATTERY BREAKER
BATTERY CABINET UPS SIDECAR OUTPUT SECTION
TO MDP-UPS
FROM IT SYSTEM EVR
BATTERY
CONVERTER
60 MINUTES UPS INTERNAL WIRING DIAGRAM
B13A
EXISTING
600A
ELEV
PANEL
150KVA
ELEC VOLTAGE
REGULATOR
EXISTING
JBOX
INTERCEPT EXISTING FEED TO
ELEV PANEL IN 8TH FLOOR MECH
ROOM. PROVIDE PULLBOX AND
EXTEND NEW FEED TO NEW
VOLTAGE REGULATOR AS SHOWN.
UTILIZE AND RESEAL EXISTING
CONDUIT PENITRATION.
AMPS 1PH, 2W, & GROUND 1PH, 3W, & GROUND 3PH, 3W, & GROUND 3PH, 4W, & GROUND 3PH, 4W, & SERVICE GROUND AMPS 3PH, 5W, & GROUND (200% NEUTRAL)AMPSAMPSAMPSAMPS
(2) #12 & 1#12 G IN 3/4" C15
(2) #12 & 1#12 G IN 3/4" C
(2) #10 & 1#10 G IN 3/4" C
(2) #10 & 1#10 G IN 3/4" C
(2) #8 & 1#10 G IN 3/4" C
(2) #8 & 1#10 G IN 3/4" C
(2) #6 & 1#10 G IN 3/4" C
(2) #6 & 1#10 G IN 3/4" C
(2) #4 & 1#10 G IN 1" C
(2) #4 & 1#8 G IN 1" C
(2) #3 & 1#8 G IN 1" C
(2) #2 & 1#8 G IN 1" C
(2) #1 & 1#8 G IN 1 1/4" C
ELECTRICAL FEEDER SCHEDULE
2 3 4 4S 5
(3) #12 & 1#12 G IN 3/4" C15
(3) #12 & 1#12 G IN 3/4" C
(3) #10 & 1#10 G IN 3/4" C
(3) #10 & 1#10 G IN 3/4" C
(3) #8 & 1#10 G IN 3/4" C
(3) #8 & 1#10 G IN 3/4" C
(3) #6 & 1#10 G IN 3/4" C
(3) #6 & 1#10 G IN 3/4" C
(3) #4 & 1#10 G IN 1" C
(3) #4 & 1#8 G IN 1 1/4" C
(3) #3 & 1#8 G IN 1 1/4" C
(3) #2 & 1#8 G IN 1 1/4" C
(3) #1 & 1#8 G IN 1 1/2" C
(4) #12 & 1#12 G IN 3/4" C15
(4) #12 & 1#12 G IN 3/4" C
(4) #10 & 1#10 G IN 3/4" C
(4) #10 & 1#10 G IN 3/4" C
(4) #8 & 1#10 G IN 3/4" C
(4) #8 & 1#10 G IN 3/4" C
(4) #6 & 1#10 G IN 1" C
(4) #6 & 1#10 G IN 1" C
(4) #4 & 1#10 G IN 1 1/4" C
(4) #4 & 1#8 G IN 1 1/4" C
(4) #3 & 1#8 G IN 1 1/4" C
(4) #2 & 1#8 G IN 1 1/4" C
(4) #1 & 1#8 G IN 1 1/2" C
(3) #1 & 1#6 G IN 1 1/2" C
(3) #1/0 & 1#6 G IN 1 1/2" C
(3) #2/0 & 1#6 G IN 2" C
(3) #3/0 & 1#6 G IN 2" C
(3) #4/0 & 1#4 G IN 2" C
(3) #250 KCMIL & 1#4 G IN 2 1/2" C
(3) #350 KCMIL & 1#4 G IN 2 1/2" C
(3) #500 KCMIL & 1#3 G IN 3" C
(3) #500 KCMIL & 1#3 G IN 3" C
2 SETS OF (3) #4/0 & 1#2 G IN 2" C
2 SETS OF (3) #250 KCMIL 1#2 G IN 2 1/2" C
2 SETS OF (3) #350 KCMIL & 1#1 G IN 3" C
2 SETS OF (3) #500 KCMIL & 1#1/0 G IN 3" C
(3) #1 & 1#6 G IN 1 1/2" C
(3) #1/0 & 1#6 G IN 1 1/2" C
(3) #2/0 & 1#6 G IN 2" C
(3) #3/0 & 1#6 G IN 2" C
(3) #4/0 & 1#4 G IN 2" C
(3) #250 KCMIL & 1#4 G IN 2 1/2" C
(3) #350 KCMIL & 1#4 G IN 2 1/2" C
(3) #500 KCMIL & 1#3 G IN 3" C
(3) #500 KCMIL & 1#3 G IN 3" C
2 SETS OF (3) #4/0 & 1#2 G IN 2" C
2 SETS OF (3) #250 KCMIL 1#2 G IN 2 1/2" C
2 SETS OF (3) #350 KCMIL & 1#1 G IN 3" C
2 SETS OF (3) #500 KCMIL & 1#1/0 G IN 3" C
(4) #1 & 1#6 G IN 1 1/2" C
(4) #1/0 & 1#6 G IN 1 1/2" C
(4) #2/0 & 1#6 G IN 2" C
(4) #3/0 & 1#6 G IN 2" C
(4) #4/0 & 1#4 G IN 2" C
(4) #250 KCMIL & 1#4 G IN 2 1/2" C
(4) #350 KCMIL & 1#4 G IN 2 1/2" C
(4) #500 KCMIL & 1#3 G IN 3" C
(4) #500 KCMIL & 1#3 G IN 3" C
(3) #12 & 1#12 G IN 3/4" C
(3) #12 & 1#12 G IN 3/4" C
(3) #10 & 1#10 G IN 3/4" C
(3) #10 & 1#10 G IN 3/4" C
(3) #8 & 1#10 G IN 3/4" C
(3) #8 & 1#10 G IN 3/4" C
(3) #6 & 1#10 G IN 3/4" C
(3) #6 & 1#10 G IN 3/4" C
(3) #4 & 1#10 G IN 1" C
(3) #4 & 1#8 G IN 1 1/4" C
(3) #3 & 1#8 G IN 1 1/4" C
(3) #2 & 1#8 G IN 1 1/4" C
(3) #1 & 1#8 G IN 1 1/2" C
3 SETS OF (3) #350 KCMIL & 1#2/0 G IN 3" C
3 SETS OF (3) #500 KCMIL & 1#2/0 G IN 3" C
4 SETS OF (3) #350 KCMIL & 1#3/0 G IN 3" C
5 SETS OF (3) #500 KCMIL & 1#4/0 G IN 3" C
6 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
7 SETS OF (3) #500 KCMIL & 1#350 KCMIL G IN 3 1/2" C
8 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
11 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
10 SETS OF (3) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
2 SETS OF (4) #4/0 & 1#2 G IN 2 1/2" C
2 SETS OF (4) #250 KCMIL 1#2 G IN 3" C
2 SETS OF (4) #350 KCMIL & 1#1 G IN 3" C
2 SETS OF (4) #500 KCMIL & 1#1/0 G IN 3 1/2" C
3 SETS OF (4) #350 KCMIL & 1#2/0 G IN 3" C
3 SETS OF (4) #500 KCMIL & 1#2/0 G IN 3 1/2" C
4 SETS OF (4) #350 KCMIL & 1#3/0 G IN 3" C
5 SETS OF (4) #500 KCMIL & 1#4/0 G IN 3 1/2" C
6 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
7 SETS OF (4) #500 KCMIL & 1#350 KCMIL G IN 3 1/2" C
8 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
11 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
10 SETS OF (4) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
(4) #12 & 1#8 G IN 3/4" C
(4) #12 & 1#8 G IN 3/4" C
(4) #10 & 1#8 G IN 3/4" C
(4) #10 & 1#8 G IN 3/4" C
(4) #8 & 1#8 G IN 1" C
(4) #8 & 1#8 G IN 1" C
(4) #6 & 1#8 G IN 1" C
(4) #6 & 1#8 G IN 1" C
(4) #4 & 1#8 G IN 1 1/4" C
(4) #4 & 1#8 G IN 1 1/4" C
(4) #3 & 1#8 G IN 1 1/4" C
(4) #2 & 1#8 G IN 1 1/4" C
(4) #1 & 1#6 G IN 1 1/2" C
(4) #1 & 1#6 G IN 1 1/2" C
(4) #1/0 & 1#6 G IN 1 1/2" C
(4) #2/0 & 1#4 G IN 2" C
(4) #3/0 & 1#4 G IN 2" C
(4) #4/0 & 1#2 G IN 2" C
(4) #250 KCMIL & 1#2 G IN 2 1/2" C
(4) #350 KCMIL & 1#2 G IN 2 1/2" C
(4) #500 KCMIL & 1#1/0 G IN 3" C
(4) #500 KCMIL & 1#1/0 G IN 3" C
2 SETS OF (4) #4/0 & 1#1/0 G IN 2 1/2" C
2 SETS OF (4) #250 KCMIL 1#2/0 G IN 3" C
2 SETS OF (4) #350 KCMIL & 1#2/0 G IN 3" C
2 SETS OF (4) #500 KCMIL & 1#2/0 G IN 3 1/2" C
3 SETS OF (4) #350 KCMIL & 1#2/0 G IN 3" C
3 SETS OF (4) #500 KCMIL & 1#2/0 G IN 3 1/2" C
4 SETS OF (4) #350 KCMIL & 1#3/0 G IN 3" C
5 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C
6 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C
7 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C
8 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C
11 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C
10 SETS OF (4) #500 KCMIL & 1#3/0 G IN 3 1/2" C
(5) #12 & 1#12 G IN 3/4" C
(5) #12 & 1#12 G IN 3/4" C
(5) #10 & 1#10 G IN 3/4" C
(5) #10 & 1#10 G IN 3/4" C
(5) #8 & 1#10 G IN 1" C
(5) #8 & 1#10 G IN 1" C
(5) #6 & 1#10 G IN 1" C
(5) #6 & 1#10 G IN 1" C
(5) #4 & 1#10 G IN 1 1/4" C
(5) #4 & 1#8 G IN 1 1/4" C
(5) #3 & 1#10 G IN 1 1/4" C
(5) #2 & 1#8 G IN 1 1/4" C
(5) #1 & 1#8 G IN 1 1/2" C
(5) #1 & 1#6 G IN 1 1/2" C
(5) #1/0 & 1#6 G IN 1 1/2" C
(5) #2/0 & 1#6 G IN 2" C
(5) #3/0 & 1#6 G IN 2" C
(5) #4/0 & 1#4 G IN 2" C
(5) #250 KCMIL & 1#4 G IN 2 1/2" C
(5) #350 KCMIL & 1#4 G IN 2 1/2" C
(5) #500 KCMIL & 1#3 G IN 3" C
(5) #500 KCMIL & 1#3 G IN 3" C
2 SETS OF (5) #4/0 & 1#2 G IN 2 1/2" C
2 SETS OF (5) #250 KCMIL 1#2 G IN 3" C
2 SETS OF (5) #350 KCMIL & 1#1 G IN 3" C
2 SETS OF (5) #500 KCMIL & 1#1/0 G IN 3 1/2" C
3 SETS OF (5) #350 KCMIL & 1#2/0 G IN 3" C
3 SETS OF (5) #500 KCMIL & 1#2/0 G IN 3 1/2" C
4 SETS OF (5) #350 KCMIL & 1#3/0 G IN 3" C
5 SETS OF (5) #500 KCMIL & 1#4/0 G IN 3 1/2" C
6 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
7 SETS OF (5) #500 KCMIL & 1#350 KCMIL G IN 3 1/2" C
8 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 3 1/2" C
11 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 4" C
10 SETS OF (5) #500 KCMIL & 1#500 KCMIL G IN 4" C
NOTES:
1. CONDUIT SIZES FOR THHN/THWN COPPER CONDUCTORS ONLY. OTHER CONDUCTOR TYPES MAY REQUIRE INCREASED CONDUIT SIZE.
2. GROUND CONDUCTORS SPECIFIED IS FOR EQUIPMENT GROUND PER N.E.C. UNLESS NOTED OTHERWISE.
TOP NUMBER REFERS TO COLUMNS
BOTTOM NUMBER REFERS TO ROWS (AMPS)
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:SEAL
Revision# Date
3/
/2
:5 1:
A
M ERIE VAMC - EXPAND EMERGENCY
POWER GENERATION - PHASE II
VA244-16-J-5508
IT JZ
135 E 38TH ST, ERIE PA 16504
E200
ELECTRICAL RISER DIAGRAM
04/12/17 100
16030
FULLY SPRINKLERED
BID DOCUMENTS
NORTH
PROJECT
NTS
ELECTRICAL RISER DIAGRAM
1. REFER TO DRAWING E001 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND NOTES.
2. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE MEP & ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
3. PROVIDE 100% RATED CIRCUIT BREAKERS NEW UPS OUTPUT PANELBOARD.
4. AS A MINIMUM, DISCONNECT SWITCHES SHALL BE RATED AS THE UPSTREAM PROTECTIVE DEVICE RATING.
5. TRANSFORMER SECONDARIES SHALL BE GROUNDED TO THE MAIN GROUND BAR VIA A COPPER GROUNDING CONDUCTOR…