36C24418B0575-0001001.pdf

PDF 167 KB Posted

Attached to
Correct AC Deficiencies in Biomedical and Mailroom Federal contract opportunity
Solicitation number
36C24418B0575
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

36C24418B0575 0001 Drawing E101, REV 1 - BIO MEDICAL SHOP LIGHTING PLAN, SCHEDULES AND DETAILS - Dated 7-27-2018.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Correct AC Deficiencies in Biomedical and Mailroom, newest first.
File Type Posted
36C24418B0575-0001002.pdf PDF
36C24418B0575-0001003.pdf PDF
36C24418B0575-0001000.docx DOCX document
36C24418B0575-004.docx DOCX document
36C24418B0575-005.docx DOCX document
36C24418B0575-003.pdf PDF
36C24418B0575-007.docx DOCX document
36C24418B0575-006.docx DOCX document
36C24418B0575-002.pdf PDF
36C24418B0575-001.docx DOCX document
36C24418B0575-000.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2

1 2

EQ STOR

31A

BIO-MED SHOP

1 2

T1

T1

T1T1

T1

T1 T1

T1T1

1 2

1 2

EQ STOR

31A

BIO-MED SHOP

T1

1 2

S1

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

KEY PLAN

7/

/2

:4 1:

A

M CORRECT AIR CONDITIONING

DEFICIENCIES IN BIOMEDICAL

SHOP AND MAILROOM

503-17-104

JG BK

JAMES E. VAN ZANDT MEDICAL CENTER

ALTOONA, PA 16602

E101

BIO MEDICAL SHOP LIGHTING PLAN,

SCHEDULES AND DETAILS

MARCH 27, 2018

17029

BID DOCUMENTS

NORTH

TRUE NORTH

PROJECT

BIO-MED SHOP

LIGHTING GENERAL NOTES

1 HALF SHADED LIGHTING FIXTURES SHALL HAVE AN INTEGRAL EMERGENCY BATTERY

BACKUP.

2 COORDINATE FINAL LOCATIONS OF FIXTURES WITH MECHANICAL OBJECTS.

3 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS.

4 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE

NECESSARY TO AVOID DUCT WORK AND HVAC SYSTEM.

5 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO

CONFORM TO NEC REQUIREMENTS.

7 ALL SCOPE INDICATED ON THIS DRAWING SHALL BE INCLUDED AS PART OF BID ITEM 1.

REFER TO SPECIFICATIONS SECTION 01 00 00.

8 UNDER BID ALTERNATE NO.1, ALL SCOPE INDICATED ON THIS DRAWING SHALL BE

EXCLUDED. REFER TO SPECIFICATIONS SECTION 01 00 00.

LIGHTING DEMOLITION KEYED NOTES

1 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE WIRES BACK TO THE

NEAREST JUNCTION BOX ABOVE CEILING. EXISTING CIRCUIT SHALL BE RE-USED.

2 EXISTING CEILING MOUNTED DEVICES SUCH AS LIGHTING CONTROL AND FIRE ALARM

DEVICES SHALL BE REMOVED AND RE-INSTALLED AFTER THE INSTALLATION OF NEW

CEILING.

1/4" = 1'-0"

BIO MEDICAL SHOP 31 - LIGHTING DEMOLITION PLAN

1/4" = 1'-0"

BIO MEDICAL SHOP 31 - LIGHTING NEW WORK PLAN

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION

BASIS OF DESIGN LAMP

TYPE

WATTAGE VOLTAGE COMMENTS

MANUFACTURER MODEL NO.

S1 4' SURFACE MOUNT LED LITHONIA LBL4 4000LM 80CRI 40K

MVOLT

LED 32 VA 120 V

T1 2'x4', RECESSED LED LITHONIA 2GTL-4-40L-MVOLT-LP840 LED 31 VA 120 V PROVIDE HALF SHADED FIXTURE WITH 1400L, 90MIN

RUN, INTEGRAL EM BATTERY (EL14L); PROVIDE A

MULTI-VOLTAGE INPUT DRIVER (MVOLT 120-277V)

1 BID RFIs 07/27/2018

# LIGHTING KEYED NOTES

1 PROVIDE NEW LIGHTING FIXTURES AND CONNECT TO THE EXISTING LIGHTING AND

CONTROLS CIRCUIT IN THIS ROOM. PROVIDE ADDITIONAL WIRES AS REQUIRED TO

EXTEND THE CIRCUIT TO THE LOCATIONS OF THE NEW LIGHTING FIXTURES.

2 COORDINATE LOCATIONS OF NEW LIGHTING FIXTURES WITH EXISTING SPRINKLER HEADS.

RELOCATE LIGHT FIXTURES TO AVOID CONFLICT.