36C24218B0371-0002000.docx

DOCX document 19 KB Posted

Attached to
RENOVATE CLC 3 Federal contract opportunity
Solicitation number
36C24218B0371
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24218B0371 0002 36C24218B0371 0002.docx

View the file

Other files for this federal contract opportunity

Other files attached to RENOVATE CLC 3, newest first.
File Type Posted
36C24218B0371-0004000.docx DOCX document
36C24218B0371-0003000.docx DOCX document
36C24218B0371-0002001.pdf PDF
36C24218B0371-0002006.pdf PDF
36C24218B0371-0002005.pdf PDF
36C24218B0371-0002004.pdf PDF
36C24218B0371-0002002.pdf PDF
36C24218B0371-0002003.pdf PDF
36C24218B0371-00001001.pdf PDF
36C24218B0371-00001000.docx DOCX document
36C24218B0371-016.pdf PDF
36C24218B0371-015.pdf PDF
36C24218B0371-014.pdf PDF
36C24218B0371-017.pdf PDF
36C24218B0371-018.pdf PDF
36C24218B0371-011.docx DOCX document
36C24218B0371-019.pdf PDF
36C24218B0371-012.pdf PDF
36C24218B0371-013.pdf PDF
36C24218B0371-000.docx DOCX document
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE

OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

BY

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 06-08-2018 528A6-17-601 00242 Network Contracting Office 2 Bath VA Medical Center 76 Veterans Avenue Bath

NY

14810 00242 Network Contracting Office 2 Bath VA Medical Center 76 Veterans Avenue Bath

NY

14810 To all Offerors/Bidders

36C24218B0371 05-16-2018

X X X

See page 2 through 4 for questions and answers to question.

Edward Kostolansky Contracting Officer

CONTINUATION PAGE

CLC 3 Questions and Answers Amendment #2

1.Notes 18 and 19 on the Architectural Demolition drawings (AD-102 and AD-103) refer to Structural Drawings, which were not issued with the bid set of documents. Please provide these drawings.
•AE Response: Refer to attached structural drawings and specification section 051200.
2.Demolition General Note 09 on Architectural Demolition drawings AD-102 and AD-103 requires that the existing sprinkler systems remain operational throughout demolition and construction. Note 13 reiterates the same. However, General Note 3 on Fire Protection Demolition drawing FD-103 states that the “Existing system shall remain until work commences in respective zone.” Please clarify the intent, as the requirement to keep the systems active throughout all construction activities will carry a higher cost to the project.
•AE Response: Sprinkler system to be maintained intact, and 100% active throughout the project until specific sprinkler system modification is required. Contractor responsible for coordination with VA COR on any specific ILSM (Interim Life Safety Measure) or other VA policies during periods of sprinkler system outage.
3.Detail 10/A502 calls for “Thin brick veneer on thin set mortar and waterproofing membrane,” but this detail also has another callout for a waterproofing membrane. Is it the intent that one membrane be applied to the cementitious sheathing and a second membrane be applied to the gypsum board?
•AE Response: Waterproofing membranes to be applied at both locations
4.Please clarify the intent of the documents in relation to the removal of the existing ACM glue dots; specifically, in relation to the staining that would be left behind by traditional removal methods. Given that numerous follow-up trades will be installing mechanical fasteners into the concrete ceiling, and the staining will contain some trace amount of ACM, should these areas be bead or shot-blasted to removal all staining from the concrete?
•AE Response: The discoloration and staining that may remain on a concrete ceiling following a ceiling tile mastic asbestos abatement is not considered an asbestos concern. The non-asbestos oils within the mastic are what penetrates and impregnates the concrete subsurface and can result in discoloration and/or staining. Depending on the type of mastic, this staining can vary from heavy to nonexistent. All bulk mastic materials shall be completely removed utilizing non-friable and non-mechanical abatement procedures. Following the bulk removal, the underlying surfaces shall be thoroughly fine cleaned utilizing a low odor liquid mastic remover. The fine cleaning procedures will most likely require multiple applications of the mastic solvent prior to achieving a stain free concrete subsurface. If all ceiling tile mastic has been properly removed, with all associated ceiling surfaces aggressively fine cleaned to the satisfactory of a New York Project Monitor, it shall be concluded that any stained surfaces remaining within the work area pose no asbestos environmental concerns.

In the hardware spec, section 1.9, there is a reference to hardware sets: “symbols for hardware sets consist of letter (e.g., “HW”) followed by a number. Each number designates a set of hardware items applicable to a door type.” There are no hardware set numbers on A600, just abbreviations for the type of hardware for the door. Will there be any more details about actual hardware sets forthcoming?

• Answer - Refer to the door schedule for all door hardware requirements. No hardware sets are used in the spec or on the drawings as they are listed out on the door schedule.

When I was reviewing the above referenced project I noticed that the volume 1 spec book table of contents lists section 149133 Linen Chute, but there were no spec pages for this section. Should this section be deleted from the table of contents or are the pages missing from the book?

Answer – See attached spec section 149122 Linen Chute

1. On the reflected ceiling plans (A107-A109), the symbol for the Patient Lift System states “Patient Lift Track CFCI, Lift Motor & Accessories OFOI”. However, Note 4 on the same sheets states “Patient lifts to be furnished and installed by the contractor”. Can you please clarify this scope of work?

Response: Lift motors and accessories have already been purchased by the VA, therefore the contractor is only responsible for providing, installing, testing the lift track and supports. Contractor MUST use a manufacturer that is compatible with the lift motors and accessories that have already been purchased by the VA. Provide supports and mounting in accordance with manufacturers requirements. Contractor to provide stamped PE calculations for mounting and attachment to the existing structure.

2. The Table of Contents lists a Section 14 91 33 – Linen Chutes, but this section is not contained in the PDF bundles distributed for the bid. Can you please provide this section?

Response: See attached spec section.

1. Are the Ceiling Mounted Patient Lift Systems, Brand name only, or can we propose a different Lift Brand? as long as we comply with the requirements of Specification 11 73 00.

Response: Contractor MUST use a manufacturer that is compatible with the lift motors and accessories that have already been purchased by the VA.

2. There are confusing statements in some of the Architectural Drawings, are the Lifts and Accessories CFCI or OFOI?

Response: Lift motors and accessories have already been purchased by the VA, therefore the contractor is only responsible for providing, installing, testing the lift track and supports.

3. The Specification 05 12 00 Structural Steel Framing is missing, it shows as a requirement in Specification 11 73 00.

Response: Provide supports and mounting in accordance with manufacturers requirements. Contractor to provide stamped PE calculations for mounting and attachment to the existing structure.

4. Drawings AI-405 and AI-411, shows Headwalls Details, but the Specification for the Headwalls is missing, are the Headwall part of this project?

Response: All the headwalls are custom and do not require a premanufactured headwall product, therefore there is no need for a specification.

•Regarding the typical patient toilet rooms; on the finish floor plans the wall finish indicator (T-13/T-14) appears to point at one wall only, but the interior elevations appear to show wall tile at different locations. Where is wall tile required at the patient toilets? All walls? Please clarify wall tile locations.
•All walls are to receive tile in resident toilet rooms.
•Regarding the typical patient toilet rooms; What is the wall tile outside corner detail? Bullnose tile or Schluter metal edge? Please clarify detail.
•Bullnose tile as referenced on finish plans, legends, and schedules
•Regarding the Staff toilet rooms; What is the wall tile accent shown on 12/AI-403. What is the manufacture of the accents called out in finish plan notes 10 & 11, on AI-101. Please clarify accent.
•Manufacturer to match T-10 tile, however color TBD
•Regarding Spa toilet 376B; on the finish floor plans the wall finish indicator (T-2/T-3) appears to point at one wall only, but the interior elevations appear to show wall tile at different locations. Where is wall tile required at the spa toilet? All walls? Please clarify wall tile locations
•This is a mistake on the drawings. Wall tile to only be on the wall where the sink is located

See attached document: S06 - 149133 - Linen chute.

See attached document: S06 - S-001.

See attached document: S06 - S-301.

See attached document: S06 - SF141.

See attached document: S06 - SF142.

See attached document: S06 -051200 (02-2016) Structural Steel Framing.