36C24218B0120-00002001.pdf

PDF 67 KB Posted

Attached to
528A7-15-712 REPLACE AHU-05 AND EF-05 Federal contract opportunity
Solicitation number
36C24218B0120
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24218B0120 00002 VA Responses to Pre-Bid RFIs.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 528A7-15-712 REPLACE AHU-05 AND EF-05, newest first.
File Type Posted
36C24218B0120-00003000.docx DOCX document
36C24218B0120-00002002.pdf PDF
36C24218B0120-00002003.pdf PDF
36C24218B0120-00002000.docx DOCX document
36C24218B0120-00001001.pdf PDF
36C24218B0120-00001000.docx DOCX document
36C24218B0120-002.pdf PDF
36C24218B0120-004.docx DOCX document
36C24218B0120-001.docx DOCX document
36C24218B0120-003.pdf PDF
36C24218B0120-000.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Request For Information (RFI)

Project Name: Replace AHU-5 & EF-05 Project #: 528A7-15-712

Solicitation#: 36C24218B0120

Syracuse, February 21, 2018

VA Medical Center Response

Question 1: In our review of the plan set we have found that performance schedules for the Heat Exchanger, Converter, and Condensate cooler are missing from the contract drawings. Please have the DOR provided updated drawings with the requisite performance schedules necessary to complete our bid.

Answer 1: Heat Exchanger, Converter, and Condensate Cooler are existing equipment scheduled to be relocated and reused.

Question 2: Please provide the make and model of the existing fire alarm system.

Answer 2: Make: Edwards & Model: EST 3.

Local Vendor: RED HAWK FIRE & SECURITY. East Syracuse, NY, Tel: 315-458-1154

Question 3: Which controls contractor is acceptable for this project? (Johnson Controls or Siemens) Johnson Controls is listed on the drawings but the extension of the Siemens system is listed in the specs.

Answer 3: We will accept either Johnson Controls or Siemens as long as their product meets the material specification requirements. All references to “Siemens” in specification 23 09 23, and all references to “Johnson Controls” on the drawings have been changed to read “Siemens or Johnson Controls”.