Amendment 1 Questions and Answers.docx
DOCX document 26 KB Posted
- Attached to
- J041--Building 2 Ground Water Replacement Federal contract opportunity
- Solicitation number
- 36C24124Q0073
About this file
This document contains questions and answers related to solicitation number 36C24124Q0073 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1 for replacing a ground water valve at Building 2. The questions seek clarification on details of the valve being replaced including whether other valves can be isolated, the flange measurements, piping material, who will perform shutoff work, and whether drain valves exist. Responses indicate most risers can be isolated, the valve size is unknown and must be measured, piping material is copper, only site staff can operate valves, and no drain valves exist on the main piping. Non-flanged ball or gate valves with solder connections would not be accepted as a replacement for the valve detailed in the statement of work.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24124Q0073_3.docx | DOCX document | |
| 36C24124Q0073_2.docx | DOCX document | |
| Combined Synopsis-Solicitation.docx | DOCX document | |
| Attachment 3_Past Performance Worksheet.xlsx | XLSX spreadsheet | |
| Attachment 2_Price Schedule.xlsx | XLSX spreadsheet | |
| Attachment 1_SOW.docx | DOCX document | |
| 36C24124Q0073_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFIs for Solicitation 36C24124Q0073 Building 2 Ground Water Replacement
1. Can the other water risers in the building be isolated with shutoff valves or must be drained to replace this valve?
Most of the risers can be shut down.
2. What is the flange-to-flange measurement of this valve (the space between the piping flanges if the valve was removed)?
Unknown, the valve will need to be measured.
3. What is the piping material the valve is installed on (copper, brass, galvanized)?
Copper.
4. Will the contractor performing the work be shutting of the cold water main or will this be performed by site staff?
Staff are the only individuals allowed to touch valves.
5. Are there drain valves on both sides of this valve for draining all water from the piping prior to disconnection?
There are no drain valves on the main only after the valves for the risers.
6. The valve detailed in the SOW is no longer manufactured, would the end user accept proposals for non-flanged 2-1/2" brass ball or gate valves with solder-to-solder end connections?
No, please keep with what is there.