Attachment_1_-_Specifications_0001.pdf
PDF 341 KB Posted
- Attached to
- FUEL STORAGE TANK Federal contract opportunity
- Solicitation number
- 140R3024Q0090
About this file
This document appears to be an attachment containing technical specifications for a federal contract opportunity to purchase two 3,000-gallon aboveground fuel storage tanks.
The key details are:
- The Bureau of Reclamation's Yuma Area Office has a requirement to purchase two 3,000-gallon aboveground fuel storage tanks.
- The tanks must meet specific salient characteristics, including UL-142 compliance, double-wall secondary containment, overfill protection, and integrated pump and dispensing equipment.
- The contractor must deliver the tanks to the Yuma Area Office within 90 days of contract award and coordinate the delivery at least 2 weeks in advance.
- Payment will be a lump-sum price upon delivery of the tanks.
The related federal contract opportunity is Solicitation Number 140R3024Q0090, issued by the Department of the Interior's Bureau of Reclamation, for the purchase of 3,000-gallon aboveground fuel storage tanks.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_4_-_Questions_and_Answers_0001.pdf | ||
| Sol_140R3024Q0090_Amd_0001.pdf | ||
| Sol_140R3024Q0090.pdf | ||
| 140R3024Q0090.pdf | ||
| 140R3024Q0090_Combined_Synopsis.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment 1
Specifications
3000 Gallon Aboveground Fuel Storage Tank
PART 1 GENERAL
1.01 DESCRIPTION
The Bureau of Reclamation, Yuma Area Office, has a requirement to purchase two 3000-gallon aboveground fuel storage tanks.
MEASUREMENT AND PAYMENT
A. The cost measurement for two Aboveground Fuel Storage Tanks (AST) includes the following:
1. Two 3000-gallon AST’s which meets or exceeds these minimum characteristics.
2. Delivery to the Bureau of Reclamation (BOR), Yuma Area Office (YAO).
B. Payment: Lump-sum price offered upon delivery of the AST’s.
PART 2 PRODUCTS
2.01 Aboveground Storage Tank Salient Characteristics:
A. Contractor must provide two fully functional and safe 3000 Gallon Aboveground Fuel Storage Tanks with the minimum characteristics of each:
1. Minimum capacity of 3000 gallons of diesel fuel.
2. Constructed to meet UL-142 compliance standards.
3. Double wall secondary containment construction.
4. Interstitial space monitoring point with dipstick and or gauge.
5. Equipped with overfill protection device.
6. All required statutory signage and markings for diesel storage.
7. Portable design and equipped with lifting lugs or eyelets for ease of lifting and transport..
8. Built in ladder for access to top fill location.
9. Bunded pump bay with lockable doors with dust seals.
10. 110-volt, 35- gallon per minute product pump housed in pump bay.
11. 100 feet of 1 inch hose on self-retracting hose reel and auto-shutoff fuel nozzle housed in pump bay.
12. High-flow product meter and inline fuel filter housed in pump bay.
PART 3 CONTRACTOR SERVICES
3.01 DELIVERY
A. The AST’s shall be delivered to:
Bureau of Reclamation Yuma Area Office 7301 Calle Agua Salada
Yuma, Az. 85364
Warehouse POC is Larry Arnold 928-343-8525
Within 90 days of the contract award date. The contractor must coordinate the delivery with the YAO at least 2 weeks in advance.
The contractor must protect all parts/equipment from corrosion, deformation, dents, dings, scratches, ruptures, breaks, punctures, abrasions, cuts, and other types of damage during storage, handling, transport, and delivery.