Site_Visit_Q_A_0001.pdf

PDF 109 KB Posted

Attached to
HVAC Replacement, Chief Factor House, Fort Vancouv Federal contract opportunity
Solicitation number
140P8323Q0012
Issued by
Department of the Interior National Park Service Pacific West Region

View the file

Other files for this federal contract opportunity

Other files attached to HVAC Replacement, Chief Factor House, Fort Vancouv, newest first.
File Type Posted
Sol_140P8323Q0012_Amd_0001.pdf PDF
Attachment_B_Drawings.pdf PDF
Attachment_C_BLDG_Description_and_Photos.pdf PDF
Attachment_A_Specifications.pdf PDF
Sol_140P8323Q0012.pdf PDF
Attachment_E_Forms_to_Return_with_Quote.docx DOCX document
Attachment_D__DOL_Wage_Determination.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFQ # 140P8323Q0012 Fort Vancouver NHS Chief Factor House HVAC

Site Visit Questions and Answers

Q: Are there twinned furnaces?

A: Each air handler unit is suppling air to separate zones. AHU-1 supplies air to the Kitchen, AHU-2 supplies air to the Chief Factor’s House main and second floor.

Q: Are there any options to enlarge the opening to the Chief Factor’s House basement mechanical room?

A: No, there is no way to enlarge the entrance to the basement mechanical room.

Q: Who does fire protection for the Chief Factors House? Can they remove the lines for the fire suppression system in the Chief Factors House basement?

A: The park holds a maintenance contract with McKinstry for fire sprinkler testing and maintenance. The Park can coordinate with them to modify the existing fire sprinkler heads if they conflict with the HVAC replacement work.

Q: Is there a fresh air intake duct?

A: Yes, there is an existing fresh air intake duct which draws in air from underneath the porch. Attachment 3 included in the solicitation shows the location of the intake.